| 2005-08-01 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE SEE PLANS MENTIONS A |
| | NEW TRANSFORMER, HOWEVER THIS COULD NOT |
| | BE LCOATED ON ELECTRICAL RISER DIAGRAM? |
| | 215.5 |
| | PLEASE REVISE DIAGRM TO INCLUDE ALL |
| | WIRING. |
| | |
| | 2)NOTE: PLEASE SEE NEW"MPC", THIS DOES |
| | NOT PROVIDE ENOUGH INFORMATION. DOES |
| | THIS HAVE A MAIN? ETC ETC. |
| | 215.5,240.4,310.16 |
| | |
| | 3)NOTE: PLEASE SEE "EQUIPMENT GROUNDING" |
| | CONDUCTORS ARE BEING SHOWN FROM METER TO |
| | "MAINS"/ FIRST MEANS OF DICSONNECT. |
| | PLEASE SEE 250.6,250.24, "EQUIPMENT |
| | GROUNDING" CONDUCTORS ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISC. |
| | |
| | 4)NOTE: PLEASE SEE FS 471.003, WHICH |
| | REQUIRED ALL PLANS FOR NEW 277/480V |
| | SYSTEMS, TRANSFORMER ETC, TO BE SIGNED |
| | DATED AND SEALED BY A FLORIDA REGISTERED |
| | PE. PLEASE BE SURE PLANS HAVE ALL |
| | CORRECT TITLE BLOCK INFORMATION AS |
| | REQUIRED UNDER FAC 61G15-23.002 FOR |
| | ENGINEER/ENGINEERING FIRM OF RECORD. |
| | |
| | 5)NOTE: PLEASE INCDICATE A PANEL |
| | SCHEDULE WITH SIZE OF OCP, AWG FOR EACH |
| | BRACH CIRCUIT. |
| | PLEASE SHOW CONDUIT, CONDUCTORS SIZES, |
| | CIRCUITS ON PLANS. |
| | 215.5,240.4,310.16 ETC |
| | |
| | 6)NOTE: PLEASE SEE 240.21,408.16 WHICH |
| | REQUIRES A MCB ON THE LOAD SIDE OF THE |
| | TRANSFORMER. |
| | |
| | 7)NOTE: PLEASE SEE A MIN OF TWO GRNDS |
| | RODS ARE REQUIRED. 250.50 |
| | |
| | 8)NOTE: PLEASE SEE BLDG REVIEW NOTES, |
| | "ALL ELECTRICALSERVICE EQUIPMENT SHALL |
| | BE INSTALLED A MIN OF 6" ABOVE BASED |
| | FLOOD ELEVATION. THIS SHOULD BE NOTED ON |
| | PLANS. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICLA |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |