| 2006-06-19 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | FROM PREVIOUS REVIEWS; ITEMS NOT |
| | ADDRESSED |
| | |
| | 1.) THE TEST REPORT SUBMITTED TO SHOW |
| | CODE COMPLIANCE FOR THE BUTT GLASS BAY |
| | WINDOW WAS AN EXPERIMENTAL REPORT WHICH |
| | DOES NOT APPEAR TO BE IN CONFORMANCE |
| | WITH THE TESTING STANDARDS REQUIRED BY |
| | FBC1707.4.2.1. |
| | |
| | IF YOU ARE USING A TEST REPORT TO SHOW |
| | CODE COMPLIANCE, A SIGNED, SEALED, DATED |
| | ORIGINALS REQUIRED, BUT ALSO MUST BE |
| | CODE COMPLIANT. |
| | |
| | 2.)THE TEST REPORT SUBMITTED DOES NOT |
| | PROVIDE ENOUGH INFORMATION ABOUT THE |
| | WINDOW UNIT TESTED.FROM THE TEST |
| | REPORT I CANNOT DETERMINE IF IT IS THE |
| | PRODUCT YOU ARE PROPOSING TO INSTALL, |
| | ARCH ALUMINUM SERIES 4500, OR IF AN |
| | EQUIVALENT PRODUCT WAS TESTED. |
| | |
| | 3.)THE WINDOW SIZES PROPOSED IS LARGER |
| | IN BOTH OVERALL SIZE AS WELL AS THE |
| | FRONT PANEL SIZE.IT IS NOT CLEAR HOW |
| | YOU HAVE ARRIVED AT THE DESIGN PRESSURE. |
| | |
| | WINDOW SIZE CHANGED BUT OVERALL SIZE IS |
| | STILL LARGER THAN THE TESTED UNIT. |
| | PANEL WIDTH LARGER THAN TESTED UNIT. |
| | |
| | 4.)THE ENGINEERING FOR THE 84X144 |
| | OPENING DOES NOT INDICATE WHICH ARCH |
| | ALUMINUM PRODUCT YOU ARE USING. |
| | |
| | 5.)ORIGINAL SIGNATURE REQUIRED ON THE |
| | LOCAL PRODUCT APPROVAL APPLICATION. |
| | |
| | 6.)WHEN RESUBMITTING, ALL DOCUMENTS |
| | WHICH YOU ARE USING TO SHOW CODE |
| | COMPLIANCE (SUCH AS ENGINEERING, |
| | CALCULATIONS OR TEST REPORTS) ARE TO BE |
| | SIGNED, SEALED ORIGINALS.ONCE A LOCAL |
| | PRODUCT APPROVAL IS ISSUED, THE ORIGINAL |
| | CAN REMAIN ON FILE AND COPIES CAN BE |
| | SUBMITTED FOR INDIVIDUAL PERMITS. |
| | |
| | NEW COMMENTS: |
| | |
| | 7.)THE PERMIT APPLICATION IS EXPIRED, |
| | OVER SIX MONTHS WITHOUT COMMENCING WORK, |
| | FBC2001 CITY OF WEST PALM BEACH |
| | AMENDMENTS 104.1.6.THE BUILDING CODE |
| | CHANGED EFFECTIVE OCTOBER 1, 2005. |
| | SUBMIT A NEW APPLICATION.ALL PAPERWORK |
| | TO COMPLY WITH FBC2004. |
| | |
| | 8.)THE LETTER OF INTENT REGARDING THE |
| | INSPECTION IS TO BE A SIGNED,SEALED, |
| | DATED ORIGINAL. |
| | |
| | 9.)THE ENGINEER'S SEAL IS EXPIRED; |
| | SHOULD SAY "LICENSE" RATHER THAN |
| | "CERTIFICATE" EFFECTIVE JAN 1, 2006. |
| | |
| | 10.)THE LOCAL PRODUCT APPROVAL |
| | APPLICATION IS TO BE A SIGNED ORIGINAL. |
| | |
| | 11.)SEE ATTACHED DESIGN PRESSURES FROM |
| | THE APPROVED PLAN.THE DP REQUIREMENT |
| | FOR THIS OPENING IS +30/-38.THE |
| | ENGINEERING SHOWS A PRODUCT LIMITATION |
| | OF +27/-30. THE OPENING SIZE ON THE PLAN |
| | CONFLICTS WITH THE ENGINEERING |
| | SUBMITTED. ADDRESS. |
| | |
| | 12.)AS DISCUSSED ON THE TELEPHONE WITH |
| | THE ENGINEER, LOCAL PRODUCT APPROVAL |
| | REQUIRED FAC9B72.LOCAL PRODUCT |
| | APPROVAL COMPLIANCE CAN BE SHOWN THROUGH |
| | AN EVALUATION REPORT RATHER THAN TESTING |
| | AND ENGINEERING.PLEASE REVIEW THE RULE |
| | FAC9B-72, LOCAL PRODUCT APPROVAL |
| | APPLICATION, AND VALIDATION CHECKLIST. |
| | THIS IS AVAILABLE ONLINE AT |
| | WWW.FLORIDABUILDING.ORG, PRODUCT |
| | APPROVAL. |