Plan Review Details - Permit 05071205
Plan Review Stops For Permit 05071205
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-03 Cont ID  
Sent By rmcdouga Date 2006-05-03 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2006-05-03 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-20 Cont ID  
Sent By rmcdouga Date 2006-04-20 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2006-04-20 Time 07:15 Sent To  
Notes
2006-04-20 00:00:00DENIED
  
 1) ENERGY CALC. FORM CONTAINS
 INFORMATION THAT DOES NOT MATCH THE
 HOUSE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-26 Cont ID  
Sent By rmcdouga Date 2006-01-26 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2006-01-26 Time 15:30 Sent To  
Notes
2006-01-27 00:00:00DENIED
 2ND REVIEW
  
 1) THE NOTICE OF COMMENCEMENT WILL NEED
 TO BE RERECORDED BEFORE THE PERMIT IS
 ISSUED. WORK ON THE PROJECT MUST START
 WITHIN 90 DAYS OF THE DATE THE NOC IS
 RECORDED PER FLORIDA STATUES.
  
 2) THE CITY OF WEST PALM BEACH
 AMENDMENTS TO FBC 1804.1.7 REQUIRE THE
 FINISH FLOOR ELEVATION OF A MONOLITHIC
 SLAB TO BE A MINIMUM OF 4" ABOVE GRADE
 AT HABITABLE AREAS. FBC 1804.1.3
 REQUIRES THE BOTTOM OF FOOTERS TO BE A
 MINIMUM OF 12" BELOW GRADE. PLEASE
 CORRECT SECTIONS ON A2 AND A11.
  
 3) THE FINISH FLOOR GRADES ON THE
 ELEVATIONS ON SHEETS 7 AND 8 DO NOT
 CORRESPOND WITH THE SECTIONS ON 2 AND
 11.
  
 4) THE SIDE LOT DIMENSIONS FOR THE SITE
 PLAN ON SHEET 1 DO NOT CONCUR WITH THE
 SURVEY.
  
 5) THE FLOOD ZONE GIVEN ON THE SURVEY IS
 NOT CORRECT. THE PROPERTY IS LOCATED IN
 A "B" ZONE.
  
 6) THE INTERNAL PRESSURE COEFFICENT ON
 SHEET 3 SHOULD A HAVE A PLUS AND MINUS
 SIGN IN FRONT OF IT TO INDICATE POSITIVE
 AND NEGATIVE PRESSURES PER ASCE 7-98.
  
 7) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE ISOKERN FIREPLACE
 AND CHIMNEY.
  
 8) THE CONDITIONED AREA ON SHEET 1 OF
 THE PLANS DOES NOT AGREE WITH THE A/C
 AREA LISTED ON THE ENERGY CALCULATIONS.
 PLEASE CORRECT.
  
 9) THE GARAGE DOOR PRESSURES IN THE
 SCHEDULE ONSHEET 7 IS FOR A 16' X 7'
 DOOR. THE PLANS SPECIFY TWO 8' X 7'
 DOORS. PLEASE CORRECT.
  
 10) THE UPLIFT VALUE IN THE SCHEDULE ON
 SHEET 9 FOR THE SIMPSON META 18 IS
 INCORRECT. THE FBC DOES NOT ALLOW A
 ONE-THIRD INCREASE IN THE STEEL
 CALCULATIONS FOR STRAPS. THE CORRECT
 VALUE IS 1450# UPLIFT. SEE CURRENT
 SIMPSON CATALOG.
  
 11) SPECIFY THE BOTTOM CORD LIVE LOAD
 FOR THE ROOF TRUSSES. THE MINIMUM IS
 10 PSF FOR ATTICS WITHOUT STORAGE. SEE
 FBC TABLE 1604.1.
  
 12) THE BASIC WINDSPEED IS INCORRECTLY
 SPECIFIED AS 120 MPH ON SHEET 9. THE
 CORRECT WIND SPEED FOR THE CITY OF WPB
 IS 140 MPH.
  
 13) PROVIDE STRUCTURAL DETAILS FOR THE
 ARCHED OPENINGS.
  
 14) FBC 2305.2.2 REQUIRES DRAFTSTOPPING
 IN THE FLOOR/CEILING ASSEMBLY SEPARATING
 IT INTO TWO OR MORE APPROXIMATE AREAS
 AREAS WITH NO GREATER THAN 500 SQFT.
 SPECIFY THE LOCATIONS AND MATERIAL THAT
 WILL BE USED (FBC 2305.2.6).
  
 15) SPECIFY THE FASTENERS AND SPACING
 FORTHE SISTERED ROOF OVERHANG SHOWN ON
 THE WALL SECTIONS ON SHEET 11.
  
 16) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 1/4" TAPCONS SPECIFIED AT THE WINDOW
 BUCK DETAIL ON SHEET 13.
  
 17) SPECIFY THE YEILD STRENGTH OF THE
 W8X31 STEEL BEAM. PROVIDE CALCULATIONS
 FOR LOADS ON THE BEAM AND SHOW THAT THE
 BEAM IS CAPABLE SUPPORTING THE GRAVITY
 LOADS OVER THE BEAM SPAN AND OF
 RESISTING THE LATERAL WINDLOADS IMPOSED
 ON THE WALL THAT IS SUPPORTED BY THE
 BEAM. SEE FBC 2203 AND AISC ALLOWABLE
 STRESS DESIGN.
  
 18) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 PLEASE SUBMIT TWO (2) COPIES OF PRODUCT
 INFORMATION AS REQUIRED.
 SUBMIT (2) COPIES OF PRODUCT APPROVALS
 FOR THE FOLLOWING:
 - 8' WIDE GARAGE DOORS
 - ROOFING MATERIAL
 - LOUVERED DOOR @ ENTRY (#101)
 - SIDE SWING DOOR TO GARAGE (#123)
 - STRUCTURAL WINDOW MULLIONS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By rmcdouga Date 2005-08-17 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2005-08-17 Time 15:34 Sent To  
Notes
2005-08-17 00:00:00DENIED
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT (2) COPIES OF A SIGNED AND
 SEALED SURVEY.
  
 4) THE CITY AMENDMENTS TO FBC 1804.1.7
 REQUIRE THE FINISH FLOOR ELEVATION OF A
 MONOLITHIC FOUNDATION TO BE A MINIMUM OF
 4" ABOVE GRADE AT HABITABLE AREAS. FBC
 18O4.1.3 REQUIRES THE BOTTOM OF FOOTINGS
 TO BE A MINIMUM OF 4" BELOW GRADE.
 SPECIFY THIS ON THE SECTIONS ON SHEETS 2
 AND 11.
  
 5) THE INTERNAL PRESSURE COEFFICENT ON
 SHEET 3 DOES NOT HAVE THE PLUS AND MINUS
 SIGNS. SEE ASCE 7-98.
  
 6) PROVIDE FIREPLACE AND CHIMNEY
 SECTIONS AND DETAILS. SEE FBC 2114 AND
 2804.
  
 7) PROVIDE A STAIR DETAIL. SPECIFY THE
 TREAD WIDTH, RISER HEIGHT, ETC. SEE FBC
 1007.3.
  
 8) PROVIDE STAIR AND BALCONY GUARDRAIL
 DETAILS. SEE FBC 1015, 1026.5 AND
 1608.2.
  
 9) PROVIDE HANDRAIL DETAILS. SEE FBC
 1007.5.
  
 10) SPECIFY THE SQUARE FOOT BREAKDOWN OF
 THE STRUCTURE.
  
 11) SPECIFY THE SIZE AND LOCATIONS OF
 THE ATTIC ACCESSES PER FBC 2309.6.
  
 12) SPECIFY ATTIC VENTILATION PER FBC
 2309.7.
  
 13) THERE IS NO CHIMNEY SHOWN ON THE
 ELEVATIONS FOR THE MASONRY FIREPLACE.
  
 14) THE DESIGN PRESSURES FOR COMPONENTS
 AND CLADDING GIVEN ON SHEET 7 ARE FOR
 EXPOSURE CATEGORY B. THE EXPOSURE
 CATEGORY YOU INDICATED FOR YOUR DESIGN
 ON SHEET 3 IS C. PLEASE ADJUST VALUES
 USING FBC TABLE 1606.2D OR CHANGE
 CATEGORY TO B.
  
 15) THE GARAGE DOOR PRESSURES ARE ALSO
 FOR EXPOSURE B. THE CORRECT TABLE IS FBC
 1606.2E.
  
 16)SOME OF THE DIMENSIONS ARE MISSING
 FROM THE SECOND FLOOR PLAN.
  
 17) SPECIFY THE LOCATIONS AND MATERIAL
 FOR THE DRAFTSTOPPING AT THE
 FLOOR/CEILING ASSEMBLY AS REQUIRED BY
 FBC 2305.2.2.
  
 18) PROVIDE A DETAIL OF THE BEAM
 SUPPORTING THE SECOND FLOOR EXTERIOR
 MASONRY WALL AT THE MASTER BATH.
  
 19) PROVIDE A BEAM/LINTEL SCHEDULE ON
 THE PLANS.
  
 20) PROVIDE A CONNECTOR SCHEDULE FOR THE
 ROOF TRUSSES.
  
 21) PROVIDE FASTENING DETAILS FOR THE
 SISTERED OUTLOOKERS AT THE ROOF
 OVERHANG.
  
 22) REVISE THE ROOF SHEATHING FASTENING
 NOTES. THE CITY AMENDMENTS TO FBC TABLE
 2306.1 REQUIRES 8D RING-SHANK NAILS AT
 4"OC AT EDGES AND 6"OC INTERMEDIATE IN
 ZONE 3. ZONE 3 INCLUDES THE OUTSIDE
 CORNERS OF HIP ROOFS.
  
 23) SPECIFY THE LOCATION OF THE VERTICAL
 REINFORCEMENT AT THE SECOND FLOOR
 MASONRY WALLS.
  
 24) PROVIDE BUCK DETAILS FOR THE
 EXTERIOR SWING DOORS AND GARAGE DOORS.
  
 25) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR THE EXTERIOR WINDOWS, DOORS, GARAGE
 DOORS, ROOFING MATERIAL, TRUSS
 CONNECTORS, ETC. (THE NOAS THAT WERE
 SUBMITTED ARE EXPIRED.)
  
 26) THE PLANS SPECIFY THE WINDOWS AS
 IMPACT RESISTANT. HOWEVER, THE PRODUCT
 APPROVALS SUBMITTED ARE FOR NON-IMPACT
 RATED WINDOWS. STORM PANELS WILL BE
 REQUIRED FOR NON-IMPACT GLAZING.
  
 27) SUBMIT STATE PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES (2
 SETS) FOR THE STORM PANELS. SPECIFY THE
 TYPE OF MOUNT, TYPE OF FASTENER AND
 FASTENER SPACING FOR EACH OPENING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-12-12 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2007-12-12 Time 08:51 Sent To PC
Notes
2007-12-12 08:51:36*** DENIED /SUBMITTAL LETTER **
  
 1) NOTE: PLEASE SUBMIT REVISED SHEET FOR FINAL RECORD
 SET OF PLANS BEFORE FINAL/CO. THE MINOR ADJUSTMENTS OF
 INSTALLATION IN FIELD CAN BE DETERMINED BY THE
 INSPECTOR. THE RECORD SET OF PLANS SHOULD REFLECT ANY
 AND ALL CHANGES FOR BOTH THE CONTRACTOR/OWNER AND
 RECORD SET FOR PUBLIC RECORD.
 THE LOCATIONS AS ADJUSTED ARE NOT VISIBLE FOR PLAN
 REVIEW CODE COMPLIANCE REVIEW PER 210.52.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-07 Cont ID  
Sent By dpalmer Date 2007-03-07 Time 15:35 Rev Time 0.00
Received By dpalmer Date 2007-03-07 Time 15:35 Sent To PC
Notes
2007-03-07 15:38:09REDLINED PLANS.
  
 NO MORE THAN 8FT OF UNPROTECTED CONDUCTORS IN TOTAL
 LENGTH INSIDE DWELLING. 230.70 90.4.
 THIS WILL BE VIF, AND MAIN W/ OVER CURRENT PROTECTION
 MAY BE REQUIRED OUTSIDE DWELLING AS STATED ON PLANS.
 AT OWN RISK TO CONTRACTOR AS RISER WAS CHANGED FROM
 ORIGINAL PLANS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 12:38 Sent To PC
Notes
2007-03-02 13:17:13 
 * UNSAT *
  
 * PLEASE KNOW AS THE RISER CHANGED FROM THE ORIGINALLY
 PERMITTED PLANS THERE IS STILLS QUESTIONS AS STATED.
  
  
 1) NOTE: PLEASE SEE RISER NOW SHOWS A NEW GUTTER WHICH
 FEEDS TWO MBC PANELS.PLEASE SEE 230.70 AS NO MORE
 THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE
 THE BUILDING. THE CODE ACTUALLY DOES NOT STATE THE
 LENGHT PERMITTED AS SOME AHJ'S REQUIRE "0" FT AND
 OTHERS ALLOW MORE. IN TEH CITY OF WEST PALM BEACH AND
 PALM BEACH COUNTY THE OLD LOCAL AMENDMENTS LIMITED THE
 LENGTHS TO 8FEET AND WE AS TEH AHJ HAS RETAINED THIS
 LMIT.
 PLEASE KNOW THAT THIS IS BASED ON THE TOTAL LENGTH AND
 IF THERE IS MORE THAN 8FT THEN, MAIN(S) WITH OVER
 CURRENT PROTECTION WOULD BE REQUIRED OUTSIDE.
 PLEASE ALSO SEE THAT EQUIPMENT GROUNDING WOULD THEN BE
 REQUIRED FROM MAINS TO ANY SUB PANELS.
 PLEASE SEE RISER AS SHOWN WOULD REQUIRE MAIN
 DISCONNECTS W/ OVER CURRENT PROTECTION OUTSIDE.
 250.6, 250.24, 250.122
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-02 Cont ID  
Sent By dpalmer Date 2007-02-02 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2007-02-02 Time 16:28 Sent To PC
Notes
2007-02-02 17:25:58 
  
 *** UNSAT ***
  
 ** PLEASE SEE RISER HAS COMPLETELY BEEN REVISED AND THE
 FOLLOWING COMMENTS APPLY.
  
 1) NOTE: PLEASE SEE RISER NOW SHOWS A NEW GUTTER WHICH
 FEEDS TWO MBC PANELS. PLEASE SEE PLANS DO NOT INDICATE
 THE LOCATION OF THE NEW GUTTER. PLEASE SEE 230.70 AS NO
 MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING.
 PLEASE SEE RISER AS SHOWN WOULD REQUIRE MAIN
 DISCONNECTS W/ OVER CURRENT PROTECTION OUTSIDE.
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS ISSUED FOR PERMIT
 WERE REDLINED AS CONDUITS FROM THE METER TO THE FIRST
 MEANS OF DISCONNECT SHALL CONTAIN ANY *EQUIPMENT
 GROUNDING CONDUCTORS*. PLEASE SEE THE PANEL SCHEDULES
 INDICATE EQUIPMENT GROUNDS AND THE RISER NOTES ALSO
 INDICATE EQUIPMENT GROUNDS.
 PLEASE SEE 250.6, 250.24B.
  
 3) NOTE:PLEASE SEE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR HAS DECREASED AND IS REQUIRED TO BE
 SIZED PER 250.66 (MIN #2) BASED ON THE SERVICE AS
 SHOWN.
 310.16
  
 4) NOTE: PLEASE SEE 210.4B, IF THE DISHWASHER AND
 DISPOSAL FEED TO THE SAME DEVICE, THEN THIS WOULD
 REQUIRE A 2-POLE BREAKER FOR EACH OF THESE. PLANS ONLY
 SEEM TO SHOW DEVICE. PLEASE VERIFY THIS AND ADJUST THE
 BRANCH BREAKER AS NEEDED.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE INDICATES THE POOL
 PUMP BEING ON A SINGLE POLE 20AMP CIRCUIT, YET THE LOAD
 CALCULATIONS INDICATE A LOAD OF 2530VA WHICH EXCEEDS
 THE RATING OF THIS.
 PLEASE ALSO SEE THE POOL LIGHTS CIRCUIT IS SHOWING
 2000VA YET ALSO ONLY ON A SP 20A CIRCUIT.
 PLEASE VERIFY THIS.
 240.4, 310.16, 230.42 ETC
  
 6) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOULD BE DIRECT
 FOR ALL CIRCUITS. PLEASE SEE 408.4.
 *REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 THIS IS IN ORDER TO VERIFY MANY ITEMS PER 240.4 AND
 310.16.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By dpalmer Date 2006-04-13 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2006-04-13 Time 15:06 Sent To P
Notes
2006-04-13 00:00:00REDLINED TO VIF>
  
 250.6,250.24B
 240.24 FOR OCP IN CLOTHES CLOSETS.
  
 PLANS STAMPED AND NO NEED FOR
 CORRECTIONS FOR ABOVE, THEY ARE ONLY
 REDLINED FOR FIELD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-09 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 14:43 Sent To M
Notes
2006-01-09 00:00:00************ UNSAT**********
  
 ** PLEASE SEE NOTES BELOW ALSO FROM
 PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE MISSING SMOKE
 DETECTOR TO BE LOCATED ON 2ND FLR
 OUTSIDE BEDRMS MAST, BEDRM #3.
 NFPA-72 11.5.1.1
 PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE AHU'S LOCATED ON 2ND
 FLR WHICH DO NOT SHOW ANY ACCESS, OR
 MEANS OF DISCONNECT REQUIRED.
 PLEASE SHOW.215.5,440
 LTS, RECEPTS. 210.70,210.63 UNABLE TO
 VERIFY, DUE TO PLANS NOT INDICATING THE
 ACCESS. ARE THESE LOCATED IN ATTIC?
 PLEASE SEE CU'S ARE NOW BEING SHOWN,
 HOWEVER DISCONNECT'S ARE BEING SHOWN
 BEHIND UNITS AND NOT MEETING 110.26.
 PREVIOUS REVIEW.
  
 3)NOTE: PLEASE SEE PLANS ARE MISSING
 SERVICE. PLEASE SEE ONE PANEL IS LOCATED
 ON FIRST FLR OUTSIDE LAUNDRY RM.
 PLEASE SEE PREVIOUS REVIEW.
 SHOW ALL EQUIPMENT AND LOCATION.
 215.5,240.24 ETC
  
 4)NOTE: PLEASE SEE RISER NOW INDICATE AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO THE MCB PANEL "A". PLEASE SEE
 250.6, 250.24 WHIC DOES NOT PERMIT AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM THE
 METER TO THE FIRST MEANS OF DISCONNECT.
 THE ONLY CONDUCTORS SHOULD BE THE "HOT"
 PHASE CONDUCTORS AND THE NEUTRAL.
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 REPEAT COMMENTS.
  
 6)NOTE: PLEASE SEE THE RECORDED NOC
 SUBMITTED ON 12/19/05 HAS SINCE EXPIRED
 PER FS 713.13(2). PLEASE KNOW, IF WORK H
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING SAID NOC, THEN THE NOC WILL
 BECOME VOID.
 THIS WILL NEED TO BE RE-RECORDED BEFORE
 PICKING UP PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 19:29 Rev Time 1.00
Received By dpalmer Date 2005-08-04 Time 19:17 Sent To M
Notes
2005-08-04 00:00:00IN ELECTRIC FOR REVIEW.
 NOTES TO FOLLOW.
 ************ UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR BOTH
 ARCHITECTUAL AND ARCHITECTUAL AND
 INTERIOR DESIGN FIRMS.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR AMES BENNETT
 AND ASSOCIATES AND MISSING ADDRESS ETC
 AS REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219
 PLEASE ALSO SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR PARKER AND
 COMPANYINTERIOR AND ARCHITECTUAL
 DESIGN. PLEASE SEE NO INFORMATION COULD
 BE LOCATED ON STATE WEBSITE (DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION)
 FOR THIS FIRM? PLEASE LIST ALL REQUIRED
 LICENSE INFORMATION AS REQUIRED UNDER
 FAC 61G1-16.004 AND FS 481.219
 ************************************
 PLEASE SEE ALL PLANS/SHEETS CONTAIN A
 "RUBBER STAMP" FOR THE REQUIRED ORIGINAL
 SIGNATURE OF ARCHITEC. PLEASE UNDERSTAND
 THIS HAS BEEN COMMENTED ON NUMEROUS
 OTHER REVIEWS ON OTHER PROJECTS, HOWEVER
 THIS IS STILL BEING DONE?
 PLEASE SEE FS 481.221
 ************************************
 PLEASE SEE ONE SET OF PLANS ARE BEING
 RETAINED AND SHALL BE SENT TO THE STATE
 LEGAL COUNSEL FOR THE BOARD OF
 ARCHITECTS WITH PREVIOUS FILED PLANS.
 *************************************
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: FBC 905.2, NFPA-72
 8-1.4.1.6.2, 8-1.4.2
 PLEASE SEE SD'S ARE REQUIRED TO BE
 "INSIDE" BEDRMS. PLEASE SEE SOME
 REDLINED ON PLANS FOR SD'S TO BE ADDED.
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING RECEPTS FOR 210.52C1
 PLEASE SEE AREAS REDLINED ON PLANS
 PLEASE ALSO SEE AREA OF WHICH APPEARS TO
 BE KITCHEN COUNTERSPACE?
  
 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 SHOWING ALL MIN CIRCUITS AS REQUIRED
 UNDER 2002 NEC.
 PLEASE INCLUDE, CIRCUIT OVERCURRENT
 PROTECTION FOR EACH, CONDUCTOR SIZES
 ETC.215.5,240.4,310.16 ETC.
 PLEASE SEE COMMENTS:
  
 7)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 SHALL BE #12 AND 20A.
  
 8)NOTE: PLEASE SEE PLANS SHOWS (GDO)
 GARAGE DOOR OPENERS, HOWEVER NONE LISTED
 IN LOAD CALCULATIONS OR LOAD CALCS.
 215.5 PLEASE ALSO LIST ON PANEL SCHEDULE
 TO BE SUBMITTED.
 PLEASE SEE SIZING OF MOTORS LOADS FOR
 BRANCH CIRCUITING. 430.
  
 9)NOTE: PLEASE SEE GARAGE RECEPTS SHALL
 BE SHOWN AS GFI/GFI PROTECTED PER
 210.8A2
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPT
 PER 210.52E,210.8 IN FRONT OF DWELLING.
  
 11)NOTE: PLEASE SEE ONLY (2) SMALL
 APPLIANCE CIRCUITS ARE SHOWN ON LOAD
 CALCULATIONS, HOWEVER A 6KW LOAD IS
 SHOWN?? PLEASE SEE 210.11C1 AND 220.16.
 A LOAD OF 1.5KW FRO EACH. IF ADDITIONAL
 CIRCUITS ARE PROVIDED, THEN LOAD SHALL
 BE INDICATED AS 1.5KW FOR EACH. PLEASE
 KNOW THE NUMBER OF CIRCUITS CAN NOT BE
 VERIFIED AT THIS TIME DUE TO MISSING
 PANEL SCHEDULE.
  
 12)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 AND DISCONNECTS AS REQUIRED PER 440.11
 PLEASE SEE AHU'S SHOWN ON PLANS, HOWEVER
 NO DISC'S ARE SHOWN?
 PLEASE SEE DISCONNECT'S FOR CU'S ARE
 SHOWN ON PLANS, HOWEVER NO CU'S ARE
 SHOWN?
 PLEASE SEE LOAD CALCULATIONS SHOW "49KW"
 OF HEAT??, HOWEVER ONLY THREE CU'S AND
 THREE AHU'S ARE SHOWN ON PLANS??
 PLEASE SEE 49KW APPEARS TO INDICATE A
 MIN OF 4-5 SYSTEMS??
  
 PLEASE ALSO SEE AHU SHOWN INSIDE HOUSE
 W/OUT INDICATION OF DISCONNECT.
 PLEASE SEE IF ROOM WITH ACCESS TO
 EXTERIOR IS INDEED MECH RM, PLEASE SHOW
 ALL EQUIPMENT. PLEASE ALSO SEE MISSING
 RECEPT PER 210.63
  
 13)NOTE: PLEASE SEE WATER HEATER SHOWN
 IN "MECH RM" HOWEVER, NO DISCONNECT IS
 SHOWN. 422.30,422.31
  
 14)NOTE: PLEASE SEE RISER DIAGRAM IS
 MISSING CONDUCTORS FROM MAIN DISCONNECT
 TO SUB PANEL AND FROM METER TO MAIN.
 PLEASE SEE 240.4,310.15B6,310.16.215.5
 PLEASE SEE RISER BELOW LOAD CALCULATIONS
 SHOW 3-#4'S FOR A 300AMP SERVICE?
 PLEASE SEE MIN SERVICE ENTRANCE
 CONDUCTORS PER 240.4,310.15B6
  
 15)NOTE: PLEASE ALSO SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANEL. 250.110,250.24 SIZE PER
 250.122
  
 16)NOTE: PLEASE SEE SUB PANEL IS BEING
 SHOWN AS MCB, WHICH IS FINE, HOWEVER
 THIS IS NOT REQUIRED.
 IF SHOWN ON PLANS, THEN A MCB WILL BE
 REQURIED TO BE INSTALLED.
 THIS IS ONLY A NOTE AND NO CORRECTION OR
 CHANGE IS REQUIRED.
  
 17)NOTE: PLEASE SHOW SERVICE EQUIPMENT
 LOCATION ON PLANS. PLEASE SEE ONLY
 SUB-PANEL IS SHOWN ON PLANS.
 PLEASE ALSO INDICATE AMERAGE ON
 METER-CAN.
 215.5,230.70
  
 18)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52. PLEASE SEE REDLINED AREAS
 DOWNSTAIRS BRKFST WALLS.
  
 19)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12.
 PLEASE SEE ALL "OUTLETS" IN BEDROOMS ARE
 REQUIRED TO BE ARC FAULT PROTECTED, THIS
 INCLUDES; RECEPTS,FANS,LTS SD'S ETC.
  
 20)NOTE: PLEASE SEE PLANS APPEAR TO SHOW
 A DEDICATED ICE FRIG AND WINE COOLER?
 IF THESE ARE DEDICATED?, PLEASE BE SURE
 TO ADD TO CIRCUITS ON PANEL SCHEDULE AND
 LOAD CALCULATIONS.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED AT LOCATIONS FOR NOTES.
 PLEASE KNOW, REDLINES IN NO WAY INDICATE
 ALL LOCATIONS OF NOTES ABOVE.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE ZONING COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 10:35 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 10:35 Sent To E
Notes
2007-12-07 10:35:54TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 15:12 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 15:11 Sent To E
Notes
2007-02-22 15:12:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 18:48 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 18:48 Sent To E
Notes
2007-01-30 18:49:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 13:39 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 13:39 Sent To M
Notes
2007-01-20 13:40:07TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-08 Cont ID  
Sent By adarroug Date 2007-01-08 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-01-08 Time 16:38 Sent To M
Notes
2007-01-08 16:38:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 10:05 Sent To M
Notes
2006-05-03 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 15:15 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 15:15 Sent To E
Notes
2006-04-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 10:42 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 10:42 Sent To E
Notes
2006-01-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 10:16 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 10:16 Sent To Z
Notes
2005-12-20 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 11:20 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 11:20 Sent To E
Notes
2005-08-04 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-18 Cont ID  
Sent By rmcdouga Date 2005-08-18 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2005-07-28 Time 18:21 Sent To  
Notes
2005-07-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 11:19 Rev Time 0.30
Received By tgordon Date 2007-01-22 Time 11:19 Sent To  
Notes
2007-01-22 11:20:18REVISION TO MACHANICAL PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 10:52 Rev Time 0.45
Received By tgordon Date 2007-01-12 Time 10:52 Sent To  
Notes
2007-01-12 10:57:58MECHANICAL REVISION
 *** DENIED ***
 1) NEED TO SHOW SIZE OF SUPPLY AIR TRUNK LINE LEAVING
 AHU #2.
  
 2) NEED TO SHOW SIZE OF BOTH RETURN AIR GRILLS TO AHU
 #2.
  
 3) PLEASE SHOW HOW MANY SUPPLY AIR DUCTS ARE GOING TO
 THE FIRST FLOOR FROM AHU #1.
  
 4) PLEASE SHOW WERE THE CLOTHES DRYER VENT IS TO
 TERMINATE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-10 Cont ID  
Sent By tgordon Date 2006-01-10 Time 08:31 Rev Time 0.45
Received By tgordon Date 2006-01-10 Time 08:31 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-14 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 15:35 Rev Time 0.35
Received By pkrauss Date 2005-08-14 Time 21:22 Sent To B
Notes
2005-08-14 00:00:00DENIED:
 PLANS SUBMITTED ARE FOR THE FIRST FLOOR
 ONLY.PLEASE PROVIDE THE SECOND FLOOR
 SO A COMPLETE PLAN REVIEW MAY BE DONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-14 Cont ID  
Sent By jleech Date 2006-04-14 Time 09:01 Rev Time 0.00
Received By jleech Date 2006-04-14 Time 09:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 08:56 Rev Time 0.50
Received By jleech Date 2006-01-13 Time 08:56 Sent To B
Notes
2006-01-13 00:00:00DENIED;
 RISER DIAGRAM; FIRST FLOOR BATHROOM MUST
 BE ON A BRANCH DRAIN NOT EACH FIXTURE ON
 THE BUILDING SEWER.
 RESIZE SIZE PIPE SIZES ON RISER
 DIAGRAM.(PIPES ARE OVER SIZED)USE
 FBC-2001 TABLE 7.10.1 (1) 4" RISERS CAN
 BE 3" BY CODE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By jleech Date 2005-08-10 Time 15:08 Rev Time 0.50
Received By jleech Date 2005-08-10 Time 15:08 Sent To M
Notes
2005-08-10 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW'S NOTE #1.
 2.RISER DIAGRAM DOESNOT MEET MINIMUM
 PLUMBING CODES. (SEE RISER DIAGRAM
 MARKED IN RED.
 3. SUBMIT MANUFACTURES SPECIFICATIONS
 FOR ICE MACHINE. DRAIN MAY BE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-26 Cont ID  
Sent By choops Date 2008-02-26 Time 13:07 Rev Time 0.00
Received By choops Date 2008-02-26 Time 13:07 Sent To PC
Notes
2008-02-26 13:08:13***APPROVED - SUBMITTAL OF LANDSCAPE PLAN***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 09:22 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 09:22 Sent To I
Notes
2006-01-07 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/GATE WITH A 5 UTILITY
 EASEMENT APPROVAL FROM CITY OF WEST PALM
 BEACH, BELLSOUTH, ADELPHIA, FPL, FLORIDA
 PUBLIC UTILITIES.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By mmclean Date 2005-08-03 Time 11:05 Rev Time 0.00
Received By mmclean Date 2005-08-03 Time 11:05 Sent To I
Notes
2005-08-03 00:00:00DENIED,
 1. MUST PROVIDE TWO COPIES OF SURVEY.
 2. MUST PROVIDE THE DIMENSION FOR THE
 DRIVEWAY/WALKWAY (LENGTH & WIDTH).
  
 **NOTE** - MUST MAINTAIN 1000SQ FT OR
 75% OF LANDSCAPE WITHIN THE FIRST 25FT
 FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720