Plan Review Details - Permit 05070910
| Plan Review Stops For Permit 05070910 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-07-22 |
Time |
14:40 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2005-07-22 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-25 |
Time |
09:08 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-25 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | ********* PROVISO/ REVISION ******** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | NEW/ REVISED CIRCUITING AND CORRELATE | | | WITH A PANEL SCHEDULE TO BE SUBMITTED. | | | INCLUDE ANY NEW LOADS. | | | 215.5,220 | | | | | | 2)NOTE: PLEASE SEE 210.8B3 IN THE 2002 | | | NEC, WHICH REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NONDWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. | | | | | | 3)NOTE: PLEASE SEE ANY CIRCUITING FOR | | | EM/EXT LTS PER 700.12E. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-26 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-26 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | ******PASSED****** | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED WHERE THEY CAN BE | | | REACHED WITHIN 75' TRAVEL DISTANCE. | | | | | | * NO MECHANICAL WORK NOTED ON PLANS | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561_ 805-6722 OR 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-26 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-22 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2005-07-22 00:00:00 | TO "BOB" #4 |
|
|
|