| Plan Review Stops For Permit 05071268 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2006-03-09 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-03-09 |
Time |
13:55 |
Rev Time |
1.00 |
| Received By |
mperson |
Date |
2006-03-09 |
Time |
13:55 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-01-17 |
Time |
07:57 |
Rev Time |
1.00 |
| Received By |
mperson |
Date |
2006-01-17 |
Time |
07:57 |
Sent To |
PC |
|
| Notes |
| 2006-01-17 00:00:00 | DENIED 4TH TIME | | | | | | REFERENCE: FBC-2001 FUEL GAS. CITY OF | | | WEST PALM BEACH AMENDMENTS TO FBC, | | | CHAPTER 1. | | | | | | THE FOLLOWING INFORMATION IS STILL | | | NEEDED FOR GAS PERMIT: | | | 1. SEC 104.2 DRAWINGS AND SPECIFICATIONS | | | 104.2.4 REQUIREMENTS: DRAWINGS DRAWN TO | | | SCALE WITH SUFFICENT CLARITY AND DETAIL | | | TO INDICATE THE NATURE AND CHARACTER OF | | | THE WORK. | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE.THIS DRAWING SHALL SHOW | | | EXISTING SYSTEM TO HOUSE WITH BTU LOAD | | | CAPACITIES TO THE APPLIANCES AND THE | | | LONGEST LENGTH FROM METER.ALSO THE REGU- | | | LATER SUBMITTED MUST BE CLEARLY | | | INDICATED ON DRAWING. | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. NEED | | | MANUFACTURE CUT OF GENERATOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2005-12-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-12-10 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-12-10 |
Time |
10:11 |
Sent To |
PC |
|
| Notes |
| 2005-12-10 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | DENIED 3RD TIME | | | 1.PLEASE "READ" AND ADDRESS PREVIOUS | | | COMMENTS ATTACHED. | | | | | | 2.GAS TABLE SUBMITTED IS NOT ADOPTED BY | | | THE CITY OF WEST PALM BEACH | | | USE FBC 2001 FUEL GAS TAB 402.(2) | | | | | | 3.SEC 104.2.1 DRAWINGS & SPECIFICATIONS. | | | DRAWINGS DRAWIN TO SCALE WITH SUFFICENT | | | CLARITY AND DETAIL TO INDICATE THE | | | NATURE AND CHARACTER OF THE WORK. | | | | | | 4. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | | | | 6. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. | | | | | | 7. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | | | | 8. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-27 |
Time |
16:43 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-09-27 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2005-09-27 00:00:00 | DENIED; | | | WHEN HOUSE WAS BUILT A GAS PERMIT WAS | | | ISSUED FOR GAS APPLIANCES IN THE HOUSE. | | | THE TOTAL BTU'S AND LONGEST DISTANCE | | | MUST BE INCLUDED IN THE CALCULATIONS FOR | | | THE ADDITION OF THE GENERATOR TO INSURE | | | ALL APPLIANCES WILL WORK UNDER A FULL | | | LOAD. THIS IS THE SECOND REQUEST FOR | | | THIS INFORMATION. | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CALL ME AT (561)805-6695. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-09 |
Time |
12:39 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-08-09 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | DENIED; | | | 1.TOTAL LOAD OF GAS APPLIANCES SHALL BE | | | CALCULATED WHEN ADDING AN ADDITIONAL GAS | | | APPIANCE. | | | 2.LONGEST RUN WOULD INCLUDE THE PIPING | | | INSIDE THE HOUSE. | | | 3.IS PIPE TO GENERATOR STRAPED TO WALL, | | | BURIED OR JUST HANG WITH NO SUPPORT? | | | 4.SUBIT A CUT SHEET FOR THE GENERATOR | | | THAT SHOWS BTU'S REQUIRED. | | | 5.THE PERSON WHO DREW THE PLAN SHALL | | | PRINT AND SIGN HIS OR HER NAME TO THE | | | DRAWING. | | | 6.SHOW TEE REQUIRED FROM METER TO GEN. | | | TO HOUSE PIPING. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-02 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-02 |
Time |
19:01 |
Sent To |
G |
|
| Notes |
| 2006-03-02 00:00:00 | TO "G" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-29 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-29 |
Time |
09:37 |
Sent To |
G |
|
| Notes |
| 2005-12-29 00:00:00 | TO "G" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-15 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-15 |
Time |
13:03 |
Sent To |
G |
|
| Notes |
| 2005-11-15 00:00:00 | TO "G" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-28 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-28 |
Time |
13:52 |
Sent To |
G |
|
| Notes |
| 2005-07-28 00:00:00 | TO "G" BOX |
|
|