Plan Review Details - Permit 05071027
Plan Review Stops For Permit 05071027
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-26 Cont ID  
Sent By jwitmer Date 2006-10-25 Time 07:36 Rev Time 22.00
Received By jwitmer Date 2006-06-28 Time 07:36 Sent To  
Notes
2006-06-28 00:00:00PERMIT: 05071027
 ADD: 2211 N FLAGLER DR
 CONT: PLAN REVIEW
 OWNER: MERCO GROUP
 TEL: (561)296-3300
 ARCH: SONG & ASSOC/ JOHN STRNDBERG
  
 TEL: (561) 655-2423
  
 -PALADIO TERRACE-
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 3RD REVIEW
 ACTION: DENIED
  
 1)LS 0.00 SHEET:
 A) OCCUPANCY CALCULATION AT THE BOTTOM
 OF SHEET, THE OCCUPANCY LOADS FOR THE
 VARIOUS FLOORS DO NOT TOTAL WHAT THE
 PLAN CALLS FOR, INDICATED 6316 ACTUAL
 COUNT IS 6186, CORRECT.
  
 B) TOP CENTER THE TABLE FOR TRAVEL
 DISTANCE AND DEAD ENDS TOTAL THE
 OCCUPANT LOAD BY FLOOR AND THE TOTAL IS
 100 LESS THAN THE OCCUPANT LOAD TABLE.
  
 C) ON THE RIGHT SIDE OF THE PAGE THERE
 IS A THIRD AREA WHICH PROVIDES THE
 OCCUPANT LOAD AND THE FIGURE STATED
 THERE (6081) DOESN'T MATCH EITHER OF THE
 OTHERS QUOTED.
  
 2)COMMENT2A FROM THE PREVIOUS REVIEW.ATRIUM.WE
 WILL BE REVIEWING FOR CODE
 COMPLIANCE UNDER SECTION 412.5 (HIGH
 RISE SMOKE CONTROL) AND SECTION 414.1-10 (ATRIUM).
  
 THE NEW LIFE SAFETY PLANS DATED 07-07-06 INDICATE THE
 NEW
 RATED WALL AND OPENING PROTECTIVES FOR TTHE ATRIUM
 AREA. THE ARCHITECTURAL PLANS NEED TO BE UPDATED TO
 REFLECT
 THE FIRE RATINGS AS WELL AS THE DOOR SCHEDULE.
 CURRENTLY THTHE A SHEETS DO NOT INDICATE ANY RATINGS AT
 ALL.
 2ND FLOOR: C207B, C205A, C206A,
 DOUBLE DOORS TO GARAGE NOT IDENTIFIED,
 C203A INDICATES 45MIN RATED, PIVOT
 DELUGE PROTECTION FRAMELESS, SEE NFPA 80
 DELUGE SYSTEM IS FOR WINDOWS NOT DOORS,
 THE SECOND ISSUE IS THE 45 MIN RATING ON
 A FRAMELESS GLASS DOOR, HOW DO YOU SEAL
 FOR SMOKE AND FIRE?
 3RD FLOOR: AREA WITH ISSUES, STILL
 UNDER CONSIDERATION IN COMMUNICATING
 WITH DESIGN TEAM.C301 PIVOT, FRAMELESS,
  
  
  
 SHEET LS1-02C HAS A 8 1/2X11 SHEET STAPLED TO THE PLAN
 INDICATING THE SEQUENCE OF OPERATION FOR THE MECHANICAL
 AND ELECTRICAL DEVISES.
 THE MECHANICAL AND ELECTRICAL SHEETS WILL NEED TO BE
 FURTHER DEVELOPED TO INCORPORATETHE SEQUENCE OF
 OPERATION ALSO.
  
 PLEASE PROVIDE COMPUTER MODELING FOR
 THE ATRIUM THERE HAS BEEN NO STUDY
 COMPLETED EITHER FOR SMOKE / FIRE PLUME.
  
 3) A SHEETS ARE RED LINED WHERE MISSING FIRE RATINGS ON
 WALLSOR DOORS ARE MISSING IDENTIFICATION.
  
 4)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) R.C. HORIZONTAL ROLLING WINDOWS LOW
 PRESSURE.
  
 B) R.C. FX100 ALUMINUM FIXED WINDOWS
 LOW PRESSURES.
  
 C) GAF MODIFIED BITAMEN ROOF FOR
 CONCRETE DECKS, THE CONTRACTOR
 DIDN'T HIGHLIGHT WHICH SUBSYSTEM
 WILL BE USED. MAY HAVE LOW PRESSURE
 DEPENDING ON THE TYPE OF SYSTEM.
 D) EXTERIOR GUARDRAIL- NO REPORT
 SUBMITTED.
 E) PANEL WALL SYSTEMS: SOFFITS, EFIS
 SYSTEMS, DENSEGLASS
  
 5)SHEET A6.01 DETAIL# 1, INDICATES THE USE OF AN
 EMERGENCY OVERFLOW DRAIN 4 INCHES ABOVE THE ROOF DECK.
 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 6 COMMENT#37 FROM THE PREVIOUS REVIEW,
 50) A6.06 MAIN GLASS CANOPY, PROVIDE
 INFORMATION ON THE CANOPY SYSTEM. ALSO
 PROVIDE INFORMATION ON THE GLAZING
 SYSTEM INDICATING COMPLIANCE WITH
 2407.2.1 ALLOWABLE GLAZING MATERIALS.
 THIS SYSTEM SHALL ALSO BE AN ENGINEERED
 SYSTEM. IT DOESN,T FIT THE PARAMETERS OF
 THE PRODUCT APPROVAL UNDER RULE 9-B, THE
 CANOPY DESIGN WILL BE SITE SPECIFIC. SEE
 "FLORIDA.BUILDING.ORG" FOR REQUIREMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By jwitmer Date 2005-12-14 Time 13:57 Rev Time 20.00
Received By jwitmer Date 2005-12-07 Time 13:56 Sent To  
Notes
2005-12-07 00:00:00 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05071027
 ADD: 2211 N FLAGLER DR
 CONT: PLAN REVIEW
 OWNER: MERCO GROUP
 TEL: (561)296-3300
 ARCH: SONG & ASSOC/ JOHN STRNDBERG
  
 TEL: (561) 655-2423
  
 -PALADIO TERRACE-
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 - NOTE-
  
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM THE PREVIOUS REVIEW,
 ALTHOUGH THERE IS A FOUNDATION PERMIT
 PLEASE SUBMIT THE FOLLOWING ITEMS SINCE
 THE FOUNDATION AND BUILDING PERMITS ARE
 STAND ALONE PERMITS.
 A) SOILS REPORT (3)
 B) THRESHOLD INSPECTION PLAN (3)
 C) THRESHOLD INSPECTOR AGREEMENT(1)
 D) NOTICE OF COMENCEMENT (1)
 E) UNITY OF TITLE
  
 2) COMMENT# 2 FROM THE PREVIOUS REVIEW,
 LS0.00 CODE ANALYSIS IS MISSING:
 THE PLANS ARE VAUGE IN THE
 DESCRIPTION WHERE AS THE FOLLOWING
 INFORMATION WAS TO BE FOUND OR IN THE
 AMOUNT OF INFORMATION PROVIDED.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 ***************************************
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". PLEASE PROVIDE ADDITIONAL INFORMATION FOR
 CODE COMPLIANCE.
  
 2A) 412.4.3 A FIRE COMMAND STATION SHALL
 CONTAIN:
  
 1. CONTROLS FOR THE ONE-WAY VOICE
 ALARM SYSTEM.
  
 2. CONTROLS FOR THE TWO-WAY FIRE
 DEPARTMENT COMMUNICATION SYSTEM.
  
 3. FIRE ALARM SYSTEM ANNUNCIATOR
 PANELS.
 PLEASE INDICATE ON SHEET E-21 ITEMS 1-3
 WILL BE UNDER FIRE ALARM PANEL.
  
  
 4. STATUS INDICATORS SHOWING
 LOCATION OF ELEVATORS IN THE HOISTWAYS
 ANDSWITCHES TO SELECTIVELY TURN
 POWER TO ELEVATORS ON OR OFF.
 THIS COMMENT NOT ADDRESSED ON SHEET
 E-21, PLEASE INDICATE LOCATION.
  
 5. STATUS INDICATORS AND CONTROLS
 FOR AIR HANDLING SYSTEMS. SEE MECHANICAL
 SHEET, SMOKE CONTROL SYSTEM WILL BE
 OPERATED THROUGH THE FIRE ALARM SYSTEM.
 THIS DOESN'T PROVIDE THE INFORMATION
 "HOW" THIS WILL BE COMPLETED. PROVIDE A
 SMOKE CONTROL STUDY FOR THE ATRUIM
 AREAS. WILL BE DISCUSSED LATER UNDER
 HEADING OF ATRIUM.
  
 6. CONTROLS FOR UNLOCKING ALL
 STAIRWAY DOORS SIMULTANEOUSLY.
 E-21 LIST WHAT PANEL THIS SHALL OCCUR.
  
 7. SPRINKLER VALVE, WATERFLOW
 DETECTOR AND FIRE PUMP DISPLAY PANELS.
 NOTE THIS INFORMATION ON E-21 UNDER THE
 HEADING F. P. ASSUMING THIS STAND FOR
 FIRE PUMP.
  
 9. A TELEPHONE FOR FIRE DEPARTMENT
 USE WITH CONTROLLED ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM.COULD NOT FIND
 ON E-21?
  
 2B) SMOKE CONTROL 412.5 PROVIDE CODE
 COMPLIANCE, ALSO REQUIRES COMPLIANCE
 WITH ALL PARTS OF THE HIGH RISE
 INCLUDING THE ATRIUM FOUND UNDER SECTION
 414. 1-10.
 * PROVIDE A SMOKE STUDY INDICATING
 THE AREAS PER FLOOR TO BE CONSIDERED
 ATRIUM, THE TOTAL AREA AND HEIGHT OF THE
 ATRIUM.
 * PROVIDE CALS FOR EXHAUST AIR AND
 FOR THE FRESH AIR INTAKE.
 * PROVIDE INFORMATION PER FLOOR HOW
 SMOKE WILL BE MANAGED.
 *PROVIDE THE WALL LAYOUT INDICATING
 THE 1 HR SEPERATION.LS0.03 IS MISSING
 THE WALL RATING AT THE RESTROOM WALLS.
 * A1.04C THERE IS (4) DOORS WITH NO DESIGNATION.
 * LABEL ALL DOORS IN SAID WALL AND
 PROVIDE MINUTE RATING.
 * INDICATE ON MECH SHEETS WHERE
 DAMPERS ARE REQUIED.
 * SHEETAC-13 INDICATE SF-34 FOR
 THE INTAKE AIR OF THE ATRIUM BUT THE
 SCHEDULE INDICATES NOT USED, IS THIS TO
 BE DRAFTED AIR?
 * ALSO INDICATE ON BOTH THE FIRE
 SPRINKLER PLAN & A SHEETS WHERE THE
 FIRE WATER CURTAIN IS TO BE PLACED ,
 PROVIDE THE SPACING OF SPRINKLER HEADS.
  
 3) PLEASE CORRECT THE MEP SHEETS TO
 DELETE THE TERM MEZZANINE OR PROVIDE
 INFORMATION INDICATING COMPLIANCE WHICH
 503.2.3 MEZANINES FOR AREA AND
 COMPLIANCE WITH 1005.7.1 FOR EXITING.
  
 4) COMMENT# 3 FROM THE PREVIOUS REVIEW
 DEALS WITH THE TERM "TOWNHOUSE" STILL
 SHOWING UP IN THE INDEX PAGES FOR THE ARCHITECTURAL &
 MEP. THE ABBRIVIATION
 "TH" IS NOW FOUND IN THE ARCHITECTURAL
 PAGES A1.05 SW/NW.
  
 5) COMMENT # 4 FROM THE PREVIOUS REVIEW,
 CONDO UNITS 1-14 (LOFT UNITS)
 ARE TO COMPLY WITH FAIR HOUSING MANUAL
 REVISED APRIL 1998, PAGE 1.32. BUILDINGS
 WITH ONE OR MORE COMMON ENTRANCES TO ALL
 DWELLING UNITS IN BUILDINGS WITH ONE OR
 MORE ELEVATORS. AT LEAST ONE COMMON
 ENTRANCE SHALL BE ON AN ACCESSIBLE
 ROUTE. SITE IMPRACTICABILITY TEST DOES
 NOT APPLY TO ELEVATORED BUILDINGS.
 PROVIDE ON THE LIFE SAFETY PLAN THE
 ACCESSIBLE ROUTE FROM THE ELEVATOR TO
 THESE UNITS.
 COMMENT 4 & 5 FROM THE FIRST REVIEW
 TIE TOGETHER. COMMENT FROM THE PREVIOUS
 REVIEW DEALS WITH THESE SAME LOFT UNITS.
 IT APPEARS THAT WE AGREE THAT THE LOFT
 UNITS WILL NEED TO MEET THE REQUIREMENTS
 FOR FAIR HOUSING ON THE LEVEL THAT YOU
 ENTER THE UNIT. THIS IS THE LEVEL 2
 PARKING GARAGE. AS YOU HAVE STATEDTHE
 ACCESSIBLE ROUTE STARTS WITH THE VEHICLE
 OR PEDESTRIAN ARRIVAL POINT.
 ON THIS LEVEL THEY CAN USE THE ELEVATOR
 TO ARRIVE AT THE LOFT ENTRY LEVEL OR
 THEY COULD DRIVE TO THIS LEVEL. ONCE ON
 THIS LEVEL THERE IS TWO PROBLEMS.
 THE FIRST IS THERE IS NO ACCESS TO THE
 PRIMARY ENTRY OF THE LOFTS THAT MEET
 FAIR HOUSING. PROVIDE AN ACCESSIBLE
 ROUTE TO THE UNIT.ON THE WEST SIDE OF
 THE GARAGE COMMENT #5 AND 23 DEAL WITH
 NO ACCESSIBLE ROUTE FROM THESE UNITS.
 THE SECOND ISSUE COMMENT # 5 FROM THE
 PREVIOUS REVIEW DELT WITH THE
 REQUIREMENT OF AN EXIT ACCESS CORRIDOR
 BEING REQUIRED AND THE COMMENT 23 DELT
 WITH THE STRIPED SECTION AGAINST THE
 WALL COULD NOT EVEN BE USED FOR ACCESS
 BECAUSE OF THE COLUMNS PRETRUDING FROM
 THE WALL. THERE YOUR RESPONCE WAS THIS
 IS NOT A MEANS OF EGRESS NOR AN
 ACCESSIBLE PATH !!!!!!!
 AGAIN THIS ENTRY POINT TO THE UNIT IS
 THE PRIMARY ENTRY SINCE THE ELEVATOR
 SERVICES THIS FLOOR SEE FAIR HOUSING
 MANUAL.
 FIRST REVIEW COMMENNT: 5) THESE UNITS
 ARE MISSING EXIT ACCESS
 CORRIDORS, DEFINITION: EXIT ACCESS. THAT
 PORTION OF A MEANS OF EGRESS WHICH LEADS
 TO AN ENTRANCE TO AN EXIT.
 SEE MEANS OF EGRESS DEFINITIONS, MEANS
 OF EGRESS. A CONTINUOUS AND UNOBSTRUCTED
 WAY OF EXIT TRAVEL FROM ANY POINT IN A
 BUILDING OR STRUCTURE TO A PUBLIC WAY,
 CONSISTING OF THREE SEPARATE AND
 DISTINCT PARTS: (1) THE WAY OF EXIT
 ACCESS, (2) THE EXIT, AND (3) THE WAY OF
 EXIT DISCHARGE. A MEANS OF EGRESS
 COMPRISES THE VERTICAL AND HORIZONTAL
 WAYS OF TRAVEL AND SHALL INCLUDE THE
 INTERVENING ROOM SPACE, DOORS,
 CORRIDORS, PASSAGEWAYS, BALCONIES,
 STAIRS, RAMPS, ENCLOSURES, LOBBIES,
 HORIZONTAL EXITS, COURTS AND YARDS.
 PROVIDE EXIT ACCESS CORRIDORS FOR
 UNITS 1-14 COMPLING WITH TABLE 1004
 TRAVEL DISTANCES FOR R2/ SPRINKLERED
 BUILDINGS MAXIMUM TRAVEL DISTANCE OF
 325 FT TO AN EXIT.
  
 6) COMMENT 7(G) FROM THE PREVIOUS REVIEW
 DEALS WITH ELEVATORS, STANDBY POWER FOR
 ELEVATORS. RESPONCE WAS THAT ALL OF THE
 ELEVATORS ARE CONNECTED TO THE STANDBY
 POWER BUT ONLY ONE PER SHAFT WILL WORK
 AT A TIME WHEN THE GENERATOR IS RUNNING.
 WILL THIS SHOW UP ON THE EMERGENCY
 POWER, EMERGENCY SYSTEMS CONTROLS AND
 STATUS INDICATORS? WILL THERE BE
 OVERRIDES SWITTCHES? 412.4.3(8).
  
 7) COMMENT# 10(D) FROM THE PREVIOUS
 REVIEW, 10D) BOTH SHEETS A1.02NE &
 A1.02SE BOTH INDICATE THE USE OF
 HORIZONTAL SLIDING DOORS C-0101-C &
 C-0101-E, 1012.4(9).
 IN APARTMENT BUILDINGS, HOTELS AND
 DORMITORIES, HORIZONTAL SLIDING DOORS
 SHALL NOT BE USED ACROSS CORRIDORS.
 THE ABOVE DOORS ARE IN A EXIT ACCESS
 CORRIDOR MAKING THEM PART OF AN EXIT.
 SEE DIFINITION OF EXIT COMPOSED OF THREE
 PARTS THE EXIT ACCESS CORRIDOR, EXIT &
 EXIT DISCHARGE.
  
 8) SHEET A1.03 BUSS DUCK CLOSETS DOORS
 SWING OVER THE 1/2 OF THE REQUIRED WIDTH
 OF THE CORRIDOR.
 1012.1.4 DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF AN AISLE,CORRIDOR, PASSAGEWAY, OR
 LANDING, NOR PROJECT MORE
 THAN 7 IN.(17.8 CM)INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN.
 MINIMUM OF 22" CLEAR.
  
 9) A1.02 SW / NW PLANS INDICATE EXHAUST
 FANS ABOVE IN GARAGE, A2.04 NW
 ELEVATION, THE BOTTOM FLOOR WINDOWS ARE
 NOT MAARKED AS TO TYPE? ARE THEY FIXED ?
 EXHAUST FROM GARAGE TO BE A MINIMUM OF
 10 FT FROM OPENINGS SEE M401.
  
 10) A2.04 WINDOW # 4 NOTE INDICATES FIRE
 RATED WHERE IS THE WINDOW SCHEDULE
 INDICATING HR / MIN RATING?
  
 11) A1.04 AT THE NORTH AND SOUTH END OF
 THE PARKING GARAGE THERE AREAS FENCED
 OFF FOR INTAKE AND EXHAUST AIR, PLEASE
 PROVIDE SIGNAGE "NO STORAGE".
  
 12) A1.04SW POOL EQUIPMENT, PROVIDE HOW
 CHORINE WILL BESTORED FOR POOL, LIQUID
 OR GAS FORM, QUANITY? THIS AREA WILL BE
 CLASSIFIED AS A H-4 (308.2)OCCUPANCY
 UNTIL FURTHER INFORMATION IS REVIEWED.
  
 13) SHEET A1.05.NE ELEVATOR# 7 PLEASE
 IDENTIFY OBJECT NEXXT TO THE ELEVATORS?
  
 14) COMMENT# 26 FROM THE PREVIOUS REVIEW
 A1.05NE UNITS DO NOT HAVE EGRESS TO
 STAIR TOWER WITHOUT TRAVEL THROUGH THE
 ELEVATOR LOBBIES SEE 412.6.2. THE
 BEDROOM TERRACE LEVEL, LOCKABLE DOORS,
 1001.1.3, MEANS OF EGRESS SHALL CONSIST
 OF CONTINUOUS AND UNOBSTRUCTED PATHS OF
 TRAVEL TO THE EXTERIOR OF A BUILDING.
 UNIT 512 OK, UNITS THAT DO NOT COMPLY
 513,514, 515, 516 & 517.
  
 15) COMMENT# 28 FROM THE PREVIOUS REVIEW
 A1.05SE UNITS DO NOT HAVE EGRESS TO
 STAIRS WITHOUT TRAVEL THROUGH THE
 ELEVATOR LOBBY, UNITS 411, 410, 409, 408
 & 404. LOCKABLE DOORS 1001.1.3.
  
 16) A1.05NW THE PASSAGEWAY OR EXIT
 ACCESS TO THE (2) NORTHWEST EXIT STAIRS
 APPEARS TO HAVE A WINDOW FROM UNIT 422
 THAT WOULD REQUIRE A FIRE RATED WINDOW,
 POOL DECK BEING A ASSEMBLY OCCUPANCY
 VERSES R-2 UNIT# 422, REQUIRING A 2HR
 WALL AND 1 1/2 HR OPENING PROTECTIVE.
 IT APPEARS THAT TO THE UNIT(LOFT)# 14
 THE BLOCK WALL TO THE EXTERIOR OF THE
 SUNDECK THIS SHOULD ALSO BE A 2 HR RATED
 WALL, PLANS DO NOT PROVIDE THE HEIGHT OF
 THIS WALL?SEE TABLE 704
  
 17) COMMENT# 29 FROM THE FIRST REVIEW
 INDICATES THAT ON THE POOL DECK LEVEL
 TOWER 7&8 WILL ALLOW RE-ENTRY. THE
 DOOR IN STAIR# 14 (POOL DECK) SWINGS THE
 WRONG WAY.WILL THIS ALLOW RE-ENTRY? THE
 OTHER STAIR ON THE POOL DECK THAT
 APPEARS TO ALLOW RENTRY IS STAIR# 9 WILL
 THIS ALLOW REENTRY? STAIR #9 ALSO HAS AN
 ALLOWABLE OCCUPANT LOAD OF 200 INDICATED
 ON THE LIFE SAFETY PLAN, BUT THE DOOR
 WILL ONLY ALLOW 170. WHERE WILL THE
 ADDITIONAL LOADING BE MADE UP? SEE
 COMMENT# 21. 1010.1.2 THERE SHALL BE NO
 REDUCTION OF WIDTH IN THE DIRECTION OF
 TRAVEL.WILL THESE DOORS ALLOW RE-ENTRY
 BACK INTO THE STAIRWELL? YOUR REPLY
 INDICATED TOWER 7&8?
  
 18A) COMMENT# 16 FROM THE FIRST REVIEW,
 A1.04C THERE IS A TRUE ISSUE OF THE
 ATRIUM VERSUS THE ELEVATOR LOBBY.BY
 DEFINITION, ATRIUM. A SPACE, INTENDED
 FOR OCCUPANCY WITHIN A BUILDING,
 EXTENDING VERTICALLY THROUGH THE
 BUILDING AND ENCLOSED AT THE TOP.SINCE
 THE 3RD FLOOR IS ENCLOSED BY GLASS, THIS
 TRUELY MAKES A SHAFT SEPERATING IT FROM
 THE REST OF THE BUILDING.
 SINCE THIS IS A HIGH RISE, AND THE
 SHAFT SEPERATES THIS AREA REMOVING THE
 ATRIUM THEORY,412.6.1 CAN NOT TAKE THE
 EXEMPTION FOR ATRIUMS MAKING AN ELEVATOR
 LOBBY REQUIRED FOR FLOORS 2,3 & 4.
 THE RESPONCE DOCUMENTS STATE THAT
 "GLASS HAS BEEN REMOVED AND PARTITION
 HAS BEEN ADDED TO MEET THE DEFINITION OF
 THE ATRIUM REQUIREMENT & TO ELIMINATE
 THE SHAFT CRITERIA."
 18A)(1)SHEET A1.04C STILL INDICATES A
 GLASS ENCLOSURE AROUND THE ATRIUM SHAFT. 18A)(2)THE
 PLANS ALSO INDICATE A PAIR OF
 SWING GLASS FRAMELESS DOORS TO BE
 INSTALLED, WITH A 45 MIN RATING PROVIDE
 MORE DETAILS.HOW WILL THE DOORS SEAL
 AGAINST SMOKE?
 18A)(3) THERE IS FOUR DOORS ON THIS
 SHEET NOT LABELED.
 18B) SMOKE CONTROL FOR THE ATRIUM, THE
 MECHANICAL PLANS SHEET AC-13 ONLY SHOWS
 THE FRESH AIR INTAKE THROUGH A PLENUM
 MOTER SF-34 NOT USED, AC- 14 SHOW THE
 EXHAUST MOTOR SF-36. THIS IS THE ONLY
 INFORMATION PROVIDED, AS STATED EARLIER
 PLEASE PROVIDE THE DOCUMENTATION AS
 REQUESTED UNDER 2B.
 18C) PLEASE PROVIDE AREA CALCULATIONS
 FOR THE FIRST FLOOR OF THE ATRIUM AND
 THE MEZZANINE LEVEL 503.2.3.2.SPACES
 ENCLOSED BENEATH THE MEZZANINE CAN NOT
 BE TAKEN INTO THE THE 1/3RD AREA TO BE
 THE MEZZANINE.
 18D) MEZZANINE LEVEL MUST MEET THE
 REQUIREMENTS OF 1005.7.3 THE SPACE
 BENEATH THE MEZZANINE MAY BE ENCLOSED
 PROVIDED THE ENCLOSED SPACE IS
 PROTECTED THROUGHOUT WITH A SMOKE
 DETECTION SYSTEM IN ACCORDANCE WITH NFPA
 72 WHICH SOUNDS AN ALARM IN THE
 MEZZANINE.
  
 19) COMMENT# 26 FROM THE PREVIOUS
 REVIEWA1.05NE UNITS DO NOT HAVE EGRESS
 TO STAIR TOWER WITH OUT TRAVEL THROUGH
 THE ELEVATOR LOBBY SEE 412.6.2. THE
 BEDROOM TERRACE LEVEL IS A PROBLEM,
 SINCE 1001.1.3 REQUIRES TRAVEL TO BE
 CONTINIOUS AND UNOBSTRUCTED PATH OF
 TRAVEL. BEDROOM DOORS ARE LOCKABLE
 DOOR.UNITSTHAT DO NOT COMPLY ARE
 513,514,515,516 & 517.
  
 20) COMMENT# 28 FROM THE PREVIOUS
 REVIEW SHEET A1.05SE UNITS DO NOT HAVE
 TRAVEL THROUGH THE ELEVATOR LOBBY ARE
 411,410,409, 408 & 404. SEE 412.6.2 &
 1001.1.3.
  
 21) SHEET LS0.05 LIFE SAFETY POOL DECK
 SHEET INDICATES THE VARIOUS STAIRWELLS
 AND THE OCCUPANT LOAD THAT EACH
 STAIRWELL CAN HANDLE.
  
 21A) PLANS (LS0.05) INDICATE THAT
 STAIRWELL# 10-13 EACH WILL ACCOMADATE
 240X4= 960 OCCUPANT LOAD FOR THESE (4)
 STAIRS. THE A1.05SW & A1.05NWINDICATE
 THE CORRESONDING ENTRY DOORS AS
 401,402,417 AND 418 AS 3'-0" DOORWAYS
 WITH AN ALLOWABLE LOAD OF 34"/.2=170 PER
 DOORWAY, 170X4=680 OCCUPANT LOAD AT THE
 DOORWAYS.PLEASE REVISE THE LOADS ON
 THE LIFE SAFETY SHEET AND INDICATE HOW
 THE ADDITIONAL LOADS WILL BE MADE UP?
 ALSO CORRECT FIGURES FOR STAIR 9 & 14.
  
 21B) PLANS (LS0.05) ALSO INDICATETHAT
 STAIRWELLS# 10-13 WILL CARRY AN
 OCCUPAANT LOAD OF 240 FOR EACH STAIROR A
 TOTAL OF 960 FOR THESE 4 STAIR TOWERS.
 TABLE 1004 FOOTNOTE 14 ALLOWS .3 TO BE
 USED DIVIDED INTO THE STAIR WIDTH OF 60"
  
 60/.3= 200 OCC LOAD X 4 STAIRS= 800 NOT
 THE 960 INDICATED ON THE LIFE SAFETY
 PLAN. ALSO CORRECT THE FIGURES FOR STAIR
 9 & 14.
  
 21C) DEPENDING ON THE DESIGNERS DECISION
 OF HOW TO CORRECT THE PROBLEM OFBOTTLE
 NECKING, FOLLOW THROUGH THE EXIT TO THE
 EXIT DISCHARGE TO SEE THAT THIS PROBLEM
 WILL NOT REOCCUR? SEE DOORWAYS AT THE
 BOTTOM OF THE STAIR.
  
  
 21) COMMENT# 33A) FROM THE PREVIOUS
 REVIEW,A1.06NE THIS COMMENT WILL
 EFFECT MOST OF THE STAIRWELL, (EXITS)
 WITHIN THE BUILDING. THE PLANS INDICATE
 A EXIT DOOR THAT LEADS DIRECTLY FROM THE
 CONDO UNIT INTO THE SMOKEPROOF EXIT
 ENCLOSURE.
 THE INTENT IS TO HAVE AN EXIT THAT
 DOESN'T TRAVEL THROUGH THE ELEVATOR
 LOBBY.THE CODE SECTION THAT DOESN'T
 ALLOW ROOMS TO EMPTY DIRECTLY INTO THE
 EXIT IS:
 1005.6.7 ACCESS TO THE STAIRWAY SHALL BE
 BY WAY OF A VESTIBULE OR BY WAY OF AN
 OPEN EXTERIOR BALCONY OF NONCOMBUSTIBLE MATERIALS.
 EXCEPTION: ACCESS BY WAY OF A
 VESTIBULE WHEN THE STAIRWAY MEETS THE
 REQUIREMENTS OF 1005.6.9.2 (1-3),
 1005.6.9.9 AND 1005.6.9.10 & IS LOCATED
 IN A FULLY SPRINKLEREDBUILDING.
 COMPLIANCE WITH THE THREE CODE
 REFRENCES STATED ABOVE WILL ALLOW DIRECT
 ENTRY TO THE STAIRWELL WITHOUT A
 VESTIBLE.
 1) 1005.6.9.2 DEALS WITH STAIRWELL PRESSURIZATION,
 WHICH IS INDICATED ON
 THE PLANS,
 2) 1005.6.9.10 IS THE REQUIEMENT FOR
 REQUIRED SMOKE DETECTORS THAT WOULD BE
 USUALLY IN THE VESTIBULE, BUT IT WOULD
 BE IN THE STAIR TOWER IF THE DOOR FROM
 THE UNIT IS OPEN ALLOWING SMOKE TO ENTER
 THE STAIR TOWER. THE SMOKE DETECTOR IS
 TO BE PLACED IN THE UNITIF ACTIVATED TO
 SHUT DOWN THE INDIVIDUAL UNIT AND
 ACTIVATING ALL SMOKE EVACUATION SYSTEMS
 IN THE STAIR TOWER. NO SMOKE DETECTORS
 ARE SHOWN ON THE ELECTRICAL SHEETS.
 3) 1005.6.9.9 EXHAUST AIR, A MINIMUM
 OF 2,500 CFM THROUGH A DAMPERED RELIEF
 OR AN EXHAUST FAN AT THE TOP OF THE
 STAIR SHAFT.
 SHEET AC31 INDICATES ONLY GOOSENECKS
 ON STAIR TOWER 5,8,9/ 6,7& 10.
 NO RELIEF DAMPER DAMPER SHOWN, AC-28
 FAN SCHEDULE IS MISSING SF 4,6 & 10.
 STAIRDETAIL 4,11 & 13 IS MISSING THE
 GOOSENECK, IT APPEARS THAT STAIRS 3,12 &
 14 ARE EXHAUSTING AIR INTO SOME ROOM?
 THERE IS A DESCREPANCY BETWEEN HOW
 THE DESIGN TEAMS ARE LISTING THE
 STAIRWELLS. SONG AND FES ARE NOT USING
 THE SAME IDENTIFICATION SYSTEM FOR
 STAIRWWELLS, CORRECT SO IF WE ARE
 LOOKING FOR A STAIRWELL ON ARCHITECTUALS
 THE SAME NOMENCLATURE WILL BE USED ON
 THE FES PLAN.
  
 22) COMMENT# 33B) THIS IS A COMMENT THAT
 IS BKOKEN OUT FROM THE FIRST REVIEW.
 A1.08NE AS IS SHOWN ON THE PLAN IS CODE
 COMPLIANT, BUT A DOOR COULD EASLY BE
 INSTALLED CREATING A SECOND BEDROOM AND
 VIOLATION 2ND MEANS OF EGRESS BLOCKED
 BECAUSE OF LOCKABLE DOORS. 1001.1.3.
  
 23) PLANS DO NOT INDICATE COMPLIANCE
 WITH 1012.1.11EVERY DOOR IN A STAIR
 ENCLOSURE SERVING MORE THAN FOUR STORIES
 SHALL PERMIT RE-ENTRY FROM THE STAIR
 ENCLOSURE TO THE INTERIOR OF THE
 BUILDING, OR AN AUTOMATIC RELEASE SHALL
 BE PROVIDED TO UNLOCK ALL STAIR
 ENCLOSURE DOORS TO PERMIT RE-ENTRY.
 SUCH AUTOMATIC RELEASE SHALL BE
 ACTUATED WITH THE INITIATION OF THE
 BUILDING FIRE ALARM, FIRE DETECTION OR
 FIRE SPRINKLER SYSTEM.THE DOOR SCHEDULE
 SHOWS NO SUCH DEVICES.
  
 24)COMMENT # 57 FROM THE PREVIOUS REVIEW
 412.8.1 ALL STAIRWAY DOORS WHICH ARE
 TO BE LOCKED FROM THE STAIRWAY SIDE
 SHALL HAVE THE CAPABILITY OF BEING
 UNLOCKED SIMULTANEOUSLY WITHOUT
 UNLATCHING UPON A SIGNAL FROM THE
 CENTRAL CONTROL STATION.THE DOORS
 SHALL BE SIMILARLY UNLOCKED UPON
 ACTIVATION OF THE SPRINKLER SYSTEM OR
 UPON POWER FAILURE.RESPONCE : NO DOORS
 AT ANY STAIRWELLS ARE SCHEDULED TO BE
 LOCKED FROM WITHIN THE BUILDING AND ONLY
 DOORS FROM THE OUTSIDE ARE DESIGNED WITH
 NO ACCESS EXCEPT KNOX BOXES ARE
 SCHEDULED AT EACH EXTERIOR DOOR FOR FIRE DEPARTMENT
 ACCESS.
 IF THIS ISTRUE THIS MEANS YOU WILL
 BE ABLE TO TRAVEL FROM FLOOR TO FLOOR
 AND INTO EACH INDIVIDUAL UNIT OF THE
 STAIR TOWER SINCE THERE IS NO PLAN FOR
 A VESTIBULE?
  
 THE SECOND HALF OF THIS COMMENT WAS
 NEVER ADDRESSED.
 412.8.2 TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS
 SYSTEMS CONNECTED TO AN
 APPROVED EMERGENCY SERVICE WHICH
 OPERATES CONTINUOUSLY SHALL BE
 PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH REQUIRED STAIRWAYWHERE
 OTHER PROVISIONS OF THIS CODE PERMIT THE
 DOORS TO BE LOCKED.
  
 25) COMMENT# 61 FROM THE PREVIOUS REVIEW
 DEALS WITH HDS (HIGH DENSITY FOAM)
 PROVIDE ADDITIONAL INFORMATION, TESTING
 REPORT WHERE THIS PRODUCT MEETS THE
 EXCEPTION OF 707.1
  
 26) A6.01 DETAIL# 2 EPS FOAM CORE
 ARCHITECTURAL TRIM, SEE 1404.1.1
 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE
 I, II AND IVCONSTRUCTION NOT MORE
 THAN THREE STORIES OR 40 FT (12.2 M)
 HIGH MAY BE OFTYPE VI CONSTRUCTION,
 AND MAY BE OF TYPE VI CONSTRUCTION ON
 ALL BUILDINGSOF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO
 THE WALLWITH METAL OR OTHER APPROVED
 BRACKETS OR FASTENERS.WHEN
 ARCHITECTURALTRIM IS LOCATED ALONG
 THE TOP OF EXTERIOR WALLS, IT SHALL BE
 COMPLETELYBACKED BY THE EXTERIOR WALL
 AND SHALL NOT EXTEND OVER THE TOP OF
 EXTERIOR WALLS.
  
 27) A6.01 DETAIL# 3, THE RAILING DETAIL
 FROM THE STUCCO FINISH TO THE BOTTOM OF
 THE GLASS RAIL IS TO BE UNDER 4" NOT A
 MAXIMUM OF 4", A 4" SPHERE IS TO REJECT
 PASSING THROUGH. 1015.3 OPENINGS. OPEN
 GUARDRAILS SHALL HAVE INTERMEDIATE RAILS
 OR ORNAMENTAL PATTERN SUCH THAT A 4-INCH
 (102 MM) DIAMETER SPHERE CANNOT PASS
 THROUGH ANY OPENING UP TO A HEIGHT OF 34
 INCHES.A BOTTOM RAIL OR CURB
 SHALL BE PROVIDED THAT WILL REJECT THE
 PASSAGE OF 2-INCH (51 MM) DIAMETER
 SPHERE.
  
 28) SHEET A0.05
 28A) THE VARIOUS FLOOR LEVELS 1-4 DO NOT
 SHOW ANY OF THE INTERIOR WALL RATINGS ON
 THE FULL FLOOR LAYOUT OR THE NE, C, SE,
 SW, P, OR NW SHEETS.
 28B) FOR LEVELS 5-17 THE INTERIOR
 PARTITIONS (P1-P6) ARE SHOWN BUT NOT THE
 WALL HOUR FIRE RATING AS DEPICTED IN THE
 LEGEND " WALL TYPE SSYMBOL LEGEND".
 PLEASE CORRECT AND INDICATE THE WALL
 HOUR FIRE RATING.
 28C) PLANS INDICATE C-1 APPEAR TO BE 2HR
 WHILE C-2 APPEARS TO BE 1 HR, PROVIDE
 FIRE RATING,THE PLAN INDICATES USE OF
 3 5/8" STUDS WHERE AS UL 420 DEPICTS 1
 5/8" STUDS, PLEASE CORRECT.
 28D) WALL TYPE C-3 REFERS TO FBC 209.1
 CHAPTER 2 DEFINITIONS ONLY GOES TO 202?
 PROVIDE U L LISTING FOR WALL ASEMBLY.
 28E) SAME COMMENT BUT REFERING TO WALL
 TYPE W1 & W2 PLEASE PROVIDE UL LISTING.
 28F)C-5 - C-8 ALL INDICATE THE USE OF
 C-H OR I STUDS WHILE THE UL LISTING
 PROVIDEDUNDER THE HEADING STEEL STUDS
 ONLY INDICATES THE USE OF C-H STUDS,
 PLEASE CORRECT.
 28G) CORRECT C-7 HEADING 2HR RATED SHAFT
 BUT REFRENCES 2 UL LISTINGS, UL 467 IS 2
 HR, DELETE UL 469 OR NEW HEADING FOR 1
 HR SEE C-8 1 HR RATING.
 28H) CONTROL JOINT DETAIL PROVIDE THE UL
 LISTING FOR 1& 2 HR RATED WALLS.
  
 29) A0.06
 29A) COULD NOT LOCATE THE UL J973 ?
  
 30)A5.01DETAIL 03. WALL C-4 INDICATES
 2 HR RATING WHEREAS A0.05 C4 DOESN'T
 INDICATE THE UL WALL RATING OR PROVIDE
 FROM THE BLOCK MANUFACTURER THE
 EQUIVALENT THICKNESS FOR THE RATED BLOCK
 TO BE USED. TABLE 709.3.1
  
 31) A5.02 DETAIL# 1 AHU LEFTSIDE OF PAGE
 MATCH A1.05 NE BUT NOT THE A/C04
 INDICATES ACCESS FOR THE A/C UNIT
 THROUGH THE ELEVATOR LOBBY, PLEASE
 CORRECT.
  
 32)COMMENT# 40 FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 33)COMMENT# 41 FROM THE PREVIOUS REVIEW,
 41) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED, STOREFRONT, OPERTABLE
 PASS THROUGHS OR GLASS BLOCK, MULLIONS
 A1) PROVIDE A WINDOW SCHEDULE THAT
 WILL CORRALATE TO WINDOW TYPES
 FOUND ON A7.13-16
 A2) NO REPORT FOR STOREFRONT
 A3)CASEMENT WINDOWS A2.03 HAS ZONES AS
  
 HIGH AS 95 & 105 BUT THE ELEVATIONS
 DO NOT INDICATE WHAT TYPE OF
 WINDOWS THESE ARE. THE SECOND ISSUE
 WILL BE THE REPORT SUBMITTED IS FOR
 LARGE MISSLE IMPACT GLAZING, WILL
 ALL THE CASEMENT WINDOWS SUPPLIED
 BE LARGE MISSLE SMALL MISSLE AND OR
 ONLY RATED FOR WIND DEPENDING ON
 THE LOCATION FROM GRADE?
 B) EXTERIOR DOORS, SOLID, SWING, GLAZED
 SLIDERS ROLL UP
 B1)NO REPORTS WERE SUBMITTED FOR SOLID
 CORE DOORS
 C) MULLIONS BOTH VERTICAL & HORIZONTAL
 D) SKYLIGHTS- 2 SEPERATE SKYLIGHT
 REPORTS WERE SUBMITTED, PARAMOUNT
 SKYLIGHT REPORT IS FOR RIDGE TYPE
 SIMPLE SKYLIGHT, PROVIDE WHERE THIS
 IS TO BE USED.
 SUPER SKY LIGHT PRODUCTS ALSO HAS
 LIMITATIONS IN MAXIMUM LIGHT SIZE OF
  
 30 SQ FT LITE SIZE, CONFIGURATIONS
 SHOWN ON SHEET B OF 7 AND DESIGN
 PRESSURE. A2.01 THE GLASS ENCLOSURE
 INDICATES PRESSURES OF +/-105. THIS
 SKYLIGHT WILL REQUIRE SITE SPECIFIC
 ENGINEERING !!!!!!!!!!!!!
 E) EXTERIOR VENTS OR LOUVERS
 NO PRODUCT APPROVALS WERE SUBMITTED
 F) EXTERIOR GUARDRAILS
 NO PRODUCT APPROVALS WERE SUBMITTED
 G) PANEL WALL SYSTEMS: SOFFITS, EFIS
 SYSTEMS, DENSEGLASS
 H) ROOFING PRODUCTS/ ASSEMBLIES
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 _X__ CONTRACTOR DID NOT INDICATE THE
 ROOF PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 34)COMMENT# 37 FROM THE PREVIOUS REVIEW,
 WILL REQUIRE THIS INFORMATION BEFORE
 ISSUANCE OF PERMIT:
 A3.04A/ A3.05A INDICATES A
 STRUCTURAL STEEL AND GLASS SKYLIGHT TO
 BE USED SHOW COMPLIANCE WITH:
 34 A)13-104.4.5 FENESTRATION ENERGY
 RATING LABELS. ENERGY PERFORMANCE VALUES
 (I.E.,U-FACTOR, SOLAR HEAT GAIN
 COEFFICIENT) OF FENESTRATION PRODUCTS
 (I.E., WINDOWS, DOORS AND SKYLIGHTS)
 SHALL BE DETERMINED BY AN ACCREDITED, IN
 DEPENDENT LABORATORY AND LABELED AND
 CERTIFIED BY THE MANUFACTURER.
 34B) 1604.3 CONCENTRATED FLOOR LIVE
 LOADS SKYLIGHT RIBS 200 LBS
 34C) MUST MEET SMALL MISSLE IMPACT
 TESTING 30'-60' FROM THE GROUND.
 34D) 1707.4.2.1.1 TEST AND LABELING OF
 SKYLIGHTS. EXTERIOR SKYLIGHTS SHALL BE
 TESTED BY AN APPROVED INDEPENDENT
 TESTING LABORATORY, AND SHALL BE LABELED
 WITH AN APPROVED LABEL IDENTIFYING THE MANUFACTURER,
 PERFORMANCE
 CHARACTERISTICS AND APPROVED PRODUCT
 EVALUATION ENTITY TO INDICATE COMPLIANCE
 WITH THE REQUIREMENTS OF THE FOLLOWING SPECIFICATION:
 AAMA/WDMA 1600/IS7,
 VOLUNTARY SPECIFICATION FOR SKYLIGHTS OR
 TAS 202 (HVHZ SHALL COMPLY WITH TAS 202) 34E)2405.3.2
 SLOPED GLAZING.GLASS
 SLOPED MORE THAN 15 DEGREES (0.26 RAD)
 FROM VERTICAL IN SKYLIGHTS, SUNSPACES,
 SLOPED ROOFS AND OTHER EXTERIOR
 APPLICATIONS SHALL BE CHOSEN TO RESIST
 THE APPLICABLE LOADS FOR COMPONENTS
 AND CLADDING.THE ALLOWABLE COMBINED
 LOAD FOR THE GLASS SHALL BE DETERMINED
 IN ACCORDANCE WITH 2405.3.2.1 THROUGH
 2405.3.2.3.
  
 35) COMMENT # 38FROM THE PREVIOUS REVIEW
 PROVIDE DETAILS FROM THE PRE-CAST
 SPECIALTY ENGINEER HOW SYSTEM ISTO BE
 ASSEMBLED. WHAT TYPE MATERIAL IS TO BE
 USED, FORCES TO BE RESISTED, UPLIFT,
 LATERAL LOADS AND GRAVITY LOADS.WILL
 REQUIRE THIS INFORMATION BEFORE ISSUANCE
 OF THIS PERMIT.
  
 36)COMMENT# 49 FROM THE PREVIOUS REVIEW,
 A6.01 RAILING DETAIL INDICATES TWO
 INCHES CLEAR FROM THE BOTTOM RAIL TO THE DECK.1015.3
 OPENINGS. A BOTTOM RAIL OR
 CURB SHALL BE PROVIDED THAT WILL REJECT
 THE PASSAGE OF 2-INCH (51 MM) DIAMETER
 SPHERE.THIS CODE SECTION REQUIRES
 REJECTION OF A 2" SPHERE, REQUIRING THE
 OPENING TO BE LESS THAN 2".
  
 37)COMMENT# 50 FROM THE PREVIOUS REVIEW,
 50) A6.06 MAIN GLASS CANOPY, PROVIDE
 INFORMATION ON THE CANOPY SYSTEM. ALSO
 PROVIDE INFORMATION ON THE GLAZING
 SYSTEM INDICATING COMPLIANCE WITH
 2407.2.1 ALLOWABLE GLAZING MATERIALS.
 THIS SYSTEM SHALL ALSO BE AN ENGINEERED
 SYSTEM. IT DOESN,T FIT THE PARAMETERS OF
 THE PRODUCT APPROVAL UNDER RULE 9-B, THE
  
 CANOPY DESIGN WILL BE SITE SPECIFIC. SEE
 "FLORIDA.BUILDING.ORG" FOR REQUIREMENTS.
  
 38)COMMENT# 54 FROM THE PREVIOUS REVIEW
 P-2 INDICATES PLUMBING IN THE EXIT
 TOWERS, TOWER 5 STAIR A, TOWER8 STAIR A. 1006.1.3.1
 PENETRATIONS INTO OPENINGS
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR INDEPENDENT STAIR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES AND
 ELECTRICAL CONDUIT SERVING THE
 STAIRWAY AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQ IN. (0.010 M^2).
 SUCH PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH ?705.4.THERE SHALL BE NO PENETRATIONS
 OR COMMUNICATING OPENINGS,
 WHETHER PROTECTED OR NOT, BETWEEN
 ADJACENT STAIR ENCLOSURES.
 EXIT STAIRWAYS ARE RATED SHAFTS THAT
 ARE VERTICAL OPENINGS EXTENDING THROUGH
 ONE OR MORE STORIES IN A BUILDING.
 STORY: THAT PORTION OF A BUILDING
 INCLUDED BETWEEN THE UPPER SURFACE OF
 THE FLOOR AND THE UPPER SURFACE OF THE
 NEXT FLOOR OR ROOF ABOVE. NO SOFFITS
 SHALL BE BUILT INTO THESE AREAS OF
 SHAFTS EVEN IF YOU RATE THEM FOR 2 HRS.
 THERE IS TO BE NO PENETRATIONS INTO
 STAIRWAY ENCLOSURES EXECT FOR THOSE
 REQUIRED FOR REQUIRED EXIT DOORS,
 DUCTWORK, EQUIPMENT REQUIRED FOR
 INDEPENDENT STAIR PRESSUREIZATION,
 SPRINKLER PIPING, STANDPIPE AND
 ELECTRICAL CONDUIT SERVING THE STAIRWAY
 .
  
 39)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By jwitmer Date 2005-09-09 Time 16:39 Rev Time 44.00
Received By jwitmer Date 2005-09-09 Time 16:38 Sent To  
Notes
2005-09-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071027
 ADD: 2211 N FLAGLER DR
 CONT: PLAN REVIEW
 OWNER: MERCO GROUP
 TEL: (561)296-3300
 ARCH: SONG & ASSOC/ JOHN STRNDBERG
  
 TEL: (561) 655-2423
  
 -PALADIO TERRACE-
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ALTHOUGH THERE IS A FOUNDATION PERMIT
 PLEASE SUBMIT THE FOLLOWING ITEMS SINCE
 THE FOUNDATION AND BUILDING PERMITS ARE
 STAND ALONE PERMITS.
 A) SOILS REPORT (3)
 B) THRESHOLD INSPECTION PLAN (3)
 C) THRESHOLD INSPECTOR AGREEMENT(1)
 D) NOTICE OF COMENCEMENT (1)
 E) UNITY OF TITLE
 F) PROVIDE A SITE PLAN W/ BUILDING LINE
  
 VS. THE PROPERTY LINE.
  
 2) LS0.00 CODE ANALYSIS IS MISSING:
 2A) 412.3.3 FIRE DEPARTMENT
 COMMUNICATION SYSTEM. A TWO-WAY FIRE
 DEPARTMENT COMMUNICATION SYSTEM SHALL BE
 PROVIDED FOR FIRE DEPARTMENT USE.
 IT SHALL OPERATE BETWEEN THE FIRE
 COMMAND STATION AND EVERY ELEVATOR,
 ELEVATOR LOBBY, ENTRY TO EVERY ENCLOSED
 EXIT STAIRWAY AND IN CORRIDORS.
  
 412.3.4 COMBINED SYSTEM. WHEN APPROVED,
 THE FIRE DEPARTMENT COMMUNICATIONS
 SYSTEM MAY BE COMBINED WITH THE VOICE
 ALARM SIGNALING SYSTEM.
  
 FIRE COMMAND STATION
  
 412.4.1 A FIRE COMMAND STATION FOR
 FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE
 FIRE DEPARTMENT.
  
 412.4.3 A FIRE COMMAND STATION SHALL
 CONTAIN:
  
 1. CONTROLS FOR THE ONE-WAY VOICE
 ALARM SYSTEM.
  
 2. CONTROLS FOR THE TWO-WAY FIRE
 DEPARTMENT COMMUNICATION SYSTEM.
  
 3. FIRE ALARM SYSTEM ANNUNCIATOR
 PANELS.
  
 4. STATUS INDICATORS SHOWING
 LOCATION OF ELEVATORS IN THE HOISTWAYS
 AND
 SWITCHES TO SELECTIVELY TURN
 POWER TO ELEVATORS ON OR OFF.
  
 5. STATUS INDICATORS AND CONTROLS
 FOR AIR HANDLING SYSTEMS.
  
 6. CONTROLS FOR UNLOCKING ALL
 STAIRWAY DOORS SIMULTANEOUSLY.
  
 7. SPRINKLER VALVE, WATERFLOW
 DETECTOR AND FIRE PUMP DISPLAY PANELS.
  
 8. EMERGENCY POWER, LIGHT AND
 EMERGENCY SYSTEM CONTROLS AND STATUS
 INDICATORS.
  
 9. A TELEPHONE FOR FIRE DEPARTMENT
 USE WITH CONTROLLED ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM.
  
 10. GENERATOR SUPERVISION DEVICES,
 MANUAL START AND TRANSFER FEATURES.
  
 PLANS INDICATE THAT THEY WILL COMPLY
 WITH FBC CHAPTER 9, SECTION 412.3 & NFPA
 72-2002. 104.2.1 W.P.B. ADMINISTRATIVE
 CODE DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 ***************
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". PLEASE PROVIDE ADDITIONAL
 INFORMATION FOR CODE COMPLIANCE.
 ***************
  
 2B)SMOKE CONTROL 412.5
 PROVIDE CODE COMPLIANCE. IF SYSTEM IS TO
 COMPLY WITH (3) 412.7.2).UNDER FIRE
 CONDITIONS, THE RETURN AND EXHAUST AIR
 SHALL BE MOVED DIRECTLY TO THE
 OUTSIDE WITHOUT RECIRCULATION TO OTHER
 SECTIONS OF THE BUILDING.THE AIR
 HANDLING SYSTEM SHALL HAVE THE
 CAPABILITY OF PROVIDING A MINIMUM OF ONE
 EXHAUST AIR CHANGE EVERY 10 MINUTES FOR
 ANY AREA WHICH MIGHT BE INVOLVED.
  
 3) LS0.03 HAS THE TERM "TOWNHOUSE"
 DESCRIBING R2 UNITS. THESE UNITS ARE
 CONDOMINIUMS NOT TOWNHOUSES. THE FL BLDG
 CODE 2001 DEFINITION OF TOWNHOUSE IS:
 202.TOWNHOUSE. A SINGLE FAMILY DWELLING
 CONSTRUCTED IN A SERIES OR GROUP OF
 ATTACHED UNITS WITH PROPERTY LINES
 SEPARATING EACH UNIT.
 IF TRUELY TOWNHOUSE CONSTRUCTION,
 PROVIDE THE RECORDED PLAT PLAN WWITH
 SEPERATE LOTS, OTHERWISE REMOVE TREM
 FROM ALL DOCUMENTS.
  
 4) CONDO UNITS 1-14 (TOWNHOUSE UNITS)
 ARE TO COMPLY WITH FAIR HOUSING MANUAL
 REVISED APRIL 1998, PAGE 1.32. BUILDINGS
 WITH ONE OR MORE COMMON ENTRANCES TO ALL
 DWELLING UNITS IN BUILDINGS WITH ONE OR
 MORE ELEVATORS. AT LEAST ONE COMMON
 ENTRANCE SHALL BE ON AN ACCESSIBLE
 ROUTE. SITE IMPRACTICABILITY TEST DOES
 NOT APPLY TO ELEVATORED BUILDINGS.
 PROVIDE ON THE LIFE SAFETY PLAN THE
 ACCESSIBLE ROUTE FROM THE ELEVATOR TO
 THESE UNITS.
  
 5) THESE UNITS ARE MISSING EXIT ACCESS
 CORRIDORS, EXIT ACCESS. THAT PORTION OF
 A MEANS OF EGRESS WHICH LEADS TO AN
 ENTRANCE TO AN EXIT.
  
 SEE MEANS OF EGRESS DEFINITIONS, MEANS
 OF EGRESS. A CONTINUOUS AND UNOBSTRUCTED
 WAY OF EXIT TRAVEL FROM ANY POINT IN A
 BUILDING OR STRUCTURE TO A PUBLIC WAY,
 CONSISTING OF THREE SEPARATE AND
 DISTINCT PARTS: (1) THE WAY OF EXIT
 ACCESS, (2) THE EXIT, AND (3) THE WAY OF
 EXIT DISCHARGE. A MEANS OF EGRESS
 COMPRISES THE VERTICAL AND HORIZONTAL
 WAYS OF TRAVEL AND SHALL INCLUDE THE
 INTERVENING ROOM SPACE, DOORS,
 CORRIDORS, PASSAGEWAYS, BALCONIES,
 STAIRS, RAMPS, ENCLOSURES, LOBBIES,
 HORIZONTAL EXITS, COURTS AND YARDS.
 PROVIDE EXIT ACCESS CORRIDORS FOR
 UNITS 1-14 COMPLING WITH TABLE 1004
 TRAVEL DISTANCES FOR R2/ SPRINKLERED
 BUILDINGS MAXIMUM TRAVEL DISTANCE OF
 325 FT TO AN EXIT.
  
 RESIDENTIAL UNITS 101-105 ARE AT
 GRADE LEVEL AND WILL NOT REQUIRE EXIT
 ACCESS CORRIDORS SINCE THEY CAN EXIT AT
 STREET LEVEL AND GO DIRECTLY TO THE WAY
 OF THE EXIT DISCHARGE.
  
 6) A0.02 NOTE# 35 CABANA CANVAS TO BE
 REMOVED AT 75MPH, STRUCTURES ARE TO BE
 DESIGNED FOR 140 MPH WIND ZONE.SEE
 FIGURE 1606.
  
 7A) A1.02C PLANS INDICATE A VALET DRIVE
 & A DROP OFF ZONE WITH A ZERO CURB
 PASSENGER DROP OFF. PROVIDE MORE
 INFORMATION ON THE DROP OFF ZONE. SHOW
 COMPLIANCE WITH FL ACCESSIBILITY FOR
 ACCESS AILSLE AT PASSENGER LOADING ZONES
 FIGURE 10 TO BE 240" LONG(ZERO CURB) AND
 60" WIDE. 11-4.1.2(1)/ 11-4.6.6.
  
 7B)A1.02NE & A1.02SE VALET DRIVE
 INDICATES "MAINTAIN 8'-0" MINIMUM
 CLEARENCE THROUGHOUT VALET DRIVE".
 11-4.6.5 VERTICAL CLEARANCE. PROVIDE
 MINIMUM VERTICAL CLEARANCE OF 114 "
 (2895 MM) AT ACCESSIBLE PASSENGER
 LOADING ZONES AND ALONG AT LEAST ONE
 VEHICLE ACCESS ROUTE TO SUCH AREAS FROM
 SITE ENTRANCE(S) AND EXIT(S).
  
 7C)11-4.1.2(7) BUILDING SIGNAGE. SIGNS
 WHICH DESIGNATE PERMANENTROOMS AND
 SPACES SHALL COMPLY WITH 11-4.30.1,
 11-4.30.4, 11-4.30.5 AND 11-4.30.6.
 OTHER SIGNS WHICH PROVIDE DIRECTION TO,
 OR INFORMATION ABOUT, FUNCTIONAL SPACES
 OF THE BUILDING SHALL COMPLY WITH
 11-4.30.1, 11-4.30.2, 11-4.30.3, AND
 11-4.30.5.ELEMENTS AND SPACES OF
 ACCESSIBLE FACILITIES WHICH SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL
 OF ACCESSIBILITY AND WHICH SHALL COMPLY
 WITH 11-4.30.7 ARE:
 11-4.1.2(7)(A) PARKING SPACES DESIGNATED
 AS RESERVED FOR INDIVIDUALS WITH
 DISABILITIES;
 11-4.1.2(7)(B) ACCESSIBLE PASSENGER
 LOADING ZONES;
 11-4.1.2(7)(C) ACCESSIBLE ENTRANCES WHEN
 NOT ALL ARE ACCESSIBLE (INACCESSIBLE
 ENTRANCES SHALL HAVE DIRECTIONAL SIGNAGE
 TO INDICATE THE ROUTE TO THE NEAREST
 ACCESSIBLE ENTRANCE);
 11-4.1.2(7)(D) ACCESSIBLE TOILET AND
 BATHING FACILITIES WHEN NOT ALL ARE
 ACCESSIBLE.
  
 7D) FOR ALL GROUPINGS OF ELEVATORS SHOW
 COMPLIANCE WITH;
 3003.4 STRETCHER REQUIREMENTS
 3003.4.1 IN ALL STRUCTURES THAT ARE
 MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THETOP
 TERMINAL LANDING EXCEEDS 25 FEET (7.6 M)
 MUST BE CONSTRUCTED TOCONTAIN AT
 LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES (1931 MM)
 LONG AND 24 INCHES (610 MM) WIDE IN THE
 HORIZONTAL POSITION.THIS ELEVATOR
 SHALL BE IDENTIFIED.
  
 7E) 3003.3 SIGNS. A PERMANENT SIGN SHALL
 BE INSTALLED IMMEDIATELY ABOVE EACH
 HALL PUSH BUTTON STATION ON EACH FLOOR
 READING:IN FIRE EMERGENCY, DO NOT
 USE ELEVATOR.USE EXIT STAIRS.THIS
 SIGN SHALL BE LETTERS NOT LESS THAN
 1/2 INCH (12.7 MM) HIGH.
  
  
 7F)EACH ELEVATOR MUST BE MADE
 ACCESSIBLE TO PHYSICALLY HANDICAPPED
 PERSONS WITH THE FOLLOWING REQUIREMENTS:
 OF 3003.4.2 (1-3)
  
 7G) PROVIDE DETAILS HOW IN EACH GROUP OF
 2 ELEVATORS ONE WILL COMPLY WITH:
 3003.5 STANDBY POWER. IN ALL BUILDINGS
 OR STRUCTURES WHERE STANDBY POWER
 IS REQUIRED OR FURNISHED TO OPERATE AN
 ELEVATOR, THE OPERATION SHALL BE AS
 FOLLOWS:
  
 1. WHERE ONLY ONE ELEVATOR IS
 INSTALLED, THE ELEVATOR SHALL TRANSFER
 TO STANDBY POWER WITHIN 60 SECONDS AFTER
 FAILURE OF NORMAL POWER.
 2. WHERE TWO OR MORE ELEVATORS ARE
 CONTROLLED BY A COMMON OPERATING
 SYSTEM, ALL ELEVATORS MAY TRANSFER TO
 STANDBY POWER WITHIN 60 SECONDS AFTER
 FAILURE OF NORMAL POWER; OR IF THE
 STANDBY POWER SOURCE IS OF
 INSUFFICIENT CAPACITY TO OPERATE ALL
 ELEVATORS AT THE SAME TIME, ALL
 ELEVATORS SHALL TRANSFER TO STANDBY
 POWER IN SEQUENCE, RETURN TO THE
 DESIGNATED LANDING AND DISCHARGE THEIR
 LOAD.AFTER ALL ELEVATORS HAVE BEEN
 RETURNED TO THE DESIGNATED LANDING, AT
 LEAST ONE ELEVATOR SHALL REMAIN OPERABLE
 FROM THE STANDBY POWER SOURCE.
  
 8A) INDICATE COMPLIANCE WITH: VAN
 PARKING:11-4.1.2(5)(B) IN PARKING
 STRUCTURES, ONE IN EVERY EIGHT
 ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL
 BE DESIGNED AS REQUIRED BY 11-4.6.3.
 THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH 11-4.6.5.ALL SUCH
 SPACES MAY BE GROUPED ON ONE LEVEL OF A
 PARKING STRUCTURE.WHEN SUCH SPACES ARE
 PROVIDED IN A PARKING STRUCTURE AND ONLY
 ONE IN EIGHT MEET THE HEIGHT REQUIREMENT
 OF 11-4.6.5 (98")AT THE PARKING SPACE
 AND ALONG AT LEAST ONE VEHICLE
 ACCESSIBLE ROUTE TO SUCH SPACES FROM
 SITE ENTRANCES AND EXITS, THEY SHALL BE
 DESIGNATED AS REQUIRED BY 11-4.6.4.
  
 9) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEETS A1.02 NORTH VALET DRIVE INDICATES
 A "TILT UP SERVICE DOOR":
  
 9A) PROVIDE DETAILS OF THIS UNIT, AND
 WHAT IT WILL BE USED FOR?
  
 9B) IT APPEARS THERE MAY BE A DISCEPANCY
 BETWEEN THE TILT UP DOOR AND THE
 UNDERGROUND PASSAGE WAY. LS0.02
 INDICATES THIS UNIT DIRECTLY OVER THE
 UNDERGROUND EXIT!LS0.01 DOESN'T INDICATE
 ANY OTHER STRUCTURE IN THIS AREA?
  
 10A) SHEET A1.02SE & A1.02NE INDICATE A
 PEDESTRAIN CROSS WALK ON THE VALET DRIVE
 AND A CROSS SECTION #6 ON A3.12. THIS
 SECTION INDICATES THIS TO BE A RAISED
 CROSS WALK RATHER THAN CURB CUTS WITH
 A DESIGNATED EGRESS LANE. SINCE THIS IS
 A ELEVATED SLAB INDICATE THE HEIGHT
 DIFFERENCE BETWEEN THE CROSS WALK AND
 ADJACENT DRIVE? IT APPEARS THE CROSS
 WALKS RAMPS MAY NOT MEET THE 1:20
 ADJOINING SLOPE REQUIREMENTS.
  
 10B)11-4.7.7 DETECTABLE WARNINGS. A CURB
 RAMP SHALL HAVE A DETECTABLEWARNING
 COMPLYING WITH 11-4.29.2.THE
 DETECTABLE WARNING SHALL EXTEND THE FULL
 WIDTH AND DEPTH OF THE CURB RAMP.
  
 10C)11-4.29.2(2) DETECTABLE WARNING
 TEXTURES ON WALKING SURFACES SHALL
 CONSIST OF EXPOSED AGGREGATE CONCRETE,
 CUSHIONED SURFACES MADE OF RUBBER OR
 PLASTIC, RAISED STRIPS, OR GROOVES.
 TEXTURES SHALL CONTRAST WITH THAT OF THE
 SURROUNDING SURFACE.RAISED STRIPS OR
 GROOVES SHALL COMPLY WITH FIGURE
 11-40(A) AND FIGURE 11-40(B).
  
 10D) BOTH SHEETS A1.02NE & A1.02SE BOTH
 INDICATE THE USE OF HORIZONTAL SLIDING
 DOORS C-0101-C & C-0101-E, 1012.4(9) 9.
 IN APARTMENT BUILDINGS, HOTELS AND
 DORMITORIES, HORIZONTAL SLIDING DOORS
 SHALL NOT BE USED ACROSS CORRIDORS.
  
 11)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A1.02 NE UNITS 18& 19 APPEAR TO
 HAVE (3) COLUMNS JUST TO THE SOUTH OF
 THESE UNITS. JUST EAST OF THESE COLUMNS
 THERE IS A GATE, THERE IS ONLY 18"
 BETWEEN THE COLUMNS AND WALL LINE. WITH
 THE GATE IN THIS PLAN IT APPEARS THAT
 THIS AREA IS TO BE USED FOR A WALKWAY?
 EXPLAIN RATIONAL?
  
 12) A1-04 HAS 2 AREAS NAMED OPEN STORAGE
 THAT ARE IN COMMON TO THE ENCLOSED
 PARKING AREAS. SEE 411.2.6 AUTOMOBILE
 PARKING GARAGES SHALL BE SEPARATED FROM
 OTHER OCCUPANCIES IN ACCORDANCE WITH
 704. PROVIDE WHAT TYPE OF STORAGE WILL
 TAKE PLACE IN THESE AREAS, RATE DOORS
 ACCORDINGLY.
  
 13) A1.04 THE REFUSE CHUTE ACCESS ROOM:
  
 13A) PLANS DO NOT INDICATE AN ACCESS
 ROOM DOOR NOR IS THERE A CUT SECTION
 PROVIDING A HORIZONTAL SECTION OF THE
 CHUTE, WALL RATINGS AND DOOR RATINGS
 .
 13B) 705.2.4.3 REFUSE CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION AND
 OPENING PROTECTIVES IN ACCORDANCE WITH
 TABLE 705.1.2. SHOW COMPLIANCE, ALSO SEE
 NFPA 82 5.2.5.3.3.THIS IS TAKEN WITH THE
 REFUSE CHUTE DOOR OPEN!!!!
  
 13C) PROVIDE DETAILS FOR FIRE SPRINKLERS
 IN ACCORDANCE WITH:
 705.2.4.6 AUTOMATIC SPRINKLERS. AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP AND AT
 ALTERNATE FLOOR LEVELS IN REFUSE AND
 LAUNDRY CHUTES AND IN THE TERMINATION
 AND INCINERATOR ROOMS.
  
 14) PLANS DO NOT HAVE A DOOR SCHEDULE .
 14A)RATED DOORS SHALL COMPLY WITH TABLE
 705.1.2
 14B) RATED DOORS ARE TO SHOW CLOSING
 DEVICES, HARDWARE, FRAMES AND SILLS
 INACCORDANCE WITH 705.1.3 AND UNDER CUT
 AS TO NFPA 80.
  
 15) PLANS DO NOT HAVE A FINISH SCHEDULE
 FOR THE COMMON AREAS.
  
 16) A1.04C THERE IS A TRUE ISSUE OF THE
 ATRIUM VERSUS THE ELEVATOR LOBBY.BY
 DEFINITION, ATRIUM. A SPACE, INTENDED
 FOR OCCUPANCY WITHIN A BUILDING,
 EXTENDING VERTICALLY THROUGH THE
 BUILDING AND ENCLOSED AT THE TOP.SINCE
 THE 3RD FLOOR IS ENCLOSED BY GLASS, THIS
 TRUELY MAKES A SHAFT SEPERATING IT FROM
 THE REST OF THE BUILDING.
 SINCE THIS IS A HIGH RISE, AND THE
 SHAFT SEPERATES THIS AREA REMOVING THE
 ATRIUM THEORY,412.6.1 CAN NOT TAKE THE
 EXEMPTION FOR ATRIUMS MAKING AN ELEVATOR
 LOBBY REQUIRED FOR FLOORS 2,3 & 4.
 16B) FOR INFORMATION AS TO SMOKE CONTROL
 FOR THE ATRIUM THE MECHANICAL PLANS
 INDICATE ON PAGE AC-01 AC-02 TO SEE
 SHEET AC-20 FOR WORK IN THIS AREA, THIS
 PAGE IS FOR THE PENTHOUSE SUITES?
 16C) PROVIDE THE AMOUNT OF CU FT OF AIR
 INCLUDED UNDER THE ATRUIM SMOKE CONTROL
 SYSTEM SEE 414.4.2 AND SHOW COMPLIANCE.
 (C)(1) LS0.03 PROVIDES THE TENANT
 SEPERATION WALLS AND OR FIRE SEPERATION
 WALLS. 414.5 ATRIUM SPACES SHALL
 SEPERATED FROM ADJACENT SPACES BY A
 1-HR FIRE SEPERATION WALL. THE
 MECHANICAL PLAN DOESN'T INDICATE ANY
 FIRE DAMPERS SO THESE AREAS?
 16D) PROVIDE INFORMATION FOR AUTOMATIC
 FIRE DETECTION IN ACCORDANCE WITH
 414.6.1 SPOT-TYPE DETECTORS OR BEAM
 DETECTORS.
 16D) PROVIDE INFORMATION, 414.7 STANDBY
 POWER. ALL EQUIPMENT REQUIRED TO PROVIDE
 SMOKE CONTROL SHALL BE CONNECTED TO A
 STANDBY POWER SYSTEM IN ACCORDANCE WITH
 412.7.
 16E) 414.10 INTERIOR FINISH. THE
 INTERIOR FINISH OF WALLS AND CEILINGS OF
 THE ATRIUM SHALL NOT EXCEED CLASS B WITH
 NO REDUCTION IN CLASS FOR SPRINKLER
 PROTECTION.
 16F) PLEASE PROVIDE AREA CALCULATIONS
 FOR THE FIRST FLOOR OF THE ATRIUM AND
 THE MEZZANINE LEVEL 503.2.3.2.
 16G) MEZZANINE LEVEL MUST MEET THE
 REQUIREMENTS OF 1005.7.3 THE SPACE
 BENEATH THE MEZZANINE MAY BE ENCLOSED
 PROVIDEDTHE ENCLOSED SPACE IS
 PROTECTED THROUGHOUT WITH A SMOKE
 DETECTION SYSTEM IN ACCORDANCE WITH NFPA
 72 WHICH SOUNDS AN ALARM IN THE
 MEZZANINE.
  
 17) A1.04C THE STAIR TOWERS TO THE LEFT
 AND RIGHT OF THE CENTER ASSEMBLY AREA
 HAVE EXIT ACCESS CORRIDORS WITH DOORS
 # 0302 N&S. WHAT IS THIS ROOM TO BE USED
 FOR. IF THIS IS SHAFT INDICATE SUCH.
 ALSO NO DOOR SCHEDULE TO INDICATE
 RATING.
  
 18) THESE SAME STAIR TOWERS INDICATE A
 CIRCLE AND SQUARE IN THE LANDINGS OF THE
 STAIR TOWER BUT NOT SHOWN ON THE
 ENLARGED PLANS A5.07 & A5.08?
  
 19) A1.04 INDICATES A HEALTH CLUB NO
 WALLS NOR DOORS SHOW RATINGS.A 5.15
 PROVIDES ELEVATIONS BUT NO CROSS SECTION
 SHOWING COMPLIANCE WITH A 2HR SHAFT.
  
 20) A1.04NE :
 A) ELEVATOR LOBBY# 7 HAS SOME
 UNIDENTIFIED ITEM WITH A DOOR IN LOBBY?
 B) THERE IS NO ELEVATOR LOBBY DOOR
 SEPERATING THE LOBBY FROM THE REST OF
 THE FLOOR.
 C) TELEPHONE ROOM APPEARS TO HAVE NO
 DOOR IT APPEARS TO HAVE THE REFUSE CHUTE
 IN THE SAME ROOM?
 D) ELEVATOR TOWERS# 3&5 INDICATES 2
 DISTINCT ELEVATOR LOBBIES BUT ENTRANCE
 IS ONLY ON ONE SIDE?
 E) IN FRONT OF UNIT 0317 THERE IS A
 AREA THAT APPEARS TO BE A SHAFT?NO
 DETAILS OR CUT SECTIONS TO INDICATE
 USAGE.
  
 21) A1.04 NW :
 A) THERE APPEARS TO BE A PASSENGER
 LOADING ZONE IN THE GARAGE JUST SOUTH OF
 ELEVATOR# 7, PROVIDE PASSENGER LOADING
 ZONE, AND ACROSS ELEVATION SECTION
 INDICATING CLEAR HEIGHT.
 B) NORTH END OF THE PARKING GARAGE HAS
 AN OPEN STORAGE AREA, THERE IS NO
 OCCUPANCY SEPERATION BETWEEN THE GARAGE
 AND STORAGE OCCUPANCY. SEE 411.2.6
 C) THE OPEN STORAGE AREA, WHAT TYPE OF
 STORAGE WILL THIS BE TO CONSIDER RATING
 OF WALLS & DOORS.
 C) AREA NOT LABELED JUST SOUTH OF
 COLUMN LINE W-37, PLEASE PROVIDE USAGE?
  
 22) A1.04SE AGAIN IT APPEARS THE THE
 ELEVATOR LOBBIES SHOULD HAVE ELEVATOR
 LOBBY DOORS , SAME OBJECT APPEARS
 UNIDENTIFIED OBJECT.
  
 23) A1.04SW/ A1.04NW THERE IS A WALKWAY
 THAT BACKS UP AGAINST THE VARIOUS
 SOCALLED (TOWNHOUSE) UNITS, IT APPEARS
 TO BE A CROSSWALK OR MEANS OF EGRESS,
 REQUIRING A 44" PATH, THE COLUMNS STICK
 OUT CUTTING OF ABOUT 1/2 OF THE PATH OF
 TRAVEL.
  
 24) A1.04P1:
 A) THE SOUTH END OF THE PARKING GARAGE
 APPEARS TO HAVE OPEN STORAGE, PROVIDE
 OCCUPANCY SEPERATION RATED WALLS AND
 DOORS. 411.2.6.
 B) PROVIDE INFORMATION FOR THE STEEL
 CABLE BARRIER SYSTEM TO WITHSTAND THE
 REQUIREMENTS IN 1608.2.3 GUARDRAIL
 PARKING.
  
 25) A1.05C :
 A) CLARIFY, PLANS INDICATE AN ELEVATOR
 LOBBY & INDICATE A STORAGE AREA NO WALLS
 OR OCCUPANCY SEPERATION?
 B) RATING OF ELEVATOR DOOR TO KITCHEN,
 WHAT WILL THIS DOOR BE USED FOR?NO NAME
 ON PLANS.
 C) COVERED TERRACE THE OCCUPANT LOAD IS
 GREATER THAN 50 REQUIRING A 2 HR
 SEPERATION.
  
 26) A1.05NE UNITS DO NOT HAVE EGRESS TO
 STAIR TOWER WITHOUT TRAVEL THROUGH THE
 ELEVATOR LOBBIES SEE 412.6.2. THE
 BEDROOM TERRACE LEVEL, LOCKABLE DOORS,
 1001.1.3, 1012.4 FOR HORIZONTAL SLIDERS
 PARTOF A MEANS OF EGRESS. UNIT 512 OK
 UNITS THAT DO NOT COMPLY 513,514, 515,
 516 & 517.
  
 27 DOOR/ROOM 436 USAGE?
  
 28) A1.05SE UNITS DO NOT HAVE EGRESS TO
 STAIRS WITHOUT TRAVEL THROUGH THE
 ELEVATOR LOBBY, UNITS 411, 410, 409, 408
 & 404. LOCKABLE DOORS 1001.1.3 AND USE
 OF HORIZONTAL SLIDERS 1012.4
  
 29) WHEN TENANTS ARE AT THE POOL DECK
 WILL THE EXIT PASSAGEWAYS ALLOW ENTRENCE
 BACK INTO THE BUILDING?
  
 30) A1.05SW:
 A) ROOM JUST NORTH OF THE POOL
 COLLECTOR TANKS, USAGE?
 B) STAIRWAY ( DOOR 401) WHAT WILL THE
 VACANT SPACE BE USED FOR WITHIN THE
 STAIR TOWER?
 B) MAIN POOL AREA, SOUTH END THE CHANGE
 IN GRADE IS GREATER THAN 6" GUARD RAILS
 OR EDGE TREAMENT SO A WHEELCHAIR COULD
 NOT JUST ROLL OVER INTO THE STEPPED
 GRASSED AREAS.
 C) DECK DRAINS OR GRATES SEE 11-5.4.5.
 D) CUT SECTION @ STAIRS 03/A6.11 NO
 HANDRAIL GUARDRAIL FOR STAIRS.
 E) NOTE STATE STATUTE FOR "EFFECTIVE
 BARRIER FOR THE PUBLIC POOLS/ SPAS
 D.O.H.64E-9.
 F) NOTE PUBLIC POOLS & SPAS
 13-412.1ABCD.2.4.2 COVERED POOLS
  
 31) A1.05 P1/P2 CABANA NOTE- SHALL BE
 DESIGNED TO 140 MPH WIND, 3 SECOND GUST.
  
 32)A1.06NE
 A) DETAIL 08/A6.14 THE BLOCK WORK THAT
 ABUTTS STRUCTURAL COLUMNS, WHAT TYPE OF
 HORIZONTAL TIE IN SYSTEM WILL BE USED/
 B) SAME SECTION INDICATES THE USE OF
 VERTICAL REBAR IN THE BLOCK CELLS NEXT
 TO OPENINGS, HOW WILL THE REINFORCING
 RODS TIE INTO THE SLAB ABOVE FOR THE
 HORIZONTAL AND VERTICAL REINFORCEMENT &
 TRANSFER OF WALL AND WINDOW/ DOOR
 LOADING?
 THIS HOLDS TRUE FOR ALL SIMILAR LOADING
 ISSUES.
  
 33) A1.06NE THIS COMMENT WILL EFFECT
 MOST OF THE STAIRWELL, (EXITS) WITHIN
 THE BUILDING. THE PLANS INDICATE A EXIT
 DOOR THAT LEADS DIRECTLY FROM THE CONDO
 UNIT INTO THE SMOKEPROOF EXIT ENCLOSURE.
 THE INTENT IS TO HAVE AN EXIT THAT
 DOESN'T TRAVEL THROUGH THE ELEVATOR
 LOBBY.THE CODE SECTION THAT DOESN'T
 ALLOW HABITABLE ROOMS TO EMPTY DIRECTLY
 INTO THE EXIT IS:
  
 1005.6.7 ACCESS TO THE STAIRWAY SHALL BE
 BY WAY OF A VESTIBULE OR BY WAY OF AN
 OPEN EXTERIOR BALCONY OF NONCOMBUSTIBLE
 MATERIALS.
 EXCEPTION: ACCESS BY WAY OF A
 VESTIBULE WHEN THE STAIRWAY MEETS THE
 REQUIREMENTS OF 1005.6.9.2 (1-3),
 1005.6.9.9 AND 1005.6.9.10 & IS LOCATED
 IN A FULLY SPRINKLEREDBUILDING.
 PLEASE INDICATE COMPLIANCE. UNITS SUCH
 AS 1615 ON SHEET A1.08NE CAN NOT MAKE
 THE ROOM CONTAINING THE SECOND EXIT A
 LOCKABLE ROOM SUCH AS A BEDROOM.
  
 34) A1.10 NE LEVEL 18 SHOWS A STAIR
 WITHIN THE UNIT GOING TO THE NEXT LEVEL
 BUT THERE IS NO FLOOR PLAN INDICATEING
 WHAT IS ON THIS LEVEL? A1.11NE DOES
 INDICATE A ROOF PLAN FOR THE NEXT LEVEL,
 IT APPEARS THIS IS THE ELEVATOR MACHINE
 ROOM LEVEL. DOES THE STAIR BELOW SERVICE
 THE ELEVATOR MACHINE ROOM?
  
 35) A1.11SE THE SAME SITUATION APPEARS
 WITH THE EXCEPTION OF CIRCULAR
 STAIRS.PLEASE PROVIDE A FLOOR PLAN FOR
 THIS LEVEL.
  
 36) PROVIDE THE DRAFT WIND PRESSURE
 REPORTCOMPLETED BY RWDI CONSULTING
 ENGINEERS, IT APPEARS THE NEGATIVE
 PRESSURES ARE LOW.
 1606.1.1 DETERMINATION OF WIND FORCES.
 WIND FORCES ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED BY THE
 PROVISIONS OF CHAPTER 6 OF ASCE 7-98.
 THE SIMPLIFIED FORM WILL NOT WORK ON
 THIS BUILDING BECAUSE OF HEIGHT AND THE
 SHAPE OF THE BUILDING.
  
  
 37) A3.04A/ A3.05A INDICATES A
 STRUCTURAL STEEL AND GLASS SKYLIGHT TO
 BE USED SHOW COMPLIANCE WITH:
 A)13-104.4.5 FENESTRATION ENERGY RATING
 LABELS. ENERGY PERFORMANCE VALUES (I.E.,
 U-FACTOR, SOLAR HEAT GAIN COEFFICIENT)
 OF FENESTRATION PRODUCTS (I.E., WINDOWS,
 DOORS AND SKYLIGHTS) SHALL BE DETERMINED
 BY AN ACCREDITED, INDEPENDENT LABORATORY
 AND LABELED AND CERTIFIED BY THE
 MANUFACTURER.
 B) 1604.3 CONCENTRATED FLOOR LIVE LOADS
 SKYLIGHT RIBS 200 LBS
 C) MUST MEET SMALL MISSLE IMPACT
 TESTING 30'-60' FROM THE GROUND.
 D) 1707.4.2.1.1 TEST AND LABELING OF
 SKYLIGHTS. EXTERIOR SKYLIGHTS SHALL BE
 TESTED BY AN APPROVED INDEPENDENT
 TESTING LABORATORY, AND SHALL BE LABELED
 WITH AN APPROVED LABEL IDENTIFYING THE
 MANUFACTURER, PERFORMANCE
 CHARACTERISTICS AND APPROVED PRODUCT
 EVALUATION ENTITY TO INDICATE COMPLIANCE
 WITH THE REQUIREMENTS OF THE FOLLOWING
 SPECIFICATION: AAMA/WDMA 1600/IS7,
 VOLUNTARY SPECIFICATION FOR SKYLIGHTS OR
 TAS 202 (HVHZ SHALL COMPLY WITH TAS 202)
 E)2405.3.2 SLOPED GLAZING.GLASS SLOPED
 MORE THAN 15 DEGREES (0.26 RAD)
 FROM VERTICAL IN SKYLIGHTS, SUNSPACES,
 SLOPED ROOFS AND OTHER EXTERIOR
 APPLICATIONS SHALL BE CHOSEN TO RESIST
 THE APPLICABLE LOADS FOR COMPONENTS
 AND CLADDING.THE ALLOWABLE COMBINED
 LOAD FOR THE GLASS SHALL BE DETERMINED
 IN ACCORDANCE WITH ?2405.3.2.1 THROUGH
 ?2405.3.2.3.
  
 38) PROVIDE DETAILS FROM THE PRE-CAASST
 SPECIALTY ENGINEER HOW SYSTEM ISTO BE
 ASSEMBLED. WHAT TYPE MATERIAL IS TO BE
 USED, FORCES TO BE RESISTED, UPLIFT,
 LATERAL LOADS AND GRAVITY LOADS.
  
 39) A3.09 DETAIL# 2FL BLD CODE
 104.2.1.2 ADDITIONAL INFORMATION
 REQUIRED, PROVIDE INFORMATION ON THE
 TENSILE FABRIC & CANOPY STRUCTURE.
  
 40)*******VERY IMPORTANT NOTE***********
 *************FOR CONTRACTOR************
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 41) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED, STOREFRONT, OPERTABLE
 PASS THROUGHS OR GLASS BLOCK
 B)EXTERIOR DOORS, SOLID, SWING, GLAZED
 SLIDERS ROLL UP
 C) MULLIONS BOTH VERTICAL & HORIZONTAL
 D) SKYLIGHTS
 E) EXTERIOR VENTS OR LOUVERS
 F) EXTERIOR GUARDRAILS
 G) PANEL WALL SYSTEMS: SOFFITS, EFIS
 SYSTEMS, DENSEGLASS
 H) LOUVERS
 I) ROOFING PRODUCTS/ ASSEMBLIES
  
 42)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 43)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 44) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED STATE TESTING
 LABORATORY OR BE ENGINEERED. IF TO BE
 USED IN CONJUNCTION WITH GLAZED UNITS
 WITH LARGE MISSLE TESTING THE MULLION
 ALSO REQUIRES LARGE MISSLE TESTING.
  
 45) A3.10 DETAIL# 2 INDICATES ATTACHMENT
 OF LIMESTONE VENEER, PROVIDE THE WEIGHT
 PSF, METHOD OF ATTACHMENT, SPACING OF
 FASTENERS SEE SECTION 1403 FOR VENEER
 WALLS .
  
 46) A4.00 DETAIL# 3 PROVIDES A DETAIL
 FOR SOFITS AND DROPPED CEILING. THE PLAN
 DOES NOT INDICATE HOW OFTEN THE TOP
 PLATE IS TO BE SECURED TO THE CONCRETE
 DECK NOR DOES THE DETAIL INDICATE WHAT
 THE LIMITATION IS FOR BRACING AT THE MID
 SPAN. THE PLAN DOESN'T INDICATE WHAT
 CENTERS THE FRAMING IS TO BE PLACED OR
 SCREW ATTACHMENT.
  
 47) A4.00 DETAIL # 5 INDICATES THE USE
 OF WOOD BUCKS. 609.2.1 TYPE I AND TYPE
 II CONSTRUCTION. PARTITIONS SHALL BE
 CONSTRUCTEDOF NONCOMBUSTIBLE
 MATERIALS.EXCEPTIONS: 1. FRAMING MEMBERS
 MAY BE OF FIRE RETARDANT TREATED WOOD.
  
 48) DETAIL# 2 INDICATES THE USE OF EFIS
 TRIM, SEE 1404.1.1 TYPE I BUILDINGS THAT
 ARE NOT OVER 3 STORIES OR 40' MAY HAVE
 TYPE VI TRIM.
  
 49) A6.01 RAILING DETAIL INDICATES TWO
 INCHES CLEAR FROM THE BOTTOM RAIL TO THE
 DECK.1015.3 OPENINGS. A BOTTOM RAIL OR
 CURB SHALL BE PROVIDED THAT WILL REJECT
 THE PASSAGE OF 2-INCH (51 MM) DIAMETER
 SPHERE.
  
 50) A6.06 MAIN GLASS CANOPY, PROVIDE
 INFORMATION ON THE CANOPY SYSTEM. ALSO
 PROVIDE INFORMATION ON THE GLAZING
 SYSTEM INDICATING COMPLIANCE WITH
 2407.2.1 ALLOWABLE GLAZING MATERIALS.
  
 51) A6.08 DETAI# 19 MAIN LOBBY
 HORIZONTAL SLIDING DOORS, PROVIDE THE
 MANUFACTURER SPECS FOR CODE COMPLIANCE
 WITH 1012.4 (1-9)
  
 52)SHEET AC-02:
 52A) THERE APPEARS TO BE A DESCREPANCY
 BETWEEN AC-02 NORTH END OF BUILDING
 WHERE THE INTAKE LOUVERS ARE INDICATES
 THIS TO BE AN ELECTRICAL ROOM VS A1.03
 WHICH CALLS FOR OPEN STORAGE. OCCUPANCY
 SEPERATION FROM THE PARKING GARAGE.
 52B) THE SAME SITUATION IS ON THE SOUTH
 END OF THE PARKING GARAGE WITH THE EF
 23,24,& 25. PROVIDE A SECTION THROUGH
 THIS AREA AND THE OPEN AREA TO THE
 SOUTH.
  
 53) THE SAME ISSUES AS 52 BUT ON AC-03.
  
 54) P-2 INDICATES PLUMBING IN THE EXIT
 TOWERS, TOWER 5 STAIR A, TOWER8 STAIR A.
 1006.1.3.1 PENETRATIONS INTO OPENINGS
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR INDEPENDENT STAIR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES AND
 ELECTRICAL CONDUIT SERVING THE
 STAIRWAY AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQ IN. (0.010 M^2).
 SUCH PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH ?705.4.THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS,
 WHETHER PROTECTED OR NOT, BETWEEN
 ADJACENT STAIR ENCLOSURES.
  
 55)P-13 INDICATES A 4" RAIN WATER LITER
 IN EXIT NOTE "TO BUILD 2HR SOFFIT W/
 ACCESS PANEL". 1006.1.4 THERE SHALL BE
 NO USABLE SPACE WITHIN AN EXIT ENCLOSURE
  
 56) 1016.4 STAIR IDENTIFICATION. AN
 APPROVED SIGN SHALL BE LOCATED AT EACH
 FLOOR LEVEL LANDING IN ALL ENCLOSED
 STAIRWAYS OF BUILDINGS FOUR OR MORE
 STORIES IN HEIGHT.THE SIGN SHALL
 INDICATE THE FLOOR LEVEL AND THE
 AVAILABILITY OF ROOF ACCESS FROM THAT
 STAIRWAY AND AN IDENTIFICATION OF THE
 STAIRWAY.THE SIGN SHALL ALSO STATE THE
 FLOOR LEVEL OF AND DIRECTION TO
 EXIT DISCHARGE.THE SIGN SHALL BE
 LOCATED APPROXIMATELY 5 FT (1524 MM)
 ABOVE THE FLOOR LANDING IN A POSITION
 WHICH IS READILY VISIBLE WHEN THE
 DOOR IS IN THE OPEN OR CLOSED POSITION.
  
 57) 412.8.1 ALL STAIRWAY DOORS WHICH ARE
 TO BE LOCKED FROM THE STAIRWAY SIDE
 SHALL HAVE THE CAPABILITY OF BEING
 UNLOCKED SIMULTANEOUSLY WITHOUT
 UNLATCHING UPON A SIGNAL FROM THE
 CENTRAL CONTROL STATION.THE DOORS
 SHALL BE SIMILARLY UNLOCKED UPON
 ACTIVATION OF THE SPRINKLER SYSTEM OR
 UPON POWER FAILURE.
  
 412.8.2 TELEPHONE OR OTHER TWO-WAY
 COMMUNICATIONS SYSTEMS CONNECTED TO AN
 APPROVED EMERGENCY SERVICE WHICH
 OPERATES CONTINUOUSLY SHALL BE
 PROVIDED AT NOT LESS THAN EVERY FIFTH
 FLOOR IN EACH REQUIRED STAIRWAYWHERE
 OTHER PROVISIONS OF THIS CODE PERMIT THE
 DOORS TO BE LOCKED.
  
 58) PROVIDE SIGNAGE AS REQUIRED BY
 11-4.30 OF FL ACCESSIBILITYAS WELL AS
 FAIRHOUSING ANSI 117.1 703 FOR STAIRS
 AND OTHER REQUIRED ELEMENTS.
  
 59) **STRUCTURAL WIND DESIGN LOADS**
 SHEET S0.02 INDICATE THE WIND DESIGN IS
 TAKEN FROM ASCE7-98 WITH A "EXPOSURE "C"
 THE PRESSURES ARE LOW FOR A BUILDING OF
 OVER 185'. TABLES FROM ASCE 7-88 FOR
 180' BUILDING FOR END ZONES INDICATE
 139.1 FOR END ZONES ON A TRIBUTARY AREA
 OF 20', WHY ARE THE PRESSURES SO LOW
 PROVIDE CALCULATIONS. WE LOOK FOR WINDOW
 AND DOOR PRESSURES +/- FOR OPENINGS IN
 BOTH, END ZONES AS WELL AS THE INTERIOR
 ZONES & THEIR TRIBUTARY AREA. THIS IS
 CRUCIAL INFORMATION REQUIRED FOR THE
 CONTRACTORS TO PROVIDE THE CORRECT
 WINDOW OR DOOR FOR THE REQUIRED
 PRESSURES.
  
 60) SHEET S0.02 INDICATES WORK NOT
 COVERED BY THE ENGINEER OF RECORD WITH
 NOTE 7825 SPECIALTY ENGINERED ITEMS,
 THE ITEMS THAT COMPOSE COMPONENTS AND
 CLADDING TO ENCLOSE THE BUILDING WILL
 NEED TO SUPPLY TECHNICAL DATA FOR THE
 BUILDING TO BE PERMITTED.ADDITIOAL
 INFORMATION REQUIRED. FL BLD CODE
 104.2.1.2*OTHER SPECIALTIES AS THE POOL
 WILL BE PERMITTED SEPERATELY.
  
 61) STRUCTURAL SHEET S4.05 HAS A NOTE
 ABOUT HDS SEE NOTES, WHERE? CONCERNS
 ABOUT 707.1 CONCEALED SPACES IN TYPES I,
 II AND IV CONSTRUCTION.COMBUSTIBLES
 SHALL NOT BE PERMITTED IN CONCEALED
 SPACES OF TYPES I, II OR IV
 CONSTRUCTION.
  
 62) DEALS WITH THE REQUIEMENTS FOR FIRE
 RESISTANCY IN TABLE 600 FOR A TYPE I
 BLDG. COLUMNS SUPPORTING MORE THAN 1
 FLOOR REQUIRE A 4 HR RATING. SUPPORTING
 1FLOOR ONLY A 3 HR RATING. TABLE 709.2.4
  
 PROVIDES THE MINIMUM DIMENSION FOR THE
 FIRE RATED COLUMNS PROVIDE THE TYPE OF
 CONCRETE TO BE USED, THEN MINIMUM FIRE
 RESISTANCY OF COLUMNS CAN BE VERIFIED.
 PLEASE NOTE ON S6.01, S6.02 & S6.03.
  
 63) S6.02 IDENTIFIES THE DIFFERENT TYPES
 OF HOOPS TO BE USED BY CONFIGURATION.
 PLEASE PROVIDE THE DIMENSIONS FOR THE
 MINIMUM REQUIRED COVERAGE OF STEEL IN
 709.2.4.2.
  
 64) A5.07-A5.13 SSTAIR TOWERS STAIRS TO
 COMPLY WITH1007.1.2 STAIRWAYS LOCATED
 IN A REQUIRED FIRE RESISTANT ENCLOSURE
 SHALL HAVE CLOSED RISERS.
  
 65) PLANS TO INDICATE COMPLIANCE WITH:
 1015.3 OPENINGS. OPEN GUARDRAILS SHALL
 HAVE INTERMEDIATE RAILS OR ORNAMENTAL
 PATTERN SUCH THAT A 4-INCH (102 MM)
 DIAMETER SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES.A
 BOTTOM RAIL OR CURB SHALL BE PROVIDED
 THAT WILL REJECT THE PASSAGE OF 2-INCH
 (51 MM) DIAMETER SPHERE.
 EXCEPTIONS:
 1. A 6 INCH (152 MM) SPHERE SHALL NOT
 PASS THROUGH THE TRIANGULAR OPENING
 FORMED BY A TREAD, RISER AND BOTTOM OF A
 GUARDRAIL.
  
  
 THE ANSWERS TO THE LISTED QUESTIONS
 ABOVE MAY RESULT IN MORE QUESTIONS IN
 THE NEXT REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 20:28 Sent To  
Notes
2006-06-25 00:00:00REVIEW BACK IN PROGRESS
  
 *** SEE NOTES BELOW.***
  
 PLEASE KNOW, PLANS ARE IN GOOD SHAPE.
 THE ELECTRICAL DESIGN TEAM HAS ADDRESSED
 COMMENTS WITH ONLY VERY MINOR ITEMS
 REDLINED.
 REVIEW PASSED. STAMPED ALL THREE SETS OF
 ELECTRICAL PLANS, GENERATOR, ATS, FIRE
 PUMP, AND FIRE PUMP CONTROLLER
 SUBMITTIALS ALONG WITH REVISED SPEC
 SHEETS.
  
 ** PLEASE SEE ONLY NOTE #1 BELOW SHOULD
 BE VERIFIED WITH THIS OFFICE BEFORE
 FINAL ELEVATION OF THE EPSS EQUIPMENT
 AND BEFORE INSTALLATION OF FORMS FOR THE
 LOCATION OFGEN RM, AND MAIN ELECTRICAL
 RM. AND THE FIRE PUMP ROOM.
  
 1) NOTE:PLEASE KNOW, THE ELEVATION OF
 EPSS "SHALL"MEET NFPA-110 2002.
 7.2.3*THE ROOMS, SHELTERS, OR SEPARATE
 BUILDINGS HOUSING LEVEL 1 OR LEVEL 2
 EPSS EQUIPMENT SHALL BE DESIGNED AND
 LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE
 FOLLOWING:
 (1) FLOODING RESULTING FROM FIRE
 FIGHTING
 (2) SEWER WATER BACKUP
 (3) SIMILAR DISASTERS OR OCCURRENCES BE
  
 ** PLEASE SEE COMMENTARY MENTIONS
 CONSIDERATIONS, HOWEVER 110, 7.1.3(3)
 ALSO STATES DETERMINATIONS SHALL BEPER
 AHJ.
 PLEASE SEE THE FOLLOWING IS TAKEN
 DIRECTLY OUT OF NFPA-110
  
 **A.7.2.3 EPSS EQUIPMENT SHOULD BE
 LOCATED ABOVE KNOWN PREVIOUS FLOODING
 ELEVATIONS WHERE POSSIBLE.
  
 **A.7.2.4(3)EPSS DESIGN SHOULD CONSIDER
 THE "100-YEAR STORM" FLOODING LEVEL OR
 THE FLOODING LEVEL PREDICTED BY THE
 SLOSH MODELS FOR A CLASS 4 HURRICANE.
  
  
 ** PLEASE SEE THE FOLLOWING ITEMS WERE
 REDLINED ON PLANS AND THERE IS NO NEED
 FOR CORRECTIONS.THESE ARE MINOR ITEMS
 MISSING AS PREVIOUSLY NOTED AND CAN BE
 REVISED AT LATER DATE AS PLANS WILL MOST
 LIKELY HAVE SOME SORT OF REVISIONS.
  
 PLEASE SEE E-24 PANEL SYMBOL REMOVED,
 HOWEVER STILL SHOWS "ELEC-PANEL".
  
 PLEASE SEE E-25 WHAT APPEARS TO BE
 DINING AREA, RECEPT CIRCUITED TO
 LIGHTING CIRCUIT. VIF.
 PLEASE ALSO SEE ON SAME SHEET THE LV
 PANEL STILL SHOWN IN CLOSET WHERE THE
 LOCATION HAD BEEN REVISED TO NEW
 LOCATION.
  
 PLEASE SEE E-36A MISSING CIRCUIT # FOR
 RECEPT IN GRAND SALON.
  
 PLEASE SEE E-39 AS LV PANEL STILL SHOWN
 IN CLOSET WHERE LOCATION HAS BEEN
 REVISED.
  
 PLEASE SEE NOTE REGARDING "BUS-DUCT'
 CURBING AS RESPONSE MENTIONS THE CLOSET
 SHALL HAVE THIS CURBING AS WAS REVISED
 ON "A" SHEET. PLANS WERE NOTED AND
 REDLINED ON BOTH RISER SHEETS FOR 368.6
  
  
 **************************************
 THE FOLLOWING WAS ONLY NOTED ON PLANS
 FOR REQ'D INFORMATION.
  
 1) A LAYOUT/MAPPING SHALL BE LOCATED IN
 THE FIRE COMMAND ROOM INDICATING ALL
 LOCATIONS OFMAINS/SERVICES, GENERATOR,
 FIRE PUMP. THIS MAPPING SHALL BE COVERED
 AND PROTECTED FROM ANY DAMAGE RO
 DETERIORATING CONDITIONS.
 SIGNAGE REQUIRED AT FCRM, AND AT EACH
 OTHER LOCATION OF MAINS AND SERVICES
 DENOTING ALL OTHER LOCATIONS OF MAINS
 ETC.
 230.2E,700.8,701.9 ETC.
  
  
 ***********************************
  
  
  
 PLEASE SUBMIT THE INFORMATION AS
 SET-FORTH IN NOTE ONE BEFORE
 CONSTRUCTION AS NOTED ABOVE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-24 00:00:00REVIEW IN PROGRESS/COMMENCED.
 REVIEW STOPPED, REVIEW TO CONTINUE ON
 SUNDAY 6/25
2006-06-21 00:00:00MEP ROLLS IN ELEC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-31 Cont ID  
Sent By dpalmer Date 2005-12-31 Time 18:21 Rev Time 0.00
Received By dpalmer Date 2005-12-31 Time 13:25 Sent To  
Notes
2005-12-31 00:00:00IN ELEC FOR REVIEW, IN PROGRESS
 *********** UNSAT 2ND REVIEW **********
  
 PALLADIO
 2211 N. FLAGLER DR.
 PLANS CONVERTED BACK TO PERMIT> THIS IS
 TECHNICALLY THE 2ND REVIEW, HOWEEVR
 FIRST REVIEW WAS UNDER "PROJECT"/PLAN
 REVIEW.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO NEW
 INFORMATION, CHANGES, CODES.
  
 1)NOTE: NOTE#1 NO. COULD NOT LOCATE
 SPECS AS REQUESTED.
 PLEASE SUBMIT ALL MANUFACTURE
 SPECIFICATION SHEETS/ CUT SHEETS FOR
 FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER,
 GENERATOR, AUTOMATIC TRANSFER SWITCH
 (ATS) AND ANY SUB BASE FUEL TANKS.
 PLEASE SURE ALL INFORMATION SUBMITTED
 MUST SHOW LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LAB. (NRTL).
 PLEASE BE SURE ALL FIRE PUMP CONTROLLERS
 ETC COMPLY WITH NFPA-20 AND OTHER
 APPLICABLE CODES.
  
 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE
 NOTES PERTAINING TO SPECS SUBMITTED.
 PLEASE SEE 16450.1 WHICH REFERENCES
 CODES FROM THE 1996 NEC.
 PLEASE SEE COLOR CODING FOR 277/480V
 SYSTEMS SHALL BE BROWN/PURPLE/YELLOW.
 PLEASE SEE 16100-2
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 YES,NO, PLEASE SEE STAIR
 AND EGRESS TUNNELS ARE OK, HOWEVER
 PLEASE SEE GARAGE AND OTHER EGRESS PATHS
 WHICH WILL REQUIRE A MIN OF 1 FT CANDLE.
 PLEASE ALSO SEE FIRE REVIOEW COMMENTS
 WITH RESPECT TO EM EGRESS LIGHTING FROM
 POOL AREA TO PUBLIC RIGHT OF WAY
 REQUIRED.
 PLEASE ALSO VERIFY THE LOBBY AREAS BEING
 USED AS A MEANS OF EGRESS FROM UNITS.
 2003 NFPA-101 7.8.1.3, 7.9.2.2
 ** PLEASE SEE NEW NOTES PERTAINING TO
 PHOTO-METRICS.
  
 7)NOTE: NOTE #7 YES,NO, PLEASE SEE MOST
 WERE ADDED HOWEVER PLEASE SEE E-21 AN
 ELECTRICAL RM AND THE FIRE COMMAND RM DO
 NOT INDICATE A CHANGE IN FIXTURE TYPE.
 700.16, LS 101 7-9, 90.4
  
 8)NOTE: NOTE #8OK.
  
 9)NOTE: NOTE #9OK
  
 10)NOTE: NOTE #10, OK.
  
 11)NOTE: NOTE #11 OK
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE SOME
 UNITS MISSING RECEPTS PER 210.52.
 PLEASE SEEONE REDLINED SET.
 "L" SOUTH, BED RM #3, "N", BR#3 #4,
 LOFTS WITH WHAT APPEARS TO BE WALL SPACE
 BY STAIRS ON LOWER LEVELS/ WITHIN 6' FRO
 THE EDGE.
  
 19)NOTE: NOTE #19 NO,PLEASE SEE
 CIRCUITING MISSING FROM SOME DEVICES
 SHOWN IN SOME OF THE UNITS. PLEASE SEE
 SD'S, RECEPTS.
 PLEASE SEE REDLINED PLANS AS MOST ARE
 CIRCIRLED.
  
 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE
 SOME AREA DESIGNATIONS ON UNITS ARE NOW
 SHOWN WHICH DINING AREAS/BREAKFAST AREAS
 ARE ON 15A #14 GEN LT CIRCUITS.
 CIR #42
 PLEASE SEE UNIT "N", "Q"
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK, HOWEVER PLEASE SEE
 NEW NOTE FOR ONE GFI LOCATION.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 OK.
  
 29)NOTE: NOTE #29 OK.
  
 30)NOTE: NOTE #30 OK.
  
 31)NOTE: NOTE #31 OK.
  
 32)NOTE: NOTE #32 NO.
 PLEASE SEE MISSING SMOKE DETECTORS
 REQUIRED UNDER NFPA-72 11.5.1.1,
 11.8.3.5
 PLEASE SEE SD'S ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING RMS AND ON EACH
 LEVELOF A MULTY LEVEL DWELLING.
 PLEASE SEE SOME MISSING, DEN IN UNIT "R"
 WILL BE REQUIRED TO HAVE A SD AS IT IS
 SHOWN WITH AN ATTACHED BATH OR CLOSET
 WHICH MAKES THIS AN ADAPTABLE SLEEPING
 RM BY AHJ. PLEASE SEE MISSING SD "Q"
 NORTH,LEADING TO FLR ABOVE.
 PLEASE SEE SD'S ARE REDLINED AT
 LOCATIONS REQUIRED IN OTHER UNITS.
  
 33)NOTE: NOTE #33 OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE THESE
 LOBBY AREAS ARE STILL UNCLEAR BY THE
 BLDG REVIEW COMMENTS IF THEY BELONG TO
 THE UNIT OR PART OF "HOUSE/COMMON" AREA.
 PLEASE SEE EXTENSIVE BLDG REVIEW
 COMMENTS.
 PLEASE SEE 210.25 WHICH STATES NO COMMON
 AREAS SHALL CONTAIN ELECTRICAL DEVICES
 FED FROM UNITS. IF THESE ARE "PRIVATE"
 LOBBIES,PLEASE SHOW HOW THESE AREAS
 CONTAIN NUMEROUS ELECTRICAL ITEMS FED
 FROM HOUSE POWER?
 PLEASE ALSO SEE NEW EXT LTS ETC ADDED TO
 UNITS.
  
 35)NOTE: NOOTE #35 OK.
  
 36)NOTE: NOTE #36 OK.
  
 37)NOTE: NOTE #37 NO, PLEASE ADD NOTE TO
 THE ROOF TOP PLANS.
 PLEASE SEE ANY PROPOSED LIGHTNING
 PROTECTION SYSTEM SHALL BE
 INSTALLED AND ACCEPTABLE PER NFPA-780.
 ALTHOUGH A LIGHTNING PROTECTION SYSTEM
 IS NOT SHOWN ON ANY PLANS, PLEASE BE
 SURE A NOTE IS PLACED ON "ROOF-TOP"
 SHEET WITH REFERENCE TO NFPA-780.
 AS NOTED IN MEETING , "LIGHTNING
 PREVENTION" SYSTEMS ARE NOT PERMITTED OR
 ACCEPTABLE IN THIS JURISTICTION.
  
 38)NOTE: NOTE #38 OK, HOWEVER SEE ELEC
 NOTES FOR SERVICE.
  
 39)NOTE: NOTE #39 OK.
  
 40)NOTE: NOTE #40,NO, PLEASE SEE
 ELECTRICAL SERVICE WAS MOVED AROUND ,
 HOWEVER THE INTENT OF ORIGINAL NOTE HAS
 NOT BEEN ADDRESSED. PLEASE SEE EM MAIN
 HAS NOW BEEN MOVED TO MAIN ELECTRICAL
 RM, WHICH WHEN SHUT OFF WILL TRIGGER THE
 GEN TO START, TRANSFER POWER OVER TO
 HXDP, WHICH IS STILL LOCATED IN THE GEN
 RM. THEMCB ADDED TO THE HXDP WOULD NOT
 BE READILY ACCESSIBLE, GROUPED OR IN
 CLOSE PROXIMITY AND OTHER HAZARDS MAY
 PREVENT THE SHUTTING DOWN OF POWER IN A
 TIMELY AND SAFE MANOR.
 THIS LOCATION WITH A 1500KW GENERATOR
 RUNNING AT FULL NOISE LEVEL, HEAT ETC
 MAY DISTRACT IN SHUTTING DOWN OF EM
 POWER IN A SAFE AND TIMELY FASHION. IT
 IS NOTED THAT THESE MAINS AND GEN WILL
 HAVE SHUNT TRIPS IN FIRE COMMAND RM,
 HOWEVER THESE ARE NOT CONSIDERED AS THE
 MEANS OF DISC. 230.76,230.79
 PLEASE SEE IT IS UNCLEAR AT THIS TIME IF
 BRKR ON GEN IS LOCATED ON THE OUTSIDE OF
 EQUIPMENT WITH A MANUAL MEANS OF
 DISCONNECT WITH EXPOSING OF LIVE PARTS.
 110.27.
 PLEASE SEE SOME OF THIS CAN NOT BE
 VERIFIED AT THIS TIME AS SPECS FOR THIS
 EQUIPMENT, GENERATOR ETC WAS NOT
 SUBMITTED.
 PLEASE SEE ROUTE, LOCATION TRAVEL
 DISTANCE ETC MAY BE GONE IN A MEETING
 WHICH MAY BE REQUESTED.
  
 41)NOTE: NOTE #41 OK.
  
 42)NOTE: NOTE #42 OK.
  
 43)NOTE: NOTE #43 OK.
  
 44)NOTE: NOTE #44 OK.
  
 45)NOTE: NOTE #45 OK.
  
 46)NOTE: NOTE #46 OK, HOWEVER NO
 CONNECTION FOR GEN GROUNDING ELECTRODE
 SYSTEM WAS SHOWN. ONLY NOTES TO GEN
 FRAME. PLEASE SEE 250.30, AS THIS GEN IS
 SEPARATELY DERIVED.
  
 47)NOTE: NOTE #47 OK.
  
 48)NOTE: NOTE #48 OK.
  
 49)NOTE: NOTE #49 OK.
  
 50)NOTE: NOTE #50 OK.
  
 51)NOTE: NOTE #51 OK.
  
 52)NOTE: NOTE #52 OK.
  
 53)NOTE: NOTE #53 OK.
  
 54)NOTE: NOTE #54 OK.
  
 55)NOTE: NOTE #55 OK.
  
 56)NOTE: NOTE #56 OK, HOWEVER SEE NEW
 NOTE AS PANEL SCHEDULES REVIEWED FOR THE
 FIRST TIME.
  
 57)NOTE: NOTE #57 OK.
  
 58)NOTE: NOTE #58 OK.
  
 59)NOTE: NOTE #59 OK.
  
 60)NOTE: NOTE #60 OK.
  
 61)NOTE: NOTE #61
  
 62)NOTE: NOTE #63, NOPLEASE SEE POOL
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT WHICH IS NOTED ON PLANS.
 THIS IS OK, HOWEVER PLEASE KNOW, IF
 THERE IS GOING TO BE ANY AFTER DUSK
 SWIMMING, THIS WILL HAVE AN IMPACT ON
 THE MIN LIGHTING LEVELS AND DESIGN FOR
 POOL DECK/EGRESS LIGHTING. PLEASE SEE
 OTHER NOTES PERTAINING TO EGRESS..
 IF NIGHT-TIME/AFTER DUSK WILL BE
 PROPOSED, SIGNED, SEALED PHOTOMETRICS
 WILL BE REQUIRED TO BE SUBMITTED TO PALM
 BEACH COUNTY HEALTH DEPT FOR REVIEW AND
 STAMPING.
  
  
  
 ******* NEW NOTES ************
  
 1)NOTE: PLEASE CORRELATE CONDUCTORS
 SHOWN ON HS FOR LS.
 215.5
 PLEASE ALSO LABEL WHICH TRANSFORMER HS
 IS FEEDING AS OTHER PANEL SCHEDULES ARE
 LABELED.
  
 2)NOTE: PLEASE SEE CIRCUITS WHICH
 REQUIRE ARC FAULT PROTECTION, PLEASE SEE
 "Q", #32, UNIT "A", #28.
  
 3)NOTE: PLEASE SEE A "MISPRINT" OF AN
 ADDITIONAL "ELEC PANEL" IN UNIT "B".
 215.5
  
 4)NOTE: PLEASE SEE NOTES WITH RESPECT TO
 ARC FAULT PROTECTION. NOTE MENTIONS
 "RECEPT" WHERE-AS ALL OTHER NOTES WERE
 CHANGED TO "OUTLETS".
  
 5)NOTE: PLEASE SEE BLDG NOTES PERTAINING
 TO MEZZANINE, AND TOWNHOUSE DESIGNATIONS
 WHICH ARE ON E-SHEETS AND OTHER
 LOCATIONS.
  
 6)NOTE: PLEASE PROVIDE THE INFORMATION
 AS REQUESTED BY FIRE AND BLDG REVIEW
 PERTAINING TO POOL EQUIPMENT ROOM AND
 ANY STORAGE OF HAZARDOUS MATERIALS.
 ADJUST ELECTRICAL AS NEEDED,PLACE NOTE
 ON PLANS.
  
 7)NOTE: PLEASE PROVIDE A BUS-DUCT CURB
 DETAIL AS REQUIRED PER 368.6, THIS
 SHOULD HAVE BEEN REQUESTED ON ORIGINAL
 REVIEW.
  
 8)NOTE: PLEASE VERIFY NEW NOTE WHICH
 MENTIONS A FLOOR? MOUNTED GFI IN BATHRM
 FOR JACUZZI TUB IN UNIT "Q". THIS SHALL
 NOT BE MOUNTED FACING UP, AND SHOWN BE
 OFF THE FLOOR/WET AREA LOCATED UNDER TUB
 ACCESS PANEL.
 PLEASE SEE MIN CLEARENCES FROM TUBS,
 410.8
  
 9)NOTE: PLEASE KNOW THE FOLLOWING MAY BE
 SET-UP AS A "PROVISO" OR MAY BE
 ADDRESSED AT THIS TIME.
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 STAIRS TOWERS, EGRESS TUNNELS, AND ALL
 OTHER PATHS FOR MEANS OF EGRESS AS
 PREVIOUSLY NOTED TO PUBLIC RIGHT-OF-WAY.
 PLEASE SEE 7.8.1.3, WHICH REQUIRES A MIN
 OF 10FT CANDLES(108 LUX) UNDER NORMAL
 POWER AT ALL WALKING SURFACES OF
 STAIRS/STAIRWAYS.
 PLEASE SEE STAIRS CAN BE REDUCED TO .8
 LUX OR 1FT CANDLE UNDER EM POWER/BATTERY
 BACK UP.
 PLEASE SEE ALL OTHER AREAS FOR EGRESS
 MUST HAVE A MIN OF 1 FT CANDLE UNDER
 NORMAL AND EM POWER ON ALL WALKING
 SURFACES.
  
  
 ** PLEASE SEE MOST OF THE ABOVE
 ITEMS ARE REDLINED ON ONE SET OF
 ELECTRICAL PLANS, HOWEVER THESE DO NOT
 IDICATE ALL POSSIBLE LOCATIONS OF NEEDED
 CORRECTIONS.
  
 **PLEASE KNOW, SOME ITEMS STILL NEED TO
 BE VERIFIED ONCE ALL INFORMATION IS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE A
 DIRECT EFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By dpalmer Date 2005-08-23 Time 18:15 Rev Time 24.00
Received By dpalmer Date 2005-08-18 Time 07:25 Sent To  
Notes
2005-08-23 00:00:00*********** UNSAT ***************
  
 PALLADIO
 2211 N. FLAGLER DR.
 PLANS SUBMITTED AND UNDER "PLAN REVIEW"
 ONLY. BROUGHT IN FOR PERMIT,HOWEVER PLAN
 REVIEW DONE UNDER PLAN REVIEW.
  
 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECIFICATION SHEETS/ CUT SHEETS FOR
 FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER,
 GENERATOR, AUTOMATIC TRANSFER SWITCH
 (ATS) AND ANY SUB BASE FUEL TANKS.
 PLEASE SURE ALL INFORMATION SUBMITTED
 MUST SHOW LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LAB. (NRTL).
 PLEASE BE SURE ALL FIRE PUMP CONTROLLERS
 ETC COMPLY WITH NFPA-20 AND OTHER
 APPLICABLE CODES.
  
 2)NOTE: PLEASE SEE SPEC BOOKS SUBMITTED
 ARE NOTED AS ELECTRICAL MECHANICAL SPECS
 BY OTHERS?
 PLEASE BE SURE THESE ARETO BE
 SUBMITTED AT THIS TIME.
  
 3)NOTE: PLEASE SEE MAIN ELECTRICAL RM
 LOCATED ON E-PH-1 WHICH SHOWS DOORS WITH
 AN "IN-SWING", PLEASE SEE DOORS ARE
 REQUIRED TO SWING OUT AND SHALL CONTAIN
 OR "PANIC " HARDWARE AS LISTED IN 110.26
 PLEASE NOTE: PANIC HARDWARE REQUIREMENTS
 ON ELECTRICAL PLANS.
 PLEASE SEE FIRE PUMP ROOM WILL BE
 REQUIRED TO HAVE DIRECT ACCES TO
 CORRIDOR WITHOUT TRAVEL THROUGH A
 "STORAGE ROOM".
 PLEASE SEE FIRE REVIEW COMMENTS ALSO.
  
 4)NOTE: PLEASE SEE MISSING REQUIRED GFI
 RECEPT(S) TO BE LOCATED WITH/IN 20' OF
 POOL(S).PLEASE SEE 680.22
  
 5)NOTE: PLEASE SEE MIN CLEARENCES
 REQUIRED FOR LANDSCAPE LIGHTING FIXTURES
 PER 680.22(B)1 5' MIN FOR HV AND GFCI
 PROTECTION REQUIRED. PLEASE ALSO SEE
 411.4 FOR LV TYPE FIXTURES AND MIN OF
 10' FROM WATER'S EDGE.
  
 6)NOTE: PLEASE SEE ALTERNATING
 CIRCUITING FOR EMERGENCY EGRESS LIGHTING
 REQUIRED IN HALLWAYS/CORRIDORS, EGRESS
 STAIRWAYS AND ("EGRESS TUNNELS").
 PLEASE SEE NFPA-101 7-9, WHICH REQUIRES
 NOT TO LEAVE ANY EGRESS PATH IN TOTAL
 DARKNESS UPON THE SWITCHING/TRIPPING OF
 A SINGLE BREAKER. PLEASE SEE BATTERY
 BACK UP TYPE OF FIXTURES WOULD NOT
 REQUIRE ALTERNATING EM CIRUITS FOR
 EGRESS LIGHTING.
  
 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL
 ROOMS, GEN RM, FIRE PUMP RM AND ELEVATOR
 EQUIPMENT ROOMS/EQUIPMENT BOILER RM
 SHALL A BATTERY BACK UP TYPE OF LIGHTING
 FIXTURE.
 700.16, LS 101 7-9, 90.4
  
 8)NOTE: PLEASE SEE 620.23 AND 620.24
 WHICH REQUIRES EQUIPMENT ROOMS/ARES TO
 HAVE A DEDICATED BRANCH CIRCUIT FOR
 RECEPTS AND LIGHTING. PLEASE KNOW, PER
 MEETING WITH OWNERS AND DESIGN TEAM,
 THIS ALSO INCLUDES ALL EQUIPMENT LOCATED
 A-TOP HOISTWAY.
 A RECEPT IN ELEVATOR EQUIPMENT CLOSET IS
 SHOWN ON PLANS.
  
 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT
 LOCATIONS OF ANY "KNOX BOX" LOCATION(S)
 WHICH MAY BE REQUIRED. ONE OR MORE
 LOCATIONS SHALL BE PLACED/NOTED ON
 PLANS.
  
 10)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS. PLEASE SEE THIS
 COMMENTS IS MAINLY FOR SOME COMMON AREAS
 MISSING DESIGNATIONS.
  
 11)NOTE: : PLEASE SEE 210.63 FOR
 REQUIMENTS OF GFI RECEPTS FOR ALL A/C
 EQUIPMENT. PLEASE SEE THESE COULD NOT BE
 LOCATED ON ROOF PLANS ETC.
  
 12)NOTE: PLEASE SEE ELEVATOR RMS,
 LAYOUTS ON E-09AND E-12, DOOR/OPEINGS
 FOR EQUIPMENT DO NOT SEEM TO CORRELATE.
  
 13)NOTE: PLEASE KNOW IT WAS MENTIONED IN
 MEETING THE "CAFE" WOULD BE A "SHELL"
 AREA ONLY, HOEVER PLEASE SEE PLANS SHOW
 ALL ELECTRICAL DEVICES BEING INSALLED?
 PLEASE SEE RISER SHOWS CONDUIT FOR
 "FUTURE" RESTAURANT. IS THIS THE SAME ?
 PLEASE CLARIFY.
  
 14)NOTE: PLEASE SEE SOME AREAS OF PLANS
 FOR COMMON AREA LIGHTING ETC WHICH ARE
 NOT "LEGALLY REQUIRED" SEEM TO BE ON THE
 EM LEGALLY REQUIRED STAND-BY POWER
 SYSTEM.
 PLEASE SEE THAT ANY "OPTIONAL STAND-BY"
 LOADS NOT LEGALLY REQUIRED MUST BE FED
 FROM A DIFFERENT TRANSFER SWITCH AND EM
 DISTRABUTION SYSTEM. PLEASE SEE 700.6D
  
 15)NOTE: PLEASE SEE AS PER MEETING WITH
 OWNERS REP/DESIGN TEAM, DRYER BOOSTER
 FANS SHALL NOT BE USED, HOWEVER THESE
 ARE STILL BEING SHOWN?
 PLEASE CORRELATE AND PLEASE SEE
 MECHANICAL REVIEW COMMENTS.
  
 16)NOTE: PLEASE SEE 210.52C2 AND 4 WITH
 REGARDS TO "SEPARATE" COUNTERSPACES FOR
 ISLANDS. PLEASE VERFIY SIZE OF COOKTOP
 AND A SAFE COUNTERSPACE FOR NTO
 EXTENDING CORDS NEAR HEAT SOURCES ETC.
 PLEASE SEE GFI RECEPTS AS SHOWN ON
 ISLANDS AT THIS TIME, APPEAR TO MEET
 CODE,PLEASE SEE THIS IS ONLY A NOTE FOR
 SIZING ETC TO BE VERIFIED.
 PLEASE SEE IF IF UNIT IS LARGER THAN IS
 SHOWN, A SEPARATE GFI AT OTHER END WILL
 BE REQUIRED.
 PLEASE BE SURE ALL ISLANDS SHOW A RECEPT
 AS REQUIED. PLEASE SEE REDLINED SETS FOR
 ANY MISSING.
  
 17)NOTE: PLEASE SEE SOME MISSING GFI
 COUNTERSPACE RECEPTS AS REQUIRED ALONG
 WALL/COUNTERSPACE. 210.52C1
 PLEASE SEE REDLINED SETS FOR LOCATIONS
 IN SOME UNITS.
 "B",DMOD, C, S.
  
 18)NOTE: PLEASE SEE SOME UNITS MISSING
 RECEPTS PER 210.52.
 PLEASE SEE REDLINED SET.
  
 19)NOTE: PLEASE SEE CIRCUITING MISSING
 FROM SOME DEVICES SHOWN IN SOME OF THE
 UNITS. PLEASE SEE GFI'S IN SOME BATHS.
 PLEASE SEE REDLINED PLANS AS MOST ARE
 CIRCIRLED. PLEASE SEE UNITS, G NORTH, L
 NORTH, E, F D NORTH MOD ETC.
  
 20)NOTE: PLEASE SEE UNIT "B" SOUTH WHICH
 DOES NOT APPEAR TO SHOW ANY DINING RM/
 AREA ON PLANS. PLEASE SEE POSSIBLE ARE
 SHOWN AS MEDIA/DEN?
 PLEASE VERIFY AS DINING RM/AREA AND THE
 LIKE SHALL BE FED FROM ONE OR MORE OF
 THE REQUIRED SMALL APPLIANCE CIRCUITS.
 210.52B1, 210.11C1 20A AND #12.
  
 21)NOTE: PLEASE SEE "D" NORTH WHICH
 SHOWS ISLAND RECEPT ON CIRCUIT #6,
 HOWEVER 6/8 IS SHOWN ON PANEL SCHEDULE
 AS OVEN. PLEASE ADJUST.
  
 22)NOTE: PLEASE SEE "L" SOUTH WHICH
 SHOWS "FRIG" ON SM APPLIANCE CIRCUIT #8,
 HOWEVER FRIG IS LISTED AS #4 ON PANEL
 SCHEDULE. FRIG CIRCUIT NOT SHOWN ON
 PLANS. PLEASE ADJUST.
  
 23)NOTE: PLEASE SEE SOME BATH(S) ARE
 MISSING THE REQUIRED GFI RECEPT WITHIN
 3' OF LAV EDGE. PLEASE SEE "N", PLEASE
 ALSO SEE PLANS FOR ANY OTHER REDLINED
 LOCATIONS.
 210.52D,210.11C3
  
 24)NOTE: PLEASE SEE SEE SOME
 "HYDRO-MASSAGE" CIRCUITS ARE NOTED ON
 PANEL SCHEDULE(S), HOWEVER THESE
 ELECTRICAL DEVICE LOCATIONS COULD NOT BE
 LOCATED ON PLANS. PLEASE SEE "K"
 NORTH,"H" NORTH AND ANY OTHER POSSIBLE
 REDLINES.
  
 25)NOTE: PLEASE SEE THAT ALL RECEPTS
 SHOWN IN CLOSETS FOR LV TRNSFORMERS TO
 BE "PLUGGED IN" SHALL BE LOCATED ATLEAST
 12" MIN FROM SHELVING. THESE MAY BE
 LOCATED ABOVE DOOR WAYS.
 PLEASE SEE PLUG-IN TYPE TRANSFORMERS
 CREATE VERY HIGH TEMPS AND SOME IN THIS
 JURISTICTION HAVE HEATED TO THE POINT OF
 MELTING, AND CUSE OF FIRE IN CLOSETS AND
 CLOSE PROIMITY TO COMBUSTIBLES. PLEASE
 SEE THIS CREATES A LIFE-SAFETY SITUATION
 AND ANY UNITS CONTAININGOCP, THERMAL
 CUT-OUT DEVICES WILL BE REQUIRED TO BE
 LOCATED AS ABOVE. 110.26,240.24D
  
 26)NOTE: PLEASE SEE MISSING ISLAND
 RECEPT(S) FOR ISLAND IN UNIT "P".
 210.52C2
 AS REDLINED.
  
 27)NOTE: PLEASESEE UNIT "N" WHICH
 APPEARS TO SHOW A FRIG #37, HOWEVER
 PLEASE SEE POSSIBLE SPACING FOR KITCHEN
 COUNTERSPACE DEPENDING ON FRIG SIZE AS
 SHOWN. PLEASE SEE "P", 210.52C1
 LOCATIONS REDLINED.
  
 28)NOTE: PLEASE SEE UNIT "P"SOUTH AND
 "Q" NORTH. PLEASE SEEUNIT "P" WITH
 LESS SQ FT SHOWS 3-HEAT-PUMPS SYSTEMS,
 HOWEVER UNIT "Q" WITH MUCH MORE SQ FT
 ONLY SHOWS 2-HEAT PUMP SYSTEMS.
 PLEASE SEE THIS IS ONLY A COMMENT AND NO
 ELECTRICAL CODE ISSUE EXISTS.
  
 29)NOTE: PLEASE SEE COUNTERSPACES
 LOCATED AT LAUNDRY RM IN "Q" NORTH, DO
 NOT SHOW ANY COUNTERSPACE GFI RECEPTS.
 PLEASE SHOW IF ANY ARE TO BE INSTALLED.
 THIS IS ONLY A NOTE AS A MIN OF ONE
 LAUNDRY CIRCUIT AS REQUIRED UNDER
 210.52C2,210.52F,220.16
 PLEASE SEE NO ADDITIONAL ARE REQUIRED AS
 LONG AS ABOVE IS MET.
 PLEASE SEE NEXT COMMENT.
  
 30)NOTE: PLEASE SEE PLANS INDICATE MANY
 OF THE UNITS PANEL SCHEDULES SHWOING TWO
 SEPARATE CIRCUITS FOR WASHER AND DRYER.
 PLEASE SEE MANY UNITS SHOW THIS
 WASHER/DRYER AS ONE UNIT. PLEASE SEE
 PREVIOUS COMMENT WITH RESPECT TO DESIGN
 OF "DUCTLESS" DRYERS. ALSO VERIFY IF
 LAUNDRY CIRCUIT REQUIRED IS THE SAME
 CIRCUIT FEEDING COMBO UNIT??
  
 31)NOTE: PLEASE ALSO SEE ABOVE "Q" UNIT
 APPEARS TO SHOW TWO PANELS, ONE WITH
 FEED THRU LUGS? HOWEVER PANEL SCHEDULE
 INDICATES ALL CIRCUITS IN ONE PANEL
 SCHEDULE.
 PLEASE SEE A MAX OF 42 OCP DEVICES ARE
 PERMITTED IN SINGLE PANEL.408.15
 PLEASE INLCUDE PANEL SCHEDULE FOR
 "FEED-THRU" PANEL. PLEASE ADJUST
 CIRCUITING AS SHOWN ON PLANS.
  
 32)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS REQUIRED UNDER NFPA-72
 8-1.4.1.6.2 , FBC ETC.
 PLEASE SEE SD'S ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING RMS AND ON EACH
 LEVELOF A MULTY LEVEL DWELLING.
 PLEASE SEE SOME MISSING, DEN IN UNIT "R"
 WILL BE REQUIRED TO AHVE A SD AS IT IS
 SHOWN WITH AN ATTACHED BATH OR CLOSET
 WHICH MAKES THIS AN ADAPTABLE SLEEPING
 RM BY AHJ. PLEASE SEE MISSING SD "Q"
 NORTH LEADING TO FLR ABOVE.
 PLEASE SEE SD'S ARE REDLINED AT
 LOCATIONS REQUIRED IN OTHER UNITS.
  
 33)NOTE:PLEASE SEE "NOTE"FOR LV
 SYSTEM(S)ON ALL ELECTRICAL SHEETS FOR
 UNITS MENTIONS THE "GENERAL CONTRACTOR'
 IS TO INSTALLED THIS LV IN HIS SCOPE OF
 WORK?
 PLEASE SEE FS 468 AND SCOPE WORK
 PERMITTED. PLEASE ALSO SEE ECLB.
 THIS APPEARS TO BE A MISPRINT.?
  
 34)NOTE; PLEASE SEE BLDG/MECH/FIRE
 REVIEW COMMENTS FOR EQUIPMENT SHOWN IN
 ELEVATOR LOBBY'S. PLEASE ALSO SEE THESE
 ELEVATOR LOBBY'S SHALL BE CONSIDERED
 PART OF UNITS AS COMMON AREAS ARE NOT
 PERMITTED TO CONTAIN CIRCUITS FROM
 UNITS. PLEASE SEE 210.25
  
 35)NOTE: PLEASE SEE ALL SD'S ARE
 REQUIRED TO BE WIRED "IN-LINE", PLEASE
 SEE UNIT WLT3, WHICH SHOWS SD'S ON
 CIRCUITS 12 AND 24. PLEASE ADJUST.
  
 36)NOTE: PLEASE SEE 210.702C FOR LOFT
 UNITS CONTAINING LANDINGS. PLEASE SEE
 THESE UNITS INDICATE 6 OR MORE RISERS IN
 BOTH DIRECTIONS, PLEASE SEE A 4-WAY SW
 WILL BE REQUIRED AT LANDING LOCATION.
  
 37)NOTE: PLEASE SEE ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL BE
 INSTALLED AND ACCEPTABLE PER NFPA-780.
 ALTHOUGH A LIGHTNING PROTECTION SYSTEM
 IS NOT SHOWN ON ANY PLANS, PLEASE BE
 SURE A NOTE IS PLACED ON "ROOF-TOP"
 SHEET WITH REFERENCE TO NFPA-780.
 AS NOTED IN MEETING , "LIGHTNING
 PREVENTION" SYSTEMS ARE NOT PERMITTED OR
 ACCEPTABLE IN THIS JURISTICTION.
  
 38)NOTE: PLEASE SEE MAINS AS SHOWN RISER
 WITHOUTDIRECT BUS-STAB INTO FPL VAULT
 AND IF THERE ARE MORE THAN 8' OF
 UNPROTECTED CONDUCTORS IN BLDG, THESE
 CONDUITS AND SEC'S SHALL BE INCASED IN A
 MIN OF 2" OF CONCRETE. PLEASE SEE 230.6,
 230.70 ALSO CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS.
  
 39)NOTE: PLEASE SEE CALCUALTIONS FOR
 BUS-DUCT #4, PLEASE INDICATE AS MAIN #4
 AS OTHERS ARE NOTED.
  
 40)NOTE: PLEASE SEE HXDP WILL BE
 REQUIRED TO HAVE A MCB. PLEASE SEE IF
 ATS CONTAINS A MANUAL MEANS OF
 DISCONNECT LOCATED ON OUTSIDE OF ATS AND
 CAPABLE OF BEING LOCKED IN THE "OPEN"
 POSITION, THEN A MCB IN HXDP. PLEASE SEE
 IN EITHER CASE THE MEANS OF DISCONNECT
 WILL BE REQUIRED TO BE IN CLOSE
 PROXIMITY TO MAIN ELECTRICAL RM FOR
 GROUPING OF MAINS. PLEASE SEE NEC DOES
 MENTIONS EM MAIN TO BE LOCATED REMOTE,
 HOWEVER A RESPONSE FROM NFPA MENTIONED
 THIS CAN BE LOCATED AS CLOSE AS 10 FEET.
 PLEASE SEE A CONCENSUS FROM ELECTRICAL
 PLAN REVIEW, FIRE MARSH.'S OFFICE AND
 CHIEF ELECTRICAL INSPECTOR RESULTS IN
 NOT HAVING THE MAIN FROM THE SECONDARY
 SIDE OF GENERATOR IN GENERATOR
 ELECTRICAL ROOM. 230.72
 THIS LOCATION WITH A 1500KW GENERATOR
 RUNNING AT FULL NOISE LEVEL, HEAT ETC
 MAY DISTRACT IN SHUTTING DOWN OF EM
 POWER IN A SAFE AND TIMELY FASHION. IT
 IS NOTED THAT THESE MAINS AND GEN WILL
 HAVE SHUNT TRIPS IN FIRE COMMAND RM,
 HOWEVER THESE ARE NOT CONSIDERED AS THE
 MEANS OF DISC. 230.76,230.79
 PLEASE SEE IT IS UNCLEAR AT THIS TIME IF
 BRKR ON GEN IS LOCATED ON THE OUTSIDE OF
 EQUIPMENT WITH A MANUAL MEANS OF
 DISCONNECT WITH EXPOSING OF LIVE PARTS.
 110.27.
 PLEASE SEE SOME OF THIS CAN NOT BE
 VERIFIED AT THIS TIME AS SPECS FOR THIS
 EQUIPMENT, GENERATOR ETC WAS NOT
 SUBMITTED.
 PLEASE SEE ROUTE, LOCATION TRAVEL
 DISTANCE ETC MAY BE GONE IN A MEETING
 WHICH MAY BE REQUESTED.
  
 41)NOTE: PLEASE SEE MISSING LOAD
 CALCULATIONS FOR MCVI, MCVII.
 215.5
  
 42)NOTE: PLEASE SHOW GROUNDING SYSTEM
 FOR ALL TRANSFORMER. PLEASE INCLUDE
 GROUNDING OF THESE TRANSFOMERS ON RISER
 DIAGRAM IN NOTES/LINE DIAGRAM.
 250.30, 250.50 ETC.
  
 43)NOTE: PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS FOR TRANSFOMERSON
 PRIMARY SIDE. 250.110,250.30 SIZED
 250.122.
  
 44)NOTE: PLEASE INDICATE OCP AT
 GENERATOR. PLEASE ALSO SEE 445.13 FOR
 SIZING OF CONDUCTORS. THIS CAN NOT BE
 VERIFIED AT THIS TIME.
  
 45)NOTE: PLEASE SEE EM MAIN INDICATES
 GFCI PROTECTION. PLEASE SEE GFCI IS
 PERSONNEL PROTECTION AND 277/480V OVER
 1000A'S 230.95,240.13. PLEASE SEE THESE
 AS GFP, GROUND FULT PROTECTION IS NOT
 THE SAME.
  
 46)NOTE: PLEASE SEE 240.13, IF SYSTEM IS
 GROUND FAULT PROTECTD, THE ATS WILL BE
 REQUIRED TO BE 4-POLE AND GENERATOR WILL
 BE REQUIRED TO BE A SEPARATELY DERIVED
 SYSTEM.
 PLEASE SEE GROUNDING FOR ANY SEPARATELY
 DERIVED SYSTEMS SHALL BE SHOWN.
 250.50 ETC
  
 47)NOTE: PLEASE CORRELATE FEEDERS FOR
 LXRA ON RISER WITH PANEL SCHEDULE.
  
 48)NOTE: PLEASE SEE PANELS LPA, LPB WITH
 X'S FOR LOADS, INFORMATION ETC???
 PLEASE COMPLETE PANELS.215.5
  
 49)NOTE:PLEASE SEE SOME PANELS ARE SHOWN
 AS POSSIBLE "FEED-THRU" PANELS WITH MORE
 THAN THE PERMITTED 42 CIRCUITS 408.15,
 HOWEVER RISER DOES NOTE CORRELATE, ONLY
 SHOWS THE INDIVIDUAL PANEL.
 215.5 PLEASE CORRELATE.
  
 50)NOTE: PLEASE SEE PANEL SCHEDULES
 SHOWS "TYPICAL" PANELS FOR TRA, TRB ,
 TRC ETC ETC, HOWEVER THESE COULD NTO BE
 LOCATED ON RISER DIAGRAM?
 215.5
  
 51)NOTE: PLEASE SEE HP ON RISER IS SHOWN
 FEEDING LP, HOWEVER PLEASE SEE HP PANEL
 SCHEDULE WHICH DOES NOT INDICATE ANY
 FEEDS TO LP? 215.5 PLEASE CORRELATE.
  
 52)NOTE:PLEASE SEE HG AS DOUBLE/FEED
 THRU PANEL, HOWEVER RISER INDICATES
 SINGLE PANEL. PLEASE SEE OTHER POSSIBLE
 PANELS, HB, LB AND PREVIOUS NOTE. #49
  
 53)NOTE: PLEASE SEE PANEL TF IS FED FROM
 LG AND LXG? PLEASE CORRELATE 215.5
  
 54)NOTE: PLEASE SEEA 600A MAIN FOR
 FUTURE REST. IS SHOWN, HOWEVER NO
 INFORMATION FOR VOLTAGE ETC WAS
 SUBMITTED. PLEASE SEE PREVIOUS COMMENT
 WITH RESPECT TO "CAFE".??
 215.5
  
 55)NOTE: PLEASE SEE NO PANEL SCHEDULE
 WAS SUBMITTED FOR PANEL HRA AT ROOF
 LEVEL??
 215.
  
 56)NOTE: PLEASE SEE NO PANEL SCHEDULES
 WERE SUBMITTED FOR PANELS , HS, LS, HXS,
 LXS,,,??
 215.5
  
 57)NOTE: PLEASE SEE HXG WHICH SHOWS FEED
 TO LX6, MISPRINT? FOR LXG?
 215.5
  
 58)NOTE: PLEASE SEE "ELB" WHICH
 INDICATES FEED TO LXRB ON RISER AND
 PANEL SCHEDULE INDICATES LXRA.
 PLEASE CORRELATE: 215.5
  
 59)NOTE: PLEASE SEE ELB FEEDS "HXRB" ON
 RISER , HOWEVER SHOWS "HXRA" ON PANEL
 SCHEDULE. PLEASE CORRELATE. 215.5
  
 60)NOTE: PLEASE SEE HXB FEEDS LXB ON
 RISER , HOWEVER THIS IS LXA ON PANEL
 SCHEDULE.215.5
  
 61)NOTE:PLEASE VERIFY2000A OCP AS
 NOTED FOR GENERATOR , HOWEVER LOAD SHOWN
 ON HXDP INDICATES LOADS ABOVE 2000A'S.
 PLEASE SEE MAIN AND ATS IS INDICATED AS
 2500AS'. PLEASE CORRELATE. 215.5
 PLEASE SEE GEN AND OCP SHALL BE SIZED
 FOR LOAD SERVED.
  
 62)NOTE: PLEASE SEE MOST OF THE ABOVE
 ITEMS ARE REDLINED ON ONE SET OF
 ELECTRICAL PLANS, HOWEVER THESE DO NOT
 IDICATE ALL POSSIBLE LOCATIONS OF NEEDED
 CORRECTIONS.
  
 63)NOTE: PLEASE SEE MUCH INFORMATION NOT
 SHOWN (PANEL SCHEDULES), (SPECS) ETC CAN
 NOT BE VERIFIED OR REVIEWED AT THIS
 TIME. PLEASE SUBMIT ALL INFOMATION.
  
 64)NOTE: PLEASE SEE POOL WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT.
 PLEASE PLACE NOTE ON PLANS.
 IF NIGHT-TIME/AFTER DUSK WILL BE
 PROPOSED, SIGNED, SEALED PHOTOMETRICS
 WILL BE REQUIRED TO BE SUBMITTED TO PALM
 BEACH COUNTY HEALTH DEPT FOR REVIEW AND
 STAMPING.
 THIS WILL BE REQUIRED WITH POOL PERMIT.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE A
 DIRECT EFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2005-08-19 00:00:00PLANS STILL IN ELEC FOR REVIEW.
 UNITS, COMMON AREAS COMPLETED.
 SERVICE STILL NEEDS TO BE REVIEWED.
 REVIEW TO CONTINUE 8/22
 NOTES TO FOLLOW.
2005-08-18 00:00:001-SET OF SPEC BOOKS AND 1-SET OF MEP'S
 IN ELECTRIC FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By mamini Date 2006-01-13 Time 15:30 Rev Time 1.00
Received By mamini Date 2006-01-13 Time 15:30 Sent To  
Notes
2006-01-13 00:00:00PASSED:
  
 1. PLEASE NOTE THAT, WORK WITHIN PUBLIC
 R.O.W REQUIRES A SEPARATE PERMIT FROM
 PUBLIC UTILITIES, AT NO COST, PLEASE
 SUBMIT M.O.T WITH THE APPLICATION IF
 REQUIRED, 494-1086, WINDEL PALMER.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By mamini Date 2005-08-02 Time 13:41 Rev Time 1.00
Received By mamini Date 2005-08-02 Time 13:41 Sent To  
Notes
2005-08-02 00:00:00FAILED:
  
 1. PLEASE SUBMIT CALCULATION FOR
 PERVIOUS AND IMPERVIOUS, BUILDING AND
 TOTAL SITE AREA.
 2. OUR RECORD SHOWS THAT THERE IS A 4"
 WATER IN 12' ABANDONED ALLEY, PLEASE
 COORDINATE WITH PUBLIC UTILITIES AND
 ENGINEERING FOR REMOVAL, ATT;JIM GAMMON.
 3. EROSION AND SEDIMENTATION CONTROL
 DEVICES MUST BE INCLUDED IN CIVIL PLANS.
 4. ADDITIONAL FHYD. NEAR THE PROPOSED
 SITE MAY BE REQUIRED, PLEASE COORDINATE
 WITH FIRE DEPT. ATT; CAPT. MIKE
 WENNERGREN.
 5. PLEASE NOTE THAT CIVIL PLANS MUST BE
 APPROVED BY THE PUBLIC UTILITIES AND
 ENGINEERING FOR ALL THE CONNECTIONS AND
 THE FINAL CIVIL SHEET MUST BE SUBMITTED
 TO THE CONSTRUCTION SERVICES DEPT. FOR
 PERMITTING.
 6. PLEASE VERIFY THE PROPOSED ELEVATIONS
 FOR THE EXFILTRATION TRENCHES WITH
 REGARD TO WATERTABLE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By mwennerg Date 2006-10-06 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2006-10-06 Time 13:30 Sent To  
Notes
2006-10-06 00:00:00***PROVISO***
  
 PLEASE NOTE THAT ALL PREVIOUS FIRE
 REVIEW COMMENTS HAVE BEEN ADDRESSED,
 HOWEVER PLEASE SEE THE FOLLOWING FOR
 CLARIFICATION OR INFORMATION REQUIRED:
  
 2ND FIRE REVIEW COMMENTS
  
 COMMENT
 7) OK- PLANS SHOW A #3 REVISION HOWEVER
 NO DETAILS ARE FOUND IN TITLE BLOCK TO
 CORRULATE.
  
 9) OK- EXPLANATION UNDERSTOOD HOWEVER
 PLEASE ADD DIMENSION NOTE TO DRAWINGS.
  
 33) IN ADDITION TO CIRCUIT NUMBERS
 INDICATED, PLEASE ILLUSTRATE DEVICE
 LOCATIONS ON DRAWINGS.
  
 35) PLEASE NOTE THAT THE SEQUENCE OF
 OPERATIONS STILL INDICATE A SUPERVISORY
 SIGNAL. PLEASE CHANGE THAT NOTE TO READ,
 DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 44) OK- IT IS PRESUMED THAT YOUR
 RESPONSE TO #43 AND #44 IS BASED ON NFPA
 101, SECTION 7.3.3.1 REFERENCING 0.2"
 PER PERSON. PLEASE VERIFY.
  
 48) PLEASE ADD NOTE TO SHT LS0.01 AND
 LS0.02 AS INDICATED IN YOUR RESPONSE
 LETTER.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-12-16 Cont ID  
Sent By mcarsill Date 2005-12-16 Time 08:59 Rev Time 0.00
Received By mcarsill Date 2005-12-16 Time 07:33 Sent To  
Notes
2005-12-16 00:00:001. MORE DETAILS REQUIRED ON THE ATRIUM.
 THIS WOULD INCLUDE FIRE SEPERATIONS,
 DEFINED AREAS, EXITING, AND MECHANICAL
 SYSTEMS. VOLUME CALCULATIONS NEEDED.
  
 2. DOOR MARKS MISSING FROM LEVEL THREE,
 PAGE A1.04C.
  
 3. ELEVATOR SHAFTS (TOPS) ON LSO.10 DO
 NOT DISPLAY ANY FIRE RATING.
  
 4. EXIT SIGNS APPEAR TO BE MISSING ON
 PAGE LSO.05A.
  
 5. AN ENGINEERING ANALYSIS WILL BE
 REQUIRED FOR THE NEW ATRIUM.
  
 6. SITE PLAN PAGE A0.03 ONLY DISPLAYS
 THREE FIRE HYDRANTS. THIS IS NOT
 SUFFICIENT FOR THE SIZE AND COMPLEXITY
 OF THIS PROJECT.
  
 7. TWO SIDE SWINGING DOORS LOCATED ON
 PAGE A1.02C APPEAR TO BE DIRECTLY NEXT
 TO CURBING.
  
 8. PLEASE HATCH AREA OF ATRIUM.
  
 9. PLEASE EXPLAIN BUS DUCT STORAGE ROOM
 DOORS. THEY APPEAR TO OPEN TOO FAR INTO
 EXIT CORRIDOR.
  
 10. PLEASE VERIFY ATRIUM SMOKE SYSTEM
 FANS, CFM'S, ETC. THERE APPEARS TO BE
 SOME DISCREPANCY WITH INFORMATION.
  
 11. COLUMN WAS OBSERVED DIRECTLY INFRONT
 OF DOOR LEADING INTO CORRIDOR FOR HEALTH
 CLUB, C-101.
  
 12. PLEASE DISPLAY EXIT ROUTES FROM
 STORAGE 00.
  
 13. PARKING CARS, COLUMN, AND SHEER WALL
 OBSERVED.
  
 14. PLEASE EXPLAIN MEZZANINE. PLEASE
 PROVIDE PRESCRIPTIVE REQUIREMENTS
 REGARDING MEZZANINE.
  
 15. PLEASE PROVIDE DETAILS ON GLASS WALL
 SYSTEM AROUND MONUMENTAL STAIR.
  
 16. POOL EQUIPMENT ROOM 00 WILL BE
 CONSIDERED HAZARDOUS UNTIL SUFFICIENT
 INFORMATION IS PROVIDED.
  
 17. JANITOR CLOSET AND CLOSET DOOR NEAR
 KICHEN C0405 OPPOSE ONE ANOTHER.
  
 18. PLEASE IDENTIFY SMALL AREA WITH DOOR
 NEAR TOWER 7 ELEVATOR LOBBY.
  
 19. WHAT INTERPRETATION IS BEING USED
 FOR DOORS OPENING ONTO EXIT ACCESS
 CORRIDORS. PLEASE SEE TELLCOM CLOSETS.
  
 20. ALL NEW ELEVATORS SHALL COMPLY WITH
 ASME A17.1 SAFETY CODE FOR ELEVATORS AND
 ESCALATORS.
  
 21. EGRESS SIGN MISSING NEAR STAIR
 LOCATED AT G25 LOCATION ON PAGE
 A1.05S-2.
  
 22. MORE DETAILS NEEDED FOR THE TWO HOUR
 RATED SLIDING DOORS SHOWN IN FRONT OF
 ELEVATORS. HOW WOULD FIRE RESCUE ACCESS
 BEYOND THESE DOORS.
  
 23. ON ELEVATION DRAWINGS A REVISION IS
 SHOWN FOR ITEM # 4 HOWEVER ON PAGE
 A2.02-N ITEM # 7 IS DEPICTED.
  
 24. WILL ANY COMBUSTIBLE MATERIALS BE
 STORED OR HANDELED UNDERNEATH THE PORTE
 COCHERE.
  
 25. PLEASE ILLUSTRATE DISTANCES OF FIXED
 GLASS ANGLED WINDOWS FOR THE ATRIUM
 ENCLOSURE TO TOWER WINDOWS. IT IS
 DIFFICULT TO DETERMINE. PLEASE SEE PAGE
 A3.05-A.
  
 26. WHAT FIRE PROTECTION IS PLANNED FOR
 THE CABANA'S.
  
 27. DUCTS OVER FOUR FEET WIDE SHALL HAVE
 FIRE SPRINKLER PROTECTION BELOW THEM.
  
 28. UNIT DOOR AND HARDWARE SCHEDULE DOES
 NOT ILLUSTRATE THAT THE GALLERY DOOR TO
 THE STAIRWELL IS FIRE RATED. PLEASE
 EXPLAIN RATIONALE. PLEASE SEE PAGE
 A4.02.
  
 29. NO FIRE RATING NOTED ON UNIT DOOR
 AND HARDWARE SCHEDULE LOCATED ON PAGE
 A4.08.
  
 30. SAME CONDITION EXISTS ON PAGES
 A4.09-20.
  
 31. PRESSURE REGULATING VALVES SHOWN ON
 PAGE SP-34. WILL THESE DEVICES BE
 FACTORY SET OR FIELD SET. FACTORY SET
 ONES ARE PREFERRED.
  
 32. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUM.
  
 33. PLEASE ILLUSTRATE EMERGENCY LIGHTING
 ON RECREATIONAL PLAZA.
  
 34. SINCE EXITING IS DIRECTED FROM THE
 GARAGE TOWARDS THE FUTURE TENANT
 BUILD-OUT AREA ON LEVEL ON PAGE E-03,
 PLEASE EXPLAIN HOW THIS WILL WORK.
  
 35. SEQUENCE OF OPERATIONS PAGE AC-38
 NEEDS TO BE REVISED. DUCT SMOKE
 DETECTORS SHALL INITIATE AN ALARM NOT A
 SUPERVISORY SIGNAL.
  
 36. ELECTRONIC SWITCHES, CHAINS AND
 LOCKS ARE REQUIRED ON THE FIRE LINE
 BACKFLOW DEVICE.
  
 37. ANY SECURITY DEVICES PLANNED SHALL
 NOT INTERFERE WITH ANY REQUIRED EXITING
 FROM THE BUILDING. PLEASE REVIEW SPECIAL
 LOCKING ARRANGEMENTS IN THE LIFE SAFETY
 CODE, 2003 EDITION.
  
 38. PLEASE PROVIDE CODE REQUIREMENTS FOR
 SECURITY DEVICES ON THE APPROPRIATE
 PAGES.
  
 39. PLEASE EXPLAIN ELEVATOR CONTROL
 PROGRAMMING. ARE THERE GOING TO BE ANY
 SPECIAL FEATURES REGARDING THE
 ELEVATORS.
  
 40. PLEASE PROVIDE FLAME SPREAD FOR CORK
 WALLCOVERINGS AND FLOOR, PAGE ID3.04.
  
 41. ADDITIONAL FIRE EXTINGUISHERS APPEAR
 TO BE REQUIRED. LARGE MECHANICAL AND
 SERVICE ROOMS APPEAR TO BE ABSENT OF
 THEM. NO FIRE EXTINGUISHERS APPEAR TO BE
 SHOWN ON THE OVERALL ROOF PLAN LS0.10.
  
 42. COULD NOT LOCATE FIRE EXTINGUISHERS
 LOCATIONS FOR LONG CORRIDORS SHOWN ON
 PAGE LSO.06.
  
 43. STAIR # 8B DISPLAYS 200 BUT IF THE
 DOOR CAN ONLY ACCOMODATE 140 PERSONS HOW
 DOES THIS WORK.
  
 44. STAIRS 10,11,12,AND 13 SHOW LARGE
 OCCUPANT LOADS BUT DOORS CAN ONLY
 SUPPORT 140 PERSONS. HOW DOES THIS WORK.
  
 45. WINDOWS APPEAR TO BE LOCATED
 DIRECTLY OPPOSITE OF EXIT STAIR DOORS ON
 THE RECREATIONAL DECK. WHAT PROTECTION
 IF ANY IS PLANNED.
  
 46.STAIR PRESSURIZATION NOTES NEED TO BE
 INCORPORATED ONTO THE LIFE SAFETY PLANS.
 PLEASE PROVIDE PRESCRIPTIVE
 REQUIREMENTS.
  
 47. THE STORE THAT IS PLANNED A SEPERATE
 TENANT OR WILL BE ANCILLARY TO THE REST
 OF THE BUILDING.
  
 48. ALL DOORS FOR EXIT ACCESS CORRIDORS
 SHALL BE SELF-CLOSING AND SELF-LATCHING.
  
 49. LISTED GUICK RESPONSE OR LISTED
 RESIDENTIAL FIRE SPRINKLERS SHALL BE
 USED IN LIVING AREAS.
  
 50. PLEASE REVIEW ALL EXIT ACCESS,
 EXITING, AND EXIT DISCHARGE CALCULATIONS
 TO ENSURE THEY ARE PROPERLY CALCULATED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 12:30 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 12:30 Sent To  
Notes
2005-09-14 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MORE DETAILS AND
 LOCATIONS OF ALL GATES. C-1, C-2.
  
 2) PLEASE CORRELATE LOCATIONS OF FIRE
 HYDRANTS ON APPROPRIATE SHEETS.
  
 3) PLEASE PROVIDE DETAILS AND FLAME
 SPREAD INFORMATION ON TENSILE FABRIC FOR
 CANOPY.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR GATES.
  
 5) ALL CONSTRUCTION, ALTERATION AND
 DEMOLOITION TO COMPLY WITH NFPA-241.
 CONSTRUCTION DEBRIS TO BE REMOVED DAILY.
  
 6) STAIRS SHALL BE MAINTAINED DURING
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDINGS REACH 3 STORIES OR 30' IN
 HEIGHT.
  
 8) ALL CUTTING/WELDING TO COMPLY WITH
 NFPA 51-B.
  
 9) ELECTONIC SWITCHES, CHAIN AND LOCK IS
 REQUIRED ON DOUBLE CHECK DETECTOR
 ASSEMBLY.
  
 10) WORK TO COMPLY WITH HIGHRISE
 REQUIREMENTS IN ACCORDANCE WITH FBC AND
 NFPA 101, SECTION 11.
  
 11) TACTILE SIGNAGE IS REQUIRED IN
 STAIRWELLS.
  
 12) KNOX BOXES WILL BE REQUIRED.
  
 13) LOCKING CAPS ARE REQUIRED FOR FIRE
 DEPARTMENT CONNECTIONS.
  
 14) EMERGENCY LIGHTING SHALL BE PROVIDED
 IN EXIT PASSAGEWAYS. SHT LS0.01
  
 15) THE EXIT SIGN APPEARS TO LEAD
 PERSONS TO THE TRASH ROOM. SHEET LS0.02
  
 16) EXIT SIGNS TO BE CLEAR/VISIBLE AND
 NOT TO EXCEED 100' APART.
  
 17) CLARIFY GATE CONTROL AT STAIR #13.
 SHT LSO.02
  
 18) PLEASE IDENTIFY ALL STRETCHER
 ACCESSIBLE ELEVATORS WITH APPROPRIATE
 SIGNAGE.
  
 19) PLEASE IDENTIFY THE MARKING AROUND
 THE ATRIUM. SHT LSO.03
  
 20) AN EXIT SIGN IS SHOWN IN FRONT OF A
 PARKING SPACE? SHT LSO.04
  
 21) ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 22) MACHINE/EQUIPMENTROOMS SHALL HAVE
 APPROPRIATE SIGNS INDICATING NO STORAGE.
  
 23) EXIT SIGNS APPEAR TO BE MISSING FROM
 A STORAGE AREA. SHT LSO.04
  
 24) PLEASE IDENTIFY ALL POOL CHEMICALS
 IN POOL EQUIPMENT ROOM. LSO.04
  
 25) PANIC HARDWARE IS REQUIRED ON DOORS
 IN AREAS THAT SERVE AN OCCUPANT LOAD
 GREATER THAN 100.
  
 26) OCCUPANT LOAD FACTORS DON'T APPEAR
 TO CORRELATE WITH TOTAL PLAZA LOAD.
  
 27) WHAT COOKING ACTIVITIES ARE PLANNED
 FOR THE KITCHEN?
  
 28) PLEASE INDICATE ON THE PLANS THAT
 APPROPRIATE WALKING SURFACES ARE TO BE
 SLIP RESISTANT.
  
 29) TACTILE SIGNAGE IS MISSING ON SHT
 LSO.05.
  
 30) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 31) PLEASE PROVIDE FINISH CLASSIFICATION
 FOR FLOOR SURFACES.
  
 32) ALL REQUIRED STAIRWELLS SHALL HAVE
 STANDPIPE CONNECTIONS WITH 2 1/2" - 1
 1/2" REDUCERS.
  
 33) EXIT SIGNS ARE MISSING NEAR STAIRS
 1-A AND 2-A. SHT LSO.08
  
 34) SMOKE DETECTORS SHALL BE INSTALLED A
 MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 35) PLEASE ILLUSTRATE ATRIUM
 REQUIREMENTS. SHT 1.02 C
  
 36) PLEASE PROVIDE MORE DETAILS ON
 AUTOMATIC DOORS.
  
 37) PLEASE EXPLAIN EGRESS GATE. SHT 1.02
  
 38)PLEASE EXPLAIN WHERE FANS WILL
 EXHAUST. PROVIDE DIMENSIONS WHERE
 APPLICABLE. SHT A 1.02 NW
  
 39) PARKING GARAGE TO COMPLY WITH NFPA
 88A AND FBC.
  
 40) PLEASE PROVIDE STRENGTH REQUIREMENTS
 FOR STEEL CABLE BARRIER. SHT A 1.02
  
 41) PLEASE PROVIDE HEIGHT AND OVERALL
 DIMENSIONS FOR ATRIUM.
  
 42) 2A- 10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' APART.
  
 43) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR GLASS GUARDRAIL. SHT A
 1.03 C
  
 44) ALL FIRE DOORS AND WINDOWS TO COMPLY
 WITH NFPA 80 AND FBC.
  
 45) TRASH CHUTES TO COMPLY WITH NFPA 82
 REQUIREMENTS.
  
 46) PLEASE PROVIDE OCCUPANT LOAD/FIXTURE
 PLAN FOR HEALTH CLUB. SHT 1.04
  
 47) PLEASE PROVIDE FLAME SPREAD DETAILS
 FOR CABANA MATERIAL.
  
 48) PLEASE PROVIDE DETAILS AND PRODUCT
 APPROVALS FOR 1 HOUR RATED GLASS SYSTEM.
 SHT A 1.04 C
  
 49) PLEASE PROVIDE A FIRE SAFETY PLAN TO
 THE BUREAU OF FIRE PREVENTION PRIOR TO
 CONSTRUCTION.
  
 50) NO STORAGE IS PERMITTED IN EXIT
 VESTIBULES.
  
 51) PLEASE EXPLAIN TYPES OF BOILERS THAT
 ARE PLANNED.
  
 52) FIRE ALARM STROBES ARE REQUIRED IN
 ALL COMMON BATHROOMS.
  
 53) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS.
  
 54) HANDRAILS ARE MISSING ON STAIRS NEAR
 THE ELEVATED PLANTER AREA. SHT 1.05
  
 55) NO GAS OR BARBECUE GRILLES PARMITTED
 TO BE USED ON BALCONIES.
  
 56) ALL APPROPRIATE FIRE SEPARATIONS
 SHALL BE GIVEN PRIORITY DURING
 CONSTRUCTION.
  
 57) ADDRESS NUMBER IS REQUIRED ON
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 58) PLEASE EXPLAIN OPEN STORAGE IN
 PARKING GARAGE. PLEASE INCLUDE CODE
 REFERENCE THAT ALLOWS THIS ARRANGEMNENT.
  
 59) ALL VERTICAL SHAFTS ARE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 60) BUILDING IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED.
  
 61) STAIRS THAT ARE SUBJECT TO INCLEMENT
 WEATHER SHALL BE SLIP RESISTANT.
  
 62) COOLING TOWER TO COMPLY WITH NFPA
 214.
  
 63) ALL PROPOSED SOFFITTS SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY
 REQUYIRED FIRE SPRINKLER HEADS.
  
 64) ALL RATED FIRE DOORS SHALL BE
 EQUIPED WITH UL LISTED CLOSERS WHICH
 SHALL CAUSE THE DOORS TO POSITIVELY
 LATCH.
  
 65) FIRE RATING IS MISSING FROM THE DOOR
 SCHEDULE. SHT A 4.08. PLEASE VERIFY ON
 OTHER SHEETS.
  
 66) ARE THE AC CLOSET DOORS NOTED IN THE
 HALLWAY RATED?
  
 67) THE FIRE ALARM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 68) THE FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 69) MINIMUM OF 2 FDC'S ARE REQUIRED FOR
 HIGHRISES.
  
 70) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 71) PLEASE EXPLAIN NOTE #1 REGARDING
 SMOKE VENTS.
  
 72) PLEASE PROVIDE MORE INFORMATION AND
 FLAME SPREAD FOR FABRIC PANELS. SHT A
 7.01.
  
 73) PLEASE SHOW ALL FDC'S ON PLANS. ALL
 SHEETS DON'T CORRELATE.
  
 74) FDV CABINETS IN THE PARKING GARAGE
 TO REMAIN ACCESSIBLE AND UNOBSTRUCTED AT
 ALL TIMES.
  
 75) WHEN SUBMITTING FIRE SPRINKLER
 DRAWINGS, PLEASE ILLUSTRATE ALL AREAS OF
 COVERAGE ON SHEETS.
  
 76) LIVING UNITS DON'T SHOW SPRINKLER
 COVERAGE ON ALL APPROPRIATE SHEETS.
  
 77) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND GENERATOR.
  
 78) PLEASE REFERENCE NEWEST EDITIONS,
 2002 AND 2003 ON SHT SP-34. NFPA 13, 14,
 20 24.
  
 79) FIRE PROTECTION HYDROSTATIC TESTS TO
 BE AT 200 PSI FOR 2 HOURS. SHT SP- 34
 #9.
  
 80) ARE CO DETECTORS TIED INTO THE FIRE
 ALARM SYSTEM OR LOCAL AV DEVICE ONLY.
  
 81) EXIT SIGNS APPEAR TO BE MISSING AT
 SOME STAIRWELLS.
  
 82) EXITS SIGNS ARE MISSING FROM EXIT
 PASSAGEWAY NEAR TOWER #3.
  
 83) SMOKE CONTROL PANEL SHALL DISPLAY A
 GRAPHIC REPRESENTAION OF THE BUILDING
 EQUIPMENT. HOA SWITCHES ONLY IS NOT
 PERMITTED.
  
 84) SMOKE DETECTORS IN LIVING UNITS
 SHALL BE INTERCONNECTED.
  
 85) DUCT SMOKE DETECTORS WHERE PROVIDED
 SHALL INITIATE A FIRE ALARM CONDITION
 WHEN ACTIVATED PER LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 11:46 Sent To  
Notes
2006-07-25 00:00:00TO "COMM" BD#9
2006-06-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-04 Time 14:33 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 14:33 Sent To  
Notes
2005-11-15 00:00:00TO "COMM" BD#38/PLANS ON RACK/12 ROLLS
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-16 Cont ID  
Sent By rbrown Date 2005-10-06 Time 16:32 Rev Time 0.00
Received By rbrown Date 2005-07-25 Time 14:11 Sent To  
Notes
2005-07-26 00:00:00TO "COMM" BD#6/PLANS ON RACK/2 ROLLS AND
 BOOKS
2005-07-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-09-23 Cont ID  
Sent By hmoser Date 2006-09-23 Time 12:25 Rev Time 0.00
Received By hmoser Date 2006-09-23 Time 12:25 Sent To  
Notes
2006-09-23 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 104.2.1.3
 CHAPTER ONE AMENDMENTS 2001 QUALITY OF
 PLANS PAGES AC-1 - AC-9.
 2) GARAGE VENTLATION MUST BE TIED IN TO
 EMERGENCY POWER,SO FANS CAN RUN WHEN
 POWER FAILS.
 3) PAGE AC-12 NEED RETURN AIR FOR
 ELEVATOR LOBBY TOWER # 7.
 4) PAGE AC-12 ALL TRASH ROOM A/C MARKED
 # 10,0N HEAT PUMP SCHEDULE A/C ARE
 MARKED 33 - 40 PAGE AC-36.
 5) PAGE AC-01 PLEASE REMOVE EF-38 FRON
 PLANS IF NOT BEING USED.
 6) PAGE AC-12 PLEASE PROVIDE DUCT SIZE
 FOR A/C # 9 BEFOR 6X6 DUCT.
 7) PAGE AC-10 CAN NOT FIND DUCT
 CONTINUATION ON PAGE AC-01.
 8) PAGE AC-2 PLANS AND DRAWING NOTES DO
 NOT MATCH.
 9) PAGE AC-13 AND A LOT OF THE PLANS
 HAVE PRINT ON TOP OF PRINT CAN NOT READ
 PLANS.
 10) PAGE AC-13 SMOKE EVAC.?
 11) PAGE AC-13 PLEASE REFER TO DASHED
 LINES FOR RETURN AIR PLENUM.
 12) PAGE AC-14 PLEASE INDECATE SIZE OF
 RETURN AIR DUCT FOR A/C # 15
 13) PAGE AC-14 PLEASE INDECATE DUCT SIZE
 OF FLEX OFF SUPLY PLENUM ON A/C # 15.
 CAN WE PLEASE SET UP A MEETING AFTER
 OCTOBER 2 TO GO OVER THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-12-20 Cont ID  
Sent By pkrauss Date 2005-12-09 Time 13:44 Rev Time 0.00
Received By pkrauss Date 2005-12-09 Time 07:39 Sent To  
Notes
2005-12-09 00:00:00DENIED:
 RESPONSE TO REVIEW COMMENTS BY HAROLD
 MOSER DATED 8-25-05:
 COMMENT #4- PLEASE SHOW SEQUENCE OF
 OPERATION FOR SF35 AND SF37.RESPONSE
 REFERENCES PLAN SHEET AC-38, SEQUENCE OF
 OPERATION.PLEASE NOTE ACCORDING THE
 FAN SCHEDULE LOCATED ON PLAN SHEET
 AC-28, SF37 IS NOT IDENTIFIED.
  
 COMMENT # 4 PLEASE SHOW SEQUENCE OF
 OPERATION OF SF-35 & SF-37.PLEASE
 NOTE, SF-37 IS NOT INDICATED ON THE FAN
 SCHEDULE (PLAN SHEET AC-28).
  
 COMMENT #6 GARAGE VENTLATION, RESPONSE
 REFERENCES 2001 FMC 403.4 & 403.4.1.
 PLEASE NOTE AS QUOTED IN RESPONSE THIS
 APPLICATION IS FOR A PUBLIC GARAGE.
 WILL ANYONE OTHER THAN TENANTS &
 EMPLOYEES BE ALLOWED TO PARK AT THIS
 FACILITY?SHOULD USE OF THE PARKING
 GARAGE BE EXCLUSIVE TO THIS BUILDING AND
 ITS TENANTS IT IS NOT CONSIDERED A
 "PUBLIC GARAGE".
  
 UNIT COMMENTS -
 COMMENT #1RESPONSE INDICATES DOORS ARE
 TO BE PAINTED WITH INTUMESCENT PAINT.
 THIS IS NOT AN APPROVED METHOD FOR NEW
 CONSTRUCTION.PLEASE INQUIRE WITH DOOR
 MANUFACTURER FOR COMPLIANCE WITH THE
 25/50 FLAME SPREAD INDEX & SMOKE
 DEVELOPED INDEX. WHEN TESTED IN
 ACCORANCE WTIH ASTM E 84 (2001 FMC
 602.2.1).
  
 COMMENT #3 BALANCED AIR RETURN, RESPONSE
 INDICATES TRANSFER DUCTS WERE REVISED.
 VARIOUS TRANSFER DUCTS DO NOT COMPLY
 WITH THE REQUIREMENT OF 2001 FBC 601.4
 EXCEPTION 1 & 3.EXAMPLE; PLAN SHEET
 AC-16 UNIT D THE INDICATES A 14" X 6"
 FOR THE "TOTAL" SUPPLY AIR INTO THE
 MASTER SUITE WHICH WOULD REQUIRE A 25" X
 6" RETURN TRANSFER DUCT.PLEASE REVISE
 ALL UNITS IN WHICH THIS OCCURS.
  
 NEW COMMENTS:
 1.PLEASE PROVIDE CALCULATIONS FOR THE
 ATRIUM.PLEASE PROVIDE TOTAL VOLUME.
  
 2.PLEASE PROVIDE A DETAIL FOR THE
 ATRIUM SECTION ONLY (ELEVATION).THIS
 INCLUDES ANY CORRIDOR OR ADJACENT SPACES
 THAT A CONSIDERED PART OF THE ATRIUM IN
 ACCORDANCE WITH 414.5 OF THE 2001 FBC.
  
 3.PLAN SHEET AC-01 INDICATES GARAGE
 EXHAUST FANS TERMINATING AT THE 1ST
 LEVEL.ARCHITECTURAL PLAN A2.04-NW
 INDICATES THE WINDOWS ON LEVEL 3 (R03) &
 4 (R04) ARE TO BE FIXED GLASS.PLANS DO
 NOT INDICATE THIS AS "TYPICAL" AND DO
 NOT SPECIFY IF THE WINDOWS AT LEVEL 2
 ARE FIXED.PER 2001 FMC 401.5, EXHAUST
 SHALL BE LOCATED A MINIMUM OF 10FT FROM
 LOT LINES & WHERE OPENINGS FRONT ON A
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF STREET.
  
 4.INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10FT FROM ANY NOXIOUS
 CONTAMINANT, 2001 FMC 401.5.1.
  
 5.PLAN SHEET AC-13 LOBBY FLOOR PLAN
 INDICATES SF-34 & ON THE EQUIPMENT
 SCHEDULE IT INDICATES SF-34 FAN WILL NOT
 BE USED.PLEASE CLARIFY.
  
 6.PLAN SHEET AC-13 THE MEZZANINE FLOOR
 PLAN INDICATES 66" X 14" UP TO SF- ON
 ROOF.IT ALSO INDICATES A 22" X 12"
 DOWN TO THE 1ST FLOOR.PLEASE INDICATE
 IF THIS IS A SHAFT.PLEASE CLARIFY IF
 THIS IS FOR THE MAKE-UP AIR FOR THE
 ATRIUM OR OUTSIDE AIR FOR THE A/C
 SYSTEM.PLEASE NOTE, PER 2001 FMC 607.4
 DUCTS EXTENDING THROUGH MORE THAN ONE
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE.FIRE DAMPERS WILL BE
 REQUIRED WHERE DUCTS PENETRATE THE RATED
 ENCLOSURE.PLEASE IDENTIFY ALL FIRE &
 COMBINATION DAMPERS, 2001 FMC 607.6.
  
 7.PLAN SHEET AC-16 NOTE #2 SPECIFIES
 "VENTLESS" DRYERS, PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA.
  
 8.LIFE SAFETY & MECHANICAL PLANS
 (AC-3) REFER TO A "MEZZANINE" LEVEL
 WHEREAS THE ARCHITECTURAL PLANS REFER TO
 THIS AREA AS "LEVEL 3", PLEASE
 CORRELATE.
  
 9.ARCHITECTURAL PLAN (A0.005)
 PARTITION/WALL TYPES, DETAILS INDICATE
 RATING OF PARTITION/WALL IS TO BE
 INDICATED UNDER THE WALL TYPE.THIS IS
 NOT REFLECTED ON THE PLANS.
  
 10. PROVIDE SEQUENCE OF OPERATION OF THE
 SMOKE EVAC FOR THE ATRIUM.
  
 11. PLAN SHEET AC-38 THE SEQUENCE OF
 OPERATION FOR FLOORS 2 THROUGH 18
 INDICATE PRESSURIZATION BUT DOES NOT
 INDICATE THE MITIGATION OF SMOKE.SMOKE
 CONTROL SHALL COMPLY WITH ONE OF THE
 ITEMS INDICATED IN 2001 FBC 412.5.
  
 12. PLEASE ANNOTATE ON THE PLANS,
 DISTANCE FROM THE EXHAUST TERMINATIONS
 (I.E. GENERATOR, GARAGE, ETC) FROM
 WINDOWS, DOORS, FRESH AIR INTAKES,
 WALKWAYS, LOT LINES & ADJACENT
 BUILDINGS.SHOW COMPLIANCE WITH 2001
 FMC 401.5, 401.5.1 & 501.3.
  
 PLEASE NOTE RESPONSE TO COMMENTS MAY
 CREATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By hmoser Date 2005-08-24 Time 14:18 Rev Time 0.00
Received By hmoser Date 2005-08-24 Time 14:18 Sent To  
Notes
2005-08-24 00:00:00PLAN DENIED
 1) PAGE AC-6 AND AC-7 NEED SMOKE FIRE
 DAMPERS AT RATED CHASE.
 2) PAGE AC-9 NEED DUCT DETECTORS ON ALL
 PACKAGE UNITS OVER 2000 CFM.SECTION
 606.2.1 FBC(M)
 3) PAGE AC-9 PLEASE SHOW MOUNTING DETAIL
 ON A/C DUCT STANDS.
 4) PLEASE SHOW SEQUENCE OF OPERATION FOR
 SF.35 AND SF.37.
 5) PLEASE REFER TO SECTION 501.5 METAL
 DUCT.
 6) GARAGE VENTILATION MUST RUN
 CONTINUOUSLY.PLEASE REMOVE CO2 SENCERS
 7)PAGE AC-32PLEASE REMOVE SMOKE
 DETECTORS FROM
 SF9,15,17,11,13,19 STAIR RISER
 UNITS
 1) PLEASE INDECATE TYPE OF DOORS USED ON
 A/C CLOSITS ON PLANS.
 2) A/C UNITS OVER 2000 CFM INCLUDING
 COMBINED AIRWITH TWO A/C UNITSMUST
 HAVE FAN SHUTDOWN SECTION 606.2.1
 3) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.
 4) DRYER BOOSTER FANS MUST BE SUBMITED
 THROUGH ALTERNATIVE METERALS ,METHODS.
 5) NEED SMOKE FIRE DAMPERS IN ALL DUCT
 GOING THROUGH RATED WALLS IN LOBBEYS.
 6) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 7) PLEASE REFER TO SECTION 602.2.1
 MATERALS EXPOSED WITHIN PLENUMS.
 8) PLEASE REFER TO SECTION 401.6 OUT
 DOOR OPENING PROTUCTION (BATHROOM
 EXHAUST CAPS NEED SCREENS)
 9) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR #3 HABITABLE ROOMS.
 10) PAGE AC-20 RETURN AIR GRILL IS NOT
 IN RETURN AIR PLENUM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-07-29 Cont ID  
Sent By kstevens Date 2006-07-29 Time 17:33 Rev Time 0.00
Received By kstevens Date 2006-07-05 Time 19:01 Sent To  
Notes
2006-07-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEWS:
  
 ****************************************
 A. COMMENTS FROM PREVIOUS REVIEW: NO
 COMMENT RESPONSES TO REVIEW WERE NOT
 SUBMITTED. COMMENT NUMBERS SHALL REMAIN
 THE SAME AS FIRST REVIEW UNTIL ADDRESSED
 ****************************************
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO
 INFORMATION ON THE SEAL HAS BEEN
 IMPRESSED ON THE SHEETS AS REQUIRED BY
 FAC 61G1-16.001. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 SHALL APPEAR ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) & (6) AND FS 481.219,
 481.2055.(NO RESPONSE, SHEETS NOT
 RESUBMITTED. PLEASE CLARIFY)
 ****RESPONSE NOTED, BUT PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT AND CA#
 STILL NOT INDICATED. SEE ATTACHED SHEET
 FROM DBPR WEBSITE.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW
 BACKING & OPENING DIMENSIONS FOR THE W/C
 OPENINGS FOR ADDITIONAL BATHROOMS PER
 BATHROOM REQUIREMENTS PAGE 7.35. THIS
 WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS'
 SHT A4.03 UNIT 'BS', SHT A4.04 UNIT
 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06
 UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15
 UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20
 UNIT 'KN', SHT A4.22 UNIT 'LS', SHT
 A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2',
 SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT
 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28
 UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT
 A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT
 'QN', SHT A4.32 UNIT 'RN', SHT A4.33
 UNIT 'RS', SHT A4.34 UNIT 'SN', SHT
 A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS',
 SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT
 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT
 A4.31.1 UNIT 'STSM'. (NO RESPONSE, NOT
 ADDRESSED. ADDITIONAL BATHROOMS IN THE
 UNIT ARE EXEMPT -ONLY- FROM MANEUVERING
 AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES)
 ****RESPONSE NOTED, BUT DIMENSIONS SHALL
 BE SHOWN IN EACH UNIT, OR INDICATE IN
 EACH UNIT WHERE THE DIMENSIONS SHALL BE
 LOCATED.
  
 13.OK
 14. NOT USED
 15. NOT USED
  
 16. SHTS A4.38, A4.39, & A4.40 ENTRY
 LEVEL TO BE COVERED PER FHA. SUBMIT
 DETAILS FOR BATHROOMS. (RESPONSE NOTED,
 BUT THE FIRST FLOOR SHALL HAVE A
 ACCESSIBLE PATH TO THE ELEVATORS).
  
 17. GROUND FLOOR CONFERENCE ROOM SINKS
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION SHALL BE SHOWN:
 A. 11-4.24.5 CLEAR FLOOR SPACE, CABINET
 DOORS SHALL BE REMOVED, NO DOORS IN THE
 CLEAR FLOOR SPACE.
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
 18. OK
 19. OK
 20. NOT USED
 21. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT INDICATE WHERE
 THE DETAIL CAN BE LOCATED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE POOL/SPA
 HEATER SHEETS HAVE NOT BEEN FOUND.
  
 E. (NEW COMMENT) PIPE SIZE INCORRECT AT
 LAST SPA HEATER. 1-1/4" REQUIRED. 1-1/2"
 REQUIRED FOR 2 SPA HEATERS. 2" REQUIRED
 FOR 3 SPA HEATERS.
  
 22.(INFORMATIONAL)
  
 23. ALL FLOOR PLAN SHEETS, SHOW THE
 LOCATION & NUMBER OF EACH RISER THRU THE
 BUILDING ON EACH FLOOR PLAN AND EACH
 LEVEL. SECTION 104.2.1. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE RISERS ARE
 ONLY SHOWN ON THE GROUND FLOOR. WHERE IS
 LEVEL 3?
  
 24.OK
  
 25. SHT P-2 SHOW THE PIPING FOR ALL
 TRENCH DRAINS WITH PIPE SIZES. THIS
 SHALL BE REFLECTED ON THE STORM RISER
 DIAGRAM. SECTION 104.3.1.1. (NO
 RESPONSE, NOT ADDRESSED FOR TRENCH DRAIN
 AT COL. LINE G/01).
 ****RESPONSE NOTED, BUT PIPING NOT SHOWN
 ON P-2 OR P-68
  
 26. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD. #3434. PLEASE CONTACT LYNN
 MASSON AT (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT APPROVAL
 REQUIRED BY LYNN MASSON FOR LOCATION AND
 MAINTENANCE.
  
 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL
 PIPE SIZES. RECALCULATE ADDITION ON SOME
 RWL'S, INDICATE RWL RISER NUMBERS, 3"
 OVERFLOW SHOWN CONNECTING TO PRIMARY
 SYSTEM AT COL. 24 BETWEEN COLS, A&B.
 PLEASE CLARIFY. SECTION 104.2.1. -(SHOW
 ALL SECONDARY ROOF DRAINS, WITH PIPE
 SIZES, SF, ETC.). (NO RESPONSE NOT
 ADDRESSED).
 ****RESPONSE NOTED, ADDITION STILL NOT
 CORRECT IN SOME PLACES. RECHECK ALL
 ADDITION OF THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. - RWL'S ARE
 NOT NUMBERED. THIS IS REQUIRED TO TRACK
 THE RISERS THRU THE BUILDING. -
 SECONDARY DRAINS ON THE 5TH FLOOR ARE
 SHOWN IN THE PLANTERS FOR SOME, AND IN
 OPEN AREAS FOR OTHERS. PLEASE CLARIFY.
  
 28. OK
 29. OK
 30. OK
  
 31. SHT P-7 SANT. PIPING NOT ALLOWED IN
 THE EGRESS STAIRWAY. NFPA-101 SECTION
 7.1.3.2.1(6). (NO RESPONSE, NOT
 ADDRESSED).RESPONSE NOTED, BUT THE
 PIPING SHALL BE POURED IN SOLID
 CONCRETE, OR DRAIN SHALL BE DESIGNED FOR
 THE VOID.
  
 32. OK
 33. OK
 34. OK
 35. SHT P-9 THE FOLLOWINGPIPING
 LAYOUTS DO NOT REFLECT RISER DIAGRAMS
 44, 47, 42, 40, 39, 20, & 4. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER #4 STILL
 DOES NOT REFLECT THE FLOOR PLAN.
  
 36. SHT P-13 PIPING FOR THE DWV AND
 STORM SYSTEMS NOT APPROVED IN EGRESS
 STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6)
 AND SECTION 1006.1.3.1. (METHOD OF
 ADDRESSING NOT APPROVED. SEE BUILDING
 PLAN REVIEW COMMENT #38).
 ****RESPONSE NOTED, BUT THE PIPING WILL
 HAVE TO BE IN A SOLID POUR, OR A DRAIN
 FOR THE VOID WILL BE REQUIRED.
  
 37. P-14. CONDENSATE IS INDICATED AS 5'
 SEPARATION FOR THE SUPPORTS. INDICATE
 MATERIAL FOR CONDENSATE PIPING. IF PVC,
 MAXIMUM 4' SEPARATION OF SUPPORTS PER
 TABLE 305.5. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 140 MPH WIND LOAD FOR
 SUPPORTS. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT S RESIDENTIAL
 TOWER ROOF LEVEL, NO DETAIL INDICATED.
  
 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON
 RISER DIAGRAM 56, 59A, 92, 93, 94, 95,
 96, 97, 98, 99, & 100. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 94 DOES
 NOT REFLECT THE FIXTURE/WALL LAYOUT.
 (SEE SHT P-17 ALSO).
  
 39. SHT P-15 PIPING NOT APPROVED IN
 EGRESS STAIRWAYS. NFPA-101 SECTION
 7.1.3.2.1(6). (METHOD OF ADDRESSING NOT
 APPROVED. SEE BUILDING PLAN REVIEW #38).
 ****RESPONSE NOTED, BUT THE PIPING SHALL
 BE IN SOLID POUR OR A DRAIN SHALL BE
 INSTALLED FOR THE VOID.
  
 41. OK
 42. OK
 43. OK
  
 44. SHT P-17 THE FOLLOWING RISERS DO NOT
 REFLECT PIPING LAYOUT: 50, 51, 52, & 55.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT 50 & 52 DOES NOT
 REFLECT THE FLOOR PLAN AND 52 SHOWS AN
 OFFSET ON SHT P-16.
  
 46. OK
  
 48. SHT P-22 CONDENSATE LINE SHOWN AS 5'
 SEPARATION BETWEEN SUPPORTS. INDICATE
 TYPE OF MATERIAL. IF PVC PER TABLE 305.5
 MAXIMUM 4' SEPARATION BETWEEN SUPPORTS.
 SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW
 THEY ARE ATTACHED TO THE ROOF AND SHOW
 COMPLIANCE WITH 140 MPH WIND LOAD. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT NO DETAIL
 LOCATED.
 49. OK
  
 50. SHT P-23 RECREATION AT LEVEL 4
 PIPING DOES NOT REFLECT THE FIXTURE
 LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT
 WITH PIPING LAYOUT. SECTION 104.2.1.
 (RISER DIAGRAM DOES NOT REFLECT FIXTURE
 LAYOUT EITHER).(W/C MISSING ON RISER
 DIAGRAM).
 ****RESPONSE NOTED, BUT THE W/C IS STILL
 MISSING AT LEVEL 4 RECREATION.
  
 51. OK
 52. OK
 53. OK
 54. OK
 55. OK
 56. OK
 57. SHT P-53 RISER 8 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RELIEF VENT
 STILL SHOWN AFTER 11 BRANCH INTERVALS.
 58. OK
 59. OK
  
 60. SHT P-54 RISER 14 LOWER OFFSET VENT
 REQUIRED. SEC. 915.3 - MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET &
 THE NEXT LOWER HORIZONTAL BRANCH. 915.3
  
 62. SHT P-55 RISER 20 BATHROOM SHOWN ON
 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON
 5TH FLOOR ON RISER. CORRELATE RISER AND
 FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH
 FLOOR NOT SHOWN ON RISER. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE BATHROOM IS
 STILL SHOWN ON THE 5TH FLOOR.
  
 63. OK
  
 64. SHT P-55 RISER 23 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 LOWER OFFSET VENT REQD. SEC. 915.3. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. SECTION
 915.3.
  
 65. OK
  
 66. SHT P-56 RISER 26 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO BRANCH CONNECTIONS ON HORIZONTAL
 OFFSET. SEC. 711.2. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. SECTION
 915.3.
  
 67. SHT P-56 RISER 28 NO HORIZONTAL DRY
 VENTS. SEC. 905.3/905.4 (16TH FLOOR).
 ****NOT ADDRESSED.
  
 68. SHT P-56 RISER 29 LOWER OFFSET VENT
 REQD. SEC 915.3. - NO CONNECTION TO
 HORIZONTAL OFFSET. SEC. 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. 915.3.
  
 69. SHT P-56 RISER 30 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. (NO RESP0NSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT OFFSETS IN THE
 STACK VENT SHALL BE ABOVE THE FLOOD
 LEVEL OF THE HIGHEST FIXTURE. 905.4.
  
 70. SHT P-56 RISER 32 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. - UPPER OFFSET VENT REQD.
 SEC. 915.2. - SEPARATE RISER SECTION AT
 BASE OF STACK FOR POWDER ROOM, INDICATE
 RISERS CONNECTING FROM UPSTREAM. (33,
 37, 37A) SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT THE LOWER OFFSET
 VENT SHALL CONNECT BETWEEN THE OFFSET
 AND THE NEXT LOWER BRANCH. 915.3.
  
 71. SHT P-56 RISER 33 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENT. SEC. 905.3/905.4
 - DOES NOT REFLECT FLOOR PLAN @ 4TH
 LEVEL. (BASE OF STACK) SEC. 104.2.1. -
 VENT FROM 1ST FLOOR FLOOR DRAIN NOT
 SHOWN ON RISER. (SEE P-3, P-4, P-67).
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT SHALL
 OFFSET ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
 72. OK
 73. OK
 74. OK
  
 75. SHT P-59 RISER 50 DOES NOT REFLECT
 THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER STILL DOES
 NOT REFLECT THE FLOOR PLAN.
  
 76. OK
  
 77. SHT P-59 RISER 52 DOES NOT REFLECT
 FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT
 REQUIRED. SEC. 915.2. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT OFFSET IS SHOWN
 ON P-15, BUT NOT ON THE RISER.
  
 78. OK
  
 79. SHT P-60 RISER 56 DOES NOT REFLECT
 THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS
 REQD. SECS. 915.2/915.3. - MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. - NO CONNECTIONS TO HORIZONTAL
 OFFSET. SEC. 711.2.- NO HORIZONTAL DRY
 VENTS. SECS. 905.3/905.4. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT VENT OFFSET
 SHALL BE ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
  
 85. SHT P-61 RISERS 63, 64 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CLARIFY
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISERS STILL DO
 NOT REFLECT THE FLOOR PLAN.
  
 86. SHT P-61 RISER 67 MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT SHALL
 OFFSET ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 87. OK
 89. OK
  
 90. SHT P-62 RISER 71 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO DRY HORIZONTAL VENT. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT THE VENT OFFSET
 SHALL BE ABOVE THE FLOOD LEVEL OF THE
 HIGHEST FIXTURE. 905.4.
  
 91. OK
  
 92. SHT P-62 RISER 73 & 74 MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 73 SHOWS
 THE RELIEF VENT AFTER 11 BRANCH
 INTERVALS.
  
 94. OK
 95. OK
 96. OK
  
 97. SHT P-64 RISERS 89,94,95,99,101,102
 & 103 DO NOT REFLECT THE FLOOR PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISER 94 STILL
 DOES NOT REFLECT THE FLOOR PLAN.
  
 98. OK
  
 99. SHT P-67 FOLLOWING ARE CORRECTIONS
 TO BE MADE TO SANT.
 - RISERS 23 & 23A MISLABELED.
 - 2" VENT UP TO RISER
 67 TO READ "TO RISER 67A". (SEE RISER
 67A). - "2" VENT FOR CONT. SEE P-53"
 INDICATE RISER VENT WILL CONNECT TO. -
 - THIS SHEET SHOWS LEVELS AS PARK,
 PARK 2, PARK 3 ECT., BUT SHEETS P-15,
 P-16. & P-17 SHOWS LEVELS AS GROUND
 FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS
 MEZZ. ECT. PLEASE CLARIFY & CORRELATE
 SHEET LEVELS. - RECHECK ADDITION OF
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SOME FIXTURES UNITS ARE NOT
 SHOWN AND ADDED TO THE SYSTEM. INDICATE
 THE SLOPE OF THE PIPE WHERE THE FIXTURES
 UNITS ARE MORE THAN ALLOWED FOR MINIMUM
 SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE
 INSTALLED IN A UNIFORM SLOPE AS REQUIRED
 IN SECTION 704.1. INDICATE ON PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ****RESPONSE NOTED, BUT RISERS 23 & 23A
 ARE STILL MISLABELED. (SHOULD NOW BE 23,
 23A, 21, NOT 23, 234. - RISER NOT
 INDICATED FOR VENT. - LEVELS STILL
 DIFFERENT FROM SHEET TO SHEET. CLARIFY.
 - STILL MISSING PIPE SIZE, AND NEED TO
 SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. ADDITION TO BE CHECKED AS IT IS
 NOT CORRECT IN SOME AREAS. - CHECK
 PROPER APPLICATION TO THE FIXTURE UNIT
 TABLES 709.1, 709.2, (FOR TRAPS LARGER
 THAN INDICATED IN 709.1), 710.1(1),
 710.1(2). - CONFLICTS IN SLOPE, SHOWS
 1/16"/FT IN SOME AREAS, BUT NOTE STATES
 "1/8"/FT FOR ALL PIPE 3" & LARGER.
 PLEASE CORRELATE.
  
 100. SHT P-68 HORIZONTAL STORM RISER
 DOES NOT REFLECT STORM PIPING IN
 BUILDING. STRUCTURES S1 THRU S9 NOT
 SHOWN. - NO ROOF DRAINS 2650SF, 2350SF,
 2450SF ECT. FOUND. - NO EXFILTRATION
 TRENCHES FOUND. - NO TRENCH DRAINS
 FOUND, RISERS SHOWS 25TH, 26TH, 27TH
 FLOORS ECT. - NO POINT OF REFERENCE TO
 FLOOR PLAN CAN BE FOUND. - RISER HARD TO
 READ, PLEASE INCREASE THE SIZE OF THE
 STORM RISER DIAGRAM AND POSSIBLY SPLIT
 UP TO TWO PAGES TO MAKE RISER EASIER TO
 READ. SECTION 104.2.1.3. (NO RESPONSE,
 NOT ADDRESSED).
 ****RESPONSE NOTED, BUT ADDITION ON
 RISER DIAGRAM AND FLOOR NEEDS TO BE
 RECHECKED. SOME INCONSISTANCIES. ALSO
 SOME AREAS OF THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CHECK
 ENTIRE RISER DIAGRAM.
  
 101. OK
 102. OK
 103. OK
  
 104. BACKFLOW PROTECTION REQUIRED FOR
 IRRIGATION, POOLS, TRASH CHUTE WASH
 DOWNS, AND COOLING TOWER MAKE UP WATER.
 SECTION 608. INDICATE METHOD OF
 PROTECTION FOR EACH SYSTEM. (NO
 RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT NO PROTECTION
 INDICATED FOR THE IRRIGATION, NOR FOR
 THE POOL MAKE UP WATER.
  
 105. PLANS ARE INCOMPLETE AT THIS TIME
 AND MORE COMMENTS MAY BE FORTHCOMING
 WITH THE NEXT REVIEW.
 ****PLANS STILL DO NOT SEEM TO BE 100%
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 (NO RESPONSE)
 ****RESPONSE NOTED, BUT ON SOME COMMENTS
 WITH MULTIPLE COMMENTS, NOT ALL SECTIONS
 OF THE COMMENT WERE ADDRESSED IN
 RESPONSE. ALSO RSPONSES WERE NOT
 DETAILED AS TO WHERE THE CORRECTION
 COULD BE FOUND.
 ****************************************
 ****************************************
  
 NEW COMMENTS: (2ND REVIEW)
  
 1B. OK
  
 2B. SHOW PIPING FOR FIXTURES IN THE
 SHEET WITH FIXTURES, NOT ON THE FLOOR
 BELOW. THIS IS CONFUSING AND IS HARD TO
 FOLLOW THE PIPING, FIXTURES, AND RISER
 DIAGRAM ISOMETRICS. SECTION 104.2.1.
 ****RESPONSE NOTED, BUT THIS IS NOT
 ACCEPTABLE. THE PIPING AS SHOWN IS STILL
 CONFUSING. SOME PIPING THAT SHOULD BE ON
 THE SAME FLOOR AS THE FIXTURES, (SUCH AS
 WASH MACHINE PIPING, LAV AND KITCHEN ARM
 PIPING, ETC.), IS SHOWN ON THE FLOOR
 BELOW ALSO. ALL PIPING SHALL BE SHOWN ON
 THE SAME FLOOR AS THE FIXTURES.
  
 3B. BUILDING PLANS SHALL BE DRAWN TO
 MINIMUM OF 1/8" SCALE. SECTION
 104.2.1.3. ( SEE SHEETS P-2 THRU P-6.
 PLEASE SUBMIT 1/8" SCALE FOR THESE
 SHEETS FOR REVIEW).
 ****RESPONSE NOTED, BUT SHT P-6 HAS NOT
 BEEN CHANGED.
  
 4B. OK
  
 5B. SHT P-1A LOCATED BETWEEN P-19 &
 P-20. INDEX CALLS FOR IT TO BE PRIOR TO
 SHT P-1. PLEASE CORRELATE SHEETS &
 INDEX. SHT 104.2.1.
 ****RESPONSE NOTED, BUT SHT P-1A IS
 INSERTED AFTER P-1. CORRELATE THE INDEX
 AND SHEETS.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 NEW COMMENTS: (3RD REVIEW)
  
 1C. SHT P-1 PIPE SIZES FOR THE SPA
 HEATERS ARE INCORRECT. 2" REQUIRED FOR 3
 HEATERS, 1-1/2" REQUIRED FOR 2 HEATERS,
 AHD 1-1/4" REQUIRED FOR THE LAST HEATER.
 TABLE 402.2
  
 2C. SHTS P-2, P-2A, P-2B, P-2C, P-2D AND
 RISER DIAGRAM P-68, P-68A, P-68B, P-68C.
 CHECK THE ADDITION OF SQUARE FOOTAGE IN
 SYSTEM. ALSO MAKE SURE THE RISER DIAGRAM
 REFLECT THE FLOOR PLAN THROUGHOUT.
 SECTION 104.2.1, TABLE 1106.2, 1106.3
  
 3C. SHT P-7 DOWNSTREAM OF RISER 24, 24A
 DOES NOT REFLECT THE FLOOR PLAN. SECTION
 104.2.1.
  
 4C. ALL FLOOR PLAN SHEETS. NO PIPING IS
 SHOWN FOR WASH MACHINE DRAINS. (SEE
 RISER 32 FOR EXAMPLE). SECTION 104.2.1.
  
 5C. SHT P-9 UNITS 'LT2' EITHER SIDE OF
 COL. LINE S.06 SHOW NO LAV FIXTURES.
 SECTION 104.2.1.
  
 6C. SHT P-9 RISERS 16 & 22 OFFSETS SHOWN
 ARE NOT SHOWN ON THE RISER DIAGRAMS. -
 SHOW PIPING TO W/C'S AND LAVS. SECTION
 104.2.1.
  
 7C. SHT P-15 RISER 73,75,76,77,78,79
 DFU'S DO NOT REFLECT DFU'F INDICATED ON
 THE RISER DIAGRAM. CORRELATE DFU'S.
 SECTION 104.2.1.
  
 8C. SHT P-16 RISER 52 OFFSET NOT SHOWN
 ON THE RISER. CORRELATE FLOOR PLAN AND
 RISER DIAGRAM. SECTION 104.2.1.
  
 9C. SHT P-17 RISERS 62 & 94 FLOOR PLANS
 DO NOT REFLECT THE RISER DIAGRAMS.
  
 10C. SHT P-17 FLOOR PLAN INDICATED
 PARTIAL SOUTH NORTH RESIDENTIAL LOFTS
 2ND LEVEL, BUT SHEET TITLE SHOWS NORTH
 RESIDENTIAL LOFTS 2ND LEVEL. PLEASE
 CORRELATE SHEET INFORMATION. 104.2.1.
  
 11C. SHT P-19 FLOOR PLAN INDICATES NORTH
 RESIDENTIAL, BUT SHEET TITLE INDICATES
 SOUTH RESIDENTIAL. CORRELATE. 104.2.1.
  
 12C. SHT P-23 RECREATION AT LEVEL 2
 SHOWS TWO WASTE ARMS FOR ONE LAV. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 13C. SHT P-37 MISLABELED AS P-39.
 104.2.1.
  
 14C. SHT P-52 RISER DIAGRAM FOR 1W UNIT,
 W/C FOR POWDER NOT VENTED. SECTION
 901.2.1.
  
 15C. SHT P-53 STACK DIAGRAM #4 DOES NOT
 REFLECT THE FLOOR PLAN AT LEVEL 4.
 PLEASE CORRELATE. 104.2.1.
  
 16C. SHT P-54 STACK RISER #12 SHOWS A
 SHOWER, BUT FLOOR PLAN SHOWS A TUB.
 PLEASE CORRELATE. 104.2.1.
  
 17C.SHT P-54 STACK RISER #16 CHECK
 VENTING LEVEL 2. SECTION 104.2.1.
  
 18C. SHT P-54 STACK RISER #18 INDICATES
 AN EXTRA BRANCH LINE BETWEEN LEVELS 3 &
 4. MORE INFORMATION REQUIRED. PLEASE
 EXPLAIN WHAT THIS CONNECTS TO. SECTION
 104.2.1.
  
 19C. SHT P-55 STACK RISER #24 HORIZONTAL
 BRANCH LINE SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. 711.2 (2
 INSTANCES).
  
 20C. SHT P-55 STACK RISER #23 HORIZONTAL
 BRANCH LINE SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. 711.2 (2
 INSTANCES LEVEL 3 & LEVEL 4).
  
 21C. SHT P-56 STACK RISER #29 DOES NOT
 REFLECT THE FLOOR PLAN LEVEL 2.
 CORRELATE. SECTION 104.2.1.
  
 22C. SHT P-59 STACK RISER #50 DOES NOT
 REFLECT THE FLOOR PLAN LEVEL 4.
 CORRELATE. SECTION 104.2.1.
  
 23C. SHT P-60 STACKS 56 & 58 HORIZONTAL
 BRANCH LINES SHALL NOT CONNECT TO THE
 HORIZONTAL STACK OFFSET. SECTION 711.2
 (2 PLACES EACH STACK).
  
 24C. SHT P-61 STACK RISER #62 HORIZONTAL
 BRANCH CONNECTIONS TO THE HORIZONTAL
 STACK OFFSETS NOT APPROVED. 711.2 (2
 PLACES).
  
 25C. SHT P-61 STACK RISER #63 FIXTURES
 NOT SHOWN ON THE FLOOR PLAN TO REFLECT
 THE RISER AT THE BOTTOM OF THE STACK.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 26C. SHT P-61 STACK RISER #64 LEVEL 4
 OFFSET NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 104.2.1.
  
 27C. ALL RISERS & FLOOR PLANS WHERE
 THERE ARE HORIZONTAL OFFSETS. HORIZONTAL
 BRANCH CONNECTIONS SHALL NOT CONNECT
 WITH IN 2FT OF OFFSETS. SECTION 711.2.
  
 28C. SHT P-64 STACK RISER #94 DOES NOT
 REFLECT THE FLOOR PLAN AT THE BASE OF
 THE STACK. CORRELATE. 104.2.1.
  
 29C. SHT P-67 MAXIMUM 2900 DFU'S ON 12"
 PIPE AT 1/16"/FT SLOPE. 3538 DFU'S
 SHOWN. NOTE INDICATED 3" OR MORE PIPE
 SIZE SHALL SLOPE 1/8"/FT. SOUTH BLDG.
 DRAIN SHOWS 1/16TH/FT SLOPE IN VARIOUS
 PLACES. CORRELATE. SECTION 104.2.1 AND
 TABLE 710.1(1)
  
 30C. SHT P-67 5" MINIMUM REQUIRED
 UPSTREAM OF RISER 102. TABLE 710.1(1).
 PLEASE INDICATE ON RISER.
  
 31C. SHT P-67 CLEANOUT MISSING UPSTREAM
 OF THE BASE OF RISER 26/27 ETC. DOES NOT
 REFLECT THE FLOOR PLAN. CORRELATE.
 104.2.1.
  
 32C. SHT P-67 SHOWS RISER 23, 234.
 SHOULD BE 23, 23A, 21. SECTION 104.2.1.
  
 33C. SHT P-67 UPSTREAM OF RISER 39, 40
 ETC., SHOWS VENT FOR FLOOR DRAINS.
 INDICATE WHERE VENT CONNECTS. SECTION
 104.2.1.
  
 34. THE FOLLOWING STACKS HAVE HORIZONTAL
 DRY VENTS AT THE TOP OF THE STACKS.
 THESE VENTS SHALL BE OFFSET ABOVE THE
 FLOOD LEVEL OF THE HIGHEST FIXTURES.
 THESE STACKS ARE ON SHEETS P-53, P-54K,
 P-55, P-56, P-59, P-60, AND P-62. -
 STACK NUMBERS 1, 2, 13, 15, 10, 12, 14,
 16, 18, 20, 22, 23, 26, 28, 30, 32, 33,
 48, 48A, 53, 55, 56, 57, 60, 67, 71, 73,
 74. SECTION 905.4.
  
 35C. SHT P-39 NO PIPING SHOWN ON THE
 FLOOR PLAN 2ND FLOOR LOFT UNITS. SHOW
 PIPING. SECTION 104.2.1.
  
 36C. ALL RISERS WITH OFFSET VENTS. LOWER
 OFFSET VENTS SHALL CONNECT BETWEEN THE
 OFFSET AND THE NEXT LOWER HORIZONTAL
 BRANCH CONNECTION. SECTION 915.3.
  
 37C. SHT P-62 RISER 72 NO LAV ARM SHOWN
 ON LEVEL 4. CLARIFY. SECTION 104.2.1.
  
 38C. SHT P-62 RISER 79 SHOWS WASH
 MACHINE PIPING FOR 2ND LEVEL, BUT NO
 WASH MACHINE SHOWN. CLARIFY. 104.2.1.
  
