Plan Review Details - Permit 05080168
Plan Review Stops For Permit 05080168
Review Stop AD ADDRESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By jhiggins Date 2005-08-09 Time 16:02 Rev Time 0.00
Received By jhiggins Date 2005-08-09 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By shill Date 2006-06-22 Time 13:34 Rev Time 0.00
Received By shill Date 2006-06-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By shill Date 2006-03-06 Time 11:23 Rev Time 0.00
Received By shill Date 2006-03-06 Time 10:35 Sent To  
Notes
2006-03-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW
  
 1.)PROVIDE A SURVEY AND SITE PLAN.
  
 PROVIDED; PLEASE KEEP IN PERMIT PACKAGE.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 ADDRESSED; PLEASE KEEP THE STAMPED FLOOR
 PLAN AND RECEIPT IN THE PERMIT PACKAGE.
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 5.)SHOW MANEUVERING CLEARANCE FOR PULL
 SIDE OF DOORS, FBC11 FIGURE 25,
 FBC11-4.13.6.MANY DOORS APPEAR
 NONCOMPLIANT.
  
 NOT PROPERLY ADDRESSED.THE 18 OR 36 IN
 REQUIREMENT IS NOT SHOWN.FOR INSTANCE,
 SEE THE DOOR BETWEEN PLAY AND OFFICE,
 BOTTOM RIGHT, DOOR AT THE STAIR.
  
 6.)ADDRESSED.
  
 7.)ADDRESSED.
  
 8.)PROVIDE A DETAIL FOR THE HANDRAIL
 FOR THE STAIRS, FBC11-4.94, FIGURE
 11-19.
  
 NOT ADDRESSED.NO EXTENSIONS SHOWN.
 DOES NOT RETURN TO THE WALL AS SHOWN ON
 PLAN VIEW, FBC11-12.9.4(2), (6).
  
 9.)ADDRESSED.
  
 10.)PROVIDE A DETAIL FOR THE HANDRAIL,
 FBC11-4.8.5.SHOW REQUIRED EXTENSIONS.
  
 NO EXTENSIONS SHOWN.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THIS MUST BE DONE PRIOR TO PERMIT
 PICKUP.
  
 NEW COMMENT:
  
 12.A2-1 REFERS TO AN INCORRECT CODE
 FBC2002 (SHOULD BE FBC2001).THIS ALSO
 HAS THE WRONG INTERNAL PRESSURE
 COEFFICIENT FOR AN ENCLOSED BUILDING.
  
 13.)WHAT IS THE HATCHED WALL AT MED
 REC 152?WHAT ARE THE HATCHED AREAS
 ALONG THE EXTERIOR WALL SOUTH SIDE,
 A2-1?
  
 14.)ARE WINDOWS BEING INSTALLED?IF
 THEY ARE, PROVIDE PRODUCT APPROVALS.
 FLORIDA STATE PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOA OR EVALUATION
 REPORT, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 15.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT PROPERLY ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By shill Date 2005-08-30 Time 10:28 Rev Time 0.00
Received By shill Date 2005-08-29 Time 18:28 Sent To  
Notes
2005-08-30 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE A SURVEY AND SITE PLAN.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)THERE ARE TWO DIFFERENT SHEET A2-1,
 BOTH SHOWING A FLOOR PLAN.I HAVE
 REVIEWED THE FLOOR PLAN ON THE SHEET
 WITH THE FURNITURE PLAN BECAUSE IT
 CONTAINS INFORMATION NOT ON THE OTHER
 SHEET.PLEASE INCORPORATE THE DETAILS
 ON THE OTHER A2-1 INTO THIS SHEET, AND
 ONLY INCLUDE ONE FLOOR PLAN/FURNITURE
 PLAN.
  
 4.)COMBUSTIBLES IN CONCEALED SPACES
 NOT ALLOWED IN TYPE IV CONSTRUCTION,
 FBC707.1; SEE THE WINDOW BUCK DETAIL,
 DOOR FRAMING.
  
 5.)SHOW MANEUVERING CLEARANCE FOR PULL
 SIDE OF DOORS, FBC11 FIGURE 25,
 FBC11-4.13.6.MANY DOORS APPEAR
 NONCOMPLIANT.
  
 6.)THE FURNITURE PLAN APPEARS TO BE
 THE SAME AS THE FLOOR PLANS.TO AVOID
 CONFUSION AND TO MAINTAIN CONSISTENCY,
 PLEASE SUPPLY ONE FURNITURE PLAN.
  
 7.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.2.IT IS NOT CLEAR WHICH
 DOORS ARE ACCESSIBLE ENTRANCES AND
 EXITS.
  
 8.)PROVIDE A DETAIL FOR THE HANDRAIL
 FOR THE STAIRS, FBC11-4.94, FIGURE
 11-19.
  
 9.)THE RAMP IS TO COMPLY WITH
 FBC11-4.8.PLEASE SEE:
  
 A.)11-4.8.6, CROSS SLOPE IS NOT TO
 EXCEED 1:50.1:12 IS SHOWN.
  
 B.)11-4.8.2, THE SLOPE IS TO BE 1 TO
 12 MAXIMUM.PROVIDE A DETAIL SHOWING
 ELEVATION CHANGES SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.
  
 C.)11-4.8.4(3), THE MINIMUM LANDING
 SIZE IS TO BE 60 X 60 WHERE THE RAMP
 CHANGES DIRECTION.
  
 D.)11-4.8.4(1) THROUGH (4), SHOW
 COMPLIANCE WITH DIMENSIONS.
  
 10.)PROVIDE A DETAIL FOR THE HANDRAIL,
 FBC11-4.8.5.SHOW REQUIRED EXTENSIONS.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-04-03 Cont ID  
Sent By dpalmer Date 2007-04-03 Time 13:51 Rev Time 0.00
Received By dpalmer Date 2007-04-03 Time 13:39 Sent To PC
Notes
2007-04-03 13:51:54REVISED PANEL SCHEDULES

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-25 Cont ID  
Sent By dpalmer Date 2007-03-25 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2007-03-25 Time 10:54 Sent To FIRE
Notes
2007-03-25 11:03:25** PLANS ROUTED TO FIRE FOR STAMPS ON FA RISER SHEETS
 AND ELECTRICAL SHEETS. ON FIRE REVIEW DESK.
 PLANS NEED FIRE STAMPS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-15 Cont ID  
Sent By dpalmer Date 2007-03-15 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2007-03-15 Time 09:16 Sent To PC
Notes
2007-03-15 12:06:09** UNSAT**
  
 1) NOTE: PLEASE SEE AS STATE IN PREVIOUS REVIEW THE
 MINIMUM LEVELS FOR ADA COMPLIANCE MUST BE STATED ON
 THESE PLANS PER FBC 2001 11-4.28.1,.2,.3(4).
  
 PLEASE SEE THAT THE PERMIT FOR THE FIRE ALARM SYSTEM
 HAS NOT BEEN ADJUSTED AND SHALL REMAIN IN A HOLD STATUS
 AND NO INSPECTIONS CAN BE DONE.
 PLEASE SEE THE PREVIOUS COMMENTS WITH RESPECT TO THE
 VALUATION OF THIS SCOPE OF WORK.
 PLEASE SEE THERE ARE FEES OWED ON THE SECURITY PERMIT
 AND NEED TO BE PAID ALSO.
 FBC 106.3.5 (2001) 108.3(2004). VALUATION SHALL INCLUDE
 ALL LABOR AND MATERIALS WHETHER OR NOT ANY EQUIPMENT OR
 MATERIALS ARE OWNER SUPPLIED.
 ANY CONTRACT/MONATERING VALUE SHALL ALSO BE INCLUDED
 (WHERE APPLICABLE).
  
 AT THIS TIME THE ELECTRICAL, FIRE ALARM AND LOW VOLTAGE
 SECURITY PERMIT WILL BE PLACED ON HOLD.
  
