Plan Review Details - Permit 05080148
Plan Review Stops For Permit 05080148
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-28 Cont ID  
Sent By rmcdouga Date 2006-03-28 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2006-03-28 Time 10:15 Sent To  
Notes
2006-03-28 00:00:00REVISED PRODUCT APPROVALS FOR ENTRY
 DOORS TO WOOD DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By rmcdouga Date 2005-11-09 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2005-11-09 Time 10:33 Sent To  
Notes
2005-11-09 00:00:00BUILDING PROVISO
  
 ANY FUTURE SUBMITALS FOR PERMIT OR
 REVISIONS WILL BE DENIED IF THE TWO
 ITEMS ADDRESSED BY THE ARCHITECT'S
 LETTER DATED 10/12/05 ARE NOT CORRECT ON
 THE DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-05 Cont ID  
Sent By rmcdouga Date 2005-10-05 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2005-10-05 Time 16:05 Sent To  
Notes
2005-10-05 00:00:00DENIED
  
 1) THE ARCHED FIXED GLASS WINDOW IN THE
 MASTER BATH IS 42 SQFT (6' X 7'). THE
 LARGEST AREA ALLOWED BY THE PRODUCT
 APPROVAL SUBMITTED IS 32 SQFT.
  
 2) THE NOTE ON A1 OF THE PLANS FOR THE
 TRANSOM ABOVE THE GREAT ROOM FRENCH
 DOORS SPECIFIES NOA 03-0508.01. THIS
 WINDOW IS SMALL MISSLE IMPACT RATED ONLY
 AND IS REQUIRED TO BE SHUTTERED IF BELOW
 30 FEET. REVISE PLANS IF LARGE MISSLE
 IMPACT IS DESIRED.
  
 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 ANCHOR BOLTS FOR THE BEAM HANGER IN
 DETAIL R ON A6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By rmcdouga Date 2005-08-24 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2005-08-24 Time 11:30 Sent To  
Notes
2005-08-24 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE TRUSS CONNECTOR LOCATIONS
 ON THE ROOF FRAMING PLAN FOR THE
 CONNECTORS LISTED IN THE ANCHOR SCHEDULE
 ON A3.
  
 3) TRUSS ANCHOR NOTE G REFERS TO DETAIL
 D6 ON PAGE A6. THAT DETAIL IS A TYPICAL
 WALL SECTION. PLEASE CORRECT.
  
 4) THE ARCHED FIXED GLASS WINDOW IN THE
 MASTER BATH IS 42 SQFT (6'X 7') AND THE
 LARGEST WINDOW IN THE PRODUCT APPROVAL
 IS 32 SQFT. SUBMIT APPROPRIATE PRODUCT
 APPROVAL.
  
 5) THE NOTE ON A1 FOR THE TRANSOM ABOVE
 THE GREAT ROOM FRENCH DOORS SPECIFIES
 NOA 03-0508.01. THIS PRODUCT APPROVAL
 WAS NOT SUBMITTED. PLEASE CORRECT.
  
 6) SPECIFY THE CONNECTIONS OF THE PORCH
 GIRDERS AND ENTRY PORCH BEAMS AT
 EXTERIOR MASONRY WALLS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 15:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 08:00 Rev Time 0.00
Received By dpalmer Date 2007-01-05 Time 07:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-12-18 Cont ID  
Sent By dpalmer Date 2006-12-18 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2006-12-18 Time 19:42 Sent To PC
Notes
2006-12-18 19:56:00** UNSAT **
  
 1) NOTE: PLEASE SEE HAND DRAWN CHANGES AND WHITE OUT IS
 NOT PERMITTED ON PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ARCHITECT OR ENGINEER. PLEASE SEE FLORIDA
 STATUTES 481.221, 471.025.
  
 2) NOTE: PLEASE SEE THE VALUE FOR ALL LOW VOLTAGE SOUND
 SYSTEMS/ HOME THEATRE AND LIGHTING CONTROLS WAS NOT
 INCLUDED IN BASE PERMIT FEES FOR HOME. PLEASE SEE FBC
 TABLES AND FEES BASED ON THIS HOME DO NOT INCLUDE THESE
 SPECIALIZED SYSTEMS. PLEASE ADJUST VALUE AND PAY THE
 ADDITIONAL FEES. PLEASE KNOW, A VALUE MAY BE ASSESSED
 BY THE REVIEW STAFF BASED ON FBC AND GUIDES ADOPTED
 INTO 108.3 OF THE FBC ADMIN SECTION.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-19 Cont ID  
Sent By btrobaug Date 2006-05-19 Time 14:18 Rev Time 0.50
Received By btrobaug Date 2006-05-19 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 19:08 Sent To PC
Notes
2006-03-23 00:00:00REDLINED:
 CONDUCTORS SHOWN ON PANEL "A" FOR POOL
 PANEL ARE NOT CORRECT. PLEASE SEE
 FEEDERS SHOWN ON RISER, THESE ARE OK.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 13:19 Rev Time 0.50
Received By dpalmer Date 2005-11-30 Time 13:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-11-08 Cont ID  
Sent By dpalmer Date 2005-11-08 Time 13:58 Rev Time 0.25
Received By dpalmer Date 2005-11-08 Time 13:46 Sent To B
Notes
2005-11-08 00:00:00PLEASE SEE SMAE NOTES FROM PREVIPUS
 REVIEW. CALLED CONTRACTOR, WAITING FOR
 NEW SHEETS FOR ELEC, PLANS SENT TO BLDG.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 18:43 Rev Time 0.50
Received By dpalmer Date 2005-09-27 Time 18:06 Sent To B
Notes
2005-09-27 00:00:00********UNSAT **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND NEW NOTES.
  
  
  
 1)NOTE: PLEASE RE-FIGURE LOAD
 CALCULATIONS AFTER SEEING FOLLOWING
 NOTES.220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT ON 2
 FT OF WALL IN BEDRM #2 STILL MISSING.
 210.52
  
 3)NOTE: PLEASE SEE ALL DEDICATED
 CIRCUITS LISTED IN "THEATRE" ARE STILL
 NOT SHOWN ON PANEL SCHEDULES OR FIGURED
 INTO LOAD CALCUALTIONS, PLEASE SEE
 NUMEROUS DEDICATED CIRCUITS??
 215.5
  
 4)NOTE: PLEASE SEE MEANS OF EGRESS
 LIGHTING FOR THEATRE IS NOT CLARIFIED ON
 PLANS???
 210.70, LS 101 7.8
  
 5)NOTE: PLEASE SEE BATH GFI CIRCUIT ON
 PANEL SCHEDULE SHOWN AS #14 AWG ON 15A
 OCP.
 210.11C3, 20A #12.
  
 PLEASE KNOW, THE ABOVE ITEMS MAY BE
 SET-UP AS A "PROVISO " IF PLANS PASS ALL
 OTHER TRADES. IF PLANS COME BACK FOR ANY
 COMMENTS , PLEASE ADDRESS AT THIS TIME.
  
 PLEASE CALL, IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By dpalmer Date 2005-08-17 Time 06:33 Rev Time 1.00
Received By dpalmer Date 2005-08-16 Time 21:25 Sent To M
Notes
2005-08-17 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE LOAD CALCUALTIONS,
 PLEASE SEE LOAD ON PANEL "A" IS SHOWN
 HIGHER THAN PANEL "B", HOWEVER FINAL
 AMERAGE IS LOWER?
 PLEASE GO OVER LOAD CALCS FOR BOTH WITH
 THE ADDED LOAD OF THE RECESSED LTS.
 PLEASE SEE NEXT COMMENT ALSO.
 215.5
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES/LOAD
 CALCULATIONS DO NOT INCLUDE THE A/C
 SYSTEM #3 AS SHOWN ON PLANS.?
 PLEASE INCLUDE AND ADJUST LAOD
 CALCULATIONS.
 215.5,220
  
 3)NOTE: PLEASE SEE NEW THEATER IS NOT
 SHOWING ANY MEANS OF EGRESS LIGHTING FOR
 ROOM? 210.70,LS 101 5-8
 PLEASE ALSO SEE THERE ARE NUMEROUS
 DEDICATED RECEPTS, CIRCUITS SHOWN ON
 PLANS, HOWEVER THESE ARE NOT SHOWN IN
 LOAD CALCULATIONS/PANEL SCHEDULE?
 PLEASE SEE POPCORN MAKER? ETC.
 1440W FOR 15A CIRCUITS, 1920W FOR 20A
 CIRCUITS.
 PLEASE ADJUST LOAD CALCULATIONS.
 215.5,220
  
 4)NOTE: PLEASE SEE SMOKE DETECTOR FOR
 MASTER BEDRM MUST BE MOVED INTO BEDRM
 AREA. PLEASE SEE NFPA-72 2-3 FOR
 LOCATION PLACEMENT.
 MUST BE LOCATED WITHIN 3' ON A SLOPED
 CEILING TO THE PEAK.
 PLEASE ALSO SEE IF WALL MOUNTED, ETC
 MUST BE 4-12" OF CEILING, ALSO 18" OF
 TOTAL CEILING HEIGHT.
  
 5)NOTE: PLEASE SEE MISSING RECEPT(S) PER
 210.52 BEDRM #2
  
 6)NOTE: PLEASE SEE CIRCUIT FOR WHIRLPOOL
 GFI IS SHOWN ON PANEL/LOAD CALCS,
 HOWEVER THIS GFI/RECEPT COULD NOT BE
 LOCATED ON PLANS.
 PLEASE SHOW.
  
 7)NOTE: PLEASE VERIFY LOADS/MOTOR LOADS
 FOR GARAGE DOOR OPENERS, PLEASE SEE ALL
 THREE MOTORS ARE SHOWN ON ONE CIRCUIT
 WITH ONLY A 400W LOAD.
 PLEASE SEE 430.53 FOR MULTIPLE MOTORS ON
 ONE CIRCUIT.
 PLEASE VERIFY HP RATING ETC OF MOTORS TO
 BE USED.
  
 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS SURVEY IS REQUIRED TO HAVE THE
 ORIGINAL SIGNATURE AND RAISED SEAL OF
 SURVEYOR. FS 472.025, FAC 61G17-17.002
 COPY.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO SUBMIT ONE SET OF ALL
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-08-16 00:00:00PLANS BE BE UNSAT.
 NOTES TO FOLLOW.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 11:19 Sent To E
Notes
2007-02-16 11:19:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 12:03 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 12:03 Sent To E
Notes
2007-01-03 12:05:04TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:44 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:43 Sent To E
Notes
2006-12-17 13:44:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 14:31 Sent To E
Notes
2006-05-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 14:34 Sent To E
Notes
2006-03-23 00:00:00TP DP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 12:54 Sent To B
Notes
2006-03-23 00:00:00TO RM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-20 Cont ID  
Sent By adarroug Date 2006-01-20 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-01-20 Time 13:40 Sent To M
Notes
2006-01-20 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 13:42 Sent To E
Notes
2005-11-29 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 15:50 Sent To I
Notes
2005-10-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 18:30 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 18:30 Sent To E
Notes
2005-09-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 13:36 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 13:36 Sent To E
Notes
2005-08-16 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-24 Cont ID  
Sent By rmcdouga Date 2005-08-24 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2005-08-04 Time 11:44 Sent To  
Notes
2005-08-04 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-26 Cont ID  
Sent By tgordon Date 2006-01-26 Time 08:30 Rev Time 0.30
Received By tgordon Date 2006-01-26 Time 08:30 Sent To  
Notes
2006-01-26 00:00:00REV. TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-23 Cont ID  
Sent By prafter Date 2005-08-23 Time 10:28 Rev Time 1.00
Received By prafter Date 2005-08-23 Time 10:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-20 Cont ID  
Sent By jleech Date 2005-08-20 Time 07:08 Rev Time 0.33
Received By jleech Date 2005-08-20 Time 07:08 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 16:36 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 16:36 Sent To I
Notes
2005-08-11 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.