Plan Review Details - Permit 05071160
Plan Review Stops For Permit 05071160
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-28 Cont ID  
Sent By alange Date 2006-02-28 Time 15:45 Rev Time 0.66
Received By alange Date 2006-02-28 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-14 Cont ID  
Sent By alange Date 2006-02-14 Time 08:37 Rev Time 1.00
Received By alange Date 2006-02-14 Time 08:37 Sent To  
Notes
2006-02-14 00:00:00REVISION NOTES;
  
 SUBMIT PRODUCT APPROVALS FOR FRENCH
 DOORS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By alange Date 2005-09-21 Time 07:36 Rev Time 1.50
Received By alange Date 2005-09-20 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By alange Date 2005-08-23 Time 15:20 Rev Time 1.50
Received By alange Date 2005-08-23 Time 14:25 Sent To  
Notes
2005-08-23 00:00:00DENIED
  
 1.PROPERTY IS NOT HOMESTEADED AS
 PRIMARY RESIDENCE AND OTHER PROPERTIES
 HAVE BEEN FOUND IN PALM BEACH COUNTY.
 A CONTRACTOR IS REQUIRED TO OBTAIN A
 BUILDING PERMIT.
  
 2.BUILDING PERMIT VALUATION IS TOO
 LOW.PERMIT VALUE SHOULD INCLUDE ALL
 MATERIALS AND LABOR AS IF A CONTRACTOR
 IS DOING THE WORK.PLEASE REVISE VALUE
 AND PAY ADDITIONAL PERMIT FEES OR WE CAN
 ADJUST IT ACCORDING TO MARSHALL AND
 SWIFT ESTIMATING GUIDE.
  
 3.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS.FOR ALL WINDOWS AND EXTERIOR
 DOORS, IMPACT PROTECTION AND STRAPS AND
 TIEDOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 18:55 Sent To B
Notes
2006-02-22 00:00:00REVISIONOK, STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-06 Cont ID  
Sent By dpalmer Date 2006-02-06 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2006-02-06 Time 18:25 Sent To M
Notes
2006-02-06 00:00:00********* UNSAT **************
  
 ** PLEASE SEE SOME ITEMS FROMPLANS
 REDLINED ON PREVIOUS REVIEW NEED TO BE
 ADDRESSED.
  
  
 1)NOTE: PANEL H SHOWS #8'S FOR FEEDERS
 TO EXISITNG PANEL "P" AND RISER SHOWS
 #6'S.
 PLEASE ADJUST, 310.16,240.4
  
 2)NOTE: PLEASE SEE MININUM VA FOR
 WASHER/LAUNDRY CIRCUIT SHALL BE 1500VA,
 220.16,210.11.
  
 3)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULES. PLEASE SEE RISER SHOWS THE CU
 BEING FED FROM PANEL "H", HOWEVER PANEL
 "H" DOES NOT LIST THIS CU NOR DOES IT
 LIST THE AHU.
 PLEASE HOWEVER SEE A PANEL SCHEDULE
 SUBMITTED FOR PANEL "S" WHICH INDICATES
 BOTH THE CU AND AHU BEING FED FROM THIS
 INDOOR PANEL.
 PLEASE CORRECT AND REVISE PLANS AS
 NEEDED.215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 19:54 Rev Time 0.75
Received By dpalmer Date 2005-09-27 Time 19:29 Sent To  
Notes
2005-09-27 00:00:00REDLINED
  
 PANEL H SHOWS #8'S FOR FEEDERS TO
 EXISITNG PANEL "P" AND RISER SHOWS #6'S.
  
  
 MIN VA FOR WASHER TO BE 1500VA, 220.16,
 210.11.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 17:17 Rev Time 0.50
Received By dpalmer Date 2005-09-10 Time 16:56 Sent To B
Notes
2005-09-10 00:00:00******** UNSAT **********
  
 PLEASE SEEE SOME COMMENTS FROM FIRST
 RREVIEW AND SOME NEW COMMENTS DUE TO
 REVISED/CHANGES IN PLANS.
  
  
 1)NOTE: PLEASE SEE NEW RISER DIAGRAM IS
 NOW SUBMITTED, AS REQUESTED ON PROEVIOUS
 REVIEW IF NEW SERVICE IS PROPOSED PLEASE
 PROVIDE THE FOLLOWING INFORMATION ON
 NOTE #2.
 PLEASE ALSO PANEL SCHEDULE "P" WHICH WAS
 SHOWN BLANK ON PREVIOUS PLANS IS NOW
 MISSING FROM PLANS, HOWEVER THIS PANEL
 IS STILL SHOWN ON PLANS??
 215.5
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52. THESE ARE REDLINED ON PLANS
 AT LOCATONS REQUIRED.
  
 4)NOTE: PLEASE SEE INCADESCENT FIXTURES
 IN CLOTHES CLOSET APPEAR TO STILL BE
 SHOWN TOO CLOSE TO SHELVES.
 410.8
  
 5)NOTE: PLEASE SEE PLANS FROM PREVIOUS
 REVIEW WHICH WERE REDLINED FOR 210.70,
 BUT WAS NOT TYPED IN NOTES.
 PLEASE SEE MISSING EGRESS LIGHTING
 CONTROL AND FIXTURES AT ALL DOORS TO
 EXTERIOR.
 THESE LOCATIONS ARE REDLINED ON PLANS.
  
 6)NOTE: PLEASE SEE NOTICE TO FS
 553.80(2)(B) IS GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 16:43 Rev Time 1.50
Received By dpalmer Date 2005-08-16 Time 16:19 Sent To P
Notes
2005-08-16 00:00:00********* UNSAT **********
  
  
 1) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE BATH GFI IS ALSO SHOWN ON
 WITH OUTSIDE RECEPT.
 PLEASE SEE BATH SHALL NOT HAVE ANY OTHER
 RECEPTS.
 MUST BE 20A AND #12
  
 2)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SOME MISSING.
  
 3)NOTE: PLEASE SEE MISSING GFI RECEPTS
 PER 210.52C1 ALONG KITCHEN COUNTERSPACE.
 210.8A6
  
 4)NOTE: PLEASE SEE MISSING FRONT AND
 REAR GFI RECEPTS PER 210.52E
  
 5)NOTE: PLEASE SEE MISSING GFI FOR A/C
 CU. 210.63, 210.8
  
 6)NOTE: PLEASE SEE MISSING A/C CU NOT
 SHOWN ON PLANS ALONG WITH DISCONNECT NOT
 SHOWN FOR CU.? 440.11
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES 50A OCP FOR HEAT/ AHU,
 HOWEVER, PLEASE SEE MECH PLANS WHICH
 SHOWS A 10KW HEATSTRIP. PLEASE SEE
 424.3B FOR A MIN OF 125% FOR OCP AND SEE
 310.16 FOR MIN AWG.
  
 8)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE IN CLOSETS FOR LIGHTING
 FIXTURES AND TYPES OF FIXTURES.
  
 9)NOTE: PLEASE SEE PLANS INDICATE PANELS
 C&H, HOWEVER PANEL SCHEDULES SUBMITTED
 SHOW PANELS H&P? PLEASE CORRELATE.
 PLEASE SHOW PANEL LOCATIONS ON PLANS
 ALONG WITH SERVICE LOCATION. PLEASE
 INDICATE IF PANELS/ SERVICE IS NEW OR
 EXISTING?
 PANELS ARE SHOWN AS NEW.
 PLEASE SEE PANEL "P" IS SHOWN AS BLANK,
 WITH NO INFORMATION ON PANEL, CIRCUITS,
 SIZE ETC .
 PLEASE SEE PANEL "H" SHOWS A 1-POLE
 CIRCUIT TO FEED PANEL "P".?
 PLEASE SEE PANEL "H" IS SHOWN AS A MLO
 WITH NO MAIN. PLEASE CLARIFY WHERE MAIN
 IS ?
 215.5,240.24,230.70,310.16,240.24 ETC
 IF THESE ARE ALL NEW, PLEASE SEE THE
 FOLLOWING COMMENT.
  
 10)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 11)NOTE: PLEASE SEE 2002 NEC 210.12,
 WHICH REQUIRES ARC FAULT PROTECTION FOR
 "ALL OUTLETS' IN BEDRMS. PLEASE SEE THIS
 INCLUDES,,, LTS, FANS, SD'S, RECEPTS
 ETC.
 PLEASE SEE ONLY TWO CIRCUITS SHOWN ON
 PANEL SCHEDULE SHOW ARC FAULT
 PROTECTION.
  
 12)NOTE: PLEASE SHOW ALL ROOM AREA/
 DESIGNATIONS ON PLANS.
  
 13)NOTE: PLEASE CALRIFY 40A OCP FOR
 DRYER, THIS IS ONLY A NOTE:
  
 14)NOTE: PLEASE INCLUDE LOAD
 CALCUALTIONS FOR NEW OR EXISTING
 SERVICE.
  
 15)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR VALUATION ADJUSTMENT FOR SCOPE OF
 WORK PROPOSED. THIS IS REQUIRED TO BE
 BASED ON FAIR MARKET VALUE, EVEN WHEN
 DONE BY AN OWNER BUILDER. PLEASE SEE FBC
 104.6.5, CITY OF WEST PALM BEACH
 ADMINISTRATIVE CODE.
 THIS IS TO INCLUDE ALL LABOR AND
 MATERIALS , EVEN IF MATERIALS ARE OWNER
 SUPPLIED.
  
 16)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY NEW "PHONE " LOCATIONS.
 THIS IS NOT REQUIRED AND IS ONLY A NOTE.
 IF PHONE LOCATIONS/WIRING WILL BE
 INSTALLED UNDER THIS PERMIT, PLEASE SHOW
 LOCATIONS ON THIS PLANS.
 IF PHONE WIRING IS NOT SHOWN, A SEPARATE
 LAYOUT AND PERMIT APPLICATION WILL BE
 REQUIRED AT A LATER DATE. THIS IS ONLY A
 NOTE AND NO CORRECTIONS ARE NEEDED.
 THIS WOULD ALSO BE RELATED TO ANY OTHER
 POSSIBLE LOW VOLTAGE INSTALLATIONS WITH
 THE EXCEPTION TO ALARM SYSTEMS.
 ALARMS ARE SEPARATE PERMITS.
  
 17)NOTE: IF CARRIAGE LTS ARE INSTALLED
 UNDER THIS PERMI ALSO, A DISCONNECTING
 MEANS AT DETACHED BLDG WILL BE REQUIRED
 225.31
  
 PLEASE SEE THERE ARE MANY ITEMS REDLINED
 ON PLANS FOR SOME OF THE ABOVE COMMENTS.
 PLEASE SEE NOT ALL LOCATIONS ARE NOTED
 DUE TO MISSING INFORMATION.
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 ANDONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE THAT ONE COPY OF ANY
 OLD/VOIDED SHEETS REMOVED SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 11:41 Sent To E
Notes
2006-02-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 19:21 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 19:21 Sent To E
Notes
2006-02-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 11:05 Sent To E
Notes
2005-09-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 10:20 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 10:20 Sent To E
Notes
2005-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 09:58 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 09:58 Sent To E
Notes
2005-08-16 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By alange Date 2005-08-23 Time 15:20 Rev Time 0.00
Received By alange Date 2005-08-09 Time 08:30 Sent To  
Notes
2005-08-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-07 Cont ID  
Sent By tgordon Date 2006-02-07 Time 10:54 Rev Time 0.30
Received By tgordon Date 2006-02-07 Time 10:54 Sent To P
Notes
2006-02-07 00:00:00*** PROVISO ***
 1) CLOTHES DRYER VENTED TO EXHAUST OUT
 DOORS, PER 2001 FBC/M 504 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-18 Cont ID  
Sent By prafter Date 2005-08-18 Time 09:22 Rev Time 1.00
Received By prafter Date 2005-08-18 Time 09:22 Sent To B
Notes
2005-08-18 00:00:00MECH.PLAN REVIEW:
 PROVISO:
  
 1. A.H.U. TO HAVE AUX. DRAIN PAN UNDER
 UNIT AND WITH DRAIN PANPROTECTION.
  
 2. CLOTH DRYER TO BE EXHAUSTED TO
 OUTSIDE.2003 FBC/M SECTION 504 .
  
 3. R/A OUT OF ROOMS TO ADHEAR TO
 BALANCED RETURN AIR.2003 FBC/M604.1
 EXCEPTION #1.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By jleech Date 2006-02-10 Time 09:21 Rev Time 0.00
Received By jleech Date 2006-02-10 Time 09:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-17 Cont ID  
Sent By jleech Date 2005-08-17 Time 07:31 Rev Time 0.25
Received By jleech Date 2005-08-17 Time 07:31 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-12 Cont ID  
Sent By mmclean Date 2005-08-12 Time 16:34 Rev Time 0.00
Received By mmclean Date 2005-08-12 Time 16:34 Sent To I
Notes
2005-08-12 00:00:00INTERNAL RENOVATION
 FOOTPRINT OF STRUCTURE DOES NOT CHANGE.