Plan Review Details - Permit 05070949
Plan Review Stops For Permit 05070949
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-10 Cont ID  
Sent By kconrad Date 2006-02-10 Time 18:31 Rev Time 1.00
Received By kconrad Date 2006-02-07 Time 19:58 Sent To I
Notes
2006-02-10 00:00:00HIRSCH CONSTRUCTION CORP.
 PERMIT #05070949/COM-REMODEL
  
 ADVISED THE ARCHITECT OF RECORD TO
 SUBMIT THIS PLAN AFTER A PREVIOUS
 INSPECTION OF THE STORE FRONT
 FRAMING.THIS PLAN SHALL REFLECT THE
 STORE FRONT FRAMING CURRENTLY INSTALLED.
 A REINSPECTION OF THE SAME SHALL BE
 PERFORMED PRIOR TO DRYWALL/WALL
 SHEATHING INSTALLATION AS PER THE FBC
 109.1/109.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 08:27 Rev Time 0.50
Received By jwitmer Date 2005-12-01 Time 12:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-03 Cont ID  
Sent By jwitmer Date 2005-10-03 Time 13:58 Rev Time 2.22
Received By jwitmer Date 2005-10-03 Time 11:41 Sent To  
Notes
2005-10-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070949
 ADD: 701 S ROSEMARY # 145
 CONT: HIRSCH CONSTTRUCTION
 TEL: (978)979-1174
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 THIS DOCUMENT HAS NOT APPEARED THIS
 REVIEW.
  
 2) COMMENT FROM ELECTRICAL DEALING WITH
 CERTIFICATE OF AUTHORIZATION REQUIRED
 FOR THE KPFF CONSULTING ENGINEERS.S1.0.
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 15:26 Rev Time 2.22
Received By jwitmer Date 2005-08-27 Time 15:16 Sent To PC
Notes
2005-08-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070949
 ADD: 701 S ROSEMARY # 145
 CONT: HIRSCH CONSTTRUCTION
 TEL: (978)979-1174
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CORRECT THE ADDRESS ON BOTH THE
 APPLICATION AND ON THE PLANS.
  
 3) SEE ELECTRICAL & PLUMBING NOTES FOR:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 STRUCTURAL CALCULATIONS PROVIDED
 INDICATE THAT INPUT PROPERTIES THE STUDS
 WILL HAVE HOLES PUNCHED 1.5"X 4.0" WHERE
 AS THE INPUT PARAMETERS INDICATE THAT
 THE SHEAR AND WEB CRIPPLING CAPACITY IS
 BASED ON " UNPUNCHED WEBS".CLARIFY?
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 THE ZELUCK PRODUCT APPROVALS DO NOT
 APPEAR ON THE FLORIDA WEB SITE. EITHER
 NEW PRODUCT APPROVALS ARE TO BE
 SUBMITTED OR SUBMIT FOR LOCAL WITH THIRD
 PARTY QUALITY ASSURANCE PROGRAM THAT IS
 LISTED WITH THE STATE. SEE LOCAL
 APPLICATION ATTACHED.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 WINDOWS
 DOORS
 EFIS SYSTEMS
  
 6)11-4.35 DRESSING AND FITTING ROOMS.
  
 11-4.35.1 GENERAL. DRESSING AND
 FITTING ROOMS REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.35
 AND SHALL BE ON AN ACCESSIBLE ROUTE.
  
 11-4.35.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN
 SHALL BE PROVIDED IN EVERYACCESSIBLE
 DRESSING ROOM ENTERED THROUGH A SWINGING
 OR SLIDING DOOR.NO DOOR SHALL SWING
 INTO ANY PART OF THE TURNING SPACE.
 TURNING SPACE SHALL NOT BE REQUIRED IN A
 PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 IN.(815
 MM) WIDE IF CLEAR FLOOR SPACE COMPLYING
 WITH 11-4.2 RENDERS THE DRESSING ROOM
 USABLE BY A PERSON USING A WHEELCHAIR.
  
 11-4.35.3 DOORS. ALL DOORS TO ACCESSIBLE
 DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH ?11-4.13.
  
 11-4.35.4 BENCH. EVERY ACCESSIBLE
 DRESSING ROOM SHALL HAVE A 24 IN. BY
 48 IN.(610 MM BY 1220 MM) BENCH FIXED
 TO THE WALL ALONG THE LONGER DIMENSION.
 THE BENCH SHALL BE MOUNTED 17 IN. TO 19
 IN.(430 MM TO 485 MM) ABOVE THE FINISH
 FLOOR.CLEAR FLOOR SPACE SHALL BE
 PROVIDED ALONGSIDE THE BENCH TO ALLOW A
 PERSON USING A WHEELCHAIR TO MAKE A
 PARALLEL TRANSFER ONTO THE BENCH.THE
 STRUCTURAL STRENGTH OF THE BENCH AND
 ATTACHMENTS SHALL COMPLY WITH 11-4.26.3.
  
 11-4.35.5 MIRROR. WHERE MIRRORS ARE
 PROVIDED IN DRESSING ROOMS OF THE SAME
 USE, THEN IN AN ACCESSIBLE DRESSINGROOM,
 A FULL-LENGTH MIRROR, MEASURING AT LEAST
 18 IN. WIDE BY 54 IN. HIGH (460 MM BY
 1370 MM), SHALL BE MOUNTED IN A POSITION
 AFFORDING A VIEW TO A PERSON ON THE
 BENCH AS WELL AS TO A PERSON IN A
 STANDING POSITION.
  
 7)SHEET A2.1 FLAME SPREAD NOTES REFRENCE
 THE UBC CODE TABLE 8-B, CORRECT.
  
 8) SHEET A2.2 REFRENCES A HANDICAPPED
 SIGNAGE PER ADA, SEE CHAPTER 11 FL BLDG
 CODE.
 THE TEXT ENCLOSED IN SHADED BOXES
 INDICATES CHANGES TO THE ADA
 ACCESSIBILITY GUIDELINES (ADAAG).
 CHANGES ARE BASED ON REQUIREMENTS
 ESTABLISHED BY FLORIDA LAW AND
 REQUIREMENTS ESTABLISHED BY 28 CFR 36
 SUBPART A AND D.
  
  
 11-1.1THIS CODE SHALL TAKE EFFECT
 OCTOBER 1, 1997.
  
 11-1.2 ALL NEW OR ALTERED BUILDINGS AND
 FACILITIES SUBJECT TO THIS CODE
 WHICH MAY BE FREQUENTED IN, LIVED IN, OR
 WORKED IN BY THE PUBLIC SHALL
 COMPLY WITH THIS CODE.
  
 11-1.3 THIS CODE ESTABLISHES STANDARDS
 FOR ACCESSIBILITY TO PLACES OF
 PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH
 DISABILITIES.THIS CODE SHALL ALSO
 APPLY:TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO ?553.503, FLORIDA
 STATUTES; TO PRIVATE CLUBS
 PURSUANT TO ?553.505, FLORIDA STATUTES;
 AND TO RESIDENTIAL BUILDINGS
 PURSUANT TO ?553.504(2), FLORIDA
 STATUTES.IT IS TO BE APPLIED DURING
 THE DESIGN, CONSTRUCTION, AND ALTERATION
 OF SUCH BUILDINGS AND FACILITIES
 AS REQUIRED BY SECTIONS 553.501-553.512,
 FLORIDA STATUTES.
  
 9) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A2.1 DETAIL 4 & 5 INDICATE AN
 EQUIPMENT PLATFORM, DOES THIS PLATFORM
 CONTINUE OVER THE RESTROOM? PROVIDE THE
 LOADING OF THIS PLATFORM?
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 10) SHEET A3.0 EXTERIOR TRIM , NO WOOD
 EXTERIOR TRIM ALLOWED. SEE:
 1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS
 OF TYPE I, II AND IVCONSTRUCTION NOT
 MORE THAN THREE STORIES OR 40 FT (12.2
 M) HIGH MAY BE OFTYPE VI
 CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGSOF TYPE
 III, V AND VI CONSTRUCTION.TRIM SHALL
 BE SECURED TO THE WALL WITH METAL OR
 OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURALTRIM IS LOCATED
 ALONG THE TOP OF EXTERIOR WALLS, IT
 SHALL BE COMPLETELYBACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIORWALLS.
  
 11) NOTE TRIM ON PAGE 11 INDICATES WOOD
 TRIM.
 NOTE:803.4 FOAM PLASTICS. FOAM PLASTICS
 SHALL NOT BE USED AS INTERIOR FINISH.
  
 EXCEPTION: FOAM PLASTIC TRIM, DEFINED
 AS PICTURE MOLDS, CHAIR RAILS,
 BASEBOARDS, HANDRAILS, CEILING BEAMS,
 DOOR TRIM AND WINDOW TRIM SHALL BE
 PERMITTED TO BE USED PROVIDED:
  
 1. THE MINIMUM DENSITY IS 20 LB/CU FT
 (320 KG/M^3).
  
 2. THE MAXIMUM THICKNESS OF THE TRIM
 IS 1/2 INCH (12.7 MM) AND THE
 MAXIMUM WIDTH IS 4 INCHES (102 MM).
  
 3. THE TRIM CONSTITUTES NO MORE THAN
 10 PERCENT OF THE AREA OF ANY WALL
 OR CEILING.
  
 4. THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84.
 THE SMOKE DEVELOPED RATING IS NOT
 LIMITED.
  
 12)A9.0 INDICATES WOOD SUB BUCKS
 609.2.1 TYPE I AND TYPE II CONSTRUCTION.
 PARTITIONS SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS.
  
 13) A9.1 DETAILS INDICATE USE OF WOOD IN
 CONCEALED SPACES:
 707.1 CONCEALED SPACES IN TYPES I, II
 AND IV CONSTRUCTION.COMBUSTIBLES
 SHALL NOT BE PERMITTED IN CONCEALED
 SPACES OF TYPES I, II OR IV
 CONSTRUCTION.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 16:21 Sent To  
Notes
2005-11-30 00:00:00REDLINED:
  
 COVER SHEETS STILL REFLECT 1999 NEC,
 HOWEVER THIS WAS CORRECTED ON ELECTRICAL
 PLANS.
  
 PLEASE KNOW NOC SUBMITTED RECORDED IN
 JULY 05 HAS SINCE EXPIRED AND WILL ONLY
 NEED TO BE RE-RECORDED. FS 713.13(2) IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORD SUCH NOTICE, THEN NOTICE SHALL BE
 VOID.
  
  
  
 ** ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-11 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 23:47 Rev Time 0.40
Received By dpalmer Date 2005-09-10 Time 23:42 Sent To  
Notes
2005-09-10 00:00:00********** UNSAT 2ND REVIEW ***********
  
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE:
 A)PLEASE SEE MISSING REQUIRED
 INFORMAITON ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 FIRM. FAC 61G1-16.004 AND FS 481.219
  
 ***************************************
 PLEASE SEE THIS WAS NOT CORRECTED AN D
 TITLE BLOCKS FOR ALL FIRMS ARE STILL
 MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATIONS NUMBERS FOR SAID FIRMS AS
 REQUIRED PER ABOVE REFERENCE FLORIDA
 STATUES AND FLORIDA AMINISTRATIVE CODES.
 ***************************************
  
 B)PLEASE SEE MISSING INFORMATION FOR
 ENGINEERING FIRM. MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE THAT ALL SETS SHALLCONTAIN
 ORIGINAL SIGNATURE, DATE AND RAISED
 SEALED.
 PLEASE SEE ABOVE REQUIRED UNDER FAC
 61G15-23.002, FS 471.023 AND FS 471.025
 *** PLEASE SEE THIS WAS NOT DONE***
  
  
  
 ** PLEASE SEE PLANS APPEAR TO BE SIGNED
 WITH INITIALS?, IF INDEED THIS IS THE
 LEGAL SIGNATURE FOR ENGINEER OF RECORD,
 PLEASE PROVIDE AND SIGNED, DATED, SEALED
 AND NOTORIZED LETTER FOR SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 THIS LTR WILL BE REQUIRED TO BE
 NOTORIZED UNDER THE STATUES IN THE STATE
 WHICH THENOTORIZATION WOULD TAKE
 PLACE.
 PLEASE SEE FS 117 FOR ANY QUESTIONS ON
 GUIDELINES AND POSSIBLE INFORMATION
 NEEDED.
 **************************************
 PLEASE SEE NO RESPONSE LTR FROM ENGINEER
 OF RECORD COULD BE LOCATED.
 PLEASE ALSO SEE NO LETTER FOR LEGAL
 SIGNATURE VERIFICATION COULD BE LOCATED
 IN PACKAGE OR PLANS?
 ***************************************
  
  
 PLEASE SEE THAT PARTS "A & B" OF NOTE
 ONE IS REQUIRED OF ALL TRADES AND FOR
 ALL PLANS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PLEASE ALSO SEE ONE SET OF
 ARCHITECTURUAL PLANS WERE NOT DATED BY
 THE ARCHITECT.
  
 2)NOTE: PLEASE SEE "NOTES" TO ELECTRICAL
 PLANS WHICH REFERENCES THE 1999 NEC.
 PLEASE SEE AS OF JULY 1ST, 2003, THE
 2002 NEC IS ADOPTED BY THE STATE.
  
 ***SAME COMMENT**** PLEASE SEE PLANS.
  
 3)NOTE: PLEASE SEE EXISTING EQUIPMENT
 GROUNDING METHODS FOR ALL EQUIPMENT WILL
 BE REQUIRED TO VERIFIED IN FIELD AND CNA
 BE SET UP AS A "PROVSIO".
  
 4)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONALS AND PLANS WITH
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE BE SURE TO SEE NOTE # 1 AND #2.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE COPY OF OLD.VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 PLEASE CALL IF THERE ARE ANY QUESTIONS
 ABOUT COMMENTS ONE AND TWO.
 TO DATE, FROM FIRST REVIEW, NO CALLS
 HAVE BEEN MADE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 18:51 Rev Time 1.25
Received By dpalmer Date 2005-08-01 Time 18:51 Sent To  
Notes
2005-08-01 00:00:00*********** UNSAT ***********
  
 1)NOTE:
 A)PLEASE SEE MISSING REQUIRED
 INFORMAITON ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. MISSING PRINTED NAME
 AND LICENSE # FOR ARCH AND MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 FIRM.
 FAC 61G1-16.004 AND FS 481.219
  
 B)PLEASE SEE MISSING INFORMATION FOR
 ENGINEERING FIRM. MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, MISSING THE
 PRINTED NAME AND LICENSE NUMBER OF PE.
 PLEASE SEE, ONE SET OF PLANS ARE
 "PHOTOCOPIES" OF THE SEIGNED, DATED AND
 SEALED PLANS. PLEASE SEE THAT ALL SETS
 SHALLCONTAIN ORIGINAL SIGNATURE, DATE
 AND RAISED SEALED.
 PLEASE SEE ABOVE REQUIRED UNDER FAC
 61G15-23.002, FS 471.023 AND FS 471.025
 ** PLEASE SEE PLANS APPEAR TO BE SIGNED
 WITH INITIALS?, IF INDEED THIS IS THE
 LEGAL SIGNATURE FOR ENGINEER OF RECORD,
 PLEASE PROVIDE AND SIGNED, DATED, SEALED
 AND NOTORIZED LETTER FOR SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 THIS LTR WILL BE REQUIRED TO BE
 NOTORIZED UNDER THE STATUES IN THE STATE
 WHICH THENOTORIZATION WOULD TAKE
 PLACE.
 PLEASE SEE FS 117 FOR ANY QUESTIONS ON
 GUIDELINES AND POSSIBLE INFORMATION
 NEEDED.
  
  
 PLEASE SEE THAT PARTS "A & B" OF NOTE
 ONE IS REQUIRED OF ALL TRADES AND FOR
 ALL PLANS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE "NOTES" TO ELECTRICAL
 PLANS WHICH REFERENCES THE 1999 NEC.
 PLEASE SEE AS OF JULY 1ST, 2003, THE
 2002 NEC IS ADOPTED BY THE STATE.
  
 3)NOTE: PLEASE SEE RISERAND NOTES TO
 RISER DO NOT MENTION THE REQUIRED
 "EQUIPMENT GROUNDING" CONDUCTORS.
 PLEASE ALSO CLARIFY METHID OF EQUIPMENT
 GROUNDING FROM MAIN IN MAIN ELECTRICLA
 ROOM AND MAIN/ GUTTER AT TENANT SPACE.
 PLEASE SEE 250.110,250.30 ETCSIZING
 PER 250.66,250.122
  
 4)NOTE: PLEASE CLARIFY THE NUMBER OF
 CIRCUITS SHOWN FOR EACH PANEL. ? PLEASE
 SEE ONLY TWO PANELS ARE SHOWN ON RISER ,
 HOWEVER EACH PANEL APPEARS TO CAONTAIN
 "FEED-THRU" LUGS TO FEED A SECTION
 "TWO"?
 PLEASESEE 408.15
 IFMORE THAN TWO PANELS, PLEASE
 INDICATE ON RISER AND PLANS.215.5
 PLEASE ALSO SEE MAIN, GUTTER ETC ARE NOT
 SHOWN ON PLANS. COULD ONLY LOCATED
 PANELS LP1 AND LP2 AND TRANSFORMER.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE COPY OF OLD.VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-28 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By mwennerg Date 2005-08-24 Time 10:53 Rev Time 0.00
Received By mwennerg Date 2005-08-24 Time 10:53 Sent To  
Notes
2005-08-24 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT NFPA 101, 2003
 EDITION SHALL BE REFERENCED.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE DISTRIBUTED TO SATISFY THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 3) PLEASE SHOW REQUIRED ADDRESS ON
 BUILDING IF NEW OR EXISTING. MINIMUM 6"
 FOR MAIN ADDRESS AND 3" FOR INDIVIDUAL
 UNIT OR SUITE.
  
 4) PLANS SHOW MIXED OCCUPANCY. HOW WILL
 THIS WORK IMPACT EXISTING FIRE
 PROTECTION EQUIPMENT FOR BUILDING?
  
 5) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS.
  
  
 MIKE WENNERGREN/CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 08:28 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 08:28 Sent To M
Notes
2006-02-21 00:00:00TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 11:36 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 11:36 Sent To  
Notes
2005-11-22 00:00:00TO "COMM" BD#10
2005-10-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 09:41 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 09:41 Sent To  
Notes
2005-09-07 00:00:00TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2005-07-22 Time 14:02 Sent To  
Notes
2005-07-25 00:00:00TO "COMM" BD#53
2005-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-02-21 Cont ID  
Sent By hmoser Date 2006-02-21 Time 08:46 Rev Time 0.00
Received By hmoser Date 2006-02-21 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-13 Cont ID  
Sent By pkrauss Date 2005-10-13 Time 11:08 Rev Time 0.45
Received By pkrauss Date 2005-10-13 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-18 Cont ID  
Sent By pkrauss Date 2005-08-18 Time 16:26 Rev Time 0.55
Received By pkrauss Date 2005-08-18 Time 16:24 Sent To  
Notes
2005-08-18 00:00:00DENIED:
 1. PLEASE PROVIDE LICENSE # AS REQUIRED
 BY FS 471.025. PLEASE NOTE, BOTH COPIES
 SUBMITTED ARE TO BE SIGNED, SEALED &
 DATED IN ACCORDANCE WITH FAC
 61GA5-023.002 (2) & PER 2001 FBC
 104.2.1.
  
 2. PLEASE PROVIDE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM AS REQUIRED BY FAC
 61G1-16.004.
  
 3. NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 4. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION REQUIRED PER 2001
 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-20 Cont ID  
Sent By kstevens Date 2005-12-20 Time 08:25 Rev Time 1.50
Received By kstevens Date 2005-12-20 Time 08:25 Sent To  
Notes
2005-12-20 00:00:00DRINKING FOUNTAIN TO MEET ALL ACCESSIBLE
 REQUIREMENTS OF SECTION 11-4.15

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-12 Cont ID  
Sent By kstevens Date 2005-10-12 Time 14:08 Rev Time 1.25
Received By kstevens Date 2005-10-12 Time 14:08 Sent To  
Notes
2005-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. ALL ARCHITECTURAL SHEETS REQUIRE THE
 SEAL TO BE DATED WHEN AFFIXED TO THE
 PLANS. FAC 61G1-16.003 - 61G1-16.004(5)
 AND FS 481.2055. - FIRM LICENSE NUMBER
 REQUIRED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.219 - 481.2055.
 2. PER TABLE 403.1 AND SECTION 403.2
 SEPARATE FACILITIES ARE REQUIRED FOR
 EACH SEX. BOTH TOILET ROOMS ARE
 REQUIRED. RESPONSE NOTED, BUT REFERENCE
 TO EMPLOYEE NOTE FOUND ON SHT A0.0.
 PLEASE CLARIFY.
 3. MECHANICAL SHEETS AND ELECTRICAL
 SHEETS, A CERTIFICATE OF AUTHROIZATION
 IS REQUIRED FOR THE ENGINEERING BUSINESS
 FOR EACH SHEET,
 **************NEW COMMENT***************
 1B. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAIN.
 2B. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM FOR THE DRINKING FOUNTAIN
 SHOWING ALL PIPE SIZES, TRAPS, VENTS,
 AND POINTS OF CONNECTION FOR SANT. AND
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTOR, (IF REQUIRED BY SECTION
 604.9), AND POINT OF CONNECTION FOR
 WATER. - NO DRINKING FOUNTAIN IS SHOWN
 ON THE DEMO/EXISTING SHEET TO INDICATE
 THE LOCATION OF EXISTING DRINKING
 FOUNTAIN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-25 Cont ID  
Sent By kstevens Date 2005-08-25 Time 08:02 Rev Time 1.29
Received By kstevens Date 2005-08-25 Time 08:02 Sent To  
Notes
2005-08-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL & SP SHEETS, THE
 PERSONAL SIGNATURE AND DATED SEAL ARE
 REQUIRED PER FAC 61G1-16.003,
 61FG1-16.004(5) AND FS 481.2055. PLEASE
 SUBMIT A DOCUMENT TO SHOW LEGAL
 SIGNATURE SUCH AS A VOTERS REGISTRATION
 CARD, DRIVERS LICENSE ECT. PLANS APPEAR
 TO HAVE INITIALS ON SEAL. - FIRM LICENSE
 NUMBER REQUIRED IN TITLE BLOCK PER FAC
 651G1-16.004(2) & FS 481.2055.
 2. PER TABLE 403.1 AND SECTION 403.2
 SEPARATE FACILITIES ARE REQUIRED FOR
 EACH SEX. BOTH TOILET ROOMS ARE
 REQUIRED. ALSO A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1.
 3. MECHANICAL AND ELECTRICAL SHEETS.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025. - ALSO A
 PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS &
 THE DATE THAT THE SIGNATURE AND THE SEAL
 IS AFFIXED SHALL BE ENTERED ON THE
 PLANS. FAC 61FG15-23.002(1) & FS
 471.0254 - PLANS APPEAR TO BE INITIALED
 AND A SIGNATURE IS REQUIRED. SUBMIT A
 DOCUMENT TO SHOW LEGAL SIGNATURE SUCH AS
 A VOTER REGISTRATION CARD, DRIVERS
 LICENSE ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy