Plan Review Details - Permit 05071332
Plan Review Stops For Permit 05071332
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-29 Cont ID  
Sent By alange Date 2005-08-29 Time 09:33 Rev Time 0.33
Received By alange Date 2005-08-29 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-26 Cont ID  
Sent By btrobaug Date 2005-09-26 Time 15:51 Rev Time 0.50
Received By btrobaug Date 2005-09-26 Time 15:51 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By btrobaug Date 2005-08-09 Time 17:30 Rev Time 0.50
Received By btrobaug Date 2005-08-09 Time 17:24 Sent To M
Notes
2005-08-09 00:00:00 
 THE RISER INDICATES THAT THE ONLY WAY
 THE "STANDBY" PANEL COULD BECOME
 ENERGIZED IS DURING NORMAL POWER FROM
 THE METER, OR BACKFED FROM THE METER
 THROUGH THE ATS. PLEASE CLARIFY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 08:43 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 08:43 Sent To E
Notes
2005-09-20 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 16:29 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 16:29 Sent To E
Notes
2005-08-08 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-29 Cont ID  
Sent By alange Date 2005-08-29 Time 09:33 Rev Time 0.33
Received By alange Date 2005-07-29 Time 16:41 Sent To  
Notes
2005-07-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-19 Cont ID  
Sent By prafter Date 2005-08-19 Time 08:43 Rev Time 0.50
Received By prafter Date 2005-08-19 Time 08:43 Sent To P
Notes
2005-08-19 00:00:00 
  
  
  
  
 MECH. PLAN REVIEW:
  
 MECH. PROVISO:
  
 ELECT. GENERATOR EXHAUST IS LOCATED
 MININUM OF TEN FEET FROM THE PROPETY LOT
 LINE OR
 FROM ADJACENT BUILDING AND THE EXHAUST
 IS DIRECTED AWAY FROM THE BUILDING.
 THIS MEET INTENT OF MECH. CODE.
  
 2001 FBC/M 804.3.3 TERMINATION.
  
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 378.2.3.2
 EXHAUST SYSTEM TERMINATION.
  
 PAT RAFTER561/805/6728 OR 805/6719
  
 PATTY KRAUSS.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-26 Cont ID  
Sent By kstevens Date 2005-08-26 Time 15:04 Rev Time 0.25
Received By kstevens Date 2005-08-26 Time 15:03 Sent To B
Notes
2005-08-26 00:00:00SEPARATE GAS PERMIT AND PLANS REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-05 Cont ID  
Sent By mmclean Date 2005-08-05 Time 11:11 Rev Time 0.00
Received By mmclean Date 2005-08-05 Time 11:11 Sent To I
Notes
2005-08-05 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.