 *
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 12:40 Sent To FIRE
Notes
2007-02-27 13:46:03*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THESE PLANS CALL FOR A COMPLETE
 FIRE ALARM INSTALLED UNDER THIS CONTRACT AND PERMIT
 HOWEVER PLEASE KNOW THAT BASED ON THE FA SYSTEM
 REQUIRED UNDER A SEPARATE PERMIT THE MAIN SETS OF PLANS
 WOULD ONLY SHOW THE SYSTEM AS REQUIRED UNDER THE FBC.
 PLEASE SEE THE LEVELS FOR ALL FA DEVICES SHALL BE
 STATED PER FBC 200111-4.28.1,.2 AND .3(4).
 PLEASE SEE THAT THE FA PERMIT HAS CURRENTLY BEEN PLACED
 INTO A *HOLD* STATUS UNTIL VALUATION FOR THE COMPLETE
 SCOPE OF WORK HAS BEEN ADJUSTED. PLEASE SEE THAT THE
 APPLIED VALUE FOR ALL WORK AS SHOWN IS VERY LOW AND
 SHALL INCLUDE ALL LABOR AND MATERIALS.
 FBC 108.3
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THAT THE PLANS SHALL INDICATE THE
 CHANGES BY CLOUDS/TRIANGLES FOR REVISIONS SINCE THE
 LAST SUBMITTED SET OF STAMPED/REVIEWED RECORD SET OF
 PLANS.
 FBC 106.1.2 ADMIN SECTION.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND
 IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 18:10 Sent To  
Notes
2006-06-12 00:00:00PLANS STAMPED.
 SCOPE OF WORK UNDER THE 2001 FBC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-23 Cont ID  
Sent By dpalmer Date 2006-02-23 Time 06:23 Rev Time 0.00
Received By dpalmer Date 2006-02-23 Time 06:17 Sent To  
Notes
2006-02-23 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE COMPLETE SETS OF
 PLANS WERE NOT SUBMITTED. PLEASE SEE THE
 ORIGINAL "A" SHEETS WERE SUBMITTED AND
 NO NEW "A" SHEETS SUBMITTED.
 PLEASE ALSO SEE NO PLANS SUBMITTED NEW
 OR OLD FOR LIGHTING, EM/ EXT LTS ETC??
  
 LS 101 7.8,7.9, 215.5
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 PLEASE SEE COMMENTS FROM OTHER TRADES AS
 COMMENTS WILL BE THE SANE AS PREVIOUS
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By dpalmer Date 2005-08-12 Time 07:11 Rev Time 0.60
Received By dpalmer Date 2005-08-12 Time 06:55 Sent To  
Notes
2005-08-12 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE CORRELATE "FOOT PRINT" OF BLDG ON
 ELECTRICAL PLANS TO MATCH NEW PROPOSED
 "FOOT PRINT" SHOWN ON BLDG PLANS.
  
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 PLEASE SEE FIRE REVIEW COMMENTS FOR EM/
 EXT LTS TO BE SHOWN.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SHOW ANY EXISTING RECEPTS W/ AN
 "E".
 PLEASE COMPLETE ALL SWITCH LEGS. MEANS
 OF CONTROL IS SHOWN FOR SOME LTS,
 HOWEVER THERE ARE MANY FIXTURES SHOWN
 WHICH DO NOT SEEM TO INDICATE HOW THEY
 ARE BEING CONTROLLED.
  
 PLEASE SEE ELECTRICAL PLANS ARE NOT
 COMPLETE FOR A FULL REVIEW.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS ARE TO BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-03-26 Cont ID  
Sent By mawillia Date 2007-03-26 Time 15:44 Rev Time 0.00
Received By mawillia Date 2007-03-26 Time 15:42 Sent To E
Notes
2007-03-26 15:44:06*****REVISIONS APPROVED*****
  
  
  
 PLAN SHEETS E100 AND E101 WERE STAMPED, INTIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 19:38 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 19:36 Sent To  
Notes
2007-03-06 19:38:00*****PROVISO*****
  
  
 REVISIONS TO BE APPROVED WHEN ELECTRICAL HAS BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-28 Cont ID  
Sent By mwennerg Date 2006-06-28 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-06-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-03-03 Cont ID  
Sent By mwennerg Date 2006-03-03 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2006-03-03 Time 15:04 Sent To  
Notes
2006-03-03 00:00:00******DENIED******
  
 IT DOES NOT APPEAR THAT THE COMMENTS
 FROM THE LAST REVIEW HAVE BEEN
 ADDRESSED.
  
