| 2005-08-12 00:00:00 | ***** UNSAT ******* |
| | |
| | 1)NOTE: PLEASE COMPLETE AND SHOW ALL |
| | CIRCUITING ON PLANS AND CORRELATE WITH |
| | THE SUBMITTED PANEL SCHEDULE. |
| | PLEASE SEE SOME ITEMS/DEVICES ON PLANS |
| | WITH NO CIRCUITING. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS.THE BRANCH CIRCUIT FEEDING |
| | THE UNIT EQUIPMENT SHALL BE THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | PLEASE COMPLETE CONTROL/CIRCUITING OF |
| | LTS ON PLANS. PLEASE SEE SOME OF LTS |
| | SHOWN DO NOT INDICATE ANY MEANS OF |
| | CONTROL OR CIRCUITING. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER 220.3, 220.10, 220.11, |
| | 220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE LOADS ON PANEL AND PANEL IS |
| | SHOWN AS "BLANK". |
| | |
| | 3)NOTE: PLEASE INDICATE WHERE PANEL IS |
| | BEING FED FROM, PLEASE SHOW LOAD ON |
| | EXISTING SERVICE FOR NEW 400A PANEL, |
| | PLEASE SEE PREVIOUS NOTE #2. |
| | PLEASE INDICATE FEEDERS, GROUNDING, ETC |
| | ON A RISER DIAGRAM. |
| | |
| | 4) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 5)NOTE: PLEASE INDICATE NEW OR EXISTING |
| | SIGN CIRCUIT PER 600.5 |
| | |
| | 6)NOTE: PLEASE SEE ALL RECEPTS WITH IN |
| | 6' OF SINKS SHALL BE SHOWN AS GFI.210.8 |
| | PLEASE SEE GFI PROTECTION REQUIRED FOR |
| | ALL RECEPTS IN KITCHEN AREAS IN OTHER |
| | THANDWELLING UNITS. PLEASE SEE 210.8B3 |
| | |
| | WHICHREQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | PLEASE BE SURE TO SEE ANY OTHER COMMENTS |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANS REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |