Plan Review Details - Permit 05070866
Plan Review Stops For Permit 05070866
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 08:53 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 08:53 Sent To PC
Notes
2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070866
 ADD: 2 FIRESTONE CIR
 CONT: TONY'S ELECTRIC
 TEL: (561)790-1852
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SURVEY COPIED 2 ORIGINALS REQUIRED:
 FL S S 472.025 / 61G17-6.002(8)(E)
  
 61G17-6.002(8)(E) ALL SURVEY MAPS AND
 REPORTS OR COPIES THEREOF ARE NOT VALID
 WITHOUT THE ORIGINAL SIGNATURE, AND THE
 ORIGINAL RAISED SEAL OF A FLORIDA FOR
 LICENSED SURVEYORS AND MAPPERS.
  
 61G17-6.002(8)(C) ALL SURVEY MAPS AND
 REPORTS MUST BEAR THE NAME, "CERTIFICATE
 OF AUTHORIZATION NUMBER", AND THE STREET
 MAILING ADDRESS OF THE BUSINESS ENITITY
 ISSUING THE MAP OR REPORT, ALONG WITH
 NAME AND LICENSE NUMBER OF THE SURVEYOR
 AND MAPPER IN RESPONSIBLE CHARGE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-03 Time 16:06 Rev Time 1.00
Received By btrobaug Date 2005-08-03 Time 15:04 Sent To M
Notes
2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESPONSIBLE FOR THE
 DRAWING MUST PRINT AND SIGN NAME TO
 SAME, 104.2.1 FBC.
  
 2} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THESERVICE
 EQUIPMENT AND THE EMERGENCY EQUIPMENT SO
 THAT COMPLIANCE WITH 225.31 THROUGH
 225.37 CAN BE DETERMINED.
  
 3} PLEASE SUBMIT TWO COPIES OF ALL
 DOCUMENTS PER 104.2.1 FBC, MANUFACTURERS
 SPECS FOR THE TRANSFER SWITCH AND
 GENERATOR.
  
 4} INDICATE THE PRIME MOVER (FUEL
 SOURCE) FOR THE GENERATOR.
  
 5) THE VALUE OF THE PROJECT INDICATED ON
 THE APPLICATION MUST INCLUDE THE VALUE
 OF ALL THE EQUIPMENT BEING INSTALLED AND
 LABOR PER 104.6.5.
  
 6} PANEL A-1 IS FED THROUGH AND FED BACK
 FROM THE TRANSFER SWITCH? IT IS ALSO AN
 MLO. PLEASE VERIFY.
  
 7} PANEL "A" INDICATES IT IS BOTH A MLO
 AND HAS A 125 AMP MAIN. PLEASE
 CORRELATE. INDICATE WHICH EQUIPMENT IS
 NEW AND WHICH IS EXISTING.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 10:14 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 10:14 Sent To E
Notes
2005-08-01 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 09:28 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 09:28 Sent To Z
Notes
2005-07-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By rregueir Date 2005-08-03 Time 19:43 Rev Time 0.00
Received By rregueir Date 2005-08-03 Time 19:43 Sent To P
Notes
2005-08-03 00:00:00DENIED:
  
 SUBMIT 2 COPIES OF GENERATOR SUBMITTAL
 DATA INDICATING FUEL TYPE TO BE USED.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 07:57 Rev Time 0.25
Received By jleech Date 2005-08-04 Time 07:57 Sent To B
Notes
2005-08-04 00:00:00GAS PERMIT REQUIRED BEFOREFINAL
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-29 Cont ID  
Sent By mmclean Date 2005-07-29 Time 18:39 Rev Time 0.00
Received By mmclean Date 2005-07-29 Time 18:39 Sent To I
Notes
2005-07-29 00:00:00GENERATOR CAN ONLY ENROACH 4FT INTO
 SETBACK.