Plan Review Details - Permit 05070913
Plan Review Stops For Permit 05070913
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-09-29 Cont ID  
Sent By btrobaug Date 2005-09-29 Time 15:46 Rev Time 0.50
Received By btrobaug Date 2005-09-29 Time 14:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-09-14 Cont ID  
Sent By dpalmer Date 2005-09-14 Time 15:50 Rev Time 0.75
Received By dpalmer Date 2005-09-14 Time 15:50 Sent To  
Notes
2005-09-14 00:00:00********** UNSAT ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS WHICH STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE:PLEASE SHOW ALL RECEPTS SERVING
 KTICHEN COUNTERSPACE AS GFI/ GFI
 PROTECTED. PER 210.8A6,
 PLEASE SEE GFI INDICATION IS ONLY SHOWN
 FOR RECEPTS WITH IN 6' OF SINK.
 THE CODE CAN NOT BE REFERENCED IN LEIU
 OF SHOWING CODE COMPLIANCE.
  
 2)NOTE: PLEASE SEE 220.31B WHICH DOES
 NOT PERMIT DE-RATING OFAHU HEAT LOADS.
 THESE MUST BE FIGURED AT 100%,PELASE
 ALSO SEE 1ST 8KW AT 100% AND REMAINDER
 AT 40%.
  
 3)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT. MUST BE SIZED A MIN OF
 125% FO RATING. IF AHU 1 IS 10KW, MIN
 OCP MUST BE 60A'S.
 PLEASE INDICATE KW RATING FOR EACH.
  
 4)NOTE:PLEASE SEE PLANS MUST CONTAIN THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/ DESIGN.
 FBC 104.2.1
  
 5)NOTE: PLEASE SEE PLANS ARE NOT
 PERMITTED TO BE SUBMITTED IN PENCIL.
 PLEASE MAKES COPIES OF BOTH AND
 RE-SUBMIT.
  
 6)NOTE: PLEASE SEE REDLINED AREA FOR
 MISSING KITCHENOCUNTERSPACE RECEPTS/
 PER 210.52C1-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 20:11 Rev Time 0.75
Received By dpalmer Date 2005-09-02 Time 20:11 Sent To  
Notes
2005-09-02 00:00:00********* UNSAT **********
  
  
 PLEASE RE-PRINT PLANS FORTHE BELOW
 ITEMS.
  
 1)NOTE: PLEASE INDICATE ALL ITEMS
 RDLINED ON PLANS AND PLEASE INCLUDE
 ADDITIONAL MISSING ITEMS.
 PLEASE SEE FBC 104.2.1, WHICH STATES,
 TECHNICAL CODE SHALL NOT BE STATED IN
 LEIU OF DETAILS ON PLANS.
 PLANS ARE REQUIRED TO SHOW CODE
 COMPLIANCE
  
 2)NOTE PLEASE SEE 210.52C1-5 FOR KITCHEN
 COUNTERSPACES AND REQ'D GFI RECEPTS.
 PLEASE SEE 210.8A6
  
 3)NOTE: PLEASE INDICATE GFI RECEPTS AT
 ALLLOCATIONS PER 210.8
  
 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1
 PLEASE SHOW ALL REQUIRED SD'S INSIDE AND
 OUTSIDE ALL BEDRMS AND ON EACH LEVEL OF
 A MULTI-LEVEL DWELLING.
  
 5)NOTE:PLEASE BE SURE PANEL SCHEDULE
 INCLUDES ALL MIN CONDUCTOR SIZES AND
 CORRELATE WITH OVER-CURRENT PROTECTION
 SHOWN.310.16, 240.4, 215.5
  
 6)NOTE: PLEASE SEE BATH CIRCUIT IS SHOWN
 ON KITCHEN CIRCUIT,
 PLEASE SEE 210.52B1,210.11C3, BOTH ARE
 REQUIRED TO BE DEDICATED CIRCUITS.
  
 7)NOTE:PLEASE INDICATE THE REQUIRED
 FRONT AND REAR GFI'S PER 210.52E, 210.8
  
 8)NOTE: PLEASE INDICATE THE REQUIRED GFI
 FOR A/C CU LOCATED OUTSIDE. 210.63
  
 9)NOTE: PLEASE SHOW LOATIONS OF AHU'S
 AND DISCONNECTS PER 440.11
  
 10)NOTE: PLEASE INDICATE DISCONNECT
 REQUIRED FOR WATER HEATER. A RECEPT IS
 SHOWN. PLEASE SEE 422.31
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 RENOVATIONS TO EXSITNG DWELLINGS. PLEASE
 SEE PLANS APPEAR TO SHOW HOUSE BEING
 RE-WIRED AND EXCEDDING 50%. PLEASE SHOW
 ALL OTHER AREAS WHICH MEET 2002 NEC OR
 SHOW ELECTRICAL TO BE UPDATED.
  
 12)NOTE: PLEASE CORRELATE ALL A/C
 SYSTEMS SHOWN. PLEASE SEE MORE THAN ONE
 SHOWN AS SYSTEM ONE ETC.
  
 13)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL SHOWN ON ELECTRICAL PANEL
 SCHEDULE SHOWN.
 215.5,220.31B
  
 14)NOTE:PLEASE RE-PRINT PLANS WITH ALL
 ITEMS SHOWN CLEAR AND DETAILED.
 FBC 104.2.1.1
 MIN 1/8" SCALE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-24 Cont ID  
Sent By btrobaug Date 2005-08-24 Time 11:02 Rev Time 0.50
Received By btrobaug Date 2005-08-24 Time 10:19 Sent To PC
Notes
2005-08-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE CLOUD OR OTHERWISE INDICATE
 THE REVISIONS TO THIS PLAN.
  
 2} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST PRINT NAME AND SIGN PER 104.2.1
 FBC.
  
 3} BEDROOMS MUST BE ARC FAULT PROTECTED
 PER 210.12.
  
 4} KITCHENS PER 210.8(A)(6), 210.52(C),
 BATHS PER 210.8(A)(1), 215.52(D),
 210.11(C)(3).
  
 5} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6 NFPA-72. ALSO SEE CHAPTER 34
 FOR OTHER GFI REQUIREMENTS.
  
 6} PLEASE SUBMIT A PANEL SCHEDULE SO
 THAT COMPLIANCE WITH BRANCH CIRCUIT
 REQUIREMENTS CAN BE DETERMINED.
  
 7} THERE IS A NOTE INDICATING NEW POOL
 WIRING. A SEPERATE APPLICATION AND
 DOCUMENTS ARE REQUIRED FOR THE POOL.
  
 8} PLEASE INCREASE THE VALUE OF THE JOB
 TO REFLECT ALL LABOR AND MATERIAL
 COST(104.6.5 FBC) RESULTING FROM THIS
 REVISION.INDICATE SAME TO PERMIT CLERK
 WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-29 Cont ID  
Sent By btrobaug Date 2005-07-29 Time 15:32 Rev Time 0.50
Received By btrobaug Date 2005-07-29 Time 15:32 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 08:46 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 08:46 Sent To E
Notes
2005-09-26 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 13:41 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 13:41 Sent To E
Notes
2005-09-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 13:21 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 13:21 Sent To E
Notes
2005-09-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 17:35 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 17:35 Sent To E
Notes
2005-08-18 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 09:23 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 09:23 Sent To E
Notes
2005-07-22 00:00:00TO "E" BOX