Plan Review Details - Permit 05080077
Plan Review Stops For Permit 05080077
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-02 Cont ID  
Sent By jhiggins Date 2005-08-02 Time 16:21 Rev Time 0.00
Received By jhiggins Date 2005-08-02 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status N Date 2008-03-12 Cont ID  
Sent By jwitmer Date 2007-09-26 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2007-09-26 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-07-19 Cont ID  
Sent By jwitmer Date 2007-07-19 Time 20:39 Rev Time 0.33
Received By jwitmer Date 2007-07-19 Time 20:39 Sent To  
Notes
2007-07-19 21:05:22BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH ST
 CONT: ALL PHASE ENVIROMENTAL
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) ONE SET OF ARCHITECTURALS ARE NOT SEALED. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.FL ATATE STAT:
 61G16.003 ARCHITECTS
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 16:41 Rev Time 0.77
Received By jwitmer Date 2007-07-06 Time 16:41 Sent To PC
Notes
2007-07-06 16:44:21PRODUCT APPROVALS:ALUMIMUM SINGLE HUNG WINDOWS NOA
 02-1223.01
 MULLION NOA 06-1130.03
 CASEMENT WINDOWS NOA 04-0317.02
 LETTER FROM ENGINEER CERTIFYING WINDOWS TO THE 2004
 FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 08:53 Rev Time 0.77
Received By jwitmer Date 2007-07-06 Time 08:53 Sent To PC
Notes
2007-07-06 08:58:33BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH ST
 CONT: ALL PHASE ENVIROMENTAL
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) COMMENT# 3 FROM THE PREVIOUS REVIEW DEELS WITH THE
 DESIGNER OF RECORD REVIEWING THE REVISION IN COMPONENTS
 AND CLADDING FOR CODE COMPLIANCE, EITHER THE ARCHITECT
 RAFAEL RODRIGUEZ OR THE ENGINEER TOMMY TAVERAS SHOULD
 REVIEW AND APPLY A SHOP DRAWING STAMP THAT THE
 SUBMITTALS ARE CODE COMPLIANT AND REVIEWED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-06-26 Cont ID  
Sent By jwitmer Date 2007-06-26 Time 10:40 Rev Time 1.55
Received By jwitmer Date 2007-06-26 Time 10:40 Sent To PC
Notes
2007-06-26 13:09:04BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH ST
 CONT: ALL PHASE ENVIROMENTAL
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) THE A-1 SHEET WILL NEED THE WINDOW SCHEDULE UPDATED
 SINCE THERE WERE ONLY TWO TYPES OF WINDOWS WHEN
 ORIGINALLY PERMITED. THE SUBMITTAL INDICATED FOUR TYPES
 SINGLE HUNG, CASEMENT,HORIZONTAL SLIDERS & FIXED
 WINDOWS. PLEASE UPDATE WINDOW SCHEDULE. 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 3)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4)PLEASE SEE THE ATTACHED E-MAIL THAT WAS SENT TO MO
 MADANI WHO'S STAFF IS OVER FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS, PRODUCT APPROVALS AND RULE 9B-72 FOR
 STATE PRODUCT APPROVALS.WE HAVE CONCERNS
 WITH THE OLDER MIAMI-DADE NOA'S THAT TOOK THE 1/3RD
 STEEL INCREASE, IF THESE PRODUCTS ARE TO BE USED,
 PLEASE HAVE A FLORIDA P E VARIFY THESE UNITS WILL MEEET
 THE 2004 FBC AND THE PRESSURE ZONES FOR THIS
 STRUCTURE.
  
 5) ADDITIONAL FEES DUE: FEES PAID FOR 1 REVISION CHANGE
 WHEREAS 5 PRODUCT APPROVALS WERE SUBMITTED. ADDITIONAL
 $40.00 DUE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-05-10 Cont ID  
Sent By jwitmer Date 2007-05-10 Time 09:51 Rev Time 0.77
Received By jwitmer Date 2007-05-10 Time 09:51 Sent To PC
Notes
2007-05-10 09:52:21REVISION, TO SECOND FLOOR BALCANY SLAB. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-04-27 Cont ID  
Sent By jwitmer Date 2007-04-27 Time 10:00 Rev Time 0.55
Received By jwitmer Date 2007-04-27 Time 10:00 Sent To PC
Notes
2007-04-27 10:03:02BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH ST
 CONT: ALL PHASE
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
  
 3)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) PLANS INDICATE A EXPOXIED BOLT PLEASE PROVIDE THE
 MANUFACTURER AND MODEL #.
 1703.4.2 SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN
 THE APPROVAL OF MATERIALS
 OR ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS
 CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
 PLANS FAIL TO INDICATE SIZE OF HOLE TO BE USED FOR
 EXPOXIED BOLT.
  
 5) PLANS ALSO HAVE HAND WRITTEN ADDRESS, PLANS DRAWN BY
 DESIGN PRODESSIONALS
 MUST ENITIAL AND DATE ANY CHANGES TO BE SUBMITTED FOR
 PUBLIC RECORD.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-04-27 Cont ID  
Sent By jwitmer Date 2007-04-27 Time 09:57 Rev Time 0.55
Received By jwitmer Date 2007-04-27 Time 09:48 Sent To PC
Notes
2007-04-27 09:59:50DOOR REVISION:
 BRUNSWICK DOOR
 NOA 03-0401.06
 20 GA. FLUSH OUTSWING STEEL DOOR (W 16G FRAME) IMPACT

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-01-09 Cont ID  
Sent By jwitmer Date 2007-01-09 Time 17:36 Rev Time 1.55
Received By jwitmer Date 2007-01-09 Time 17:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-11-17 Cont ID  
Sent By jwitmer Date 2006-11-17 Time 08:33 Rev Time 3.33
Received By jwitmer Date 2006-11-17 Time 08:33 Sent To  
Notes
2006-11-17 09:40:39BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH STREET
 CONT: WEST PALM BEACH HOUSING AUTHORITY
 TEL: (561)719-2217
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING PLAN REVIEW
 5TH REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2A) MISSING THE ORIGINAL APPLICATION, THE
 DESCRIPTION OF WORK FROM A COPIED PERMIT
 APLICATION AND THE SUBMITTAL SHEET
 DOESN'T MATCH. THE SUBMITTAL SHEET
 INDICATES A COMPLETE CHANGE OF PLANS.
 THIS COULD BE TAKEN AS A COMPLETE
 RENOVATION OF THE BUILDING, WHAT IS THE
 ACTUAL WORK TO BE ACCOMPLISHED UNDER
 THIS PERMIT.106.1.2*. ADD INFO.
  
 2B) FROM THE MEETING HELD WITH THE CONTRACTOR AND
 DESIGN TEAM, THE INTERIOR WALLS ARE CEMENT BLOCK/
 STUCCO
 THIS WAS TO BE MENTIONED ON THE PLAN, AS NO DRYWALL
 ON INTERIOR WALLS.
 NOTE: A-5NOTE# 2 ON INTERIOR FINISHES INDICATES THE
 USE
 OF CEMENT BOARD USE IN THE TUB WALL AREAS,
 IF BLOCK WALLS OCCUR THE USE OF CEMENT BOARD WOULD
 NOT BE NEEDED.
 THE OTHER ISUE WITH THE USE OF CEMENT BOARD IS USED IN
  
 CONJUNCTION WITH EITHER WOOD OR METAL STUDS NO MENTION
  
 TO A VAPIOR BARRIER TO BE USED BEHIND THE CEMENT
 BOARD,
 THIS STOPS ANY MOISTURE FROM TRAVELING THROUGH THE
 WALL
 CAUSING FUNGESS ON THE BACK SIDE OF THE DRYWALL.
  
 2C)THE OTHER ISSUE THE COPIED PERMIT APPLICATION ALSO
 INDICATES
 BALCONY SLAB REPAIR, A NOTE ON SHEET A-4 SEE DRAWINGS
 BY TECTON
 ENGINEERING FOR BALCONY SLAB REPAIRS. NO SUCH DRAWINGS
 WERE
 INCORPORATED IN THESE PLANS. EITHER CORRECT THE PERMIT
 APPLICATION
 DESCEPTION OF WORK OR PROVIDE THEINFORMATION TO
 BALCONY REPAIRS BEING MADE.
 NOTE NO MENTION OF ANY BALCONY RAILINGS BEING REPLACED
 UNDER THIS PERMIT.
  
 3) AS A RESULT OF THE MEETING WITH THE CONTRACTOR AND
 THE DESIGN TEAM A NEW
 EXTERIOR WALL SECTION X/A-5 WAS INCORPORATED INTO THE
 PLANS.
 NOTE OF REFRENCE NOT SHOWN ON THE PLAN.THE PLANS
 INDICATE THE USE OF
 5/8" STUCCO ON GALVANIZED WIRE MESH ON 5/8" CDX
 PLYWOOD. THE PLANS
 DO NOT INDICATE THE GAUGE OF WIRE MESH NOR THE TYPE OF
 WIRE MESH TO
 BE USED NOR THE SIZE NAIL OR PATERN OF NAILING.
 SECTION 2510.3 LATHING AND FURRING FOR CEMENT PLASTER
 (STUCCO). INSTALLATION
 INDICATES COMPLIANCE WITH ASTM C-1063.
 TABLE 3 PROVIDES THE NOMINAL WEIGHT OF THE METAL
 PLASTER BASE, SPACING AND TYPE OF
 METAL WIRE LATH .
 NOTE FOOTNOTE "D" WHERE PLYWOOD IS USED FOR SHEATHING,
 METAL PLASTER BASES SHALL BE FURRED AWAY
 FROM VERTICAL SUPPORTS OR SOLID SURFACES AT LEAST 1/4"
 . SELF FURRING LATH MEETS FURRING REQUIREMENTS ;
 EXCEPT, FURRING EXPANDED METAL LATH IS NOT REQUIRED ON
 SUPPORTS HAVING A BEARING SURFACE OF 1 5/8" OR LESS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-29 Cont ID  
Sent By jwitmer Date 2006-09-29 Time 15:02 Rev Time 2.22
Received By jwitmer Date 2006-09-29 Time 14:07 Sent To PC
Notes
2006-09-29 00:00:00PERMIT: 05080077
 ADD: 542 19TH ST
 CONT:WEST PALM BEACH HOUSING
 AUTHORITY
 TEL: (561)719-2217
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PLAN REVIEW
 4TH REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) MISSING THE ORIGINAL APPLICATION, THE DESCRIPTION OF
 WORK FROM A COPIED PERMIT APLICATION AND THE SUBMITTAL
 SHEET
 DOESN'T MATCH. THE SUBMITTAL SHEET
 INDICATES A COMPLETE CHANGE OF PLANS.
 THIS COULD BE TAKEN AS A COMPLETE
 RENOVATION OF THE BUILDING, WHAT IS THE
 ACTUAL WORK TO BE ACCOMPLISHED UNDER
 THIS PERMIT.106.1.2*. ADD INFO.
  
 3) SHEET S-1, THE TITLE BLOCK IS SIGNED
 AND SEAL BY THE ARCHITECT OF RECORD.
 THERE IS ALSO AN AREA FOR THE ENGINEER
 OF RECORD TO SIGN, THE PRINTED NAME AND
 ENGINEERS LICENSE NUMBER IS ON THIS
 SHEET, WHO IS TAKING RESPONSIBLIITY FOR
 THIS WORK.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) AGAIN WITH NOT KNOWING WHAT WILL TAKE
 PLACE WITH MECHANICAL, THE ELECTRICAL
 SHEETS INDICATE A/C 1800 VA, PLEASE
 PROVIDE THE APPROPRIATE ENERGY FORMS.
  
 5) 2004 FBC
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 13:51 Rev Time 0.55
Received By jwitmer Date 2006-04-04 Time 13:50 Sent To PC
Notes
2006-04-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 542 19TH ST
 CONT:WEST PALM BEACH HOUSING
 AUTHORITY
 TEL: (561)719-2217
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) TECTRON ENGINEERING CORP NO
 CERTIFICATE OF AUTHORIZATION ON PLANS,
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-23 Cont ID  
Sent By jwitmer Date 2005-12-23 Time 16:42 Rev Time 2.22
Received By jwitmer Date 2005-12-23 Time 16:42 Sent To  
Notes
2005-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 524 19TH ST UNIT A, B, C & D
 CONT: W. P. B. HOUSING AUTHORITY
 TEL: (561)719-2217
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) NALYWAJKO & ASSOCIATES SUBMITTAL IS
 ONLY (1) SET OF DETAILS. TWO SETS ARE
 REQUIRED FOR PUBLIC RECORD, SIGNED AND
 RAISED SEAL.
  
 2) PLEASE CORRALATE PLANS INTO 2 STAPLED
 SETS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 13:17 Rev Time 1.55
Received By jwitmer Date 2005-08-28 Time 13:14 Sent To  
Notes
2005-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080077
 ADD: 524 19TH ST UNIT A, B, C & D
 CONT: W. P. B. HOUSING AUTHORITY
 TEL: (561)719-2217
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) NALYWAJKO & ASSOCIATES SUBMITTALS ARE
 COPIES AND NO RAISED SEAL NOR ORIGINAL
 SIGNATURES.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) THERE APPEARS TO BE (2) STRUCURAL
 ENGINEERS ON THIS JOB, THE ABOVE
 MENTINED, & REDDY CHUNDI PLEASE EXPLAIN?
  
 3) PROVIDE THE FOLOWWING INFORMATION:
 601.2.1 EVERY BUILDING SHALL BE
 CLASSIFIED BY THE BUILDING OFFICIAL
 INTO ONE OF THE TYPES OF CONSTRUCTION AS
 SET FORTH IN THIS SECTION.
  
 TYPE ITYPE V
 TYPE II1-HOUR PROTECTED
 TYPE IIIUNPROTECTED
 TYPE IV TYPE VI
 1-HOUR PROTECTED1-HOUR PROTECTED
 UNPROTECTED UNPROTECTED
 ALSO PROVIDE HOW MANY STORIES, SQ FT PER
 FLOOR, AND IF FIRE SPRINKLERED?
  
 4) THE 81/2X 11 NALYWAJKO PLAN DOESN'T
 INDICATE THE STRAPPING FOR THE
 INDIVIDUAL STUDS?
 NOR DOES THE DETAIL INDICATE THE TYPE
 OF SUBSHEATHING OR FINISH MATERIAL.
 THE THIRD ITEM MISSING ON THIS SAME
 DETAIL IS THE WEATHERPROOFING OF THE
 BOTTOM PLATE- NO WATER INTRUSION INTO
 THE HABITABLE SPACE.
  
 5) PROVIDE THE WINDOW SIZE FOR THE
 BEDROOM WINDOWS, PRODUCT APPROVALS
 SUBMITTED INDICATE CASEMENT PROVIDE THE
 CLEAR AREA FOR BEDROOM WINDOWS.
  
 6)THE REPORT SUBMITTED FOR PGT CASEMENT
 WINDOWS WITH THE FL# 245 INDICATES THE
 2001 CODE WHILE ON LINE THE REPORT READS
 2004?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2007-09-26 Cont ID  
Sent By dpalmer Date 2007-09-26 Time 07:54 Rev Time 0.00
Received By dpalmer Date 2007-09-25 Time 16:46 Sent To  
Notes
2007-09-26 07:56:41** NOTES:
  
 PREVIOUS COMMENT REQUESTED TO CLARIFY REV #4 ON SHEETS
 E-3 AND E-4, AND RESPONSE MENTIONS THESE SHEETS WILL
 NOT BE SUBMITTED. HOWEVER THESE SHEETS WERE SUBMITTED
 FOR A SECOND TIME FOR REVISION. SHEET E-1 AND E-2 WERE
 STAMPED OK, AND E-3 AND E-4 WERE FOLDED OVER AND NOT
 STAMPED.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2007-06-27 Cont ID  
Sent By dpalmer Date 2007-06-27 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2007-06-27 Time 19:27 Sent To I
Notes
2007-06-27 20:04:42*** UNSAT***
  
 1) NOTE: PLEASE SEE PERMITTED ISSUED PLANS WERE
 REDLINED AND NOTED THAT THE RISER CONDUIT SHOWN AS 2
 1/2 INCHES WAS NOT LARGE ENOUGH BASED ON THE NEC.
 PLEASE SEE CHAPTER 9, TABLE 4 AND 5 FOR FIGURING
 CONDUIT FILL OR SEE TABLE C8 FOR DIRECT CONDUIT FILL.
 IN EITHER CASE THE MINIMUM CONDUIT SIZE NEEDS TO BE
 3INCH RMC.
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE WHICH NOW INDICATE
 THE REMOVAL OF THE RANGE AND WATER HEATER AS ELECTRIC
 AND ONLY INDICATE SINGLE POLE 20AMP CIRCUITS FOR
 CONTROL HOWEVER PLEASE SEE THE SPARE SPACES STILL
 INDICATE THE CONDUCTOR SIZES AS #8 AND #12 AS INSTALLED
 FOR *B* PHASE.
 PLEASE ADJUST AS PLANS ARE NEEDED TO BE 100% FOR
 FINAL.
  
 3) NOTE: PLEASE SEE THE SHEETS E-3 AND E-4 AS THE TITLE
 BLOCKS INDICATE A REVISION #4 HOWEVER NOT REVISION #4
 COULD BE LOCATED ON EITHER OF THESE SHEETS?
 PLEASE ONLY SUBMIT SHEETS BEING REVISED OR PLEAS
 INDICATE THE REVISION TAKING PLACE.
 FBC 106.1.2, 106.1
  
 4) NOTE: PLEASE VERIFY THE LOCATION OF THE CONTROLS FOR
 THE NEW GAS WATER HEATERS AS THEY ARE NOW SHOWN OUTSIDE
 AND THE LOCATION OF THE RECEPTACLES ARE BEING SHOWN AT
 THE OLD/PREVIOUS WATER HEATER LOCATION.
 PLEASE CLARIFY THIS: PLEASE KNOW IF THESE RECEPTACLES
 ARE FOR THESE UNITS OUTSIDE, PLEASE INDICATE AT THAT
 LOCATION ALONG WITH GFI INDICATIONS.
 FBC 106.1.2
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-06-27 19:28:20PLANS REMOVED FROM INCOMING, WILL BE RETURNED TO
 INCOMING WHEN ELECTRICAL REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 12:20 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 12:03 Sent To PC
Notes
2007-02-27 12:22:56REDLINED SIZE OF RISER, NEEDS TO BE 3" MIN PER PIPE
 FILL IN CHAPTER 9 OF THE NEC.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-02-23 Cont ID  
Sent By dpalmer Date 2007-02-23 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2007-02-23 Time 08:21 Sent To P
Notes
2007-02-23 09:44:03*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH
 MENTIONED THAT DUE TO THE PERMIT APPLICATION BEING
 DUPLICATED, THE ELECTRICAL CONTRACTOR WHO WAS
 ORIGINALLY SIGNED ON ORIGINALAPPLICATION NEEDED TO
 SIGN THE DUPLICATE APPLICATION.
  
 PLEASE KNOW IF THE ELECTRICAL SUB CONTRACTOR IS
 "VOIDED" FROM THE GC'S PERMIT APPLICATION THEN THE
 REVIEW CAN BE CHANGED TO A "PASSED' STATUS AND THE SUB
 CONTRACTOR WILL APPLY FOR THE ELECTRICAL PERMIT AFTER
 MAIN PERMIT IS ISSUED AT A FEE OF $50.
 THE OTHER OPTION IS FOR THE QUALIFIER TO COME IN AND
 SIGN PERMIT APPLICATION BEFORE ALL REVIEWS ARE DONE.
  
 PLEASE CONTACT THIS OFFICE TO GO OVER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-12-24 Cont ID  
Sent By dpalmer Date 2006-12-24 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 16:42 Sent To  
Notes
2006-12-24 18:33:08*** UNSAT 6TH REVIEW ***
  
  
 *** PLEASE SEE THAT SOME COMMENTS FROM PREVIOUS REVIEWS
 HAVE STILL NOT BEEN ADDRESSED.
 PLEASE SEE COMMENTS BELOW.
 IT IS GOING TO BE THE ATTEMPT OF THIS REVIEW TO TRY AND
 INDICATE EVERY ITEM AS THE RESPONSE LETTER SEEMS TO
 LEND TO MISUNDERSTANDING OF THE COMMENTS OR THE CODE
 SECTIONS GIVEN.
  
 ** PLEASE KNOW THAT TO DATE OF THIS REVIEW NO CONTACT
 HAS BEEN MADE BY THE DESIGNER OR DESIGN TEAM TO GO OVER
 NOTES FOR QUESTIONS OR COMMENTS.
 AT THE END OF EACH PREVIOUS REVIEW THIS REVIEWER HAS
 PLACED THE DIRECT PHONE NUMBER AND E-MAIL ADDRESS FOR
 THIS PURPOSE.
  
 1) NOTE: PLEASE KNOW A 4X TIME FEE FOR THE PLAN REVIEW
 PORTION OF THE PERMIT FEE HAS NOW BEEN ASSESSED TO THE
 DESIGNER OF RECORD DUE TO COMMENTS BEING REPEAT
 COMMENTS FOR CODE COMPLIANCE.A NOTICE TO FLORIDA
 STATUTES 553.80(2)(B) WAS GIVEN ON PREVIOUS REVIEW.
 PLEASE KNOW THAT THE FEE OF $1,359.60 IS DUE BEFORE
 PLANS MAY BE RESUBMITTED AND IS THE RESPONSIBILITY OF
 THE DESIGNER OF RECORD FOR ELECTRICAL. THIS IS NOT
 ASSESSED TO THE CONTRACTOR OR OWNER OF RECORD. PLEASE
 ALSO KNOW PLANS ARE BEING RETAINED BY THIS OFFICE ONCE
 AGAIN AND NOW MAY BE TURNED INTO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW.
  
 2) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES
 AND LOAD CALCULATIONS SUBMITTED. PLEASE SEE THIS
 COMMENT HAS BEEN MADE ON EACH OF THE PREVIOUS REVIEWS.
  
 A) PLEASE SEE THE PANEL SCHEDULE AT THE TOP MENTIONS
 "LOAD IN (AMPS)" HOWEVER THIS SEEMS TO BE IMPOSSIBLE AS
 SHOWN. SOME SHOWN IN AMPS, AND OTHER SHOWN IN VA.
  
 B) PLEASE SEE FOR INSTANCE THE LOAD FOR THE RANGE IS
 SHOWN AT 40A?S, HOWEVER THIS DOES NOT CORRELATE WITH
 THE VA IN LOAD CALCULATIONS.
  
 C) PLEASE SEE SEVERAL OTHER CIRCUITS WHICH LOADS ARE
 SHOWN IN AMPS WHICH IS OK, HOWEVER THE AMPERAGE AS
 SHOWN NEEDS TO CORRELATE WITH THE VA SHOWN IN THE LOAD
 CALCULATIONS TO THE LET OF THE PANEL SCHEDULE.
  
 D) PLEASE THEN SEE SOME LOADS ON PANEL SCHEDULE ARE
 BEING SHOWN IN WHAT APPEARS TO BE THE VA FOR EACH
 CIRCUIT. (EXAMPLE, PLEASE SEE SMALL APPLIANCE CIRCUITS
 SHOWN AT 1.5? ARE THESE AMPS AS NOTED ON PANEL SCHEDULE
 OR THE ACTUAL VA, WHICH IS 1500VA? PLEASE ALSO SEE BATH
 ROOM CIRCUIT ETC.
  
 E) PLEASE SEE TOTAL CONNECTED LOAD ON PANEL SCHEDULE
 SHOWS 20.8, YET LOAD CALCULATIONS INDICATE 19,768.
  
 F) PLEASE SEE WASHER IS STILL BEING SHOWN ON A SINGLE
 POLE 30A CIRCUIT WITH #10 AWG, YET PLEASE SEE UPPER
 PLANS WHICH MENTION A 10AMP CIRCUIT FOR WASHER? (THE
 MINIMUM REQUIRED AND LOADS NEED TO CORRELATE FOR THIS.
 PLEASE ALSO SEE 210.21(B)3 FOR MAX OVER CURRENT
 PROTECTION FOR A RECEPTACLE DEVICE.
  
 G) PLEASE SEE UPPER RIGHT HAND CORNER OF PLANS WHICH
 STILL INDICATE A 20A /240V CIRCUIT FOR BATHROOM.
  
 H) PLEASE SEE LOAD ON REFRIGERATOR ON LOAD CALCULATIONS
 INDICATE 1500VA, YET, THE AMPERAGE ON THE PANEL
 SCHEDULE ONLY SHOWS 12A'S? PLEASE CORRELATE
  
 I) PLEASE SEE PANEL SCHEDULE IS STILL ONLY SHOWING 18
 CIRCUITS, WHERE PANEL SCHEDULE IS NOTED AS HAVING 24.
 PLEASE SEE THERE ARE TWO SPACES WHICH INDICATE 20A
 BREAKERS BEING INSTALLED, HOWEVER NO LOADS ARE SHOWN.
 IF THESE ARE SPARES, PLEASE INDICATE AS SUCH.
  
 J) PLEASE SEE HOUSE PANEL WHICH IS SHOWING 1500VA FOR
 EACH LIGHTING CIRCUIT, YET PANEL SCHEDULE LOAD IN AMPS
 IS SHOWN MUCH LESS.
 PLEASE SEE TOTAL CONNECTED LOAD AS SHOWN ON PANEL
 SCHEDULE AND THAT OF THE LOAD SHOW IN LOAD CALCULATIONS
 ARE NOT THE SAME.
  
 K) PLEASE SEE RESPONSE LETTER MENTIONS THE DRYER IS NOW
 REMOVED AS SHOWN ON PANEL SCHEDULE AND CIRCUITS FROM
 PREVIOUS PLANS, HOWEVER PLEASE SEE PLANS STILL INDICATE
 240V CIRCUITS TO TWO OF THESE LOCATIONS.PLEASE SEE
 PLANS SHOW 16/18 FOR UNITS FC AND FA. PLEASE CORRELATE
 CIRCUITING ON PLANS WITH THAT OF THE CIRCUITING ON
 PANEL SCHEDULE(S) TYPICAL.
  
 PLEASE CORRELATE ALL OF THE ABOVE.
 310.16, 240.4, 210.11C2, 210.11C3, 220.16, 220. 408.4
 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE 700.12E
 FOR CIRCUITING OF EMERGENCY LIGHTS HOWEVER PLEASE SEE
 THESE ARE BEING SHOWN ON A DEDICATED CIRCUIT. PLEASE
 SEE THE FOLLOWING IS BEING EXTRACTED FROM THE CODE
 EXACTLY WORD FOR WORD.
  
 "THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES."
  
 THESE SECTIONS ARE INTENDED FOR THE EVENT OF THE
 TRIPPING OF A SINGLE BREAKER/OVER CURRENT PROTECTION
 DEVICE WHICH THE NORMAL LIGHTING IS CONNECTED WILL NOT
 LEAVE IN ONE AREA IN TOTAL DARKNESS. PLEASE SEE IF THE
 NORMAL CIRCUIT AS SHOWN WHICH IS HP-1 TRIPS, THE
 EMERGENCY LIGHT FIXTURES WILL NOT COME ON AND LIGHT UP
 ANY EGRESS AREA IN THE EVENT OF AN EMERGENCY FOR
 OCCUPANTS OR FIRE PERSONNEL.
 PLEASE ADJUST CIRCUITING.
  
 PLEASE ALSO SEE NFPA-101 2003 7.9.2.2
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR 210.12
 WHICH REQUIRED CIRCUITING OF ALL OUTLETS IN BEDROOMS.
 THE NOTE MENTIONED NOT ONLY RECEPTACLES ARE TO BE
 PROTECTED. PLEASE SEE SMOKE DEVICES ARE STILL NOT
 SHOWING THE CIRCUITING FOR THIS. PLEASE SEE PLANS.
 PLEASE SEE IF INDEED THESE ARE "SD" SMOKE DETECTORS AS
 SHOWN, THEN BY THE DEFINITIONS IN NFPA-72 THESE ARE
 BEING CONNECTED TO A FIRE ALARM SYSTEM WHICH WOULD BE
 LOW VOLTAGE WHICH IS NOT SHOWN.
 IF THESE ARE 110/120V UNITS AND THEY ARE DETECTION AND
 ALARM DEVICES, THESE WOULD BE "SA" FOR SMOKE ALARMS PER
 NFPA-72 DEFINITIONS AND WOULD BE REQUIRED TO CIRCUIT TO
 OTHER ARC FAULT PROTECTED CIRCUIT(S) AS SHOWN.
  
 5) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" BEING INSTALLED FROM
 THE GUTTER TO EACH OF THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE THIS WAS NOT PART OF THE PREVIOUS REVIEW
 NOTES AS THIS EQUIPMENT GROUNDING CONDUCTOR WAS NOT
 SHOWN ON RISER AS IT IS NOW. PLEASE SEE 250.6 AND
 250.24B AS THIS CONDUCTOR IS ONLY TO BE INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT. PLEASE SEE THE FOLLOWING
 IS EXTRACTED FROM THE CODE WORD FOR WORD.
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE CURRENT. THE
 GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS,
 SURGE ARRESTERS, AND CONDUCTIVE NON-CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND ARRANGED
 IN A MANNER THAT WILL PREVENT OBJECTIONABLE CURRENT
 OVER THE GROUNDING CONDUCTORS OR GROUNDING PATHS.
 250.24
 (B) GROUNDED CONDUCTOR BROUGHT TO SERVICE EQUIPMENT.
 WHERE AN AC SYSTEM OPERATING AT LESS THAN 1000 VOLTS IS
 GROUNDED AT ANY POINT, THE GROUNDED CONDUCTOR(S) SHALL
 BE RUN TO EACH SERVICE DISCONNECTING MEANS AND SHALL BE
 BONDED TO EACH DISCONNECTING MEANS ENCLOSURE. THE
 GROUNDED CONDUCTOR(S) SHALL BE INSTALLED IN ACCORDANCE
 WITH 250.24(B)(1) THROUGH (B)(3).
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED A LETTER,
 SIGNED, DATED, SEALED AND NOTARIZED LETTER PER FS
 117.05 FOR SIGNATURE VERIFICATION AS PLANS CONTAINED
 WHAT APPEARED TO BE INITIALS AND RESPONSE LETTERS
 CONTAINED A COMPLETELY DIFFERENT SIGNATURE FOR THE
 DESIGNER OF RECORD. PLEASE SEE RESPONSE LETTER MENTIONS
 THE DESIGNER OF RECORD WOULD NOW SIGN PLANS WITH LEGAL
 SIGNATURE, HOWEVER PLEASE SEE SOME SHEETS STILL CONTAIN
 THE OLD ?INITIALS?.
 PLEASE SEE FS 471.025, FAC 61G15-23.002.
 PLEASE SUBMIT LETTER AS PREVIOUSLY REQUESTED AS IT WILL
 BE PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE.
  
 7) NOTE: PLEASE SEE A "DUPLICATE" PERMIT APPLICATION IS
 NOW SUBMITTED IN PACKAGE; HOWEVER PLEASE SEE THAT NOT
 ALL THE SUB CONTRACTORS ARE SIGNED ON APPLICATION AS
 SIGNED ON ORIGINAL PERMIT APPLICATION.
 PLEASE SEE MISSING ELECTRICAL CONTRACTOR WHICH WAS J
 LINN ELECTRIC INC.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-11-15 Cont ID  
Sent By dpalmer Date 2006-11-15 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2006-11-15 Time 08:27 Sent To  
Notes
2006-11-15 14:22:02******** UNSAT 5TH REVIEW ********
  
 *** PLEASE SEE THAT THERE ARE MANY COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING
 ALONG WITH SOME NEW COMMENTS BASED ON PLANS SUBMITTED
 WHICH CONTAIN DIFFERENT ITEMS FROM THE PREVIOUS
 REVIEW.
 THIS IS THE 5TH REVIEW, HOWEVER THE 2ND REVIEW FOR THIS
 NEW DESIGNER OF RECORD.
  
 *** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH EITHER AND "OK" OR A "NO" WITH
 FURTHER EXPLANATION ADDED.
 PLEASE SEE SOME COMMENTS MAY BE LABELED OK/NO, AS PART
 OF THE COMMENT MAY HAVE BEEN ADDRESSED AND PART OF THE
 COMMENT MAY NOT HAVE BEEN ADDRESSED.
  
 **PLEASE SEE ANY COMPLETELY NEW NOTES WILL BE ADDED TO
 THE END OF THESE NOTES AND LABELED "NEW NOTES 5TH
 REVIEW".
  
 ** PLEASE KNOW THAT TO DATE OF THIS REVIEW NO ONE HAS
 CONTACTED THIS REVIEWER TO GO OVER ANY COMMENTS OR HAVE
 MADE ANY INQUIRIES IF ANY OF THE COMMENTS WERE NOT
 UNDERSTOOD IN ANY FASHION.
  
 1) NOTE:NO, PLEASE SEE THE ORIGINAL PERMIT
 APPLICATION HAS STILL NOT BEEN SUBMITTED BACK. WE DO
 NOT KEEP THE APPLICATIONS ARE THEY ARE RETURNED WITH
 THE PLANS WHEN THEY ARE PICKED UP. PLEASE KNOW THAT IN
 WORST CASE SCENARIO, A NEW PERMIT APPLICATION MAY BE
 FILLED OUT AND SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE THE PERMIT APPLICATION SUBMITTED BACK IN
 FACT A PHOTO-COPY OF THE ORIGINAL APPLICATION. MUST
 SUBMIT THE ORIGINAL APPLICATION FOR PROCESSING AND
 PERMITTING OF PROJECT.
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE SEE THE RESPONSE LETTER MENTIONS
 THE PLANS WILL NOW BE SIGNED WITH THE ENGINEER'S LEGAL
 SIGNATURE AND NOT INITIALS; HOWEVER PLEASE SEE THE
 PLANS DO NOT STILL SEEM TO INDICATE INITIALS. PLEASE
 SEE THE RESPONSE LETTER WHICH IS "SIGNED" FROM THE
 ENGINEER OF RECORD CONTAINS A COMPLETELY DIFFERENT
 SIGNATURE OF THAT ON PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE FS 471.025 AS THIS REQUIRES THE PLANS TO BE
 SIGNED WITH LEGAL SIGNATURE. PLANS SEEM BE SIGNED WITH
 WHAT APPEARS TO BE INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION. LETTER IS ALSO REQUIRED
 TO BE PROPERLY NOTARIZED UNDER FS 117.05.
 PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE
 FOR ANY FURTHER REFERENCE.
  
 4) NOTE: NO, PLEASE SEE PANEL SCHEDULE(S) AND LOAD
 CALCULATIONS NOW INDICATE TWO SMALL APPLIANCE CIRCUITS;
 HOWEVER THE 2ND SMALL APPLIANCE CIRCUIT IS LOCATED
 FEEDING THE LIVING ROOM RECEPTACLES. PLEASE SEE
 250.52B1, AS THIS IS NOT PERMITTED. PLEASE SEE THE SAME
 CODE ARTICLE GIVEN WHICH DEPICTS THE LOCATIONS
 PERMITTED AND MAY NOT FEED ANY OTHER AREAS. PLEASE ALSO
 SEE ONE OF THE SMALL APPLIANCE CIRCUITS ALSO FEEDS GFI
 RECEPTACLES LOCATED OUTSIDE WHICH IS ALSO NOT
 PERMITTED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING TWO MINIMUM SMALL APPLIANCE CIRCUITS
 FROM PLANS, AND PANEL SCHEDULES, ALTHOUGH THESE ARE
 NOTED IN LOAD CALCULATIONS??
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 5) NOTE: OK.
  
 6) NOTE: OK, THE DISHWASHERS WERE REMOVED FROM PLANS
 AND IN RESPONSE LETTER HOWEVER SEE NEW NOTES.
  
 7) NOTE:OK, HOWEVER SEE NEW NOTES PERTAINING TO
 CIRCUITING AND DESIGNATIONS ON PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM 4TH REVIEW **
 PLEASE LIST ARC FAULT PROTECTION ON THE PANEL SCHEDULE
 FOR ALL OUTLET LOCATED ON BEDROOMS. PLEASE SEE 2002 NEC
 210.12, WHICH REQUIRES AFP FOR ALL, NOT ONLY RECEPTS AS
 SHOWN ON PLANS.
  
 8) NOTE: OK, A/C'S REMOVED.
  
 9) NOTE: NO, PLEASE SEE THE TOTAL LOADS SHOWN ON PANEL
 SCHEDULES STILL DO NOT CORRELATE WITH THE LOAD
 CALCULATIONS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE NEC FOR LOAD CALCULATIONS. PLEASE SEE TOTAL
 ON PANEL SCHEDULES DO NOT CORRELATE WITH CALCULATIONS.
 PLEASE SEE DE-RATING TWICE IS NOT PERMITTED. THE TOTAL
 LOAD ON EACH PANEL MAY BE DE-RATED FOR PANEL, BUT NOT
 FOR TOTALS FOR THE TABLE DE-RATINGS IN 220.32. PLEASE
 SEE THE HOUSE LOADS ARE TO BE SHOWN SEPARATELY, AND
 ADDED TO TOTAL.
 PLEASE SEE NEC 220, ALL.
 PLEASE SEE ALL OTHER COMMENTS AS THE LOADS WILL BE
 CHANGING.
 215.5, 220,
 FBC ADMIN SECT 106.1.2
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK/ NO. PLEASE SEE A NOTE WAS ADJUSTED AND
 NOW READS "FOOTER-STEEL IF AVAILABLE". PLEASE KNOW THIS
 IS OK, HOWEVER AS NOTED IN THE PREVIOUS REVIEW NOTE;
 PLEASE SEE THAT THE CODES BEING REFERENCED ARE NOT FROM
 THE 2002 NEC (NFPA-70) AND DO NOT MATCH WITH THE
 REQUIREMENTS OF THE GROUNDING ELECTRODE SYSTEM. PLEASE
 BE SURE TO SEE THE 2002 AS THE STATE OF FLORIDA HAS NOT
 YET ADOPTED THE 2005 NEC.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE GROUNDING ELECTRODE RISER INDICATE FOOTER
 STEEL TO BE PART OF THE GE SYSTEM?
 PLEASE KNOW IN NEW CONSTRUCTION IT IS AVAILABLE AND IS
 REQUIRED TO BE A PART OF THE SYSTEM, HOWEVER PLEASE SEE
 THAT THIS IS AN EXISTING BUILDING AND ATTACHING TO THE
 EXISTING FOOTER IS NOT REQUIRED, HOWEVER MAY BE DONE.
 PLEASE KNOW, THIS MAY AFFECT THE STRUCTURAL INTEGRITY
 OF THE EXISTING.
 ** PLEASE SEE THE NEC CODES BEING REFERENCE ARE NOT
 FROM THE CURRENT NEC 2002. PLEASE REVISE.
 PLEASE KNOW, SINCE EXISTING FOOTER STEEL CAN NOT BE
 VERIFIED EVEN IF THE ATTACHMENT IS MADE, A MIN OF TWO
 GROUND RODS WILL BE REQUIRED.
 250.50, 250.56
  
 13) NOTE: NO, PLEASE SEE NO PHOTO-METRICS WERE
 SUBMITTED OR ANY LIGHTING LEVELS SHOWN.
 PLEASE ALSO SEE THAT NOW THAT LIGHTING HAS BEEN ADDED
 PLEASE SEE NEW NOTES FOR THIS REVIEW WITH RESPECT TO
 CIRCUITING AND CONTROL OF THESE NEW LIGHTS ADDED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING LIGHTING FOR EGRESS STAIRS PER LS
 101 7.8.1.3,
 7.9.2.2.
 PLEASE NOTE AND SHOW A MIN OF 10FT CANDLES REQUIRED FOR
 STAIRS UNDER NORMAL, AND 1FT CANDLE MIN REQUIRED UNDER
 EMERGENCY POWER.
 PLEASE SHOW.
  
 14) NOTE:NO, PLEASE SEE CIRCUITS ARE ADDED AND SHOWN,
 HOWEVER AS STATED ON THE PREVIOUS REVIEW NOTE, PLEASE
 KNOW THESE DEDICATED CIRCUIT(S) MUST MEET 210.11C3.
 THERE ARE ONLY TWO WAYS THIS CANE BE DONE. IN EITHER
 CASE, THESE MAY NOT FEED ANY OTHER RECEPTACLES IN ANY
 OTHER AREAS. (OUTSIDE ETC)
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE MISSING THE REQUIRED DEDICATED BATH(S)
 CIRCUIT(S) AS REQUIRED PER 210.52D,210.11C3, MUST BE
 20A AND #12 AWG.
  
 15) NOTE: NO, PLEASE SEE NEW PANEL SCHEDULE WERE
 SUBMITTED, HOWEVER THE CIRCUITS, SPARES AND NUMERICAL
 DESIGNATIONS OF THE PANEL SIZE AND NUMBER OF POLES
 STILL DO NOT CORRELATE. PLEASE ALSO SEE NEW NOTES DUE
 TO THE NEW REVISED PANEL SCHEDULE SUBMITTED AND THE
 NOTES ADDED TO PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE PLANS INDICATE CIRCUITS WHICH ARE NOT ON
 PANEL SCHEDULE(S). IN FACT, THESE CIRCUITS ON PANEL
 SCHEDULES ARE SHOWN AS SPARES??
 PLEASE ADJUST.
  
 16) NOTE: OK.
  
 17) NOTE: OK/NO. PLEASE SEE THE FIXTURE(S) SEEM TO HAVE
 BEEN MOVED ON TWO OF THE CLOSETS, HOWEVER NOT ALL.
 PLEASE ALSO SEE EVEN OF A FIXTURE HAS BEEN MOVED TO THE
 WALL ABOVE DOOR, AS THE FIXTURE DESCRIPTION IS NOT
 INDICATED ON SYMBOL LEGEND, THEN AT THIS TIME IT IS NOT
 KNOWN WHETHER OR NOT THESE FIXTURE MOVED MEET CODE AS
 OF YET. PLEASE SEE ALL CLOSETS WITH STORAGE CONTAINING
 EASILY IGNITABLE MATERIALS AND COMBUSTIBLES MUST MEET
 THIS SECTION.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SEE 410.8 FOR THE MINIMUM REQUIRED CLEARANCES
 FOR CLOSET LT'S.
 PLEASE SEE CODE AS A 18" ASSUMED SHELVING LINE IS
 SHOWN.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE: NO, SAME NOTE. PLANS ARE REQUIRED TO SHOW
 SERVICE AS SHOWN ON RISER ON PLANS. PLANS ONLY SHOW ONE
 DISCONNECT AND ONE METER.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #4**
 PLEASE SHOW ALL METERS/MAINS/SERVICE EQUIPMENT ON
 PLANS.
 RISER SEEMS TO NOW INDICATE SERVICE AS EXISTING,
 HOWEVER THIS LOCATION AND BUILDING DOES NOT SEEM THIS
 IS EXISTING, AND /OR FEEDERS AND SEC'S BEING STILL
 INTACT FROM THE PICTURES OF THIS PROJECT.
 THIS SHOULD BE VERIFIED.
 310.16,240.4,215.5, ETC.
  
  
 ******* NEW NOTES FOR REVIEW #5 ************
 THIS IS DUE TO CHANGES IN PLANS SUBMITTED WHICH WERE
 NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE AS LIGHTING HAS BEEN ADDED TO THE
 PLANS FOR EGRESS AS NOTED ABOVE, PLEASE SEE THESE ARE
 REQUIRED TO BE CIRCUITED AND ALL EMERGENCY LIGHTING
 SHALL BE CIRCUITED PER 700.12E. PLEASE SEE A NOTE WAS
 ADDED WHICH MENTIONS THEY ARE CIRCUITED TO THE "SAME
 ROOM"? AS PLANS DO NOT INDICATE ANY ROOM FOR THIS
 PLEASE ADJUST AND CIRCUIT AS REQUIRED.
 PLEASE ALSO SEE PLANS DO NOT INDICATE ANY MEANS OF
 CONTROL FOR THESE LIGHTS. THIS MUST BE AN AUTOMATED
 CONTROL OF SOME SORT. (PHOTOCELL/ASTRONOMICAL TIME
 CLOCK ETC).
 LS-101 NFPA-101 7.8.1.3, 7.9.2.2 ETC.
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE A HOUSE PANEL ON
 RISER, HOWEVER NO PANEL SCHEDULE WAS SUBMITTED SHOWING
 THE OVER CURRENT PROTECTION DEVICE AND CONDUCTOR SIZES
 ETC.
 PLEASE SUBMIT.
 FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
 NEC 408.4, 240.4, 310.16 ETC.
  
 3) NOTE: PLEASE SEE A NOTE AT THE BOTTOM OF THE LOAD
 CALCULATIONS SUBMITTED NOW CONTAINS A NOTE WHICH
 STATES: ?FEEDER SIZE SHALL BE BASED UPON 175A'S??
 PLEASE CLARIFY THIS NOTE AS IT SEEMS TO BE LOCATED JUST
 BELOW THE CALCULATIONS FOR COMMERCIAL HOUSE PANEL,
 HOWEVER THE HOUSE PANEL IS BEING SHOWN AS 100A?S AND
 SERVICE ENTRANCE CONDUCTORS TAPPED FROM GUTTER ARE
 BASED ON 100A?S.
 THIS NOTE IS UNCLEAR AND IS NOT KNOWN TO THIS REVIEWER
 WHAT IT HAS TO DO WITH ANYTHING AS SUBMITTED AND SHOWN
 ON PLANS.
 FBC ADMIN SECT 106.1.2, NEC 215.5
  
 4) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #15, PLEASE
 CORRELATE ALL CIRCUITING AS SHOWN ON PLANS WITH PANEL
 SCHEDULES. PLEASE SEE DESIGNATIONS FOR BEDROOMS WHICH
 SEEM TO BE REVERSED.
 408.4,
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE DRYER IS BEING SHOWN ON TWO SINGLE
 POLE 20AMP CIRCUITS WHERE THE DRYER IS SHOWN AS A 5KW
 UNIT IN LOAD CALCULATIONS. PLEASE ALSO SEE NOTE CLOUDED
 NOTE AREA ON THE UPPER RIGHT HAND CORNER OF THE PLANS
 ON E-2 AND E-2 INDICATE THE REQUIRED CIRCUITS AND THE
 NOTE FOR THE DRYER DOES NOT CORRELATE.
 PLEASE RE-FIGURE THE MINIMUM OVER CURRENT PROTECTION
 FOR THIS AS, 5KW AT 240V IS HIGHER THAN 20A'S AS SHOWN.
 PLEASE ALSO SEE THIS WOULD NOT BE ON TOW 1-POLE
 CIRCUITS.
 240.4, 310.16, 220.18, 422 ETC
  
 6) NOTE: PLEASE SEE RANGE LOAD IS SHOWN AT 33A'S.
 PLEASE SEE 8KW @ 240V'S. MAY GO UP, HOWEVER MAY NOT GO
 DOWN ON THE FINAL OUT COME OF THAT FIGURE WHEN THE
 CALCULATIONS ARE DONE.
 PLEASE SEE 220.31, 220.19 ETC
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE IS LABELED AS
 3-PHASE ON SCHEDULE, YET THE PANEL AND SERVICE IS
 SINGLE PHASE??
 PLEASE SEE PHASE? A, B, C BEING SHOWN??
 PLEASE CORRELATE.
 408.4, 230.70
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE PANEL DESIGNATIONS ON PLANS HAVE
 NOW BEEN CHANGED. PLEASE SEE PLANS INDICATE AN "F" IN
 FRONT OF ALL THE PANELS. (EXAMPLE) FA, FB, FC AND FD,
 YET PANEL SCHEDULE AND CIRCUITING INDICATES A, B, C AND
 D ONLY.
 WHERE DOES THE F COME INTO THE DESIGN?
 NEC 408.4,
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE NOTE #6 FROM 4TH REVIEW WHICH SPOKE
 OF THE MULTIPLE CIRCUITS FOR THE DISHWASHER, YET THE
 DISHWASHERS WERE REMOVED.
 PLEASE SEE CLOUDED AREA ON UPPER RIGHT HAND SIDE OF
 PLANS WHICH INDICATE CIRCUITS REQUIRED WHICH STILL
 MENTIONS DISHWASHER(S)?
 THIS IS NOT CLEAR AS LETTER MENTIONS REMOVED, YET NOTED
 ON PLANS AS BEING REQUIRED.
 PLEASE CORRELATE AND COMPLETE SCOPE WHICH IS BEING
 DONE.
 408.4, 310.16,
 FBC ADMIN SECTION 106.1.2
  
 10) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS.
 PLEASE ALSO KNOW THAT ONE SET OF EACH ELECTRICAL HAVE
 NOW BEEN RETAINED.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2006-09-16 Time 19:34 Sent To  
Notes
2006-09-17 00:00:00REVIEW COMMENCED
 ******** UNSAT 4TH REVIEW ********
  
 *** PLEASE SEE COMPLETELY NEW PLANS ARE
 BEING SUBMITTED AND COMMENTS ARE BEING
 TYPED AS NEW ALTHOUGH MANY OF THE SAME
 COMMENT FROM THE PREVIOUS THREE REVIEWS
 ARE THE SAME.
 THESE SUBMITTED PLANS ARE NOW DONE BY A
 NEW DESIGNER OF RECORD.
  
 1) NOTE: PLEASE SEE THE PERMIT
 APPLICATION SUBMITTED BACK IN IN FACT A
 PHOTO-COPY OF THE ORIGINAL APPLICATION.
 MUST SUBMITTED THE ORIGINAL APPLICATION
 FOR PROCESSING AND PERMITTING OF
 PROJECT.
  
 2) NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS FOR ENGINEERING
 FIRM PER FAC 61G15-23.002.
 FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THIS
 REQUIRES THE PLANS TO BE SIGNED WITH
 LEGAL SIGNATURE. PLANS SEEM BE SIGNED
 WITH WHAT APPEARS TO BE INITIALS, IF
 INDEED THIS IS THE LEGAL SIGNATURE,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION. LETTER
 IS ALSO REQUIRED TO BE PROPERLY
 NOTARIZED UNDER FS 117.05.
 PLEASE KNOW THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FURTHER REFERENCE.
  
 4) NOTE: PLEASE SEE MISSING TWO MINIMUM
 SMALL APPLIANCE CIRCUITS FROM PLANS, AND
 PANEL SCHEDULES, ALTHOUGH THESE ARE
 NOTED IN LOAD CALCULATIONS??
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 5) NOTE: PLEASE SEE THAT ALL
 CIRCUITS/RECEPTS IN AREAS IN
 CONSIDERATION OF 210.52B1, SHALL ALSO BE
 FIGURED. 210.11C1,220.16 PLEASE ADJUST
 CALCS.
  
 6) NOTE: PLEASE SEE UNITS WHICH CIRCUIT
 AND INDICATE MORE THAN ONE RECEPT FOR
 THE DISHWASHER???
 PLEASE SEE ALSO WHERE OF THE TWO
 RECEPTS, SOME ARE SHOWN BOTH AS GFI AND
 SOME UNITS ONLY SHOW ONE??
 PLEASE SEE SOME UNITS ALSO SHOW RECETPS
 LOCATED OUTSIDE ON THE DISHWASHER
 CIRCUIT(S)??
 PLEASE REVISE AND ADJUST ALL.
  
 7) NOTE: PLEASE LIST ARC FAULT
 PROTECTION ON THE PANEL SCHEDULE FOR ALL
 OUTLET LOCATED ON BEDROOMS. PLEASE SEE
 2002 NEC 210.12, WHICH REQUIRES AFP FOR
 ALL, NOT ONLY RECEPTS AS SHOWN ON PLANS.
  
 8) NOTE: PLEASE CLARIFY A/C'S?? PLEASE
 SEE LOAD CALCS ONLY INDICATE 1800VA??
 YET LOAD ON PANEL SCHEDULE IS HIGHER?
 PLEASE VERIFY HEAT / COLLING ETC
 PLEASE ALSO SEE CALCS MENTIONS, "A/C AT
 100% OR", ? WHAT IS THE OR/
 220.31
  
 9) NOTE: PLEASE SEE NEC FOR LOAD
 CALCULATIONS. PLEASE SEE TOTAL ON PANEL
 SCHEDULES DO NOT CORRELATE WITH
 CALCULATIONS. PLEASE SEE DERATING TWICE
 IS NOT PERMITTED. THE TOTAL LOAD ON EACH
 PANEL MAY DERATED FOR PANEL, BUT NOT FOR
 TOTALS FOR THE TABLE DE-RATINGS IN
 220.32
 PLEASE SEE THE HOUSE LOADS ARE TO BE
 SHOWN SEPARATELY, AND ADDED TO TOTAL.
 PLEASE SEE NEC 220, ALL.
 PLEASE SEE ALL OTHER COMMENTS AS THE
 LOADS WILL BE CHANGING.
 215.5, 220,
 FBC ADMIN SECT 106.1.2
  
 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW MAINS. 110.9.
 106.1.2 FBC ADMIN SECT.
  
 11) NOTE: PLEASE SEE RISER NOTES FEEDERS
 FROM HOUSE PANEL. WHERE ARE THESE GOING
 ?
 PLEASE VERIFY AND COMPLETE.
 215.5
  
 12) NOTE: PLEASE SEE GROUNDING ELECTRODE
 RISER INDICATE FOOTER STEEL TO BE PART
 OF THE GE SYSTEM?
 PLEASE KNOW IN NEW CONSTRUCTION IT IS
 AVAILABLE AND IS REQUIRED TO BE A PART
 OF THE SYSTEM, HOWEVER PLEASE SEE THAT
 THIS IS AN EXISTING BUILDING AND
 ATTACHING TO THE EXISTING FOOTER IS NOT
 REQUIRED, HOWEVER MAY BE DONE. PLEASE
 KNOW, THIS MAY AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING.
 ** PLEASE SEE THE NEC CODES BEING
 REFERENCE ARE NOT FROM THE CURRENT NEC
 2002. PLEASE REVISE.
 PLEASE KNOW, SINCE EXISTING FOOTER STEEL
 CAN NOT BE VERIFIED EVEN IF THE
 ATTACHMENT IS MADE, A MIN OF TWO GRNDS
 RODS WILL BE REQUIRED.
 250.50, 250.56
  
 13) PLEASE SEE MISSING LIGHTING FOR
 EGRESS STAIRS PER LS 101 7.8.1.3,
 7.9.2.2.
 PLEASE NOTE AND SHOW A MIN OF 10FT
 CANDLES REQUIRED FOR STAIRS UNDER
 NORMAL, AND 1FT CANDLE MIN REQUIRED
 UNDER EM POWER.
 PLEASE SHOW.
  
 14) NOTE: PLEASE SEE MISSING THE
 REQUIRED DEDICATED BATH(S) CIRCUIT(S) AS
 REQUIRED PER 210.52D,210.11C3, MUST BE
 20A AND #12 AWG.
  
 15) NOTE: PLEASE SEE PLANS INDICATE
 CIRCUITS WHICH ARE NOT ON PANEL
 SCHEDULE(S). IN FACT, THESE CIRCUITS ON
 PANEL SCHEDULES ARE SHOWN AS SPARES??
 PLEASE ADJUST.
  
 16) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR HWH, PER 422.31.
  
 17) NOTE: PLEASE SEE 410.8 FOR THE MIN
 REQUIRED CLEARANCES FOR CLOSET LT'S.
 PLEASE SEE CODE AS A 18" ASSUMED
 SHELVING LINE IS SHOWN.
  
 18) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS AS THE "S" SHEETS DID NOT GET
 SIGNED, DATED OR SEALED BY THE
 STRUCTURAL ENGINEER AS LISTED.
 THIS IS ONLY NOTED, AND NOT AN
 ELECTRICAL ITEM.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING
 CODES AT A MINIMUM IS STATED ON THE
 ELECTRICAL PLANS.
 2002 NFPA-70 (NEC), NFPA-101 2003, 2002
 NFPA-72.
  
 20) NOTE: PLEASE SHOW ALL
 METERS/MAINS/SERVICE EQUIPMENT ON PLANS.
 RISER SEEMS TO NOW INDICATE SERVICE AS
 EXISTING, HOWEVER THIS LOCATION AND
 BUILDING DOES NOT SEEM THIS IS EXISTING,
 AND /OR FEEDERS AND SEC'S BEING STILL
 INTACT FROM THE PICTURES OF THIS
 PROJECT.
 THIS SHOULD BE VERIFIED.
 310.16,240.4,215.5, ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-09-16 00:00:00IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 19:15 Sent To  
Notes
2006-03-06 00:00:00*********** UNSAT 3RD REVIEW *******
  
  
 1)NOTE: PLEASE SEE THE EXACT SAME PLANS
 SUBMITTED ON PREVIOUS REVIEW ARE BEING
 SUBMITTED ONCE AGAIN WITHOUT ARCHITECT
 AS REQUIRED UNDER FS 481.229.
 PLEASE SEE NO CORRECTIONS WERE AMDE TO
 PLANS FOR CODE COMPLIANT COMMENTS.
  
 ** PLEASE HAVE AN ARCHITECT DRAWN UP
 PLANS WITH MIN INFORMATION AS REQUIRED
 PER NFPA-70.
 ** PLEASE HAVE PLANS DRAWN WITH
 DRAFTSMAN QUALITY.
 ** PLEASE ADDRESS ALL PREVIOUS CODE
 COMMENTS.
  
 2)NOTE: PLEASE SEE NOTICE OF
 COMMENCEMENT SUBMITTED HAS SINCE
 EXPIRED. PLEASE SEE FS 713.13(2,IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING NOC, THE NOC SHALL BECOME VOID
 AND WILL BE REQUIRED TO BE RE-RECORDED.
 PLEASE SEE NOC SUBMITTED WAS RECORDED IN
 JUNE 05.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT PLANS SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 13.27 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 11:22 Sent To  
Notes
2005-12-21 00:00:00*********** UNSAT ***************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 1)NOTE:PLEASE SEE FS BELOW ,AS SCOPE
 OF WORK REQUIRES PLANS TO BE DONE BY ANY
 ARCHITECT AT A MIN.
 PLEASE ALSO SEE FBC 104.6.3.4.3 WHICH,
 WHEN NOT REQUIRED TO BE DONE ANY
 ARCHITECT, REQUIRES THE CONTRACTOR
 DESIGNING PLANS TO PRINT NAME AND SIGN
 ALL SHEETS OF SAID DOCUMENTS. PLEASE SEE
 FS 481.229 W
 PLEASE SEE ALL COPIES OF ENGINEERING,
 PLANS SPECS ETC MUST BE SIGNED, DATED
 AND SEALED WITH ORIGINAL SIGNATURE,
 RAISED SEAL. PLEASE SEE BLDG REVIEW
 COMMENTS FOR ENGINEERING DETAILS
 SUBMITTED WHICH ARE PHOTOCOPIES OF
 SIGNED AND SEALED DETAILS,
 FS 471.025,FAC 61G15-23.002
  
 2)NOTE:OK
  
 3)NOTE: OK, HOWEVER SEE NEW NOTE FOR
 GROUNDING ELECTRODE CONDUCTOR
  
  
 4)NOTE: PLEASE SEE SOME EELCTRICAL
 DEVICE FOR WHAT APPEARS TO BE ITEMS FROM
 HOUSE PANEL, ARE NOT CIRCUITED ON PLANS.
 PLEASE SEE REDLINED PLANS.
 PLEASE SEE PLANS SEEM TO LABEL ALL UNITS
 ARE TYPICAL.
 PLEASE SEE NOW AN EGRESS STAIR ETC IS
 SHOWN WIHT NEW LTS.
 PLEASE SEE LS-101 7.8 WHICH REQUIRES A
 MIN OF BATTERY BACK UP LIGHTING TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE SEE THAT A MIN OF 10 FT CANDLES
 UNDER NORMAL POWER IS REQUIRED, MAY BE
 RATED AT 1FT CANDLE UNDER EMERGENCY
 OWER.
  
 5)NOTE:OK
  
 6)NOTE:OK
  
 7)NOTE: OK, HOWEVER PLEASE SEE TWO BATH
 GFI CIRCUITS SHOWN ON PANEL SCHEDULE,
 AND PLANS ONLY SHOW ONE BATHRM.
  
 8)NOTE: OK
  
 9)NOTE: OK
  
 10)NOTE: OK
  
 11)NOTE: OK
  
 12)NOTE: OK
  
 13)NOTE: OK
  
 14)NOTE: OK
  
 15)NOTE:NO, NOTHING COULD BE LOCATED
 ON PLANS FOR DEVICES MEETING THESE
 REQUIREMENTS.
 PLEASE SEE FAIR HOUSING ACT
 REGUALTIONS,24 CFR 100.205 FOR MIN
 HEIGHTS ON DEVICES AND LOCATIONS.
  
 NEW NOTE:
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR SHALL BE SIZED ACCORD TO
 250.66 A 1/0 MIN WILL BE REQUIRED FOR
 500MCM.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By pschmitz Date 2005-08-27 Time 12:51 Rev Time 1.25
Received By dpalmer Date 2005-08-11 Time 07:05 Sent To  
Notes
2005-08-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT PLANS FOR COMPLETE
 SCOPE OF WORK BEING DONE. PLEASE SEE FS
 481.229 WHICH REQUIRES PLANS TO BE DONE
 AN ARCHITECT. PLANS MUST BE SIGNED,
 DATED AND SEALED.
 PLEASE SEE ALL COPIES OF ENGINEERING,
 PLANS SPECS ETC MUST BE SIGNED, DATED
 AND SEALED WITH ORIGINAL SIGNATURE,
 RAISED SEAL. PLEASE SEE BLDG REVIEW
 COMMENTS FOR ENGINEERING DETAILS
 SUBMITTED WHICH ARE PHOTOCOPIES OF
 SIGNED AND SEALED DETAILS,
 FS 471.025,FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE CONDUIT FILL FOR 1"
 SCHEDULE 80 PVC IS EXCEEDED WITH
 CONDUCTORS AS SHOWN.
 PLEASE ADJUST.300.17
  
 3)NOTE: PLEASE SEE NOTES MENTION 350 MCM
 IS REATED FOR 350A'S. PLEASE SEE 110.14,
 UNLESS ALL EQUIPMENT , LUGS ETC ARE
 RATED FOR 90 DEGREES, ONLY THE 75 DEGREE
 COL FOR AMPERE RATINGS MAY BE USED.
 PLEASE SEE A 400A RATED SERVICE IS BEING
 SUPPLIED, SEC'S ARE TO BE RATED AT A MIN
 FOR 400A'S. (500MCM)
 240.4,310.16
  
 4)NOTE: PLEASE SUBMIT COMPLETE PLANS
 SHOWING ALL CIRCUITING AND CORRELATE
 WITH PANEL SCHEDULE(S) TO BE SUBMIITED.
 PANEL SCHEDULE SHALL CONTIAN ALL MIN
 CIRCUITING AS REQUIRED PER NEC 2002.
 PLEASE SEE PLANS MISSING WALL AREAS ON
 LOWER UNITS.
 PLEASE SEE PLANS MENTIONS SAME AS ABOVE,
 HOWEVER PLEASE SEE THAT SECOND FLR UNITS
 ARE REQUIRED TO MENAS OF EGRESS LIGHTING
 PER 210.70, LS 101 5-8
  
 5)NOTE: PLEASE SEE PLANS INDICATE GAS
 WATER HEATER AND WALL HEATER, HOWEVER,
 LOAD CALCS INDICATE ELECTRIC??
 PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIRED. LOAD
 CALCULATION INDICATE TWO, HOWEVER PLANS
 ONLY INDICATE ONEAND ONE CIRCUIT?
 210.52B1,210.11C1,220.16
  
 7)NOTE: PLEASE ALSO INDICATE THE MIN
 DEDICATED BATH(S) CIRCUIT(S).
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE BATH RM BEING SHOWN ON WITH
 SD'S AND GEN LTS?
  
 8)NOTE: PLEASE SEE 210.11C2, 220.16
 WHICH REQUIRES A MIN OF ONE LAUNDRY
 CIRCUIT. IF GEN FACILITIES ARE SUPPLIED
 PLEASE SHOW ON PLANS.
  
 9)NOTE: PLEASE SEE ALL CONTINUOUS
 "HOUSE" LOADS SHALL BE SHOWN @ 125%.
 215.3.230.42 ETC.
  
 10)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN FROM
 METER TO MAINS/FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE 250.6, AN "EQUIPMENT
 GROUNDING" CONDUCTOR IS ONLY AFTER THE
 FIRST MEANS OF DICSONNECT.
 250.24
  
 11)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE OF CLOST LIGHTING FIXTURES.
  
 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 13)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 210.12
  
 14)NOTE: PLEASE SEE RANGE IS SHOWN ON
 LOAD CALCULATIONS, HOWEVER PLANS MENTION
 NIC?
 PLEASE CORRELATE.
  
 15)NOTE: PLEASE SEE FAIR HOUSING ACT
 REGUALTIONS,24 CFR 100.205 FOR MIN
 HEIGHTS ON DEVICES AND LOCATIONS.
 PLEASE SHOW.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICLA PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 20:04 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 19:42 Sent To  
Notes
2007-07-26 20:04:30*****UNSAT*****
  
 SHEETS A-3, E-1, AND E-2 WERE STAMPED, INITIALED, AND
 DATED AS APPROVED ON 02/23/2007;HOWEVER THE REVISED
 DRAWINGS NEED TO BE RECTIFIED AS LISTED BELOW:
  
  
 1.ON DRAWING A-3,NO UNIT LETTER SHOWN/DISPLAYED ON
 THE UPPER APT./UNITS.
  
 2.ON DRAWING A-3, SINCE THIS AN EVEN NUMBERED
 ADDRESSED BUILDING, THE FRONT OF THE STRUCTURE IS AT
 THE NORTH ELEVATION.
  
 3.COULD YOU PLEASE EXPLAIN THE REFERENCE TO UNIT 6F
 ATTACHED TO THE ADDRESS AND ITS RELEVANCE?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-11-16 Cont ID  
Sent By mawillia Date 2006-11-16 Time 09:04 Rev Time 0.00
Received By mawillia Date 2006-11-16 Time 09:04 Sent To  
Notes
2006-11-16 09:26:30*****PROVISO*****
  
  
  
  
 1.PLEASE SHOW THE ADDRESS OF THE PROPOSED STRUCTURE
 ON THE ELEVATION SHEET.BE ADVISED THAT THE
 APARTMENT/UNIT ALPHABET OR NUMBER FOR THE FRONT
 ENTRANCE SHOULD NOT BE ON THE DOORS, BUT INSTEAD ON THE
 BUILDING ABOVE OR NEAR THE DOOR OPPOSITE OF THE SWING
 OF THE DOOR.IF THE UNITS ARE EQUIPPED WITH REAR
 DOORS, THE ALPHABET OR NUMBER MAY BE ON THE DOOR.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-804-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-09-22 Cont ID  
Sent By mawillia Date 2006-09-22 Time 09:12 Rev Time 0.00
Received By mawillia Date 2006-09-22 Time 09:12 Sent To  
Notes
2006-09-22 00:00:00*****UNSAT*****
  
  
  
  
 1.) SHOW/DISPLAY THE ADDRESS ON THE
 STRUCTURE AS WELL AS THE APT/UNIT NUMBER
 OR ALPHABET. AS PER WEST PALM BEACH
 CODE, THE NUMERICAL ADDRESS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNITS SHALL BE NO
 LESS THAN 3" IN HEIGHT.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.)ENTRANCES, CORRIDORS, AND EXITS ARE
 TO BE CLEAR AND UNOBSTRUCTED.
  
 4.) INTERIOR WALLS AND CEILING SHALL BE
 CLASS "A" OR CLASS "B".
  
 5.) PLEASE SHOW THE LOCATION OF 2A10BC
 RATED FIRE EXTINGUISHERS, WHETHER
 INTERIOR OR EXTERIOR.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 13:42 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 13:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 10:18 Rev Time 0.00
Received By mwennerg Date 2005-08-31 Time 10:18 Sent To  
Notes
2005-08-31 00:00:00******DENIED******
  
 1) PLANS SHOW SMOKE DETECTORS OUTSIDE
 THE SLEEPING ROOMS. IN ACCORDANCE WITH
 NFPA 101, SECTION 30.3.4.5.2, SMOKE
 DETECTORS ARE REQUIRED INSIDE SLEEPING
 ROOMS IN ADDITION TO OUTSIDE UNLESS THE
 BUILDING IS FIRE SPRINKLERED. "ANY
 ALTERATION OR ANY INSTALLATION OF NEW
 EQUIPMENT SHALL MEET AS NEARLY AS
 PRACTICABLE, THE REQUIREMENTS FOR NEW
 CONSTRUCTION", NFPA 101, SECTION 4.6.8.
  
 2) PLEASE SHOW LOCATIONS OF 2A-10B,C
 RATED FIRE EXTINGUISHERS. INSTALLATION
 SHALL NOT EXCEED 75' TRAVEL DISTANCE
 REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By kstevens Date 2007-09-29 Time 06:39 Rev Time 0.00
Received By kstevens Date 2007-09-28 Time 18:54 Sent To  
Notes
2007-09-29 06:48:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ONLY U/G PIPE
 INDICATED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--TOTAL BTU LOAD NOT CORRECT.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).-- BOTH RISERS CAN NOT BE
 THE SAME TOTAL DEVELOPED LENGTH.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. FOR THE W/H.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. SEPARATE GAS PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 08:43 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 08:43 Sent To  
Notes
2007-09-25 15:53:33TO "COMM" BD#29--EXPEDITED--
2007-09-13 08:43:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 16:28 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 16:28 Sent To B
Notes
2007-07-05 16:28:53TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 16:28 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 16:28 Sent To B
Notes
2007-06-19 16:28:30TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 14:36 Sent To  
Notes
2007-06-29 10:53:33TO "COMM" BD#13
2007-06-15 14:36:25WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 10:37 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 10:37 Sent To B
Notes
2007-05-08 10:38:10TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 10:25 Sent To B
Notes
2007-04-25 10:26:18TO "JWITMER" DESK/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 12:01 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 12:01 Sent To E
Notes
2007-02-22 12:01:57TO "DPALMER" DESK/EXPEDITED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 10:06 Sent To  
Notes
2006-12-22 10:06:47TO "COMM" BD#36--EXPEDITED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 14:57 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 14:57 Sent To B
Notes
2006-11-09 14:58:24TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 14:46 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 14:46 Sent To  
Notes
2006-09-14 00:00:00TO "COMM" BD#2--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 19:04 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 19:04 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#24
2006-02-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 14:37 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 14:30 Sent To  
Notes
2005-12-02 00:00:00TO "COMM" BD#12
2005-11-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-08-31 Time   Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 11:07 Sent To  
Notes
2005-08-03 00:00:00TO "COMM" BD#34

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-10-05 Cont ID  
Sent By kstevens Date 2007-09-29 Time 06:38 Rev Time 0.00
Received By kstevens Date 2007-09-28 Time 18:54 Sent To  
Notes
2007-09-29 06:38:57REVISIONS OK - SHTS P-1, P-2 & P-3

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-07-30 Cont ID  
Sent By pschmitz Date 2007-07-30 Time 09:42 Rev Time 0.00
Received By pschmitz Date 2007-07-30 Time 09:42 Sent To PC
Notes
2007-07-30 09:56:10PLUMBING PLAN REVIE DENIED
  
  
 PREVIOUS COMMENT BY KEN STEVENS NOT ADDRESSED DATED
 01-02-07
 WATER RISER DIAGRAM PAGE P-2
  
 WATER HAMMER ARRESTORS ARE REQUIRED AT THE AUTOMATIC
 CLOTHES WASHERS. PLEASE SHOW ON DRAWING.
 ****** RESPONSE NOTED, BUT THE ARRESTORS ARE NOT SHOWN
 ON BOTH THE HOT AND COLD WATER SUPPLIES. ( ONLY THE
 COLD) .
 PLEASE SHOW ON BOTH SUPPLY LINES. SECTION 604.9
  
 REVIEW BY PAUL SCHMITZ 561-805-6692

Review Stop P PLUMBING
Rev No 7 Status P Date 2007-02-24 Cont ID  
Sent By pschmitz Date 2007-02-24 Time 06:07 Rev Time 0.00
Received By pschmitz Date 2007-02-24 Time 06:04 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-01-02 Cont ID  
Sent By kstevens Date 2007-01-02 Time 16:31 Rev Time 0.00
Received By kstevens Date 2007-01-02 Time 16:31 Sent To  
Notes
2007-01-02 16:41:47DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW BY JOHN LEECH:
  
 4. ENGINEER IS REQUIRED TO SIGN PLANS, NOT INITIAL.
 ****RESPONSE NOTED, BUT P-3 STILL NOT SIGNED. FAC
 61G15-23.002(2) & FS 471.2055.
  
 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE
 SHOW ON DRAWING.
 ****RESPONSE NOTED, BUT THE ARRESTORS ARE NOT SHOWN ON
 BOTH THE HOT AND COLD WATER SUPPLIES. (ONLY THE COLD).
 PLEASE SHOW ON BOTH SUPPLY LINES. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-11-17 Cont ID  
Sent By jleech Date 2006-11-17 Time 07:32 Rev Time 0.00
Received By jleech Date 2006-11-17 Time 07:32 Sent To B
Notes
2006-11-17 07:41:52DENIED;
 1. AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR
 PLAN, PAGE A-1 AND A-2. PLEASE ADD.
 2. AUTOMATIC CLOTHES WASHERS BRANCH DRAIN IS REQUIRED
 TO BE 3". FBC-2004 PLUMBING SECTION 406.3.
 3. PLEASE SIZE ALL PIPING ON RISER DIAGRAMS.
 4. ENGINEER IS REQUIRED TO SIGN PLANS NOT INITIAL.
 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE
 SHOW ON DRAWING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-09-23 Cont ID  
Sent By pschmitz Date 2006-09-23 Time 11:29 Rev Time 0.00
Received By pschmitz Date 2006-09-23 Time 11:29 Sent To  
Notes
2006-09-23 00:00:00PAUL SCHMITZ, PLUMBING PLANS EXAMINER
 [email protected]
 FBC PLUMBING 2001
 DENIED
 1) SHT P-1
 TABLE 403.1 MINIMUM FACILITIES
 ONE AUTOMATIC CLOTHES WASHER CONNECTION
 REQUIRED PER UNIT (E)
 2) SHT P-2
 WATER RISER
 ?P604.9 WATER HAMMER. THE FLOW VELOCITY
 OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER.A WATER-
 HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED,
 UNLESS OTHERWISE APPROVED.THE ARRESTOR
 SHALL BE LOCATED WITHIN AN
 EFFECTIVE RANGE OF THE QUICK-CLOSING
 VALVE.WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.ACCESS SHALL BE
 PROVIDED TO WATER-HAMMER ARRESTORS.
 3) SHT P-3
 WATER HEATER DETAIL RELIEF VALVE.
 ?P504.7.1 DISCHARGE. THE RELIEF VALVE
 SHALL DISCHARGE FULL SIZE TO A
 SAFE PLACE OF DISPOSAL SUCH AS THE
 FLOOR, OUTSIDE THE BUILDING OR AN
 INDIRECT WASTE RECEPTOR.THE
 DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED
 SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER.
 THE DISCHARGE SHALL BE INSTALLED IN A
 MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY TO OCCUPANTS IN THE IMMEDIATE
 AREA OR STRUCTURAL DAMAGE TO THE
 BUILDING.
 4) WATER HEATER PAN DRAIM SIZE.
 ?P504.8.1 PAN SIZE AND DRAIN. THE PAN
 SHALL NOT BE LESS THAN 1-1/2
 INCHES (38 MM) DEEP AND SHALL BE OF
 SUFFICIENT SIZE AND SHAPE TO RECEIVE
 ALL DRIPPING OR CONDENSATE FROM THE
 TANK OR WATER HEATER.THE PAN SHALL
 BE DRAINED BY AN INDIRECT WASTE PIPE
 HAVING A MINIMUM DIAMETER OF 3/4
 INCH.
  
 END OF COMMENTS
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-25 Cont ID  
Sent By pschmitz Date 2006-03-25 Time 11:07 Rev Time 0.00
Received By pschmitz Date 2006-03-25 Time 11:06 Sent To  
Notes
2006-03-25 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 DENIED
 1)
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)
 SEE PREVIOUS NOTES FROM OTHER TRADES.
  
 3)
 REMOVE SHEETS ADDRESSING PLUMBING THAT
 ARE NOT SIGNED AND SEALD BY ENGINEER OF
 RECORD, OR HAVE THEM SIGNED AND SEALED.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 08:36 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 08:36 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
 SEE COMMENT #1 OF THE ELECTRICAL PLAN
 REVIEW. PLANS TO BE DESIGNED BY A
 PROFESSIONAL ARCHITECT WHERE REQUIRED
 AND PLANS TO HAVE PRINTED NAME AND
 SIGNATURE WHERE NOT REQUIRED BY FS.
 481.2055 & SECTION 104.2.1 & 104.2.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-27 Cont ID  
Sent By pschmitz Date 2005-08-04 Time 18:08 Rev Time 0.00
Received By pschmitz Date 2005-08-27 Time 12:51 Sent To  
Notes
2005-08-27 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC 2001
 DENIED
 !.SEE NOTES FROM ELECTRICAL PLAN
 REVIEW.
 PLANS TO BE SIGNED AND SEALED.
 END OF COMMENTS
  