Plan Review Details - Permit 05071011
Plan Review Stops For Permit 05071011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By spalmer Date 2005-09-12 Time 14:53 Rev Time 0.00
Received By spalmer Date 2005-09-12 Time 14:53 Sent To  
Notes
2005-09-12 00:00:00OKAY PER JIM WITMER ON PINK SLIP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By jwitmer Date 2005-07-28 Time 15:32 Rev Time 1.22
Received By jwitmer Date 2005-07-28 Time 15:32 Sent To  
Notes
2005-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071011
 ADD: 4 HARVARD CIR# 800
 CONT: MARFRAK CONST
 TEL: (561)736-0313
 BLD CODE= 2001 FLORIDA BUILDING CODE *
 WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SUITE# 800 SEE DORS ON 45% ANGLE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) SEE ELEC COMMENTS ABOUT CERTIFICATE
 OF AUTHERIZATION REQUIREMENTS UNDER FL S
 S 481.219.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 14:41 Rev Time 0.25
Received By dpalmer Date 2005-08-30 Time 14:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 20:48 Rev Time 0.30
Received By dpalmer Date 2005-07-26 Time 20:48 Sent To  
Notes
2005-07-26 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON ARCHITECT'S
 TITLE BLOCK FOR FIRM.
 PLEASE SEE FAC61G1-16.004, FS 481.219
 FOR REQUIRE CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS IS REQUIRED OF ALL TRADES
 AND FOR ALL SHEETS WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE SEE TRADE SHEETS SEEM TO SHOW
 KAMM CONSULTING AS TAKING PLACE OF
 "NICHOLS/ PAGE"??
 PLEASE SEE TITLE BLOCK ALSO SHOWS KAMM
 AS ARCHITECTS'/DESIGNERS"??
 PLEASE CORRECT TITLE BLOCKS.
  
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By jwitmer Date 2005-09-12 Time 15:07 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-09-12 00:00:00OK TO ISSUE PER M. CARSILLO 9-12-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 09:57 Sent To  
Notes
2005-08-02 00:00:00******DENIED******
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) PLEASE SHOW THE LOCATIONS OF NEW OR
 EXISTING ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING FACILITIES.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 18:40 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 18:40 Sent To  
Notes
2005-08-24 00:00:00TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 18:39 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 14:49 Sent To  
Notes
2005-07-26 00:00:00TO "BOB"#5
2005-07-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-02 Cont ID  
Sent By hmoser Date 2005-08-02 Time 18:30 Rev Time 0.00
Received By hmoser Date 2005-08-02 Time 18:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 09:28 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 09:22 Sent To M
Notes
***NONE***