| 2005-07-29 00:00:00 | *********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| | LOADS ON PANEL SCHEDULES ARE SHOWN AS |
| | "BLANK". |
| | PLEASE COMPLETE LOAD CALCS AND SHOW ALL |
| | NEW AND EXSITNG LOADS. |
| | 220.3,220.10,220.11,220.13 AND |
| | CONTINUOUS @125%. 215.3,230.42 ETC |
| | |
| | 2)NOTE: PLEASE SEE NEW MAIN DISC'S |
| | APPEAR OT BE SHOWN. PLEASE INDICATE THE |
| | AIC RATING FOR NEW MAINS. AIC RATING IS |
| | SHOWN FOR PANELS. |
| | 110.9,215.5 |
| | |
| | 3)NOTE: PLEASE CLARIFY METHOD OF |
| | EQUIPMENT GROUNDING FROM MAIN |
| | DISCONNECTS TO SUB PANELS. |
| | PLEASE SEE IF EMT, AN EQUIPMENT |
| | GROUNDING CONDUCTOR WILL BE REQUIRED. |
| | 250.110,,250.24,250.122 |
| | |
| | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | REQUIRED SIGN CIRCUIT PER 600.5.EACH |
| | COMMERCIAL BUILDING AND EACH COMMERCIAL |
| | OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE |
| | OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR OUTLINE LIGHTING SYSTEM USE. THE |
| | OUTLET(S) SHALL BE SUPPLIED BY A BRANCH |
| | CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. |
| | |
| | 5)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES A RTU #2, HOWEVER PLANS |
| | INDICATE A RTU#1? IS THERE TWO UNITS? |
| | PLEASE CORRELATE. |
| | PLEASE ALSO SEE PANEL SCHEDULE DOES NOT |
| | SHOW ANY INFORMATION FOR RTU#2, MOCP, |
| | AWG, KW RATING ETC. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 7)NOTE: PLEASE SEE SIGNAGE SHALL BE |
| | REQUIRED FOR BOTH MAIN FEEDING THE SAME |
| | SPACE. 1 OF 2 AND 2OF 2. |
| | 230.2E ETC. |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECTELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ANY OLD SHEETS |
| | MARKED OLD/VOIDED SHEEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2005-07-28 00:00:00 | IN ELEC FOR REVIEW |