Plan Review Details - Permit 05071340
Plan Review Stops For Permit 05071340
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-18 Cont ID  
Sent By alange Date 2005-08-18 Time 08:52 Rev Time 1.66
Received By alange Date 2005-08-18 Time 07:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By btrobaug Date 2006-03-07 Time 12:30 Rev Time 0.50
Received By btrobaug Date 2006-03-07 Time 11:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-17 Cont ID  
Sent By btrobaug Date 2006-02-17 Time 11:13 Rev Time 0.50
Received By btrobaug Date 2006-02-17 Time 07:46 Sent To PC
Notes
2006-02-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE COMPLETE THE LOAD
 CALCULATIONS. SHOW TOTALS AND INDICATE
 CALCULATION USED. EG: 220.30,220.31.
  
 2} PLEASE INDICATE ROOM DESIGNATION ON
 THE PLANS.
  
 3} PLEASE SHOW ( AND DESIGNATE) ALL
 ELECTRICAL SERVICE EQUIPMENT ON THE
 PLAN.
  
 4} THE PANEL SHOWN INSIDE THE HOUSE IN
 WHAT APPEARS TO BE A CLOSET MUST COMPLY
 WITH 240.24, MAY HAVE TO BE MOVED OR
 MADE TO COMPLY. PLEASEV SEE ARTICLE.
  
 5} PLEASE SEE THAT SMOKE DETECTORS ARE
 REQUIRED BY NFPA-72 8-1.4.2 AND FBC
 905.2.5.
  
 6} RECEPTALE SPACING MUST COMPLY WITH
 210.52(A) & (B). SEE REVIEWED PLAN FOR
 SOME AREAS MISSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-08-10 Cont ID  
Sent By btrobaug Date 2005-08-10 Time 15:41 Rev Time 0.50
Received By btrobaug Date 2005-08-10 Time 12:48 Sent To M
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-07-29 Cont ID  
Sent By dalvarez Date 2005-07-29 Time 16:23 Rev Time 0.15
Received By dalvarez Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 15:56 Sent To E
Notes
2006-02-16 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 09:57 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 09:56 Sent To E
Notes
2005-08-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-18 Cont ID  
Sent By alange Date 2005-08-18 Time 08:52 Rev Time 0.00
Received By alange Date 2005-08-01 Time 08:09 Sent To  
Notes
2005-08-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By tgordon Date 2006-03-07 Time 14:09 Rev Time 0.30
Received By tgordon Date 2006-03-07 Time 14:09 Sent To  
Notes
2006-03-07 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By pkrauss Date 2005-08-22 Time 09:26 Rev Time 0.45
Received By pkrauss Date 2005-08-22 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By pkrauss Date 2005-08-15 Time 08:05 Rev Time 0.35
Received By pkrauss Date 2005-08-15 Time 06:48 Sent To B
Notes
2005-08-15 00:00:00DENIED:
 1.PLAN SHEET MP-1, MISSING DUCT SIZES
 FOR THE BRANCH DUCTS AND ALSO ONE GRILLE
 SIZE.
  
 2.PLAN SHEET MP-1, MECHANICAL NOTE
 INDICATES 4" SLAB FOR THE CONDENSER.
 PER 2001 FBC(M)304.7, SLAB SHALL EXTEND
 A MINIMUM OF 2" ABOVE THE ADJOINING
 GRADE.
  
 3.AUXILIARY DRAIN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By mmclean Date 2005-08-09 Time 15:44 Rev Time 0.00
Received By mmclean Date 2005-08-09 Time 15:44 Sent To I
Notes
***NONE***