Plan Review Details - Permit 05080017
Plan Review Stops For Permit 05080017
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-17 Cont ID  
Sent By shill Date 2005-10-17 Time 09:02 Rev Time 1.00
Received By shill Date 2005-10-17 Time 08:48 Sent To PC
Notes
2005-10-17 00:00:00REVISION P1, E1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-02 Cont ID  
Sent By shill Date 2005-09-02 Time 06:41 Rev Time 0.50
Received By shill Date 2005-09-02 Time 06:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-08 Cont ID  
Sent By shill Date 2005-08-08 Time 08:38 Rev Time 0.50
Received By shill Date 2005-08-08 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 16:04 Rev Time 0.25
Received By dpalmer Date 2005-10-08 Time 16:00 Sent To  
Notes
2005-10-08 00:00:00** REDLINED 700.12E FOR EM/EXT LTS.
  
 THESE SHALL BE CIRCUITED TO LOCAL BRANCH
 CIRCUIT FEEDING AREA OF NORMAL LIGHTING.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 18:55 Rev Time 0.25
Received By dpalmer Date 2005-08-04 Time 18:55 Sent To  
Notes
2005-08-04 00:00:00****** PROVISO /NOTES ********
  
  
 1)NOTE: PLEASE SEE PANELS FOR EACH SPACE
 COULD NOT BE LOCATED IN TENANT SPACES ON
 PLANS?
 240.24B
  
 PLANS ARE TO BE REVISED AND SUBMITTED
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED. IN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-10-11 Cont ID  
Sent By mwennerg Date 2005-10-11 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2005-10-11 Time 09:33 Sent To  
Notes
2005-10-11 00:00:00REVISION DATED 9/28/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 10:34 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 10:34 Sent To  
Notes
2005-09-09 00:00:00PLANS SHOW FIRE ALARM DEVICES. SEPARATE
 SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 REMODEL IF APPLICABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By mwennerg Date 2005-08-09 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2005-08-09 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 09:34 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 09:34 Sent To  
Notes
2005-10-04 00:00:00TO "BOB" 5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 16:33 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 16:33 Sent To  
Notes
2005-08-30 00:00:00TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-12 Cont ID  
Sent By kstevens Date 2005-08-12 Time 10:32 Rev Time 0.00
Received By kstevens Date 2005-08-01 Time 11:21 Sent To  
Notes
2005-08-01 00:00:00TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 17:16 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 17:14 Sent To  
Notes
2005-08-03 00:00:00NO PLANS 8/3/05 HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By kstevens Date 2005-09-07 Time 18:16 Rev Time 0.33
Received By kstevens Date 2005-09-07 Time 18:16 Sent To  
Notes
2005-09-07 00:00:00PASSED/PROVISO
  
 INSULATION OF PIPES/NO SHARP EDGES -
 WRIST BLADE HANDLES ON FAUCETS AS SHOWN
 IN RESTROOM REFERENCE NOTE "C' REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By shill Date 2005-08-12 Time 09:11 Rev Time 1.33
Received By kstevens Date 2005-08-12 Time 09:11 Sent To  
Notes
2005-08-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR TOILET ROOMS
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 W/C'S TO BE 18" OFF WALL TO CENTERLINE
 OF FIXTURE, AND LAVS TO BE MIN. 15" OFF
 WALL TO CENTERLINE OF FIXTURE. FIG. 28.
 FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES AND SURFACES
 D. 11-4.19.5 FAUCETS
 2. SHT A-1 DETAIL #4 SHOW THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES AND SURFACES
 D. 11-4.24.7 FAUCETS
 3. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED.- SUBMIT A DETAIL FOR
 DRINKING FOUNTAIN SHOWING COMPLIANCE
 WITH SECTIONS 11-4.1.3(10)(A)
 (PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING), AND
 11-4.15 AND ALL SUBSECTIONS.
 4. SHT P-1 SANT. RISER DIAGRAM. SECTION
 909.1 ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1 -NEW SINKS SHALL CONNECT TO THE
 BLDG DRAIN DOWNSTREAM OF THE BATHROOM
 FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]