  
 1) SHT E-101 SHOWS FIRE ALARM EQUIPMENT.
 IS THIS NEW OR EXISTING? PLEASE INDICATE
 IF FIRE ALARM AND FIRE SPRINKLER SYSTEMS
 ARE PART OF THE SCOPE OF THIS WORK.
  
 2) DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEM WHERE
 CAPACITY IS GREATER THAN 2000 CFM.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) PLEASE SHOW ALL LOCATIONS OF
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING FACILITIES.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS,
 CLASS A,B OR C.
  
 6) PLEASE INCLUDE ALL NEW SHEETS WHEN
 SUBMITTING PLANS.
  
 7) STAIRS AND RAMP SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 10:35 Sent To  
Notes
2005-09-01 00:00:00******DENIED******
  
 1) ELECTRICAL SHEET INDICATES WHAT
 APPEARS TO BE ILLUMINATED EXIT SIGNS,
 HOWEVER THIS IS NOT ILLUSTRATED ON THE
 LEGEND. PLEASE CLEARLY IDENTIFY THE
 LOCATIONS OF EXIT LIGHTS AND EMERGENCY
 LIGHTING FACILITIES, EXISTING AND OR
 NEW.
  
 2) PLEASE SHOW THE LOCATIONS OF 2A-10B,C
 RATED FIRE EXTINGUISHERS TO BE MOUNTED
 TO SATISFY 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 3) IS THERE EXISTING FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS?
  
 4) PLEASE INCLUDE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS
 THAT IS PERTINENT TO THIS OCCUPANCY
 TYPE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 12:02 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 12:02 Sent To E
Notes
2007-03-24 12:03:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 16:29 Sent To E
Notes
2007-03-16 16:30:09TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 16:06 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 16:06 Sent To E
Notes
2007-03-13 16:06:59TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 16:20 Sent To E
Notes
2007-02-16 16:21:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-14 Cont ID  
Sent By pkrauss Date 2006-07-14 Time 08:59 Rev Time 0.00
Received By pkrauss Date 2006-07-14 Time 08:59 Sent To M
Notes
2006-07-14 00:00:00SUBMITTAL TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 13:38 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 13:38 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#52
2006-05-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 15:02 Sent To M
Notes
2006-03-06 00:00:00TAKEN FROM "COMM" BD BY SAMANTHA.
 ROUTED TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 11:39 Sent To  
Notes
2006-02-22 00:00:00TO "COMM" BD#14
2006-01-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-14 Cont ID  
Sent By adarroug Date 2005-09-14 Time 17:17 Rev Time 0.00
Received By mmclean Date 2005-08-09 Time 16:43 Sent To  
Notes
2005-08-10 00:00:00TO "COMM" BD#8
2005-08-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-24 Cont ID  
Sent By hmoser Date 2007-04-24 Time 16:03 Rev Time 0.00
Received By hmoser Date 2007-04-24 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-18 Cont ID  
Sent By tgordon Date 2006-07-18 Time 08:40 Rev Time 1.15
Received By tgordon Date 2006-07-18 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By tgordon Date 2006-03-06 Time 16:03 Rev Time 0.25
Received By tgordon Date 2006-03-06 Time 16:03 Sent To  
Notes
2006-03-06 00:00:00*** DENIED ***
 1) PLEASE SHOW ON MECHANICAL PLANS THE
 MAIN AIR RETURN TO THE AIR HANDLERS,
 DUCT AND GRILL (WITH SIZES).
  
