Plan Review Details - Permit 05071010
Plan Review Stops For Permit 05071010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-16 Cont ID  
Sent By jwitmer Date 2005-09-16 Time 07:48 Rev Time 0.66
Received By jwitmer Date 2005-09-16 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By jwitmer Date 2005-07-28 Time 16:22 Rev Time 1.22
Received By jwitmer Date 2005-07-28 Time 16:22 Sent To  
Notes
2005-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071010
 ADD: 5 HARVARD CI.
 CONT: MARFRAK CONST
 TEL: (561)736-3622
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SEE ELEC COMMENTS REGUARDING THE
 CERTIFICATE OF AUTHERIZATION FL S S
 481.219.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) EXISTING DOORS WITH 45% OPENINGS SEE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 12:25 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 12:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 20:30 Rev Time 0.30
Received By dpalmer Date 2005-07-26 Time 20:30 Sent To  
Notes
2005-07-26 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON ARCHITECT'S
 TITLE BLOCK FOR FIRM.
 PLEASE SEE FAC61G1-16.004, FS 481.219
 FOR REQUIRE CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS IS REQUIRED OF ALL TRADES
 AND FOR ALL SHEETS WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 THIS IS NOT A COMMENT FOR KAMM
 CONSULTING ENG'S.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS THE WORK FOR NEW BATH ONLY. NO
 OTHER ELECTRICAL NEEDS TO BE SHOWN BUT
 IS OK.
 PLEASE SEE HOWEVER ALL RECEPTS(EXSITING)
 AND NEW ARE SHOWN ON ONE CIRCUIT??
 PLEASE SEE 220.11, A MIN OF 180VA SHALL
 BE FIGURED FOR ALL OUTLETS IN OTHER THAN
 DWELLING UNITS. PLEASE SEE SINGLE
 CIRCUIT SHOWN EXCEEDS 20A CAPACITY.
  
 PLEASE ADJUST.
  
 PLEASE REMOVE ANY OL/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-16 Cont ID  
Sent By mwennerg Date 2005-09-16 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2005-09-16 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 15:43 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 15:43 Sent To  
Notes
2005-08-02 00:00:00******DENIED******
  
 1) APPLICATION INDICATES SCOPE OF WORK
 LIMITED TO THE BATHROOM ONLY. IF THIS
 NEEDS CLARIFICATION, PLEASE ADVISE.
  
 2) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101,
 "2003" EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 16:26 Sent To  
Notes
2005-09-07 00:00:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-16 Cont ID  
Sent By mwennerg Date 2005-08-04 Time   Rev Time 0.00
Received By mwennerg Date 2005-07-25 Time 14:56 Sent To  
Notes
2005-07-26 00:00:00TO "BOB" #4
2005-07-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 16:14 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 16:08 Sent To  
Notes
2005-08-03 00:00:00NO PLANS HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By jleech Date 2005-09-14 Time 14:49 Rev Time 0.75
Received By jleech Date 2005-09-14 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 15:02 Rev Time 0.75
Received By jleech Date 2005-08-04 Time 14:53 Sent To  
Notes
2005-08-04 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE 1
 MISSING INFORMATION.
 2.PERMIT APPLICATION DISCRIPSION BLOCK (
 ADDING TOILET) P-2.1 SHOWS ONLY ADDING A
 LAV. NEED FOTHER EXPLANATION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6685
  
  
  
  
  
  
  
  
  
  
  