Plan Review Details - Permit 05071014
Plan Review Stops For Permit 05071014
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 17:23 Rev Time 0.50
Received By shill Date 2005-07-25 Time 17:23 Sent To Z
Notes
2005-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE VOID PERMIT #05051023 AS YOU
 HAVE NOW APPLIED FOR THE SAME SCOPE OF
 WORK UNDER A DIFFERENT PERMIT NUMBER.
  
 2.)PROVIDE CURRENT STRUCTURAL PLANS
 FOR THE SCREEN ROOM ADDITIONK,
 FBC104.2.1, 104.3.1.1, CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FBC.INCLUDE
 DESIGN CRITERIA FBC1606.1.7.
  
 3.)THE OLD ENGINEERING DATED 5/6/04
 CANNOT BE USED DUE TO THE FOLLOWING:
  
 A.)THE SCREEN ENCLOSURE PLAN DOES NOT
 HAVE A TITLE BLOCK FAC61G15-23.002.
  
 B.)THE COMPANY ANDREW MORGAN SERVICES
 IS REQUIRED TO HAVE A CERTIFICATE OF
 AUTHORIZATION.BOTH THE CA NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT ARE TO BE ON THE PLAN.
  
 C.)THE PLANS WERE PREPARED PRIOR TO
 THE HURRICANES OF SEPTEMBER 2004.AFTER
 THE FAILURE OF MANY SCREEN ENCLOSURES IT
 WAS DETERMINED THAT MANY ENGINEERS HAD
 BEEN USING THE 1/3 STRESS INCREASE WHICH
 IS NOT ALLOWED FBC1609.4.3(2).IF MR.
 ANDREW RECERTIFIES THE SAME ENGINEERING
 WITH A NEW DATE, HAVE HIM INCLUDE A NOTE
 INDICATING THAT HE HAS DESIGNED THIS
 ENCLOSURE WITHOUT THIS STRESS INCREASE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved