Plan Review Details - Permit 05080080
Plan Review Stops For Permit 05080080
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-05-29 Cont ID  
Sent By lmartine Date 2007-05-29 Time 14:25 Rev Time 0.00
Received By lmartine Date 2007-05-29 Time 14:23 Sent To  
Notes
2007-05-29 14:24:46RESTAMP PLANS AND ISSUE NEW PERMIT CARD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-05-15 Cont ID  
Sent By lmartine Date 2007-05-15 Time 16:25 Rev Time 0.00
Received By lmartine Date 2007-05-15 Time 15:22 Sent To  
Notes
2007-05-15 17:31:15RE-STAMP SUBMITTAL COMMENTS
  
  
 1)
 SHEET A-1 , WALL SECTION DETAILS #5, #6 ARE NOT ON THE
 APPROVED RECORDED SET. ALSO THE FOUNTAIN SHOWN ON THE
 NORTH WALL HAS BEEN OMITTED ACCORDING TO OUR OFFICE
 COPY.
  
 2)
 SHEET A-4 , SHOWS THE INSTALLATION OF SOLAR PANELS ,
 ALSO NOT ON OUR OFFICE COPY.
  
 3)
 SHEET S-4 WAS NOT PROVIDED WITH YOUR PACKAGE.
  
 4)
 SHEET S-05 , IS A NEW SHEET THAT IS NOT IN OUR
 APPROVED SET.
  
 5)
 SHEET E-1 , SHOW'S NEW REVISION #7 FOR SOLAR PANELS.
  
 6)
 SHEET P-1 , PLEASE INCLUDE ALL RED LINES AND REVISION
 WITH YOUR SUBMITTAL.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-02-20 Cont ID  
Sent By rnuquist Date 2007-02-20 Time 19:08 Rev Time 0.00
Received By rnuquist Date 2007-02-20 Time 19:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 16:52 Rev Time 0.60
Received By alange Date 2006-09-05 Time 16:52 Sent To  
Notes
2006-09-05 00:00:00DOOR REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 13:52 Rev Time 0.50
Received By alange Date 2006-05-31 Time 13:52 Sent To  
Notes
2006-05-31 00:00:00REVISED STRUCTURAL DETAILS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-04 Cont ID  
Sent By alange Date 2006-05-04 Time 08:52 Rev Time 0.50
Received By alange Date 2006-05-04 Time 08:52 Sent To  
Notes
2006-05-04 00:00:00FOUNDATION REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 13:32 Rev Time 1.25
Received By alange Date 2005-12-15 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-15 Cont ID  
Sent By alange Date 2005-11-21 Time 07:31 Rev Time 2.50
Received By alange Date 2005-11-21 Time 07:30 Sent To  
Notes
2005-11-21 00:00:00DENIED
  
  
 3.PROPERTY IS IN AN AREA OF
 QUESTIONABLE SOILS.SUBMIT A SOILS
 REPORT INCLUDING FOOTING AND FOUNDATION
 RECOMMENDATIONS.
  
  
 6.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR STRAPS AND TIE-DOWNS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By alange Date 2005-09-06 Time 08:54 Rev Time 4.50
Received By alange Date 2005-09-02 Time 16:38 Sent To  
Notes
2005-09-06 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS FOR
 SKYLIGHT.
 PRODUCT APPROVALS SUBMITTED SHALL HAVE
 THE FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.SUBMIT SPECS FOR SECOND FLOOR GAS
 GRILL AND HOOD THAT WILL BE USED WITH
 IT.
  
 3.PROPERTY IS IN AN AREA OF
 QUESTIONABLE SOILS.SUBMIT A SOILS
 REPORT INCLUDING FOOTING AND FOUNDATION
 RECOMMENDATIONS.
  
 4.SHOW BOTTOM CORD TRUSS LOADS FOR
 ATTIC STORAGE AREA.
  
 5. SHOW HOW SMOKE DETECTORS WILL COMPLY
 WITH FBC 905.2 SEE ALSO ELECTRICAL
 REVIEW NOTE NUMBER 16.
  
 6.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR STRAPS AND TIE-DOWNS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 18:21 Sent To PC
Notes
2006-12-06 18:47:23REV OK, REDLINED ADDRESS AS TITLE BLOCK IS STILL
 SHOWING 6425 AND SHOUDL BE 6429

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 11:55 Sent To PC
Notes
2006-11-28 13:04:05**** UNSAT ****
 REVISION #7
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS PLANS ARE
 COMING BACK WITH SOME REVISIONS; HOWEVER THERE ARE
 ITEMS NOW SHOWN AGAIN WHICH WERE COMMENTED ON AND
 CORRECTED FROM 2 REVIEWS AGO.
 PLEASE GO OVER PLANS CAREFULLY AND PLEASE CALL IF THERE
 ARE ANY QUESTIONS OR COMMENTS BASED ON THE FOLLOWING
 NOTES TYPED FOR THIS REVIEW.
 THIS IS REVISION NUMBER #7, UNLIKE THE PLANS WHICH
 INDICATE REVISION #5.
  
 1) NOTE: PLEASE KNOW ONE ITEM WHICH HAS BEEN GETTING
 REDLINED ON PLANS FROM THE PREVIOUS REVIEWS INCLUDING
 THE JOBSITE PLANS IS THE ADDRESS. PLEASE SEE THE
 ADDRESS IN OUR SYSTEM AND THE PERMITTED ADDRESS IS
 "6429", WHERE THE PLANS INDICATE "6425". THIS REVIEWER
 HAS BEEN CHANGING THIS BY HAND ON PLANS TO HELP IN
 GETTING THE REVISIONS DONE, HOWEVER AS PLANS ARE COMING
 BACK FOR OTHER COMMENTS PLEASE ADJUST THIS AT THIS
 TIME.
 PLEASE DO NOT KEEP SUBMITTING PLANS WITH THE OLD
 ADDRESS.
 FAC 61G1-16.004
  
 2) NOTE: PLEASE SEE THE POOL PANEL IS NOW MISSING FROM
 THE PLANS??? PLEASE SEE THE RISER STILL SHOWS THIS
 PANEL AND THERE IS A PANEL SCHEDULE SUBMITTED FOR THIS,
 YET PLANS WHICH PREVIOUSLY SHOWED THIS PANEL NO LONGER
 DOES?
 PLEASE SHOW.
 110.26, 240.24 ETC
 FBC ADMIN SECTION 106.1.2
  
 3) NOTE: PLEASE SEE PLANS NOW REPLACE THE DESIGNATION
 FOR WHAT USED TO BE THE SUB PANEL "B" TO NOW
 DESIGNATION FOR A SUB PANEL "E". PLEASE SEE THE RISER
 AND THE PANEL SCHEDULES DO NOT CORRELATE WITH THIS.
 IS THERE ANOTHER PANEL??
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE SUB PANEL B HAS NOW CHANGED THE
 FEEDERS ON THE RISER; HOWEVER THE PANEL SCHEDULE "A"
 STILL SHOWS #4'S??
 PLEASE CORRELATE THE SIZE OF THE FEEDERS AND VERIFY THE
 PANEL SIZE AS IT IS NOT KNOW THAT A 70A PANEL IS MADE?
 PLEASE KNOW IF THIS IS A 100A MLO, IT IS OK SHOWING A
 70A BREAKER IN PANEL ?A? FEED TO THIS PANEL.
 PLEASE CORRELATE AND SIZE CORRECTLY.
 408.4, 310.16, ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE AHU WHICH HAS NOW CHANGED TO 8KW,
 YET STILL SHOWS 10KW? PLEASE CORRELATE AND ADJUST THE
 OVER CURRENT PROTECTION, CONDUCTOR SIZES ETC AS NEED.
 310.16, 424.3B, 240.4 ETC
  
 6) NOTE: PLEASE SEE ONE OF THE WATER HEATERS WHICH WERE
 SHOWN AS GAS ON THE PREVIOUS PLANS, HAVE NOW CHANGED TO
 ELECTRIC SHOWING A 4.5KW LOAD YET STILL SHOW FEEDING
 THIS WATER HEATER WITH A SINGLE POLE 20A CIRCUIT?
 PLEASE ADJUST AND CORRELATE. IF SOLAR THEN PLEASE
 SUBMIT THE SPEC/INFORMATION FOR THIS AS THIS IS THE
 FIRST PLAN WHICH INDICATES ANY SOLAR WATER HEATER.
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THIS
 EQUIPMENT. 110.3, 90.7
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE NOTES WHICH WERE ON PREVIOUS PLANS
 WHICH MENTIONED THE SMOKE DETECTORS BEING PART OF THE
 LOW VOLTAGE SECURITY, YET THESE NOTES HAVE BEEN REMOVED
 FROM BOTH SHEETS? PLEASE CLARIFY. IF THIS IS INDEED THE
 CASE PLEASE REPLACE NOTES, IF NOT PLEASE INDICATE AS
 "SA" FOR SMOKE ALARMS WHICH IS PART OF A 120V SYSTEM
 WHICH CONTAINS AN DETECTION AND ALARM IN THE SAME UNIT
 DEVICE.
 PLEASE SEE NFPA-72 DEFINITIONS FOR THIS.
  
 **** AS MENTIONED ON ALL PREVIOUS REVIEWS, IF THERE ARE
 ANY QUESTIONS, COMMENTS OR IF ANY OF THE COMMENTS ARE
 CONFUSING OR NOT UNDERSTOOD IN ANY WAY, PLEASE CALL.
 TO DATE THIS OFFICE HAS NOT RECEIVED ANY CALLS FROM THE
 ARCHITECT OF RECORD OVER THE LAST 6 OR SO REVIEWS WHICH
 HAVE BEEN DONE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 08:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 16:43 Sent To PC
Notes
2006-11-02 18:59:21******** UNSAT *********
  
 1) NOTE: PLEASE SEE PLANS STILL INDICATE A PANEL "E"
 AND RISER DOES NOT . PLEASE SEE COULD NOT LOCATE THE
 POOL PANEL?
 PLEASE CORRELATE AND SHOW.
 PLEASE SEE RISER AND PANEL SHOWS SUB PANEL "B" BEING
 FED FROM MAIN PANEL "A"WITH A 2P-70A AND #4, AND
 PLEASE SEE RISER SHOWS #6'S. PLEASE SEE SUB PANEL "B"
 IS SHOWN AS 70A MLO, HOWEVER THIS WOULD BE A 100A MLO
 WITH THE 70A BREAKER FROM THE MAIN PANEL "B".?
  
 2) NOTE: PLEASE SEE JACUZZI TUB WHICH HAS NOW REMOVED
 CIRCUITING HOWEVER ALSO REMOVED GFI INDICATION FOR
 PROTECTION. PLEASE SEE SYMBOL ON PLANS STILL INDICATES
 A 220V JACUZZI PER THE SYMBOL LEGEND?
 PLEASE CORRELATE IF 220V OR 120V AND INDICATE THE GFI
 PROTECTION EITHER AT THE JACUZZI TUB UNIT OR THE PANEL
 BREAKER.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE(S) WHICH STILL
 INDICATE 20A BREAKERS ON #14 CONDUCTORS?
 240.4, 310.16
  
 4) NOTE: PLEASE SEE SA'S SHOULD ALSO BE NOTED ON THE
 ARC FAULT NOTE. PLEASE SEE NOTE SHOWS A "&" BUT THE
 SA'S SD'S WAS REMOVED ?
 210.12
  
 5) NOTE: PLEASE SEE AHU#2 SHOWS 10KW AND 8KW FOR LOAD
 ON THE SAME UNIT, PLEASE SEE 424.3B IN EITHER CASE AND
 CORRELATE WITH THE LOAD CALCULATIONS.
  
 6) NOTE: PLEASE SEE COUNTER SPACE RECEPT MISSING GFI
 DESIGNATION. ()THIS COULD HAVE BEEN REDLINED) HOWEVER
 PLEASE CORRECT AT THIS TIME.
 210.8A6
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 16:46 Sent To PC
Notes
2006-10-13 18:48:57****UNSAT ****
  
 1) NOTE: PLEASE CORRELATE RISER , PLANS AND PANEL
 SCHEDULE SUBMITTED. PLEASE SEE PANEL "E" WAS NOT SHOWN,
 HOWEVER TWO 200A PANEL "A"'S ARE??
 FBC106.1.2 PLEASE KNOW AT THIS TIME SOME REVIEW OF
 ITEMS CAN NOT BE VERIFIED FOR CODE COMPLIANCE. PLEASE
 SEE THAT IS IS BEING "ASSUMED" THAT THE SECOND PANEL
 "A" IS ACUTALLY PANEL "E", YET THIS PANEL LOAD DOES NOT
 CORRELATE WITH LOAD ON PANEL "B" WHICH IS NOTED AS
 FEEDING "E". PLEASE ALSO SEE THIS PANEL IS BEING SHOWN
 AS 200A.
  
 2) NOTE: PLEASE CORRELATE PANEL SCHEDULES WITH PLANS
 AND CIRCUITING. PLEASE SEE THAT THERE ARE NUMEROUS
 ITEMS WHICH DO NOT MATCH. PLEASE SEE MANY OF THESE
 ITEMS ARE REDLINED ON PLANS HOWEVER A FEW ARE NOTED
 BELOW TO SEE WHAT IS BEING MENTIONED.
 PLEASE SEE JACUZZI/WHIRLPOOL TUB, SHOWS 220V AND ON TWO
 PHASES AS 220V, YET SCHEDULE SHOWS 1-POLE?
 PLEASE SEE B-24 WHICH IS SHOWN AS ICE MAKER, YET PLANS
 ALSO SHOW THIS FEEDING FAN IN OFFICE.
 PLEASE SEE B-29 WHICH IS SHOWN FEEDING FAN ALSO FEEDS
 THE SAME JACUZZI CIRCUIT ABOVE.
 PLEASE SEE A-15 WHICH FEEDS BATH(S) RECEPTS ALONG WITH
 NUMEROUS RECEPTS IN LIVING ROOM AND GARAGE. (PLEASE SEE
 210.11C3,AS THE REQUIRED DEDICATED BATH(S) CIRCUIT(S)
 ARE NOT PERMITTED TO FEED ANY OTHER AREAS.
 PLEASE SEE SMOKE ALARMS BEING SHOWN ON MORE THAN ONE
 CIRCUIT IS IS NOT POSSIBLE AS THESE ARE REQUIRED TO BE
 WIRED "INLINE". IFON MORE THAN ONE CIRCUIT THIS WOULD
 NOT WORK OR CREATE 220V TO A 120 UNIT.
 PLEASE SEE B-30, SHOWS WINE UNIT ON PLANS, YET B-30 IS
 PART OF THE CIRCUIT WHICH IS SHOWN FEEDING PANEL "E"
 PLEASE SEE WH AND CENTRAL VAC BEING SHOWN ON THE SAME
 CIRCUIT. A-18.
 ETC.
  