 39C. INDICATE THE LOCATION FOR THE VENTS
 FOR THE CONDENSATE RISERS. VENTS ARE NOT
 ALLOWED IN THE WALLS, OR IN THE A/C ROOM
 IF THE ROOM IS A PLENUM. SECTION
 104.2.1.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By kstevens Date 2006-01-30 Time 07:50 Rev Time 0.00
Received By kstevens Date 2006-01-26 Time 17:16 Sent To  
Notes
2006-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****************************************
 A. COMMENTS FROM PREVIOUS REVIEW: NO
 COMMENT RESPONSES TO REVIEW WERE NOT
 SUBMITTED. COMMENT NUMBERS SHALL REMAIN
 THE SAME AS FIRST REVIEW UNTIL ADDRESSED
 ****************************************
  
 1. SHT A0.04C ACCESSIBILITY REQUIREMENTS
 PER SECTIONS 11-4.16.5, 11-4.19.5 AND
 11.4.21.7 TO BE SHOWN ON PLANS. (SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART.)
 2. SHT A0.04.4 DETAIL 04.(NOT SHOWN AS
 DETAIL 10) SUBMIT CALCULATIONS FOR GRAB
 BAR BACKING PER SECTION 609.8 OF THE
 ANSI A117.1 STANDARD FOR THE SUPPORTIVE
 STRUCTURE. INDICATE GUAGE OF METAL
 PLATE. (NOT ADDRESSED, NO RESPONSE)
 3. SHT C1 SURVEY NOT SIGNED, SEALED, AND
 DATED AS REQUIRED BY FAC 61G15-23.002 &
 FS 471.025. (NO RESPONSE, NOT ADDRESSED)
 4. SHTS C-2 THRU C-5 ENGINEERS SEAL
 SHALL IMPART INFORMATION REQUIRED BY FAC
 61G15-233.001 & FS 471.025 ON EACH
 SHEET. THE INFORMATION REQUIRED ON SEAL
 HAS NOT BEEN IMPRESSED ON EACH SHEET AS
 REQUIRED. - THE SIGNATURE REQUIRED
 APPEARS TO BE INITIALS WHICH ACCORDING
 TO FBPE IS NOT APPROVED AND A SIGNATURE
 IS REQUIRED. IF INDEED THIS IS YOUR
 LEGAL SIGNATURE, PROVIDE A SIGNED,
 SEALED, DATED, AND NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR
 FILES. (NO RESPONSE, NOT ADDRESSED)
 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO
 INFORMATION ON THE SEAL HAS BEEN
 IMPRESSED ON THE SHEETS AS REQUIRED BY
 FAC 61G1-16.001. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 SHALL APPEAR ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) & (6) AND FS 481.219,
 481.2055.(NO RESPONSE, SHEETS NOT
 RESUBMITTED. PLEASE CLARIFY)
 6. SHT A1.02C DETAIL 04 SHOW TURNING
 AREA IN THE STAFF TOILET AS REQUIRED BY
 SECTION 11-4.22.3. (TURNING AREA TO BE
 UNOBSTRUCTED, AND AS SHOWN IS IN TWO
 SEPARATE ROOMS WITH THE WALL IN THE
 MIDDLE OF THE TURNING AREA).
 7. SHT A1.02C DETAIL 01 SHOW TURNING
 AREA IN THE RESTROOMS, NOT IN THE
 STALLS. SECTION 11-4.22.3. (NO RESPONSE,
 NOT ADDRESSED).
 8. SHT A1.02C A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AND WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. (NO RESPONSE, NOT ADDRESSED).
 9. SHT 1.05C DETAIL 02 SHOW THE TURNING
 AREA IN RESTROOM NOT IN THE STALL.
 SECTION 11-4.22.3. (NO RESPONSE, NOT
 ADDRESSED).
 10. PLEASE INDICATE IF THE KITCHEN WILL
 BE BUILT-OUT ON THIS PERMIT OR WILL IT
 BE A SEPARATE PERMIT, AS THE PLANS WILL
 HAVE TO BE ROUTED TO DBPR RESTURANT AND
 HOTEL DIVISION PRIOR TO APPROVAL.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 11. SHTS A1.05, A1.09, A1.10, & A1.11.
 SS-1 SUBMIT CALCULATIONS FOR PRIMARY &
 SECONDARY ROOF DRAINS. SHOW TOTAL AREA,
 1/2 AREA OF ALL VERTICAL WALLS,
 (INCLUDING PARAPETS), ALL AREAS OF ROOFS
 ADDED TO ROOF AREA FROM ABOVE ADDED TO
 ROOF AREA IN CALCULATIONS. INDICATE
 TOTAL AREA DRAINED BY EACH ROOF DRAIN. -
 THIS IS REQUIRED FOR EACH ROOF LEVEL AND
 FOR THE RECREATION LEVEL. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS
 AND SCUPPERS. INDICATE THE SIZE OF ALL
 SCUPPERS AND SUBMIT A DETAIL SHOWING THE
 HEIGHT, WIDTH AND THE HEIGHT OF THE FLOW
 LINE OFF THE ROOF. SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW
 BACKING & OPENING DIMENSIONS FOR THE W/C
 OPENINGS FOR ADDITIONAL BATHROOMS PER
 BATHROOM REQUIREMENTS PAGE 7.35. THIS
 WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS'
 SHT A4.03 UNIT 'BS', SHT A4.04 UNIT
 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06
 UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15
 UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20
 UNIT 'KN', SHT A4.22 UNIT 'LS', SHT
 A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2',
 SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT
 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28
 UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT
 A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT
 'QN', SHT A4.32 UNIT 'RN', SHT A4.33
 UNIT 'RS', SHT A4.34 UNIT 'SN', SHT
 A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS',
 SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT
 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT
 A4.31.1 UNIT 'STSM'. (NO RESPONSE, NOT
 ADDRESSED. ADDITIONAL BATHROOMS IN THE
 UNIT ARE EXEMPT -ONLY- FROM MANEUVERING
 AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES)
 13. SHTS A4.10 - A4.16 CLEAR FLOOR SPACE
 SHALL BE FLUSH WITH THE CONTROL WALL FOR
 SHOWERS AND PARALLEL TO SHOWER. PAGE
 7.56. (NO RESPONSE, NOT ADDRESSED).
 16. SHTS A4.38, A4.39, & A4.40 ENTRY
 LEVEL TO BE COVERED PER FHA. SUBMIT
 DETAILS FOR BATHROOMS. (RESPONSE NOTED,
 BUT THE FIRST FLOOR SHALL HAVE A
 ACCESSIBLE PATH TO THE ELEVATORS).
 17. GROUND FLOOR CONFERENCE ROOM SINKS
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (NO RESPONSE, NOT
 ADDRESSED).
 18. SHT P-1 REGULATORS SHOW 7"W/C -
 TABLE 402(2) IS FOR 1/2 PSI WHICH IS 11"
 TO 14"W/C. PLEASE CLARIFY AND VERIFY
 INPUT PRESSURE FOR GAS SYSTEM. (NO
 RESPONSE, NOT ADDRESSED).
 19. SHT P-1 INDICATE MATERIAL TO BE USED
 FOR THE REGULATOR VENT PIPING. (NON
 COMBUSTABLE REQUIRED). (NO RESPONSE, NOT
 ADDRESSED).
 21. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. (NO RESPONSE, NOT
 ADDRESSED).
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (DOWNSTREAM OF REGULATOR). (NO RESPONSE,
 NOT ADDRESSED).
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506. (NO RESPONSE, NOT
 ADDRESSED).
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 22. SEPARATE GAS PERMIT REQUIRED. AT
 TIME OF APPLICATION, CONTRACTOR SHALL
 SUBMIT A PICTURE I.D. OF THE WELDER,
 WELDING CERTIFICATION, AND A COPY OF THE
 WELDING PROCEDURE. (INFORMATIONAL)
 23. ALL FLOOR PLAN SHEETS, SHOW THE
 LOCATION & NUMBER OF EACH RISER THRU THE
 BUILDING ON EACH FLOOR PLAN AND EACH
 LEVEL. SECTION 104.2.1. (NO RESPONSE,
 NOT ADDRESSED).
 24.SHT P-2 RISER DESIGNATIONS 35, 36,
 45, 46, 46A, & 47 ARE NOT SHOWN. (NO
 RESPONSE, NOT ADDRESSED).
 25. SHT P-2 SHOW THE PIPING FOR ALL
 TRENCH DRAINS WITH PIPE SIZES. THIS
 SHALL BE REFLECTED ON THE STORM RISER
 DIAGRAM. SECTION 104.3.1.1. (NO
 RESPONSE, NOT ADDRESSED FOR TRENCH DRAIN
 AT COL. LINE G/01).
 26. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD. #3434. PLEASE CONTACT LYNN
 MASSON AT (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. (NO
 RESPONSE, NOT ADDRESSED).
 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL
 PIPE SIZES. RECALCULATE ADDITION ON SOME
 RWL'S, INDICATE RWL RISER NUMBERS, 3"
 OVERFLOW SHOWN CONNECTING TO PRIMARY
 SYSTEM AT COL. 24 BETWEEN COLS, A&B.
 PLEASE CLARIFY. SECTION 104.2.1. -(SHOW
 ALL SECONDARY ROOF DRAINS, WITH PIPE
 SIZES, SF, ETC.). (NO RESPONSE NOT
 ADDRESSED).
 28. SHT P-4 STATES "3"S FOR CONT. SEE
 P-4 HEALTH CLUB". THIS WAS NOT FOUND ON
 SHT P-4. PLEASE CLARIFY. (NO RESPONSE,
 NOT ADDRESSED).
 29. SHT P-4 INDICATE WHAT THE
 DESIGNATION FOR "DL" REPRESENTS. (NO
 RESPONSE, NOT ADDRESSED).
 30. SHT P-7 RISER DESIGNATIONS 35, 36,
 38, 45, 46, & 46A NOT SHOWN. PLEASE SHOW
 ALL RISERS FOR EACH FLOOR LEVEL. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 31. SHT P-7 SANT. PIPING NOT ALLOWED IN
 THE EGRESS STAIRWAY. NFPA-101 SECTION
 7.1.3.2.1(6). (NO RESPONSE, NOT
 ADDRESSED).
 32. SHT P-8 OFFSETS SHOWN FOR RISERS 6,
 10, 11, 12, 15, & 17, 18, 19, 20 ARE NOT
 SHOWN ON THE RISER DIAGRAMS. SECTIONS
 104.2.1, & 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 33. SHT P-9 OFFSETS SHOWN FOR RISERS 42,
 44, 47, 30, 34, 35, 36, 21, 25, 1, AND
 TO TOILET ROOMS RECREATION LEVEL 4 ARE
 NOT SHOWN NO THE RISER DIAGRAMS.
 SECTIONS 104.2.1, & 104.3.1. (NO
 RESPONSE, NOT ADDRESSED).
 34. SHT P-9SHOW THE TYPICAL PIPING
 LAYOUTS FOR RISERS 16, 22, 28, & 29.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 35. SHT P-9 THE FOLLOWINGPIPING
 LAYOUTS DO NOT REFLECT RISER DIAGRAMS
 44, 47, 42, 40, 39, 20, & 4. SECTION
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 36. SHT P-13 PIPING FOR THE DWV AND
 STORM SYSTEMS NOT APPROVED IN EGRESS
 STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6)
 AND SECTION 1006.1.3.1. (METHOD OF
 ADDRESSING NOT APPROVED. SEE BUILDING
 PLAN REVIEW COMMENT #38).
 37. P-14. CONDENSATE IS INDICATED AS 5'
 SEPARATION FOR THE SUPPORTS. INDICATE
 MATERIAL FOR CONDENSATE PIPING. IF PVC,
 MAXIMUM 4' SEPARATION OF SUPPORTS PER
 TABLE 305.5. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 140 MPH WIND LOAD FOR
 SUPPORTS. (NO RESPONSE, NOT ADDRESSED).
 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON
 RISER DIAGRAM 56, 59A, 92, 93, 94, 95,
 96, 97, 98, 99, & 100. (NO RESPONSE, NOT
 ADDRESSED).
 39. SHT P-15 PIPING NOT APPROVED IN
 EGRESS STAIRWAYS. NFPA-101 SECTION
 7.1.3.2.1(6). (METHOD OF ADDRESSING NOT
 APPROVED. SEE BUILDING PLAN REVIEW #38).
 41. SHT P-15 THE FOLLOWING PIPING
 LAYOUTS DO NOT REFLECT THE RISER
 DIAGRAMS: 48, 48A, 49, 50, 51, 56, 58,
 59, 59A, 61, 62, 64, 67, & 67A. - NOT
 ALL PIPING SHOWN ON THE RISER DIAGRAMS.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 42. SHT P-16 NO PIPING TO W/M SHOWN AT
 EITHER SIDE OF STAIRS COL. LINE N.05,
 BETWEEN UNITS NLT103 & NLT104. INDICATE
 WHICH RISERS THESE W/M'S CONNECT TO.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 43. SHT P-17 MAXIMUM 6' FROM POINT OF
 VENT TO TUB TRAP. (NEAR RISER 95) TABLE
 906.1. (NO RESPONSE, NOT ADDRESSED).
 44. SHT P-17 THE FOLLOWING RISERS DO NOT
 REFLECT PIPING LAYOUT: 50, 51, 52, & 55.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 46. SHT P-18 RISER 102 INDICATES 3"V DN
 TO RISER #3W. THIS IS NOT SHOWN ON SHT
 P-17 NOR ON RISER 102. PLEASE CLARIFY.
 SECTION 104.2.1. - WHAT IS RISER #3W?
 WHERE IS IT LOCATED? SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 48. SHT P-22 CONDENSATE LINE SHOWN AS 5'
 SEPARATION BETWEEN SUPPORTS. INDICATE
 TYPE OF MATERIAL. IF PVC PER TABLE 305.5
 MAXIMUM 4' SEPARATION BETWEEN SUPPORTS.
 SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW
 THEY ARE ATTACHED TO THE ROOF AND SHOW
 COMPLIANCE WITH 140 MPH WIND LOAD. (NO
 RESPONSE, NOT ADDRESSED).
 49. SHT P-23 BATHROOM MAIN LOBBY LEVEL 1
 SHOWN 36FU, BUT IS SHOWN AS 34FU ON SHT
 P-2. CORRELATE PLANS. SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 50. SHT P-23 RECREATION AT LEVEL 4
 PIPING DOES NOT REFLECT THE FIXTURE
 LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT
 WITH PIPING LAYOUT. SECTION 104.2.1.
 (RISER DIAGRAM DOES NOT REFLECT FIXTURE
 LAYOUT EITHER).(W/C MISSING ON RISER
 DIAGRAM).
 51. SHT P-23 RECREATION AT LEVEL 2
 INDICATES 40FU FOR FUTURE GYM, BUT ONLY
 44FU AFTER ADDING MEN'S & WOMEN'S TOILET
 ROOMS. PLEASE RECALCULATE FU'S. (ALSO
 ADJUST ON RISER DIAGRAM). SECTION
 104.2.1. (CHECK ADDIDION, NOW READS
 94FU).
 52. SHT P-23 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-68". P-68 SHOWS STORM RISER
 ONLY. PLEASE CLARIFY. SECTION 104.2.1.
 (ONE STILL READS P-68).
 53. SHT P-39 FLOOR DRAIN NOT SHOWN
 BETWEEN 1ST & 2ND WLI UNITS FIRST FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1. (ALSO
 NEW PIPING DOES NOT REFLECT PIPING SHOWN
 ON SHT P-1. - UNITS AR REFERRED TO AS
 UNITS LW101, THRU LW105 ON SHT P-1, BUT
 AS UNITS WL1 & WL2 ON SHT P-39. PLEASE
 CLARIFY AND CORRELATE UNIT DESIGNATIONS
 BETWEEN SHEETS. - INDICATE LOCATION OF
 RISER DIAGRAM. P-67 STATES "SEE P-53",
 BUT RISERS ARE NOT LOCATED ON SHT P-53).
 54. SHT P-52 SANT. RISER DIAGRAM UNIT
 TOWNHOME, MAXIMUM 4FU ON 2" WET VENT PER
 TABLE 909.3. (NO RESPONSE, NOT
 ADDRESSED).
 55. SHT P-52 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-69". CONT. NOT FOUND ON
 P-69. PLEASE CLARIFY. SECTION 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 56. SHT P-53 RISER 13 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - DRY HORIZONTAL VENTS NOT APPROVED 17TH
 FLOOR. SECTIONS 905.3/905.4. (NO
 RESPONSE, NOT ADDRESSED).
 57. SHT P-53 RISER 8 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 58. SHT P-54 RISER 10 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - HORIZONTAL
 BRANCH CONNECTIONS NOT APPROVED ON THE
 HORIZONTAL OFFSET. SECTION 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 59. SHT P-54 RISER 12 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - 4" VENT TO RISER #6 READS "FROM RISER
 6. PLEASE CORRELATE RISERS. SECTION
 104.2.1.(CHANGED FROM RISER #8 TO RISER
 #6). (NO RESPONSE, NOT ADDRESSED).
 60. SHT P-54 RISER 14 LOWER OFFSET VENT
 REQUIRED. SEC. 915.3 - MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 62. SHT P-55 RISER 20 BATHROOM SHOWN ON
 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON
 5TH FLOOR ON RISER. CORRELATE RISER AND
 FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH
 FLOOR NOT SHOWN ON RISER. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 63. SHT P-55 RISER 22 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 64. SHT P-55 RISER 23 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 LOWER OFFSET VENT REQD. SEC. 915.3. (NO
 RESPONSE, NOT ADDRESSED).
 65. SHT P-56 RISER 25 SINK MISSING 17TH
 FLOOR. SEC. 402.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 66. SHT P-56 RISER 26 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO BRANCH CONNECTIONS ON HORIZONTAL
 OFFSET. SEC. 711.2. (NO RESPONSE, NOT
 ADDRESSED).
 67. SHT P-56 RISER 28 NO HORIZONTAL DRY
 VENTS. SEC. 905.3/905.4 (16TH FLOOR)
 68. SHT P-56 RISER 29 LOWER OFFSET VENT
 REQD. SEC 915.3. - NO CONNECTION TO
 HORIZONTAL OFFSET. SEC. 711.2. (NO
 RESPONSE, NOT ADDRESSED).
 69. SHT P-56 RISER 30 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. (NO RESP0NSE, NOT
 ADDRESSED).
 70. SHT P-56 RISER 32 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. - UPPER OFFSET VENT REQD.
 SEC. 915.2. - SEPARATE RISER SECTION AT
 BASE OF STACK FOR POWDER ROOM, INDICATE
 RISERS CONNECTING FROM UPSTREAM. (33,
 37, 37A) SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 71. SHT P-56 RISER 33 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENT. SEC. 905.3/905.4
 - DOES NOT REFLECT FLOOR PLAN @ 4TH
 LEVEL. (BASE OF STACK) SEC. 104.2.1. -
 VENT FROM 1ST FLOOR FLOOR DRAIN NOT
 SHOWN ON RISER. (SEE P-3, P-4, P-67).
 (NO RESPONSE, NOT ADDRESSED).
 72. SHT P-57. RISERS 39, 40,41, 42, 43,
 44 DO NOT REFLECT THE FLOOR PLANS AT THE
 BASE OF RISER. SEC. 1-4.2.1. (NO
 RESPONSE, NOT ADDRESSED).
 73. SHT P-57 RISER 42 VENT FROM FIRST
 FLOOR FLOOR DRAINS NOT SHOWN. PLEASE
 CLARIFY. SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 74. SHT P-58 RISERS 45, 46, 47 DO NOT
 REFLECT FLOOR PLANS FOR 4TH LEVEL.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 75. SHT P-59 RISER 50 DOES NOT REFLECT
 THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 76. SHT P-59 RISER 51 DOES NOT REFLECT
 THE FLOOR PLAN AT BASE OF RISER AND ON
 THE 4TH LEVEL. PLEASE CLARIFY SEC.
 104.2.1. (NO RESPONSE, NOT ADDRESSED).
 77. SHT P-59 RISER 52 DOES NOT REFLECT
 FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT
 REQUIRED. SEC. 915.2. (NO RESPONSE, NOT
 ADDRESSED).
 78. SHT P-59 RISERS 53, 55 DO NOT
 REFLECT THE FLOOR PLAN 4TH LEVEL.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 79. SHT P-60 RISER 56 DOES NOT REFLECT
 THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS
 REQD. SECS. 915.2/915.3. - MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. - NO CONNECTIONS TO HORIZONTAL
 OFFSET. SEC. 711.2.- NO HORIZONTAL DRY
 VENTS. SECS. 905.3/905.4. (NO RESPONSE,
 NOT ADDRESSED).
 80. SHT P-60 RISER 58 DOES NOT REFLECT
 THE FLOOR PLAN, CHECK LOCATION OF
 CONNECTION OF RISER 59. - RISER 58 & 61
 NOT TIED TOGETHER ON FLOOR PLAN. - UPPER
 OFFSET VENT REQD. 915.2. (NO RESPONSE,
 NOT ADDRESSED).
 81. SHT P-60 RISER 61 DOES NOT REFLECT
 THE FLOOR PLAN LEVEL 17. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 82. SHT P-60 RISER 57 DOES NOT REFLECT
 THE FLOOR PLAN UPPER LEVEL. - MAX 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 83. SHT P-60 RISER 60 DOES NOT REFLECT
 THE FLOOR PLAN. SHOWS CONNECTING TO
 HORIZONTAL DRAIN LINE. (GROUND FLOOR?) -
 UPPER OFFSET VENT REQD. SEC. 915.2. -
 DOES NOT REFLECT THE FLOOR PLAN AT THE
 TOP OF THE RISER. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 (NO RESPONSE, NOT ADDRESSED).
 84. SHT P-61 RISER 62 DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 85. SHT P-61 RISERS 63, 64 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CLARIFY
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 86. SHT P-61 RISER 67 MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 87. SHT P-61 RISER 67A DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 89. SHT P-62 RISER 70 LOWER OFFSET VENT
 REQD. SEC 915.3. (NO RESPONSE, NOT
 ADDRESSED).
 90. SHT P-62 RISER 71 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO DRY HORIZONTAL VENT. SECS. 905.3
 905.4. (NO RESPONSE, NOT ADDRESSED).
 91. SHT P-62 RISER 72 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 3.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 92. SHT P-62 RISER 73 & 74 MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. (NO RESPONSE, NOT ADDRESSED).
 94. SHT P-62 RISER 79 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 4.
 SEC. 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 95. SHT P-63 RISERS 75,76,77,78,87,88
 DO NOT REFLECT THE FLOOR PLAN PIPING
 LAYOUTS LEVEL 4. SECTION 104.2.1. (NO
 RESPONSE, NOT ADDRESSED).
 96. SHT P-63 RISER 80 FLOOR DRAIN LEVEL
 16 ROOF NOT SHOWN ON RISER DIAGRAM.
 SECTION 104.2.1. CORRELATE RISER/FLOOR
 PLAN. (NO RESPONSE, NOT ADDRESSED).
 97. SHT P-63 RISERS 89,94,95,99,101,102
 & 103 DO NOT REFLECT THE FLOOR PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 98. SHT P-67 HORIZONTAL SANT. RISER
 DIAGRAM MISLABELED AS "WATER RISER
 DIAGRAM". PLEASE CLARIFY. SEC. 104.2.1.
 (NO RESPONSE, NOT ADDRESSED).
 99. SHT P-67 FOLLOWING ARE CORRECTIONS
 TO BE MADE TO SANT. RISER DIAGRAM: -
 RISERS 35 & 36 NOT SHOWN. - PIPING
 LAYOUT DOWNSTREAM OF RISER 33,37,37 DOES
 NOT REFLECT FLOOR PLAN FOR POWDER ROOM.
 - RISERS 23 & 23A MISLABELED. - PIPING
 BETWEEN RISERS 6,10,11,12,15 & RISER
 9,13 DOES NOT SHOW POWDER ROOM OR WASH
 MACHINE. - OFFSETS & PIPING LAYOUT SHOWN
 ON SHT P-9 ARE NOT SHOWN ON RISER
 DIAGRAM. - NO VENT SHOWN FOR GREASE
 LINE. - GREASE LINE DOES NOT REFLECT THE
 FLOOR PLAN, AND IS NOT SHOWN ON FLOOR
 PLANS P-15 THRU P-18. -4"-34FU FOR CONT.
 SEE P-23 SHOWS 36FU ON SHT P-23.
 CORRELATE SHEETS. - 2" VENT FROM 2 SINKS
 SHOWS 3" VENT ON SHTS P-3, P-4, & P-5.
 CORRELATE SHEETS. (VENTS NOW NOT FOUND
 ON SHEET). - 2" VENT UP TO RISER
 67 TO READ "TO RISER 67A". (SEE RISER
 67A). - "2" VENT FOR CONT. SEE P-53"
 INDICATE RISER VENT WILL CONNECT TO. -
 "UNITS WL1, WL2 & UNITS 1T THRU 10T,
 4"-28FU FOR CONT. SEE P-53. NOT FOUND ON
 SHT P-53. PLEASE CLARIFY - 6" LINE FROM
 RISER 92,93,94,95,96,97,98, 99,100 DOES
 NOT SHOW OFFSET ON RISER SHOWN ON SHT
 P-15. - THIS SHEET SHOWS LEVELS AS PARK,
 PARK 2, PARK 3 ECT., BUT SHEETS P-15,
 P-16. & P-17 SHOWS LEVELS AS GROUND
 FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS
 MEZZ. ECT. PLEASE CLARIFY & CORRELATE
 SHEET LEVELS. - RECHECK ADDITION OF
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SOME FIXTURES UNITS ARE NOT
 SHOWN AND ADDED TO THE SYSTEM. INDICATE
 THE SLOPE OF THE PIPE WHERE THE FIXTURES
 UNITS ARE MORE THAN ALLOWED FOR MINIMUM
 SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE
 INSTALLED IN A UNIFORM SLOPE AS REQUIRED
 IN SECTION 704.1. INDICATE ON PLANS.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 100. SHT P-68 HORIZONTAL STORM RISER
 DOES NOT REFLECT STORM PIPING IN
 BUILDING. STRUCTURES S1 THRU S9 NOT
 SHOWN. - NO ROOF DRAINS 2650SF, 2350SF,
 2450SF ECT. FOUND. - NO EXFILTRATION
 TRENCHES FOUND. - NO TRENCH DRAINS
 FOUND, RISERS SHOWS 25TH, 26TH, 27TH
 FLOORS ECT. - NO POINT OF REFERENCE TO
 FLOOR PLAN CAN BE FOUND. - RISER HARD TO
 READ, PLEASE INCREASE THE SIZE OF THE
 STORM RISER DIAGRAM AND POSSIBLY SPLIT
 UP TO TWO PAGES TO MAKE RISER EASIER TO
 READ. SECTION 104.2.1.3. (NO RESPONSE,
 NOT ADDRESSED).
 101. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES AND INDICATE
 MATERIAL. SECTION 104.3.1.1. (PIPING
 MATERIAL NOT INDICATED)
 102. SUBMIT A P/T VALVE DISCHARGE RISER
 DIAGRAM SHOWING ALL PIPE SIZES AND
 INDICATE PIPING/FITTING MATERIAL.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 103. SUBMIT AN EMERGENCY PAN DRAIN RISER
 DIAGRAM FOR THE WATER HEATERS. INDICATE
 PIPE SIZES AND MATERIAL FOR PIPE AND
 FITTINGS. (NO RESPONSE, NOT ADDRESSED).
 104. BACKFLOW PROTECTION REQUIRED FOR
 IRRIGATION, POOLS, TRASH CHUTE WASH
 DOWN, AND COOLING TOWER MAKE UP WATER.
 SECTION 608. INDICATE METHOD OF
 PROTECTION FOR EACH SYSTEM. (NO
 RESPONSE, NOT ADDRESSED).
 105. PLANS ARE INCOMPLETE AT THIS TIME
 AND MORE COMMENTS MAY BE FORTHCOMING
 WITH THE NEXT REVIEW.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 (NO RESPONSE)
 ****************************************
 ****************************************
  
 NEW COMMENTS:
  
 1B. SHT P-1, THE GAS RISER DIAGRM SHOWS
 THE POOL HEATERS ADD UP TO 2400 BTU, BUT
 NOTE INDICATING "GAS RISER DIAGRAM" ONLY
 SHOWS 2200 BTU. PLEASE CORRELATE RISER &
 NOTE. SECTION 104.2.1.
 2B. SHOW PIPING FOR FIXTURES IN THE
 SHEET WITH FIXTURES, NOT ON THE FLOOR
 BELOW. THIS IS CONFUSING AND IS HARD TO
 FOLLOW THE PIPING, FIXTURES, AND RISER
 DIAGRAM ISOMETRICS. SECTION 104.2.1.
 3B. BUILDING PLANS SHALL BE DRAWN TO
 MINIMUM OF 1/8" SCALE. SECTION
 104.2.1.3. ( SEE SHEETS P-2 THRU P-6.
 PLEASE SUBMIT 1/8" SCALE FOR THESE
 SHEETS FOR REVIEW).
 4B. RESUBMIT ALL PLUMBING SHEETS MARKED
 UP FROM THE FIRST REVIEW TO AID IN
 SPEEDING UP THE REVIEW PROCESS.
 5B. SHT P-1A LOCATED BETWEEN P-19 &
 P-20. INDEX CALLS FOR IT TO BE PRIOR TO
 SHT P-1. PLEASE CORRELATE SHEETS &
 INDEX. SHT 104.2.1.
  
 ****************************************
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 PLANS FOR COMPAIRSON. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ****************************************
 ****************************************
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By kstevens Date 2005-10-06 Time 10:18 Rev Time 0.00
Received By kstevens Date 2005-08-27 Time 16:02 Sent To  
Notes
2005-10-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A0.04C ACCESSIBILITY REQUIREMENTS
 PER SECTIONS 11-4.16.5, 11-4.19.5 AND
 11.4.21.7 TO BE SHOWN ON PLANS.
 2. SHT A0.04.4 DETAIL 04. SUBMIT
 CALCULATIONS FOR GRAB BAR BACKING PER
 SECTION 609.8 OF THE ANSI A117.1
 STANDARD FOR THE SUPPORTIVE STRUCTURE.
 INDICATE GUAGE OF METAL PLATE.
 3. SHT C1 SURVEY NOT SIGNED, SEALED, AND
 DATED AS REQUIRED BY FAC 61G15-23.002 &
 FS 471.025.
 4. SHTS C-2 THRU C-5 ENGINEERS SEAL
 SHALL IMPART INFORMATION REQUIRED BY FAC
 61G15-233.001 & FS 471.025 ON EACH
 SHEET. THE INFORMATION REQUIRED ON SEAL
 HAS NOT BEEN IMPRESSED ON EACH SHEET AS
 REQUIRED. - THE SIGNATURE REQUIRED
 APPEARS TO BE INITIALS WHICH ACCORDING
 TO FBPE IS NOT APPROVED AND A SIGNATURE
 IS REQUIRED. IF INDEED THIS IS YOUR
 LEGAL SIGNATURE, PROVIDE A SIGNED,
 SEALED, DATED, AND NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR
 FILES.
 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO
 INFORMATION ON THE SEAL HAS BEEN
 IMPRESSED ON THE SHEETS AS REQUIRED BY
 FAC 61G1-16.001. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 SHALL APPEAR ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) & (6) AND FS 481.219,
 481.2055.
 6. SHT A1.02C DETAIL 04 SHOW TURNING
 AREA IN THE STAFF TOILET AS REQUIRED BY
 SECTION 11-4.22.3.
 7. SHT A1.02C DETAIL 01 SHOW TURNING
 AREA IN THE RESTROOMS, NOT IN THE
 STALLS. SECTION 11-4.22.3
 8. SHT A1.02C A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AND WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 9. SHT 1.05C DETAIL 02 SHOW THE TURNING
 AREA IN RESTROOM NOT IN THE STALL.
 SECTION 11-4.22.3
 10. PLEASE INDICATE IF THE KITCHEN WILL
 BE BUILT-OUT ON THIS PERMIT OR WILL IT
 BE A SEPARATE PERMIT, AS THE PLANS WILL
 HAVE TO BE ROUTED TO DBPR RESTURANT AND
 HOTEL DIVISION PRIOR TO APPROVAL.
 SECTION 101.4.7.
 11. SHTS A1.05, A1.09, A1.10, & A1.11.
 SS-1 SUBMIT CALCULATIONS FOR PRIMARY &
 SECONDARY ROOF DRAINS. SHOW TOTAL AREA,
 1/2 AREA OF ALL VERTICAL WALLS,
 (INCLUDING PARAPETS), ALL AREAS OF ROOFS
 ADDED TO ROOF AREA FROM ABOVE ADDED TO
 ROOF AREA IN CALCULATIONS. INDICATE
 TOTAL AREA DRAINED BY EACH ROOF DRAIN. -
 THIS IS REQUIRED FOR EACH ROOF LEVEL AND
 FOR THE RECREATION LEVEL. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS
 AND SCUPPERS. INDICATE THE SIZE OF ALL
 SCUPPERS AND SUBMIT A DETAIL SHOWING THE
 HEIGHT, WIDTH AND THE HEIGHT OF THE FLOW
 LINE OFF THE ROOF. SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS.
 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW
 BACKING & OPENING DIMENSIONS FOR THE W/C
 OPENINGS FOR ADDITIONAL BATHROOMS PER
 BATHROOM REQUIREMENTS PAGE 7.35. THIS
 WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS'
 SHT A4.03 UNIT 'BS', SHT A4.04 UNIT
 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06
 UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15
 UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20
 UNIT 'KN', SHT A4.22 UNIT 'LS', SHT
 A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2',
 SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT
 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28
 UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT
 A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT
 'QN', SHT A4.32 UNIT 'RN', SHT A4.33
 UNIT 'RS', SHT A4.34 UNIT 'SN', SHT
 A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS',
 SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT
 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT
 A4.31.1 UNIT 'STSM'.
 13. SHTS A4.10 - A4.16 CLEAR FLOOR SPACE
 SHALL BE FLUSH WITH THE CONTROL WALL FOR
 SHOWERS AND PARALLEL TO SHOWER. PAGE
 7.56.
 14. SHT A4.36 SUBMIT USABLE BATH DETAIL.
 15. SHT A4.37 SUBMIT USABLE BATH DETAIL.
 16. SHTS A4.38, A4.39, & A4.40 ENTRY
 LEVEL TO BE COVERED PER FHA. SUBMIT
 DETAILS FOR BATHROOMS.
 17. GROUND FLOOR CONFERENCE ROOM SINKS
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 18. SHT P-1 REGULATORS SHOW 7"W/C -
 TABLE 402(2) IS FOR 1/2 PSI WHICH IS 11"
 TO 14"W/C. PLEASE CLARIFY AND VERIFY
 INPUT PRESSURE FOR GAS SYSTEM.
 19. SHT P-1 INDICATE MATERIAL TO BE USED
 FOR THE REGULATOR VENT PIPING. (NON
 COMBUSTABLE REQUIRED).
 20. GAS RISER INDICATES 6396 MBH, BUT
 ADDS UP TO 6196 MBH. PLEASE CLARIFY. -
 LAST PIPE SECTION TO SPA @ 300 MBH SHALL
 BE 1" NOT 3/4" AS SHOWN. TABLE 402(2). -
 ALL PIPE SECTIONS SHALL SHOW THE LENGTH
 OF EACH SECTION ON THE RISER DIAGRAM.
 SOME SECTIONS DO NOT SHOW A LENGTH.
 21. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (DOWNSTREAM OF REGULATOR).
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 22. SEPARATE GAS PERMIT REQUIRED. AT
 TIME OF APPLICATION, CONTRACTOR SHALL
 SUBMIT A PICTURE I.D. OF THE WELDER,
 WELDING CERTIFICATION, AND A COPY OF THE
 WELDING PROCEDURE.
 23. ALL FLOOR PLAN SHEETS, SHOW THE
 LOCATION & NUMBER OF EACH RISER THRU THE
 BUILDING ON EACH FLOOR PLAN AND EACH
 LEVEL. SECTION 104.2.1.
 24.SHT P-2 RISER DESIGNATIONS 35, 36,
 45, 46, 46A, & 47 ARE NOT SHOWN.
 25. SHT P-2 SHOW THE PIPING FOR ALL
 TRENCH DRAINS WITH PIPE SIZES. THIS
 SHALL BE REFLECTED ON THE STORM RISER
 DIAGRAM. SECTION 104.3.1.1.
 26. GREASE INTERCEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 WASTE ORD. #3434. PLEASE CONTACT LYNN
 MASSON AT (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected].
 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL
 PIPE SIZES. RECALCULATE ADDITION ON SOME
 RWL'S, INDICATE RWL RISER NUMBERS, 3"
 OVERFLOW SHOWN CONNECTING TO PRIMARY
 SYSTEM AT COL. 24 BETWEEN COLS, A&B.
 PLEASE CLARIFY. SECTION 104.2.1. - SHOW
 ALL SECONDARY ROOF DRAINS, WITH PIPE
 SIZES, SF, ECT. INDICATE SF OF DRAIN
 BETWEEN COLS. S.06 & S.05 BETWEEN COLS.
 20 & 21, AND THE DRAIN BETWEEN COLS. H &
 I, AND BETWEEN COLS 18 & 19.
 28. SHT P-4 STATES "3"S FOR CONT. SEE
 P-4 HEALTH CLUB". THIS WAS NOT FOUND ON
 SHT P-4. PLEASE CLARIFY.
 29. SHT P-4 INDICATE WHAT THE
 DESIGNATION FOR "DL" REPRESENTS.
 30. SHT P-7 RISER DESIGNATIONS 35, 36,
 38, 45, 46, & 46A NOT SHOWN. PLEASE SHOW
 ALL RISERS FOR EACH FLOOR LEVEL. SECTION
 104.2.1.
 31. SHT P-7 SANT. PIPING NOT ALLOWED IN
 THE EGRESS STAIRWAY. NFPA-101 SECTION
 7.1.3.2.1(6).
 32. SHT P-8 OFFSETS SHOWN FOR RISERS 6,
 10, 11, 12, 15, & 17, 18, 19, 20 ARE NOT
 SHOWN ON THE RISER DIAGRAMS. SECTIONS
 104.2.1, & 104.3.1.1.
 33. SHT P-9 OFFSETS SHOWN FOR RISERS 42,
 44, 47, 30, 34, 35, 36, 21, 25, 1, AND
 TO TOILET ROOMS RECREATION LEVEL 4 ARE
 NOT SHOWN NO THE RISER DIAGRAMS.
 SECTIONS 104.2.1, & 104.3.1.
 34. SHT P-9SHOW THE TYPICAL PIPING
 LAYOUTS FOR RISERS 16, 22, 28, & 29.
 SECTION 104.3.1.1.
 35. SHT P-9 THE FOLLOWINGPIPING
 LAYOUTS DO NOT REFLECT RISER DIAGRAMS
 44, 47, 42, 40, 39, 20, & 4. SECTION
 104.2.1.
 36. SHT P-13 PIPING FOR THE DWV AND
 STORM SYSTEMS NOT APPROVED IN EGRESS
 STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6)
 AND SECTION 1006.1.3.1.
 37. P-14. CONDENSATE IS INDICATED AS 5'
 SEPARATION FOR THE SUPPORTS. INDICATE
 MATERIAL FOR CONDENSATE PIPING. IF PVC,
 MAXIMUM 4' SEPARATION OF SUPPORTS PER
 TABLE 305.5. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 140 MPH WIND LOAD FOR
 SUPPORTS.
 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON
 RISER DIAGRAM 56, 59A, 92, 93, 94, 95,
 96, 97, 98, 99, & 100.
 39. SHT P-15 PIPING NOT APPROVED IN
 EGRESS STAIRWAYS. NFPA-101 SECTION
 7.1.3.2.1(6).
 40. SHT P-15 RISER DIAGRAM 72 NOT SHOWN
 ON SHEET. SECTION 104.2.1.
 41. SHT P-15 THE FOLLOWING PIPING
 LAYOUTS DO NOT REFLECT THE RISER
 DIAGRAMS: 48, 48A, 49, 50, 51, 56, 58,
 59, 59A, 61, 62, 64, 67, & 67A. - NOT
 ALL PIPING SHOWN ON THE RISER DIAGRAMS.
 SECTION 104.3.1.1.
 42. SHT P-16 NO PIPING TO W/M SHOWN AT
 EITHER SIDE OF STAIRS COL. LINE N.05,
 BETWEEN UNITS NLT103 & NLT104. INDICATE
 WHICH RISERS THESE W/M'S CONNECT TO.
 SECTION 104.2.1.
 43. SHT P-17 MAXIMUM 6' FROM POINT OF
 VENT TO TUB TRAP. (NEAR RISER 95) TABLE
 906.1.
 44. SHT P-17 THE FOLLOWING RISERS DO NOT
 REFLECT PIPING LAYOUT: 50, 51, 52, & 55.
 SECTION 104.2.1.
 45. SHT P-18 INDICATED AS LEVEL (5-15)
 PLEASE CLARIFY.
 46. SHT P-18 RISER 102 INDICATES 3"V DN
 TO RISER #34. THIS IS NOT SHOWN ON SHT
 P-17 NOR ON RISER 102. PLEASE CLARIFY.
 SECTION 104.2.1. - WHAT IS RISER #3W?
 WHERE IS IT LOCATED? SECTION 104.2.1.
 47. SHT P-20 PIPING FOR KIT SINKS NOT
 SHOWN. RISER #61. SECTION 104.3.1.
 48. SHT P-22 CONDENSATE LINE SHOWN AS 5'
 SEPARATION BETWEEN SUPPORTS. INDICATE
 TYPE OF MATERIAL. IF PVC PER TABLE 305.5
 MAXIMUM 4' SEPARATION BETWEEN SUPPORTS.
 SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW
 THEY ARE ATTACHED TO THE ROOF AND SHOW
 COMPLIANCE WITH 140 MPH WIND LOAD.
 49. SHT P-23 BATHROOM MAIN LOBBY LEVEL 1
 SHOWN 36FU, BUT IS SHOWN AS 34FU ON SHT
 P-2. CORRELATE PLANS. SECTION 104.2.1.
 50. SHT P-23 RECREATION AT LEVEL 4
 PIPING DOES NOT REFLECT THE FIXTURE
 LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT
 WITH PIPING LAYOUT. SECTION 104.2.1.
 (RISER DIAGRAM DOES NOT REFLECT FIXTURE
 LAYOUT EITHER).
 51. SHT P-23 RECREATION AT LEVEL 2
 INDICATES 40FU FOR FUTURE GYM, BUT ONLY
 44FU AFTER ADDING MEN'S & WOMEN'S TOILET
 ROOMS. PLEASE RECALCULATE FU'S. (ALSO
 ADJUST ON RISER DIAGRAM). SECTION
 104.2.1.
 52. SHT P-23 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-68". P-68 SHOWS STORM RISER
 ONLY. PLEASE CLARIFY. SECTION 104.2.1.
 53. SHT P-39 FLOOR DRAIN NOT SHOWN
 BETWEEN 1ST & 2ND WLI UNITS FIRST FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1.
 54. SHT P-52 SANT. RISER DIAGRAM UNIT
 TOWNHOME, MAXIMUM 4FU ON 2" WET VENT PER
 TABLE 909.3.
 55. SHT P-52 RISER DIAGRAMS STATE "FOR
 CONT. SEE P-69". CONT. NOT FOUND ON
 P-69. PLEASE CLARIFY. SECTION 104.2.1.
 56. SHT P-53 RISER 13 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - DRY HORIZONTAL VENTS NOT APPROVED 17TH
 FLOOR. SECTIONS 905.3/905.4.
 57. SHT P-53 RISER 8 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 58. SHT P-54 RISER 10 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - HORIZONTAL
 BRANCH CONNECTIONS NOT APPROVED ON THE
 HORIZONTAL OFFSET. SECTION 711.2
 59. SHT P-54 RISER 12 LOWER OFFSET VENT
 REQUIRED. SECTION 915.3. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SECTION 914.1.
 - 4" VENT TO RISER #8 READS "FROM RISER
 8. PLEASE CORRELATE RISERS. SECTION
 104.2.1.
 60. SHT P-54 RISER 14 LOWER OFFSET VENT
 REQUIRED. SEC. 915.3 - MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 61. SHT P-54 RISER 17 LOWER OFFSET VENT
 REQD. SEC. 915.3. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SECT. 914.1.
 62. SHT P-55 RISER 20 BATHROOM SHOWN ON
 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON
 5TH FLOOR ON RISER. CORRELATE RISER AND
 FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH
 FLOOR NOT SHOWN ON RISER. SEC. 104.2.1.
 63. SHT P-55 RISER 22 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 64. SHT P-55 RISER 23 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 LOWER OFFSET VENT REQD. SEC. 915.3.
 65. SHT P-56 RISER 25 SINK MISSING 17TH
 FLOOR. SEC. 402.1.1.
 66. SHT P-56 RISER 26 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO BRANCH CONNECTIONS ON HORIZONTAL
 OFFSET. SEC. 711.2.
 67. SHT P-56 RISER 28 NO HORIZONTAL DRY
 VENTS. SEC. 905.3/905.4 (16TH FLOOR)
 68. SHT P-56 RISER 29 LOWER OFFSET VENT
 REQD. SEC 915.3. - NO CONNECTION TO
 HORIZONTAL OFFSET. SEC. 711.2.
 69. SHT P-56 RISER 30 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4
 70. SHT P-56 RISER 32 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1 -
 NO HORIZONTAL DRY VENTS. SEC.
 905.3/905.4. - UPPER OFFSET VENT REQD.
 SEC. 915.2. - SEPARATE RISER SECTION AT
 BASE OF STACK FOR POWDER ROOM, INDICATE
 RISERS CONNECTING FROM UPSTREAM. (33,
 37, 37A) SEC. 104.2.1.
 71. SHT P-56 RISER 33 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENT. SEC. 905.3/905.4
 - DOES NOT REFLECT FLOOR PLAN @ 4TH
 LEVEL. (BASE OF STACK) SEC. 104.2.1. -
 VENT FROM 1ST FLOOR FLOOR DRAIN NOT
 SHOWN ON RISER. (SEE P-3, P-4, P-67).
 72. SHT P-57. RISERS 39, 40,41, 42, 43,
 44 DO NOT REFLECT THE FLOOR PLANS AT THE
 BASE OF RISER. SEC. 1-4.2.1.
 73. SHT P-57 RISER 42 VENT FROM FIRST
 FLOOR FLOOR DRAINS NOT SHOWN. PLEASE
 CLARIFY. SEC. 104.2.1.
 74. SHT P-58 RISERS 45, 46, 47 DO NOT
 REFLECT FLOOR PLANS FOR 4TH LEVEL.
 SECTION 104.2.1.
 75. SHT P-59 RISER 50 DOES NOT REFLECT
 THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1.
 76. SHT P-59 RISER 51 DOES NOT REFLECT
 THE FLOOR PLAN AT BASE OF RISER AND ON
 THE 4TH LEVEL. PLEASE CLARIFY SEC.
 104.2.1.
 77. SHT P-59 RISER 52 DOES NOT REFLECT
 FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT
 REQUIRED. SEC. 915.2.
 78. SHT P-59 RISERS 53, 55 DO NOT
 REFLECT THE FLOOR PLAN 4TH LEVEL.
 SECTION 104.2.1.
 79. SHT P-60 RISER 56 DOES NOT REFLECT
 THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS
 REQD. SECS. 915.2/915.3. - MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1. - NO CONNECTIONS TO HORIZONTAL
 OFFSET. SEC. 711.2.- NO HORIZONTAL DRY
 VENTS. SECS. 905.3/905.4.
 80. SHT P-60 RISER 58 DOES NOT REFLECT
 THE FLOOR PLAN, CHECK LOCATION OF
 CONNECTION OF RISER 59. - RISER 58 & 61
 NOT TIED TOGETHER ON FLOOR PLAN. - UPPER
 OFFSET VENT REQD. 915.2
 81. SHT P-60 RISER 61 DOES NOT REFLECT
 THE FLOOR PLAN LEVEL 17. SEC. 104.2.1.
 82. SHT P-60 RISER 57 DOES NOT REFLECT
 THE FLOOR PLAN UPPER LEVEL. - MAX 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1.
 83. SHT P-60 RISER 60 DOES NOT REFLECT
 THE FLOOR PLAN. SHOWS CONNECTING TO
 HORIZONTAL DRAIN LINE. (GROUND FLOOR?) -
 UPPER OFFSET VENT REQD. SEC. 915.2. -
 DOES NOT REFLECT THE FLOOR PLAN AT THE
 TOP OF THE RISER. - MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1.
 84. SHT P-61 RISER 62 DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3.
 85. SHT P-61 RISERS 63, 64 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CLARIFY
 SEC. 104.2.1.
 86. SHT P-61 RISER 67 MAX 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO HORIZONTAL DRY VENTS. SECS. 905.3
 905.4.
 87. SHT P-61 RISER 67A DOES NOT REFLECT
 THE FLOOR PLAN. - LOWER OFFSET VENT REQD
 SEC. 915.3.
 88. SHT P-61 RISER 68 FIXTURES NOT SHOWN
 FOR 4TH LEVEL ON THE RISER. PLEASE
 CLARIFLY. SECTION 104.2.1.
 89. SHT P-62 RISER 70 LOWER OFFSET VENT
 REQD. SEC 915.3
 90. SHT P-62 RISER 71 MAX. 10 BRANCH
 INTERVALS TO RELIEF VENT. SEC. 914.1. -
 NO DRY HORIZONTAL VENT. SECS. 905.3
 905.4.
 91. SHT P-62 RISER 72 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 3.
 SECTION 104.2.1.
 92. SHT P-62 RISER 73 & 74 MAX. 10
 BRANCH INTERVALS TO RELIEF VENT. SEC.
 914.1.
 93. SHT P-62 RISER 74A DOES NOT REFLECT
 THE FLOOR PLAN LEVEL 4. SECTION 104.2.1.
 94. SHT P-62 RISER 79 DOES NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT LEVEL 4.
 SEC. 104.2.1.
 95. SHT P-63 RISERS 75,76,77,78,87,88
 DO NOT REFLECT THE FLOOR PLAN PIPING
 LAYOUTS LEVEL 4. SECTION 104.2.1.
 96. SHT P-63 RISER 80 FLOOR DRAIN LEVEL
 16 ROOF NOT SHOWN ON RISER DIAGRAM.
 SECTION 104.2.1. CORRELATE RISER/FLOOR
 PLAN.
 97. SHT P-63 RISERS 89,94,95,99,101,102
 & 103 DO NOT REFLECT THE FLOOR PLANS.
 SECTION 104.2.1.
 98. SHT P-67 HORIZONTAL SANT. RISER
 DIAGRAM MISLABELED AS "WATER RISER
 DIAGRAM". PLEASE CLARIFY. SEC. 104.2.1.
 99. SHT P-67 FOLLOWING ARE CORRECTIONS
 TO BE MADE TO SANT. RISER DIAGRAM: -
 RISERS 35 & 36 NOT SHOWN. - PIPING
 LAYOUT DOWNSTREAM OF RISER 33,37,37 DOES
 NOT REFLECT FLOOR PLAN FOR POWDER ROOM.
 - RISERS 23 & 23A MISLABELED. - 2" VENT
 UP TO RISER 42 NOT SHOWN ON RISER 42. -
 PIPING BETWEEN RISERS 6,10,11,12,15 &
 RISER 9,13 DOES NOT SHOW POWDER ROOM OR
 WASH MACHINE. - OFFSETS & PIPING LAYOUT
 SHOWN ON SHT P-9 ARE NOT SHOWN ON RISER
 DIAGRAM. - NO VENT SHOWN FOR GREASE
 LINE. - GREASE LINE DOES NOT REFLECT THE
 FLOOR PLAN, AND IS NOT SHOWN ON FLOOR
 PLANS P-15 THRU P-18. -4"-34FU FOR CONT.
 SEE P-23 SHOWS 36FU ON SHT P-23.
 CORRELATE SHEETS. - 2" VENT FROM 2 SINKS
 SHOWS 3" VENT ON SHTS P-3, P-4, & P-5.
 CORRELATE SHEETS. - 2" VENT UP TO RISER
 67 TO READ "TO RISER 67A". (SEE RISER
 67A). - "2" VENT FOR CONT. SEE P-53"
 INDICATE RISER VENT WILL CONNECT TO. -
 "UNITS WL1, WL2 & UNITS 1T THRU 10T,
 4"-28FU FOR CONT. SEE P-53. NOT FOUND ON
 SHT P-53. PLEASE CLARIFY - 6" LINE FROM
 RISER 92,93,94,95,96,97,98, 99,100 DOES
 NOT SHOW OFFSET ON RISER SHOWN ON SHT
 P-15. - THIS SHEET SHOWS LEVELS AS PARK,
 PARK 2, PARK 3 ECT., BUT SHEETS P-15,
 P-16. & P-17 SHOWS LEVELS AS GROUND
 FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS
 MEZZ. ECT. PLEASE CLARIFY & CORRELATE
 SHEET LEVELS. - RECHECK ADDITION OF
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SOME FIXTURES UNITS ARE NOT
 SHOWN AND ADDED TO THE SYSTEM. INDICATE
 THE SLOPE OF THE PIPE WHERE THE FIXTURES
 UNITS ARE MORE THAN ALLOWED FOR MINIMUM
 SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE
 INSTALLED IN A UNIFORM SLOPE AS REQUIRED
 IN SECTION 704.1. INDICATE ON PLANS.
 SECTION 104.2.1.
 100. SHT P-68 HORIZONTAL STORM RISER
 DOES NOT REFLECT STORM PIPING IN
 BUILDING. STRUCTURES S1 THRU S9 NOT
 SHOWN. - NO ROOF DRAINS 2650SF, 2350SF,
 2450SF ECT. FOUND. - NO EXFILTRATION
 TRENCHES FOUND. - NO TRENCH DRAINS
 FOUND, RISERS SHOWS 25TH, 26TH, 27TH
 FLOORS ECT. - NO POINT OF REFERENCE TO
 FLOOR PLAN CAN BE FOUND. - RISER HARD TO
 READ, PLEASE INCREASE THE SIZE OF THE
 STORM RISER DIAGRAM AND POSSIBLY SPLIT
 UP TO TWO PAGES TO MAKE RISER EASIER TO
 READ. SECTION 104.2.1.3.
 101. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES AND INDICATE
 MATERIAL. SECTION 104.3.1.1.
 102. SUBMIT A P/T VALVE DISCHARGE RISER
 DIAGRAM SHOWING ALL PIPE SIZES AND
 INDICATE PIPING/FITTING MATERIAL.
 SECTION 104.3.1.1.
 103. SUBMIT AN EMERGENCY PAN DRAIN RISER
 DIAGRAM FOR THE WATER HEATERS. INDICATE
 PIPE SIZES AND MATERIAL FOR PIPE AND
 FITTINGS.
 104. BACKFLOW PROTECTION REQUIRED FOR
 IRRIGATION, POOLS, TRASH CHUTE WASH
 DOWN, AND COOLING TOWER MAKE UP WATER.
 SECTION 608. INDICATE METHOD OF
 PROTECTION FOR EACH SYSTEM.
 105. PLANS ARE INCOMPLETE AT THIS TIME
 AND MORE COMMENTS MAY BE FORTHCOMING
 WITH THE NEXT REVIEW.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****************************************
 ****************************************
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-24 Cont ID  
Sent By eschneid Date 2006-07-24 Time 09:37 Rev Time 0.00
Received By eschneid Date 2006-07-24 Time 09:37 Sent To  
Notes
2006-07-28 00:00:001) THE BUILDING FOOTPRINT AND POOL DECK
 DOES NOT MATCH THOSE APPROVED BY ORD.
 NO. 3804-04.A MINOR AMENDMENT APPROVAL
 IS REQUIRED FOR THE NEW LAYOUT.
  
 2) PARKING DETAILS FOR REGULAR, COMPACT
 AND DISABLED SPACES AT ALL ANGLES ARE
 REQUIRED.WHEEL STOPS ARE TO BE TWO
 FEET FROM THE END OF THE SPACE TO THE
 EDGE OF THE WHEEL STOP PER CITY ZONING
 REGULATIONS.PARKING SPACES SHALL BE
 STRIPED FOR THE ENTIRE DEPTH OF THE
 PARKING SPACE.THIS NEEDS TO BE
 CORRECTED NOT ONLY ON THE DETAIL BUT
 ALSO THE PARKING SPACE SHEETS.
  
 3) SPACES 1-037, 1-038 AND 1-039 ON
 SHEET A 1.02 P2; 2-037, 2-038 AND 2-040
 (ANGLED) ON SHEET A 1.03 P2; AND 3-037,
 3-038 AND 3-039 ON SHEET A 1.04 P2 DO
 NOT HAVE THE WHEEL STOPS IN THE CORRECT
 LOCATIONS (REPEAT COMMENT).THE ANGLE
 SHALL BE STATED ON THE PLANS AND PARKING
 DETAIL.
  
 4) ALL AREAS BETWEEN SUPPORT COLUMNS
 THAT ARE NOT PARKING SPACES (TOO NARROW)
 SHALL BE MARKED AS ?NO PARKING.?
  
 5) SPACE 2-039 LABELED AS 2-040.SPACES
 ON THE RAMPS MISLABELED. TWO SPACE
 3-133, NO SPACE 3-139.SPACES 3-044 TO
 3-050 IN MIDDLE AISLE ARE MISLABELED.
  
 6) VERIFY THE TURNING RADIUS WORKS FOR
 SUVS ON LEVELS 2 AND 3 IN THE NORTHEAST
 CORNER OF THE GARAGE.
  
 7) PARKING COUNT CHART ON SHEET A0.02
 SHALL BREAK DOWN THE SMALL SPACES ON
 EACH LEVEL AND PER THE PARKING DIRECTOR
 THE VALET SPACES (NOTE - NOT ALL VALET
 SPACES MAY BE SMALL SPACES).THE
 PARKING COUNTS ARE INCORRECT.SEE
 BELOW:
  
 A) THE SMALL SPACE MARKED AS 1-076 MAY
 NOT BE COUNTED AS A SPACE OF ANY KIND AS
 IT HAS SUPPORT COLUMNS ON EITHER SIDE OF
 THE SPACE ENTRANCE WITHOUT SUFFICIENT
 WIDTH TO FUNCTIONALLY USE.THIS REDUCES
 THE PROVIDED PARKING BY 1 SPACE - 204 +
 2 HC ON 1ST LEVEL.
  
 B) THERE ARE NO SPACES 2-066 AND 2-067,
 AND SPACE 2-050 DOES NOT HAVE ADEQUATE
 BACK OUT AREA.HC SPACES 201 AND 202
 ARE NOT SHOWN AT THE REQUIRED 12 FEET
 WIDTH. THIS REDUCES THE PROVIDED PARKING
 BY 3 SPACES AND 2 HC SPACES - 154 + 2 HC
 ON 2ND LEVEL.
  
 C) HC SPACES 301 AND 302 ARE NOT SHOWN
 AT THE REQUIRED 12 FEET WIDTH. THIS
 REDUCES THE PROVIDED PARKING BY 2 HC
 SPACES - 2 HC ON 3RD LEVEL.
  
 D) ONLY 153 PARKING SPACES ARE PROVIDED
 ON THE 3RD LEVEL, NOT 161 AS STATED.
  
 8) TOTAL PARKING PROVIDED IN THE GARAGE
 IS 605 SPACES (UNKNOWN ON-STREET
 PARKING).OF THESE 74 ARE SMALL SPACES
 AND 6 SPACES ARE HANDICAP SPACES.THE
 ADDENDUM SHEET TO ORD. NO. 3804-04,
 SECTION 6, STATES THAT THERE ARE 704
 PARKING SPACES REQUIRED.CHANGING
 (LOWERING) THE AMOUNT OF REQUIRED
 PARKING MAY ONLY BE APPROVED BY THE CITY
 COMMISSION THROUGH THE MAJOR AMENDMENT
 PROCESS.
  
 9) THE REQUIRED PARKING SHALL BE
 CALCULATED USING THE FORMULA APPROVED BY
 ORD. NO. 3804-04, NOT THE INCORRECT
 FORMULA INCLUDED ON SHEET A0.02.
 10) WHAT ARE THE SPACES LISTED AS 1-S01,
 1-S02 AND 1-S03 ON SHEET A 1.02?WHY
 ARE THESE NOT INCLUDED IN THE PARKING
 COUNTS?THESE NEED TO SHOW MORE DETAILS
 (SPACE SIZE AND ANGLE AND DRIVE AISLE
 WIDTH).
  
 11) ADJUST THE CURBING BY THE PARALLEL
 SPACES BY THE WEST ENTRANCE ISLAND TO
 HAVE 45 DEGREE ANGLES FOR EASIER PARKING
 (REPEAT COMMENT).THE ENDS OF THE
 OUTSIDE SPACES SHOULD HAVE THE 45 DEGREE
 ANGLE, LIKE THE PARKING SPACES
 ON-STREET.
  
 12) PROVIDE A PLAN SHOWING THE
 DIMENSIONS AND COUNTS OF THE PROPOSED
 ON-STREET PARKING SPACES.ADDITIONALLY,
 PROVIDE A LETTER FROM THE CITY?S
 ENGINEERING AND PARKING DEPARTMENTS
 APPROVING THE SIZE AND LOCATION OF THE
 SPACES, INCLUDING ANY HANDICAP SPACE
 REQUIRED AND PROVIDED.
  
 14) PER THE CONSTRUCTION SERVICES
 DEPARTMENT, THERE NEED TO BE HANDICAP
 PARKING SPACES PROVIDED THAT MAY BE SELF
 PARKED.
  
 15) THE ENTRY GATE ON 23RD STREET HAS
 BEEN MOVED TO SHORTEN THE STACKING
 DISTANCE FROM WHAT WAS APPROVED IN ORD.
 NO. 3804-04.EITHER REVISE THE BUILDING
 PERMIT PLANS OR A MINOR AMENDMENT
 APPROVAL IS REQUIRED.
  
 16) NO CIVIL AND LANDSCAPE PLANS
 INCLUDED TO REVIEW.ANY CHANGES TO THE
 LANDSCAPE PLAN FROM ORD. NO. 3804-04
 WOULD REQUIRE MINOR AMENDMENT APPROVAL.
  
 17) SIGN ON PLANS DOES NOT MATCH
 APPROVED SIGN FROM ORD. NO. 3804-04.
 MINOR AMENDMENT APPROVAL REQUIRED.
  
 18) A CHART SHOWING THE UNIT BREAKDOWN
 IS REQUIRED.
  
 19) WHY ARE ONLY THE 14 TOWNHOUSE TYPE
 UNITS AND NOT THE 5 LIVE WORK UNITS
 EXCLUDED FROM THE FHA HANDICAP PARKING
 REQUIREMENTS?
  
 20) PLEASE NOTE THAT IF A MAJOR
 AMENDMENT IS PURSUED, THEN THE MINOR
 AMENDMENT ITEMS WILL BE INCLUDED WITH
 THE MAJOR AMENDMENT.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.
2006-07-24 00:00:00NOTES FORTHCOMING.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-27 Cont ID  
Sent By eschneid Date 2006-01-27 Time 11:00 Rev Time 0.00
Received By eschneid Date 2006-01-11 Time 9:03 Sent To  
Notes
2006-01-27 00:00:001) THE BUILDING FOOTPRINT AND POOL DECK
 DOES NOT MATCH THOSE APPROVED BY ORD.
 NO. 3804-04.PROVIDE A PLAN SHOWING THE
 DIFFERENCES.DEPENDING ON THE SCALE OF
 THE CHANGES, EITHER A MINOR OR MAJOR
 AMENDMENT WILL BE REQUIRED.
  
 2) PARKING DETAILS FOR REGULAR, COMPACT
 AND DISABLED SPACES ARE REQUIRED.
  
 3) ALL DRIVE AISLES HAVING 90 DEGREE
 PARKING STALLS REQUIRE A 24 FOOT WIDTH.
 THIS STANDARD IS NOT MET ON THE NORTHERN
 AND WESTERN MOST PARKING AISLES ON
 LEVELS 1, 2 AND 3 AND THE EASTERNMOST
 AISLES ON LEVELS 2 AND 3.
  
 4) COMPACT SPACES SHALL BE CLEARLY
 MARKED ON ALL SHEETS.
  
 5) THE PARKING SPACE LABELS/COUNTS ON
 SHEET A1.02 ARE INCORRECT AND
 MISLABELED.
  
 6) SUPPORT COLUMNS MAY NOT BE LOCATED IN
 THE DOUBLE STRIPED AREA ON BOTH SIDES OF
 A REGULAR SPACE AS THIS RENDERS THE
 SPACE TOO NARROW TO PROVIDE ADEQUATE
 TURNING RADIUS.
  
 7) THE SPACE LABELS AS 1-233 DOES NOT
 ALLOW FOR ADEQUATE TURN RADIUS TO USE.
 THE WALL BY THE SPACE BLOCKS THE ABILITY
 OF SPACES 1-233 AND 1-234 TO SAFELY BACK
 OUT.
  
 8) THE STOP BARS AT THE ANGLED SPACES BY
 THE ENTRANCE ARE INCORRECTLY PLACED.
  
 9) 13 DISABLED SPACES, NOT 9 ARE
 REQUIRED FOR THE PROJECT.
  
 10) LOCATION OF STOP BARS INCORRECT FOR
 COMPACT SPACES.
  
 11) SPACE 1-196 TOO NARROW.SPACE 1-236
 MARKED INCORRECTLY.SPACE 1-035 IS NOT
 DEEP ENOUGH.
  
 12) WALLS ENCROACH INTO SPACES 1-047,
 1-048, 1-065, 1-066, 1-068, 1-069,
 1-086, 1-087, 1-104, 1-105, 1-122,
 1-123, 1-125, 1-126, 1-143, 1-144,
 1-166, 1-167, 1-178, 1-179, 1-184,
 1-185, 1-204 AND 1-205.
  
 13) ADJUST THE CURBING BY THE PARALLEL
 SPACES BY THE WEST ENTRANCE ISLAND TO
 HAVE 45 DEGREE ANGLES FOR EASIER
 PARKING.
  
 14) SPACES 2-001, 2-002, 2-053, 2-092,
 2-131, 2-172, 2-206 AND 2-207 HAVE
 COLUMNS INTRUDING IN THEM.
  
 15) THE DISABLED ACCESS WAY BY SPACE
 2HC-004 HAS COLUMNS INTRUDING IN IT.
  
 16) SPACE 2-037 IS NOT DEEP ENOUGH.
 SPACES 2-198 AND 2-199 ARE NOT STRIPED
 CORRECTLY.
  
 17) THE SPACE LABELED AS 2-202 MAY NOT
 BE COUNTED AS IT DOES NOT CONFORM TO ANY
 OF THE CODE REQUIREMENTS.
  
 18) THE WALL ADJACENT TO SPACE 2-202
 SPACE BLOCKS THE ABILITY OF SPACES 2-202
 AND 2-203 TO SAFELY BACK OUT.THE WALL
 ALSO EXTENDS INTO THE DRIVE AISLE.
  
 19) THE COLUMN ADJACENT TO SPACE 2-036
 EXTENDS INTO THE DRIVE AISLE.
  
 20) THE COLUMN BETWEEN SPACES 2-198 AND
 2-199 EXTENDS INTO THE DRIVE AISLE.
  
 21) WALLS ENCROACH INTO SPACES 2-049,
 2-050, 2-070, 2-071, 2-088, 2-089,
 2-127, 2-128, 2-168, 2-169, 2-180, AND
 2-181.
  
 22) SPACES 3-001, 3-002, 3-053, 3-122,
 3-161 AND 3-162 HAVE COLUMNS INTRUDING
 IN THEM.
  
 23) SPACE 3-037 IS NOT DEEP ENOUGH.
 SPACES 3-148 AND 3-149 ARE NOT STRIPED
 CORRECTLY.
  
 24) THE WALL ADJACENT TO SPACE 3-152
 SPACE BLOCKS THE ABILITY OF SPACES 3-152
 AND 3-153 TO SAFELY BACK OUT.THE WALL
 ALSO EXTENDS INTO THE DRIVE AISLE.
  
 25) THE COLUMN ADJACENT TO SPACE 3-036
 EXTENDS INTO THE DRIVE AISLE.
  
 26) THE COLUMN BETWEEN SPACES 3-148 AND
 3-149 EXTENDS INTO THE DRIVE AISLE.
  
 27) WALLS ENCROACH INTO SPACES 3-049,
 3-050, 3-067, 3-068, 3-070, 3-071,
 3-088, 3-089, 3-108, 3-109, 3-118,
 3-119, 3-130, 3-131, 3-136 AND 3-137.
  
 28) IT APPEARS THAT THE RETAINING WALL
 ATTACHED TO THE BUILDING IS OUTSIDE OF
 THE PROPERTY LINE ON THE NORTH SIDE OF
 THE SITE AND MAY BE AN ISSUE IN THE
 SOUTHEAST CORNER.ALL RETAINING WALLS,
 PLANTER BOXES AND OTHER FEATURES
 ATTACHED TO THE BUILDING SHALL BE INSIDE
 THE PROPERTY LINE NOT IN THE PUBLIC
 RIGHT-OF-WAY.ENSURE THAT THIS
 REQUIREMENT IS MET AROUND THE ENTIRE
 BUILDING.SHOW THE PROPERTY LINES ON
 THE ELEVATIONS TO VERIFY THERE IS NO
 ENCROACHMENT.
  
 29) A LANDSCAPE PLAN AND A SURVEY
 SHOWING THE BUILDING FOOTPRINT ARE
 REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By eschneid Date 2005-09-28 Time 09:58 Rev Time 0.00
Received By eschneid Date 2005-09-28 Time 09:57 Sent To  
Notes
2005-09-28 00:00:001) 900 SQUARE FEET ON 23RD ST. & FLAGLER
 NEEDS TO BE DEDICATED ON SITE PLAN (SEE
 COND. #8 OF ORD. NO. 3804-04)
 2) PLANS SHALL INDICATE THAT THE
 STREETSCAPE WILL COMPLY WITH THE CMUD
 MASTER STREETSCAPE PLAN.
 3) PLANTER BOXES ALONG THE BASE OF THE
 BUILDING ARE SHOWN IN THE PUBLIC
 RIGHT-OF-WAY. THESE NEED TO BE MOVED
 ONTO THE PROPERTY, UNLESS THEY ARE PART
 OF THE CMUD MASTER STREETSCAPE PLAN. ANY
 PLANTER BOXES OR OTHER MATERIAL LOCATED
 IN THE RIGHT-OF-WAY AS PART OF THE CMUD
 MASTER STEETSCAPE PLAN MAY NOT BE
 ATTACHED TO THE BUILDING.
 4) NO C.O. WILL BE ISSUED FOR THE
 PROJECT UNTIL PICADILLY CIRCLE PARK IS
 APPROVED BY A FACE OF THE CITY
 RESOLUTION AND THE PARK IS COMPLETED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.