Plan Review Details - Permit 05071284
Plan Review Stops For Permit 05071284
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By jwitmer Date 2005-08-10 Time 15:14 Rev Time 4.44
Received By jwitmer Date 2005-08-10 Time 15:14 Sent To M
Notes
2005-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071284
 ADD: 5800 CORPORATE WAY
 CONT: PYRAMID BUILDERS OF PALM
 BEACH, INC.
 TEL: (561)882-3992
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS INDICATE DESIGN TO FL BLDG CODE
 2001, IT WAS AGREED ON THAT THE DESIGN
 CRITERIA WOULD BE TO THE FL 2004 CODE.
 THE 2004 CODE WILL PROVIDE THE DESIGNER
 GREATER LATITUDES IN SESIGN.
  
 3) UNDER THE 2004 CODE REVISIT THE
 MINIMUM BLDG TYPE FOR DESIGN.TABLE 503.
  
 4) SEE 110.1.2* REQUIREMENTS FOR
 CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12.
  
 5) SITE PLAN IS NOT SIGNED NOR SEALED:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
 6) NO PLANS FOR MODULAR BUILDING, PLANS
 ARE TO BE DESIGNED TO:
 2004 FL BLDG CODE. PROVIDE:
 1609.3 BASIC WIND SPEED
 1609.4 EXPOSURE CATEGORY
 1609.5 IMPORTANCE FACTOR
 1609.6 .2 WIND PRESSURES.
 FLOOR PLAN
 CUT SECTIONS THROUGH WALL
 1609.6.3 EDGE ZONES/ END ZONE PRESSURES
 1609.4 MAIN WIND FORCE RESISTING
 SYSTEM
 1609.6.5 COMPONENTS AND CLADDING
 1609.6.7ROOF SYSTEMS
  
 7) PROVIDE DETAILS FOR ACCESSIBILITY
 PATH INCLUDING RAMPS.
  
 8) 13-101 ENERGY CODE CALCULATIONS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
 .
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By mwennerg Date 2005-08-10 Time 14:44 Rev Time 0.00
Received By mwennerg Date 2005-08-10 Time 14:43 Sent To  
Notes
2005-08-10 00:00:00******DENIED******
  
 1) PLEASE INCLUDE MORE INFORMATION FOR
 REVIEW. PLANS DON'T SHOW ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 2) DOES THE FIRE ALARM SYSTEM EXTEND TO
 THE MODULAR CLASSROOM?
  
 3) PLEASE SHOW LOCATIONS OF 2A-10B,C
 RATED FIRE EXTINGUISHERS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-29 Cont ID  
Sent By ptjomsto Date 2005-07-29 Time 09:32 Rev Time 0.00
Received By ptjomsto Date 2005-07-29 Time 09:32 Sent To  
Notes
2005-07-29 00:00:00SUBMITTAL GIVEN TO LUIS MARTINEZ

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By pkrauss Date 2005-08-11 Time 08:11 Rev Time 0.00
Received By pkrauss Date 2005-08-11 Time 08:11 Sent To  
Notes
2005-08-11 00:00:00DENIED:REVIEWED UNDER THE 2004 FBC
 NO MECHANICAL PLANS SUBMITTED OR
 ANALYSIS SUBMITTED FOR REVIEW.PLEASE
 PROVIDE THE FOLLOWING INFORMATION.
  
 1.PLEASE INDICATE EXISTING HVAC &
 EXHAUST SYSTEMS IN ACCORDANCE WITH 2004
 FBC(M)401.3.PLEASE NOTE, CORRIDORS
 SHALL NOT BE USED AS RETURN AIR PLENUMS
 PER 2004 FBC 423.15.2.
  
 2.PROVIDE EQUIPMENT SCHEDULE (NEW OR
 EXISTING).
  
 3.INDICATE ANY NEW WORK OR
 MODIFICATION TO DUCT & GRILLE LAYOUT.
  
 4.PLANS DO NOT INDICATE FIRE RATING OF
 WALLS, PARTITIONS OR SEPARATION
 REQUIREMENTS.PLEASE PROVIDE DETAILS
 FOR PENETRATIONS.
  
 5.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2004 FBC(M) TABLE 403.3.
  
 6.BATHROOM EXHAUST SHALL BE A MINIMUM
 OF 50 CFM PER WATER CLOSET OR URINAL.
 BATHROOMS SHALL BE CONTINUOUSLY
 VENTILATED DURING BUILDING OCCUPANCY OR
 COMPLY WITH EXCEPTION UNDER 2004 FBC
 423.15.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By kstevens Date 2005-08-12 Time 08:02 Rev Time 1.00
Received By kstevens Date 2005-08-12 Time 08:02 Sent To  
Notes
2005-08-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 1 OF 1 SITE PLAN. IF THE DESIGN
 PROFESSIONAL IS A LANDSCAPE ARCHITECT
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF LANDSCAPE
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART 11, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS. SECTION
 106.1 - ALL TITLE BLOCK INFORMATION
 REQUIRED IN FAC 61G1-16.004 & FS
 481.2055 SHALL BE ON EACH SHEET.
 2. SHT 1 0F 1 UTILITY CONNECTION PLAN.
 IF THE DESIGN PROFESSIONAL IS AN
 ENGINEER LEGALLY REGISTERED UNDER THE
 LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR OFFICIAL
 SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. SECTION 106.1 - ALL
 TITLE BLOCK INFORMATION REQUIRED BY FAC
 61G15-23.002(2) SHALL BE ON EACH SHEET.
 FS 471.025.
 3. A FLOOR PLAN FOR THE MODULAR
 CLASSROOM IS REQUIRED SHOWING ALL
 REQUIRED FIXTURES. TABLE 403.1. - MORE
 COMMENTS MAY FOLLOW AFTER THE FLOOR PLAN
 IS SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  