Plan Review Details - Permit 05071270
Plan Review Stops For Permit 05071270
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 08:46 Rev Time 0.50
Received By dpalmer Date 2005-08-11 Time 08:46 Sent To  
Notes
2005-08-11 00:00:00NO GENERATOR INCLUDED.
 OONLY ATS TO BE INSTALLED WITH SERVICE
 CHANGE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By dpalmer Date 2005-07-29 Time 12:06 Rev Time 1.00
Received By dpalmer Date 2005-07-29 Time 12:06 Sent To  
Notes
2005-07-29 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE REVISE RISER DIAGRAM
 WHICH SHOWS SERVICE FROM FPL COMING
 DIRECTLY INTO ATS?
 215.5
  
 2)NOTE: PLEASE INDICATE IF MAIN IS IN
 CLOSE PROXIMITY TO SERVICE ATS.
 THE MAIN MAY BE DIRECTLY BEHINED OR
 AJACENT TO ATS.
 230.72,240.4 ETC.
  
 3)NOTE: PLEASE SEE 250.66 FOR GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE #6 SHOWN IS
 NOT LARGE ENOUGH.
  
 4)NOTE: PLEASE PROVIDE MANUFACTURE
 SHEETS FOR ATS. THESE SHOULD INDICATE
 EQUIPMENT BEING SERVICE ENTRANCE RATED.
 215.5
  
 5)NOTE: PLEASE INCLUDE COLD WATER PIPE
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM.
 250.50
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 12:42 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 12:42 Sent To E
Notes
2005-08-04 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 17:28 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 17:28 Sent To E
Notes
2005-07-28 00:00:00TO "E" BOX