| 2005-08-04 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR THE |
| | ACCORDION SHUTTERS. DADE COUNTY NOA |
| | ALONE IS NOT AUTOMATICALLY AN STATE WIDE |
| | FLORIDA PRODUCT APPROVAL. IF |
| | MANUFACTURER DOESN'T HAVE A FLORIDA |
| | PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| | APPLY FOR LOCAL PRODUCT APPROVAL USING |
| | THE DADE COUNTY NOA BY COMPLETING THE |
| | LOCAL PRODUCT APPROVAL FORM DOWNLOADED |
| | FROM WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- KEY SUBMITTED INDICATES THAT EGRESS |
| | OPENINGS ARE GOING TO HAVE SHUTTERS. |
| | NEED TO HAVE AT LEAST ONE MEANS OF |
| | EMERGENCY ESCAPE AS REQUIRED BY SEC. |
| | 1005.4.5 FBC 2001. SPECIFY WHICH ONE. |
| | |
| | 3- A) ENGINEER DRAWINGS FOR STRUCTURAL |
| | MODIFICATION ARE NOT CLEAR IF STRUCTURAL |
| | TUBE IS FOR OPENING #1 ONLY OR IF IT |
| | APPLIES TO OTHER OPENINGS AS WELL. IF |
| | SO, SPECIFY WHICH ONES. |
| | *NOTE THAT DWG SHOW SHUTTER SPAN OF 57". |
| | |
| | B) CLARIFY WHY STRUCTURAL MULLION IS |
| | SHOWN AT BOTTOM ONLY. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001 |
| | |
| | 4- NOTICE OF COMMENCEMENT IS EXPIRED IF |
| | WORK IS NOT STARTED AFTER 90 DAYS OF |
| | RECORDING. NEED TO RE-RECORD IT. |
| | |
| | 5- REVISE INSTALLATION SCHEDULE. IT |
| | CALLS FOR TAPCONS AT ALL OPENINGS. BUT, |
| | SOME SHUTTERS ARE TO BE INSTALLED INTO |
| | THE STRUCTURAL TUBE. REVISE AS REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |