Plan Review Details - Permit 05080070
Plan Review Stops For Permit 05080070
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-14 Cont ID  
Sent By jgomez Date 2005-09-14 Time 16:21 Rev Time 0.33
Received By jgomez Date 2005-09-14 Time 16:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-02 Cont ID  
Sent By jgomez Date 2005-09-02 Time 12:53 Rev Time 0.33
Received By jgomez Date 2005-09-02 Time 12:53 Sent To PC
Notes
2005-09-02 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- ACCORDING TO ANCHOR CHART #7 ON SHEET
 5 OF 5:SOME ANCHORS NEED TO BE SPACED
 AT 18"O.C. NOT 24"O.C. (SEE OPENINGS #7
 AND #8) AND REVISE AS REQUIRED.
 *INSTALLATION SCHEDULE WAS NOT REVISED
 TO REFLECT THIS CHANGE.
  
 2- RESPONSE TO COMMENT 2(B) FROM
 PREVIOUS CHECKLIST WAS THAT OPENINGS 2
 THRU 6 WERE FOR CONCRETE TOP AND
 CONCRETE BLOCK BOTTOM ANCHORS. BUT,
 INSTALLATION SCHEDULE WAS NEVER REVISED
 TO REFLECT THIS CHANGE. REVISE AS
 REQUIRED.
  
 3- FOLDING SHUTTER CORPORATION COVER
 PAGE INDICATES THAT PRODUCT APPROVAL
 COMPLIANCE REPORT IS AN SBCCI REPORT.
 REPORT SUBMITTED IS A DADE COUNTY NOA
 (WHICH, CORRESPONDS TO THE REPORT THAT
 WAS SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL). REVISE COVER PAGE TO REFLECT
 THE DADE COUNTY NOA NOT THE SBCCI.
 NOTE: DADE COUNTY NOA'S AND SBCCI
 REPORTS ARE TWO DIFFERENT REPORTS. WE
 ONLY NEED THE ONE THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By jgomez Date 2005-08-09 Time 08:44 Rev Time 0.50
Received By jgomez Date 2005-08-09 Time 08:43 Sent To PC
Notes
2005-08-09 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY RULE 9B-72 FROM DCA. SEE
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION REGARDING THE MANDATORY
 PRODUCT APPROVALS. ACCORDING TO THE
 BUILDING OFFICIAL DADE COUNTY NOA ALONE
 IS NOT AN STATEWIDE FLORIDA PRODUCT
 APPROVAL. MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL USING THE DADE
 COUNTY NOA BY COMPLETING THE LOCAL
 PRODUCT APPROVAL FORM DOWNLOADED FROM
 WWW.FLORIDABUILDING.ORG.
  
 2- ACCORDING TO ANCHOR CHART #7 ON SHEET
 5 OF 5: A) SOME ANCHORS NEED TO BE
 SPACED AT 18"O.C. NOT 24"O.C. (SEE
 OPEN'G 7 & 8).
 B) CLARIFY WHY OPENINGS 2 AND 3 HAVE 24"
 SPACING ON TOP AND 21" SPACING AT
 BOTTOM. ACCORDING TO CHART #7 BOTH SHALL
 BE SPACED AT 21" O.C.
  
 3- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING AND NO WORK
 IS STARTED. NEED RE-RECORDED N.O.C.
  
 4- FOLDING SHUTTER CORPORATION COVER
 PAGE INDICATES THAT PRODUCT COMPLIANCE
 REPORT IS AN SBCCI REPORT. REPORT
 SUBMITTED IS A DADE COUNTY NOA. REVISE
 AS REQUIRED TO MATCH INFORMATION
 REQUESTED ON ITEM #1 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 14:02 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 14:01 Sent To B
Notes
2005-09-13 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 11:05 Sent To B
Notes
2005-09-01 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 09:57 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 09:57 Sent To B
Notes
2005-08-02 00:00:00TO "MISC" BOX#1