 3) NOTE: PLEASE SEE 20A BREAKER(S) ON CONDUCTORS ONLY
 RATED FOR 15A'S PER 310.16. PLEASE SEE 240.4.
  
  
 ** PLEASE KNOW, AS THERE ARE MANY ITEMS WHICH NEED
 CORRELATING , PLEASE BE SURE TO CALL IF THERE ARE NAY
 QUESTIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-09 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 12:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-14 Cont ID  
Sent By dpalmer Date 2005-12-14 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2005-12-14 Time 14:25 Sent To B
Notes
2005-12-14 00:00:00**** UNSAT 3RD REVIEW ****
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND NEW NOTES DUE TO CHANGES IN PLANS.
  
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW WHICH REQUESTED TO SHOW THE
 POWER/OUTLET LOCAION ON PLANS FOR
 JACUZZI TUB. THIS WAS DONE , HOWEVER NOW
 THIS ISNOW SHOWING CIRCUITING ON PLANS
 FOR A 2-POLE UNIT(CIRCUITS 35 AND 37),
 PLEASE SEE PANEL SCHEDULE SHOWS THIS A A
 1-POLE 30A.
 PLEASE CORRELATE
  
 2)NOTE: PLEASE SEE NOTE #21 FROM
 PREVIOUS REVIEWS WHICH REQUESTED THE
 NEED TO CORRELATE THE RISER DIAGRAM,
 PANEL SCHEDULES ETC.
  
 A) PLEASE SEE RISER DIAGRAM STILL SHOWS
 TWO 200A DISCONNECTS WITH 200A FUSES,
 ALTHOUGH PANEL SCHEDULES ARE SUBMITTED
 INDICATING THESE AS 200A PANELS
 ("C"&"D") WITH NO INDICATION OF HAVING
 MCB'S???
  
 B)PLEASE ALSO SEE RISER INDICATES PANELS
 "A" AND "B" AS MAIN BREAKER PANELS, AND
 THESE PANEL SCHEDULES SHOWS MLO (MAIN
 LUG ONLY)??
  
 C)PLEASE NOW ALSO SEE PANEL SCHEDULES C
 AND D, INDICATE #2 FOR THE 200A FEED TO
 PANELS A AND B. PLEASE SEE 240.4, AND
 310.15B6/16 FOR THE MIN 2/0.
  
 3)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
 REVIEW WHICH STATED THE SD'S WERE ON
 MORE THAN ONE CIRCUIT A-19 AND B-13.
 PLEASE SEE CIRCUITING WAS REVISED ON 2ND
 FLR TO CIRCUIT A-24, HOWEVER FIRST FLR
 IS SHOWN AS A-13??
 ** PLEASE KNOW, THE SD'S ARE REQUIRED TO
 BE WIRED "INLINE" AND CAN NOT BE ON TWO
 SEPARATE CIRCUITS. THIS WOULD BE SENDING
 220V TO THE 120V SD"S.
 PLEASE ALSO SEE PLANS NOW HAVE A NOTE
 ADDED FOR SD'S WHICH REFERENCE THE OLD
 NFPA-72 8-1
 PLEASE SEE AS OF JAN 1ST, 2005, NFPA-72
 HAS CHANGED TO THE 2002 EDITION AND
 CODES FOR SD'S REFERENCE SHOULD BE
 11.5.1.1.
  
 4)NOTE: PLEASE SEE PREVIOUS NOTE #5
 WHICH MENTIONED CIRCUITING FOR MASTER
 BATH WAS IN ERROR. PLEASE SEE CIRCUITING
 FOR THIS MASTER BATH HAS NOW BEEN
 REVISED, HOWEVER PLEASE SEE PANEL
 SCHEDULE NOW MENTIONS THIS AS ARC FAULT
 AND ON THE SAME CIRCUIT AS THE MASTER
 BEDROOM.
 PLEASE SEE 210.52D,210.11C3
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 THE DESIGN PROFESSIONAL AND REPEAT
 COMMENTS FOR CODE COMPLIANCE. IF PLANS
 COME BACK FOR REVIEW WITH ANY OF THE
 SAME CODE COMPLIANCE COMMENTS NOT
 ADDRESSED THIS OFFICE WILL HAVE NO
 CHOICE BUT TO ISSUE A 4X THE FEE FOR
 SAID REVIEW COMMENTS.
 THIS AMOUNT WOULD BE $12,600.00.
 ** TO THIS DATE NO ONE HAS CALLED TO GO
 OVER ANY COMMENTS IF THERE WERE ANY
 QUESTIONS, PLEASE KNOW IT IS STRONGLY
 SUGGESTED THAT A MEETING BE HELD TO GO
 OVER COMMENTS AND PLANS BEFORE
 RE-SUBMITTING PLANS FOR REVIEW AND ANY
 POSSIBLITY OF THE ABOVE BEING
 IMPLEMENTED.
  
 PLEASE DO NOT HESITATE IN CONTACTING
 MYSELF TO MEET AND/OR GO OVER THE ABOVE
 REFERENCED COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-09 Cont ID  
Sent By dpalmer Date 2005-11-09 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2005-11-09 Time 17:34 Sent To P
Notes
2005-11-09 00:00:00***** UNSAT ****
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH SOME COMMENTS DUE TO CHANGES ETC.
  
 1)NOTE: PLEASE INDICATE THE POWER OUTLET
 LOCATION FOR JACUZZI TUB AT TUB
 LOCATION.
  
 2)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULES.
 PLEASE KNOW THIS IS PART OF NOTES #5AND
 #7 FROM PREVIOUS REVIEW.
 PLEASE SEE RISER INDICATES 200A FUSED
 DISCONNECTS, HOWEVER PLANS AND PANEL
 SCHEDULES SEEM TO INDICATE THESE AS MCB
 PANELS? PLEASE ADJUST.
 PLEASE ALSO SEE WHAT APPEARS TO BE TWO
 PANELS OUTSIDE AND TWO INSIDE ARE ALL
 LABELED AS "A"S AND "B". PLEASE SEE
 MAYBE THESE SHOULD BE"A" AND "A1" AND
 "B" AND "B2" OR SOME OTHER METHOD OF
 LABELING EACH ONE SPECIFIC.
 PLEASE SEE PREVIOUS NOTES MENTIONED THE
 LOAD ABOVE THE 150A PANELS SHOWN,
 HOWEVER PANELS FOR "B" AND "B" ARE STILL
 SHOWN AS 150A WITH LOADS EXCEEDING THIS
 RATING.
 PLEASE SEE RISER HOWEVER SHOWS 200A'S AS
 ADJUSTED FROM NOTES.
 PLEASE CORRELATE ALL.
 215.5,240.4,310.16 ETC.
  
 3)NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING RECEPT FOR 2' OF WALL. LIV RM
  
 4)NOTE: PLEASE SEE SD'S ON FIRST FLR ARE
 CIRCUITED TO A-13, HOWEVER 2ND FLR MOST
 DO NOT INDICATE THE CIRCUIT, ALTHOUGH
 ONE AT MASTER BEDRM SEEMS TO SHOW
 "B-13",
  
 5)NOTE: PLEASE SEE MASTER BATH CIRCUIT
 AS A-19, YET PANEL SCHEDULE SHOWS AS
 SPARE.
 PLEASE ALSO SEE ICE MAKER SHOWN AS WINE
 COOLER, BATH CIRCUIT B-21 , LABEL AS
 EXTERIOR RECEPTS, ALTHOUGH THERE ARE EXT
 RECEPTS ON THE SAME B-21 CIRCUIT.
 PLEASE ADJUST AND CORRELATE AS MUCH AS
 POSSIBLE AT THIS TIME.
 IT WILL BE INEVITABLE THAT OTHER
 REVISIONS AND CHANGES DURING
 CONSTRUCTION WILL HAPPEN.
  
 ** PLEASE SEE ZONING COMMENTS, IT IS
 NOTED BY ELECTRICAL REVIEW, THAT A
 REVISED "SITE-PLAN" AND SURVEY WAS
 SUBMITTED.
 THIS DID NOT AFFECT ELECTRICAL PLANS AT
 THIS TIME.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 21:07 Rev Time 2.00
Received By dpalmer Date 2005-08-16 Time 19:22 Sent To M
Notes
2005-08-16 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE ZONING COMMENTS WHICH
 WILL HAVE A DIRECT AFFECT ON ELECTRICAL
 AND OTHER PLANS FOR HOUSE.
 PLEASE SEE BLDG REVIEW COMMENTS, SURVEY
 MUST CONTAIN AN ORIGINAL SIGNATURE FROM
 THE SURVEYOR OF RECORD. FS 472.025, FAC
 61G17-7.002
  
 2)NOTE: PLEASE SEE POOL/ POOL WIRING
 SHALL BE UNDER A SEPARATE PERMIT.
  
 3)NOTE: PLEASE CORRELATE ALL CIRCUITING
 SHOWN ON PLANS WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE SEE THERE ARE NUMEROUS
 CIRCUITS ON PLANS ETC WHICH DO NOT
 MATCH.
 PLEASE SEE COOK-TOP, TWO SETS OF
 DISHWASHER/ DISP,(NOT ON PLANS), SEE
 FLOOD LTS, WHIRLPOOL ETC.
 MMANY OF THESE HAVE BEEN REDLINED ON
 PLANS.
  
 4)NOTE: PLEASE SEE WHIRLPOOL WHICH IS
 SHOWN AS GEN LTS AND BEDRM CIRCUIT, IS
 REQUIRED TO HAVE GFI PROTECTION. PLEASE
 NOTE ON PANEL SCHEDULE, PLEASE SHOW
 LOCATION OF POWER OUTLET LOCATED AT WP
 TUB. PLEASE INDICATE REQUIRED ACCESS.
  
 5)NOTE: PLEASE SHOW LOCATIONS OF ALL
 SERVICE EQUIPMENT ON PLANS. PLEASE SEE
 METER ONLY SEEMS TO SHOW A DISC LOCATED
 NEXT TO IT.
 PLEASE SEE PANEL SCHEDULES ARE INDICATED
 AS "MAIN DISC'S" AND RISER SHOWS THESE
 AS MCB PANELS? PLEASE VERIFY IF THESE
 ARE "FEED- THRU" PANELS OR IS THERE OCP
 LOCATED IN EACH OF THESE PANELS FEEDING
 SUB-PANELS?
 215.5
  
 6)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS, FPL TO USE 1/0 ALUM? PLEASE
 VERIFY THIS WITH A FPL SERVICE PLANNER
 AS SERVICE AND LOADS PROPOSED WOULD
 EXCEED FPL STANDARDS FOR 1/0'S AND A
 400A SERVICE.
 215.5
  
 7)NOTE: PLEASE SEE MAIN/PANEL "B" LOAD
 EXCEEDS, "FUTURE" PLANNING FOR ADDED
 LOADS. PLEASE SEE PANEL "B" WILL BE
 REQUIRED TO BE UPGRADED TO A MIN OF
 200A'S. PLEASE ADJUST.
 90.4,90.8
  
 8)NOTE: PLEASE SEE AN "EUIPMENT
 GROUNDING" CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE AN EQUIPMENT GRND IS SHOWN
 FROM METER TO MAIN.
 250.6, 250.24 PLEASE REMOVE.
  
 9)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR IS TO BE A 1/0 BASED
 ON 250.66, 310.15B6
 PLEASE ADJUST, #2 SHOWN.
  
 10)NOTE: PLEASE SEE 210.52C1 AND
 REDLINED PLANS FOR GFI RECEPTS REQUIRED
 ALONG KITCHEN COUNTERSPACE.
  
 11)NOTE: PLEASE SEE 210.8, ALL RECEPTS,
 LOCATED OUTSIDE, WITIN 6' OF ANY SINK,
 ETC SHALL BE GFI/GFI PROTECTED. PLEASE
 SEE , BAR AREAS, LAUNDRY RMS ETC.
 MANY OF THESE REDLINED ON PLANS.
  
 12)NOTE: PLEASE SEE ALL RECEPT SHOWN
 WITHIN 10' OF POOL ARE NOT PERMITTED AND
 MUST BE REMOVED. PLEASE SEE 680.22
 AMIN OF (1) GFI RECEPT IS REQUIRED
 WITH 20' OF A POOL BUT MUST BE ATLEAST
 10' FROM WATERS EDGE. PLEASE SEE THERE
 ARE RECEPTS SHOWN WITHIN THE 10' WHICH
 PROMOTES A "LIFE SAFETY" SITUATION.
 PLEASE ALSO SEE 680.22B4, FOR LIGHT
 FIXTURES NOT PERMITTED WITHIN 5'OF
 POOL'S WATER EDGE. PLEASE SEE ANY LTS
 WITHIN 5-10' , MUST BE ATLEAST 5' ABOVE
 MAX WATER LINE AND MUST ALSO BE GFI
 PROTECTED. PLEASE SEE SOME FIXTURES MAY
 NOT BE INSTALLED AT ALL , AS THEY ARE
 LESS THAN 5' FROMWATER'S EDGE.
 THIS IS A "LIFE SAFETY" SITUATION.
  
 13)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS PER 2', 6', AND 12' RULE.
 PLEASE SEE MANY OF THESE AREAS ARE
 REDLINED ON PLANS AT LOCATIONS BUT NOT
 ALL.
 PLEASE SEE ATRIUM,OFFICE, FAMILY RM,
 LIVING RM ETC.
  
 14)NOTE: PLEASE SEE RECEPT SHOWN FOR
 OUTSIDE WINE CU, TO BE GFI 210.8
  
 15)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARNECE REQUIRED FOR A/C CU
 DISCONNECTS.440.11
  
 16)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4,
 NFPA-72 8-1.4.1.6.2
 PLEASE NOTE INSTALLATION PER NFPA-72
 8-1.4.2 ON PLANS.
 PLEASE SEE MANY OF THE SMOKE DETECTORS
 ARE REDLINED ON PLANS. PLEASE SEE OFFICE
 WILL BE REQUIRED TO HAVE A SD.
  
 17)NOTE: PLEASE SEE A "NOTE" ON PLANS
 E-1, MENTIONS ARC FAULT PROTECTION FOR
 RECEPTS ONLY.
 PLEASE SEE 2002 NEC 210.12,WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 "OUTLETS". PLEASE SEE E-2 SEEMS TO NOTE
 THIS.
  
 18)NOTE: PLEASE SEE PLANS "GEN NOTES"
 #1, REFERENCE "PALM BEACH COUNTY",
 PLEASE SEE, SINCE THIS PROJECT IS
 LOCATED IN THE CITY LIMITS, PLANS WOULD
 BE REQUIRED TO REFERENCE CITY OF WEST
 PALM BEACH.
  
 19)NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATION(S) ON ELECTRICAL PLANS.
 215.5
  
 20)NOTE: PLEASE SHOW ALL "CONTINUOUS
 LOADS" (3 OR MORE HRS)ARE SHOWN AT 125%
 ON LOAD CALCULATIONS.
 215.3,230.42 ETC.
  
 21)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 ** PLEASE SEE THERE ARE OVER 110
 RECESSED LT FIXTURES SHOWN.
 PLEAS ADJUST LOAD CALCULATIONS.
  
 22)NOTE: PLEASE SEE "POOL EQUIPMENT" MAY
 NOT BE LOCATED AT LOCATION SHOWN AS
 BEING "UNDER" WOOD DECK WITHIN THE POOL
 AREA OF 5'.
 680.22 ETC. PLEASE ALSO SEE POSSIBLE
 COMMENTS FORM OTHER TRADES.
  
 23)NOTE: PLEASE SEE NUMEROUS BATH
 RECEPTS CIRCUITS WHICH ARE SHOWN AS #14,
 15A CIRCUITS. PLEASE SEE 210.52,210.11C3
 WHICH REQUIRES DEDICATED BATH(S)
 CIRCUIT(S). PLEASE SEE THESE ARE
 REQUIRED TO BE 20A AND #12, PLEASE
 ADJUST CIRCUITING AND PANEL SCHEDULES.
  
 24)NOTE: PLEASE VERIFY OCP SHOWN FOR
 AHU#3, THIS IS SHOWN AS A 7.5KW UNIT,
 HOWEVER LOAD CALCULATIONS AND OCP SHOW
 THIS AS A 10KW UNIT. PLEASE CORRELATE
 AND ADJUST.
  
 25)NOTE: PLEASE VERIFY GARAGE DOOR
 OPENERS AND LOAD (HP RATING) FOR EACH.
 PLEASE SEE 430.53 AND POSSIBLE A MIN OF
 TWO GDO CIRCUITS.
  
 26)NOTE: PLEASE SEE PLANS AND VERIFY ALL
 PHONE AND CATV LOCATIONS WHICH ARE GOING
 TO BE INCLUDED UNDER THIS PERMIT.
 (MASTER BEDRM PHONE?)
 THIS IS ONLY A NOTE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE ONE SET OF ALL OLD/VOIDED
 SHEETS REMOVED ARE SUBMITTED BACK FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 21 Status P Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 11:10 Sent To B
Notes
2007-04-23 11:10:25TO "LMARTINEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 17:58 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 17:58 Sent To B
Notes
2006-12-16 17:59:01TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 10:43 Sent To E
Notes
2006-12-01 10:44:11TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 17:01 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 17:01 Sent To E
Notes
2006-11-21 17:01:57TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 17:32 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 17:32 Sent To E
Notes
2006-11-09 17:32:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-11-02 Cont ID  
Sent By adarroug Date 2006-11-02 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-11-02 Time 11:49 Sent To E
Notes
2006-11-02 11:49:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 08:46 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 08:46 Sent To E
Notes
2006-10-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:32 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:32 Sent To M
Notes
2006-10-02 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 08:44 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 08:44 Sent To B
Notes
2006-09-05 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 14:27 Sent To B
Notes
2006-05-27 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 12:14 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 12:14 Sent To B
Notes
2006-05-04 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 14:26 Sent To B
Notes
2006-05-03 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 10:57 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 10:57 Sent To E
Notes
2006-01-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 11:36 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 11:36 Sent To Z
Notes
2005-12-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 09:41 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 09:41 Sent To E
Notes
2005-12-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-07 Cont ID  
Sent By adarroug Date 2005-12-07 Time 11:23 Rev Time 0.00
Received By adarroug Date 2005-12-07 Time 11:23 Sent To Z
Notes
2005-12-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 13:53 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-22 Time 09:05 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 09:01 Sent To E
Notes
2005-10-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 15:53 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 15:53 Sent To Z
Notes
2005-09-30 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 15:10 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 15:10 Sent To E
Notes
2005-08-16 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-06 Cont ID  
Sent By alange Date 2005-09-06 Time 08:55 Rev Time 0.00
Received By alange Date 2005-08-05 Time 15:46 Sent To  
Notes
2005-08-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-11-17 Cont ID  
Sent By tgordon Date 2005-11-17 Time 16:30 Rev Time 0.20
Received By tgordon Date 2005-11-17 Time 16:29 Sent To B
Notes
2005-11-17 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By prafter Date 2005-08-23 Time 10:50 Rev Time 0.75
Received By prafter Date 2005-08-23 Time 10:50 Sent To B
Notes
2005-08-23 00:00:00MECH. PLAN REVIEW:
  
 A/C-1 AND A/C-2 DO NOT REFLECT A/C
 DUCT WORK OR EQUIPMENT INFORMATION.
  
 PLEASE COMPLETE A/C PLANS AND
 EQUIPMENT INFORMATION AND RESUBMIT.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-11-17 Cont ID  
Sent By jleech Date 2005-11-17 Time 16:01 Rev Time 0.75
Received By jleech Date 2005-11-17 Time 16:01 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By jleech Date 2005-08-17 Time 14:39 Rev Time 0.75
Received By jleech Date 2005-08-17 Time 14:39 Sent To M
Notes
2005-08-17 00:00:00DENIED;
 RISER DIAGRAM CODE VIOLATIONS MARKED ON
 PLAN IN RED.
 TWO W/C'S NOT VENTED.
 HORIZONTAL DRY VENT NOT PER. CODE SEC.
 905.3 AND 905.4.
 PLUMBING NOTES. PLEASE CHANGE NOTE 14 TO
 READ WATER HAMMER ARRESTORS PER.
 FBC-2001 PLUMBING SEC. 604.9
 CLEANOUTS FOR W/M STACK SHOULD BE
 INSTALLED AT 48" ABOVE FINISH FLOOR FOR
 ACCESS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 11:16 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 11:16 Sent To I
Notes
2006-01-07 00:00:00NOTE: PIER & LIGHT MUST BE A MAXIMUM
 HEIGHT OF 4FT WITHIN THE 25FT FRONT
 SETBACK.
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATES WITH UTILITY
 EASEMENT APPROVAL FROM THE CITY OF WEST
 PALM BEACH AND SITE WALL DETAIL
 ATTACHED.
  
 PROVISO: THE MAXIMUM HEIGHT THE
 STRUCTURE WILL BE BUILT AT 33FT,WHICH
 INCLUDES THE 10% FOR CHIMNEY.
  
 NOTE: THE NEW FOUNTAIN WAS OMITTED ON
 THE SITEPLANS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2005-12-09 Cont ID  
Sent By mmclean Date 2005-12-09 Time 08:28 Rev Time 0.00
Received By mmclean Date 2005-12-09 Time 08:28 Sent To I
Notes
2005-12-09 00:00:00DENIED,
 1. THE NEW FOUNTAIN MUST BE 5FT FROM
 PROPERTY LINE.
  
 NOTE: THE HEIGHT OF THE STRUCTURE MUST
 BE A MAXIMUM OF 33FT (INCLUDING
 CHIMENY).
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/GATE/COLUMNS/WALL/POOL/SPA/SCREEN
 ENCLOSURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-10-17 Cont ID  
Sent By mmclean Date 2005-10-17 Time 15:08 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 15:08 Sent To  
Notes
2005-10-17 00:00:00DENIED,
 1. SITEPLAN & SURVEY MUST MATCH WITH
 DIMENSION OF LOT AND SETBACKS.
 (SITEPLANS SHOWS 69.73 AND SURVEY SHOWS
 69.70 FRONT LOT), (SITEPLANS SHOWS 10FT
 ON THE SIDE & SURVEY SHOWS 9.9FT),
 (SITEPLANS SHOWS 116.53 FOR LOT WIDTH &
 SURVEY SHOWS 117.50)
 2. SIDE SETBACK MUST BE A TOTAL OF 15FT
 WITH MINIMUM OF 5FT.
 3. FRONT SETBACK OF THE STRUCTURE SHOWS
 25.3 ON SURVEY AND SITEPLAN SHOWS 25.4.
 4. BOTH DOCUMENTS MUST MATCH.
  
 ****************************************
  
 NOTE: PIER & LIGHT MUST BE A MAXIMUM
 HEIGHT OF 4FT WITHIN THE 25FT FRONT
 SETBACK.
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATES WITH UTILITY
 EASEMENT APPROVAL FROM THE CITY OF WEST
 PALM BEACH AND SITE WALL DETAIL
 ATTACHED.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 17:38 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 17:38 Sent To I
Notes
2005-08-11 00:00:00DENIED,
 1. SITEPLAN & SURVEY MUST MATCH WITH
 DIMENSION OF LOT, SETBACKS.
 2. SIDE SETBACK MUST BE A TOTAL OF 15FT
 WITH MINIMUM OF 5FT.
 3. REAR SETBACK MUST BE 10% OF LOT DEPTH
 OR 15FT WHICHEVER IS LESS.
 4. PIER & LIGHT MUST BE A MAXIMUM HEIGHT
 OF 4FT WITHIN THE 25FT FRONT SETBACK.
 5. MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.
 6. MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATES WITH UTILITY
 EASEMENT APPROVAL FROM THE CITY OF WEST
 PALM BEACH AND SITE WALL DETAIL
 ATTACHED.
 7. CAN ONLY HAVE ONE COOKING FACILITY ON
 PROPERTY, MUST CHANGE NAME ON PLAN
 (KIT/BAR) AND MUST CHANGE REFRIDGERATOR
 IN KIT/BAR & BAR TO UNDER COUNTER
 REFRIDGERATOR.
 8. STRUCTURE & CHIMNEY IS OVER THE
 ALLOWABLE HEIGHT.STRUCTURE CAN ONLY BE
 30FT IN HEIGHT WITH 10% ALLOWED FOR
 CHIMENY 33FT. STRUCTURE SHOWS 33FT AND
 CHIMENEY 36+/37FT. MUST REDUCE
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720