 2) PLEASE NOTE ON MECH. PLANS IF A/C
 EQUIPMENT IS NEW OR EXISTING. IF NEW
 PROVIDE SEER, OR EER ON PLANS
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-26 Cont ID  
Sent By hmoser Date 2005-08-26 Time 14:42 Rev Time 0.00
Received By hmoser Date 2005-08-26 Time 14:02 Sent To  
Notes
2005-08-26 00:00:00NO MECHANICAL PLANS.HM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 10:09 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 09:51 Sent To  
Notes
2006-07-02 00:00:00RE-SUB
 2 D/F ADDED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-02 Cont ID  
Sent By pschmitz Date 2006-03-02 Time 11:10 Rev Time 0.00
Received By pschmitz Date 2006-03-02 Time 11:10 Sent To  
Notes
2006-03-02 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODE PLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 SEE PREVIOUS COMMENTS NOT ADDRESSED.
  
  
 DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. ALTHOUGH NO PLUMBING IS SHOWN ON THE
 PLANS, MINIMUM FACILITIES SHALL BE SHOWN
 ON THE PLANS. 2 DRINKING FOUNTAINS ARE
 REQUIRED PER TABLE 403.1. ALSO SEE
 SECTION 410.1. PLEASE INDICATE ON THE
 FLOOR PLANS THE LOCATION OF THE REQUIRED
 FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 10:22 Rev Time 0.51
Received By kstevens Date 2005-09-10 Time 10:22 Sent To  
Notes
2005-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. ALTHOUGH NO PLUMBING IS SHOWN ON THE
 PLANS, MINIMUM FACILITIES SHALL BE SHOWN
 ON THE PLANS. 2 DRINKING FOUNTAINS ARE
 REQUIRED PER TABLE 403.1. ALSO SEE
 SECTION 410.1. PLEASE INDICATE ON THE
 FLOOR PLANS THE LOCATION OF THE REQUIRED
 FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-05 Cont ID  
Sent By mmclean Date 2006-07-05 Time 09:27 Rev Time 0.00
Received By mmclean Date 2006-07-05 Time 09:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-06-20 Cont ID  
Sent By mmclean Date 2006-06-20 Time 14:50 Rev Time 0.00
Received By mmclean Date 2006-06-20 Time 14:50 Sent To  
Notes
2006-06-20 00:00:00DENIED,
 1. THE INFORMATION ON SURVEY MUST BE
 PROVIDED IN INK ONLY AND MARKED
 CORRECTLY.
  
 NOTE:THE FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENT STATES IN SEC
 106.13 QUALITY OF BUILDING PLANS -
 BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD
 RETENTION PROGRAM.THIS POLICY MAY
 INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS
 RELATED TO RECODS MANAGEMENT.
  
 2. MUST PROVIDE THE SIDE SETBACK OF THE
 PROPOSED STAIR/S.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-02-27 Cont ID  
Sent By mmclean Date 2006-02-27 Time 14:08 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 17:56 Sent To  
Notes
2006-02-27 00:00:00DENIED,
 1. THE SURVEY PROVIDED DOES NOT PROVIDE
 THE INFORMATION NEEDED TO COMPLETE
 REVIEW ON PLANS.
 2. MUST PROVIDE A COMPLETE SITEPLAN OF
 THE PROPERTY WITH SETBACKS, SHOWING THE
 STAIRS & ADDITION WITH SETBACKS
 3. FLOOR PLANS SHOWS STAIRS (2) NEED TO
 SEE THE SETBACK OF THE STAIRS FROM
 PROPERTY LINE.
 4. IF THE ADDITION OF OFFICE DOES NOT
 CHANGE THE FOOTPRINT, PLEASE INDICATE SO
 ON THE SITEPLAN.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By mmclean Date 2005-09-14 Time 17:15 Rev Time 0.00
Received By mmclean Date 2005-09-14 Time 17:15 Sent To  
Notes
2005-09-14 00:00:00DENIED,
 1. NEED TO PROVIDE A COMPLETE SITEPLAN
 OR CURRENT SURVEY.
 2. NEED TO SHOW THE CHANGE IN FOOTPRINT
 ON ADDITION (EXTERIOR STAIRS)THAT
 AFFECTS THE SETBACKS OR ENCROACHMENT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy