Plan Review Details - Permit 05080069
Plan Review Stops For Permit 05080069
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 13:31 Sent To M
Notes
2006-03-10 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 13:49 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 13:49 Sent To M
Notes
2006-02-28 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-15 Time 13:49 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 15:10 Sent To  
Notes
2006-02-14 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-13 Cont ID  
Sent By tgordon Date 2006-03-13 Time 14:12 Rev Time 0.20
Received By tgordon Date 2006-03-13 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-01 Cont ID  
Sent By tgordon Date 2006-03-01 Time 09:44 Rev Time 0.30
Received By tgordon Date 2006-03-01 Time 09:43 Sent To  
Notes
2006-03-01 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 2/15/06.
 PLANS MUST HAVE (ON ALL SHEETS), STILL
 MISSING COMPANY ADDRESS, PHONE NUMBER,
 LICENSE NUMBER, AND PRINTED NAME OF
 DESIGN PERSON.
  
 2) TWO SETS OF PLANS MUST BE SUBMITTED.
  
 3) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By tgordon Date 2006-02-15 Time 13:35 Rev Time 0.30
Received By tgordon Date 2006-02-15 Time 13:35 Sent To  
Notes
2006-02-15 00:00:00*** DENIED ***
 1) MECHANICAL PLANS MUST HAVE (ON ALL
 SHEETS) JOB ADDRESS, COMPANY NAME,
 ADDRESS, PHONS NUMBER, LIC. NUMBER, NAME
 AND SIGNURE OF DESIGN PERSON.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 2) PLEASE SUBMIT A PROPOSAL SHOWING
 SCOPE OF WORK, AND PRICE SIGNED BY
 CUSTOMER.
  
 3) ONE 6" SUPPLY AIR DUCT GOING TO FIRST
 FLOOR IS FEEDING TWO 6" DUCTS AND ONE 4"
 DUCT, PLEASE EXPLAIN OR CORRECT.
  
 4) PLEASE SHOW SIZE OF RETURN AIR GRILL
 ON MECH. PLANS, AND IF TO SMALL PLEASE
 ENLARGE TO CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  