Plan Review Details - Permit 05070866
| Plan Review Stops For Permit 05070866 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-13 |
Time |
08:53 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2005-08-13 |
Time |
08:53 |
Sent To |
PC |
|
| Notes |
| 2005-08-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070866 | | | ADD: 2 FIRESTONE CIR | | | CONT: TONY'S ELECTRIC | | | TEL: (561)790-1852 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) SURVEY COPIED 2 ORIGINALS REQUIRED: | | | FL S S 472.025 / 61G17-6.002(8)(E) | | | | | | 61G17-6.002(8)(E) ALL SURVEY MAPS AND | | | REPORTS OR COPIES THEREOF ARE NOT VALID | | | WITHOUT THE ORIGINAL SIGNATURE, AND THE | | | ORIGINAL RAISED SEAL OF A FLORIDA FOR | | | LICENSED SURVEYORS AND MAPPERS. | | | | | | 61G17-6.002(8)(C) ALL SURVEY MAPS AND | | | REPORTS MUST BEAR THE NAME, "CERTIFICATE | | | OF AUTHORIZATION NUMBER", AND THE STREET | | | MAILING ADDRESS OF THE BUSINESS ENITITY | | | ISSUING THE MAP OR REPORT, ALONG WITH | | | NAME AND LICENSE NUMBER OF THE SURVEYOR | | | AND MAPPER IN RESPONSIBLE CHARGE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-08-03 |
Time |
16:06 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2005-08-03 |
Time |
15:04 |
Sent To |
M |
|
| Notes |
| 2005-08-03 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON RESPONSIBLE FOR THE | | | DRAWING MUST PRINT AND SIGN NAME TO | | | SAME, 104.2.1 FBC. | | | | | | 2} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE PHYSICAL LOCATION OF THESERVICE | | | EQUIPMENT AND THE EMERGENCY EQUIPMENT SO | | | THAT COMPLIANCE WITH 225.31 THROUGH | | | 225.37 CAN BE DETERMINED. | | | | | | 3} PLEASE SUBMIT TWO COPIES OF ALL | | | DOCUMENTS PER 104.2.1 FBC, MANUFACTURERS | | | SPECS FOR THE TRANSFER SWITCH AND | | | GENERATOR. | | | | | | 4} INDICATE THE PRIME MOVER (FUEL | | | SOURCE) FOR THE GENERATOR. | | | | | | 5) THE VALUE OF THE PROJECT INDICATED ON | | | THE APPLICATION MUST INCLUDE THE VALUE | | | OF ALL THE EQUIPMENT BEING INSTALLED AND | | | LABOR PER 104.6.5. | | | | | | 6} PANEL A-1 IS FED THROUGH AND FED BACK | | | FROM THE TRANSFER SWITCH? IT IS ALSO AN | | | MLO. PLEASE VERIFY. | | | | | | 7} PANEL "A" INDICATES IT IS BOTH A MLO | | | AND HAS A 125 AMP MAIN. PLEASE | | | CORRELATE. INDICATE WHICH EQUIPMENT IS | | | NEW AND WHICH IS EXISTING. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-01 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-01 |
Time |
10:14 |
Sent To |
E |
|
| Notes |
| 2005-08-01 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-22 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-22 |
Time |
09:28 |
Sent To |
Z |
|
| Notes |
| 2005-07-22 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-08-03 |
Time |
19:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-08-03 |
Time |
19:43 |
Sent To |
P |
|
| Notes |
| 2005-08-03 00:00:00 | DENIED: | | | | | | SUBMIT 2 COPIES OF GENERATOR SUBMITTAL | | | DATA INDICATING FUEL TYPE TO BE USED. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-04 |
Time |
07:57 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-08-04 |
Time |
07:57 |
Sent To |
B |
|
| Notes |
| 2005-08-04 00:00:00 | GAS PERMIT REQUIRED BEFOREFINAL | | | INSPECTION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-07-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-29 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-29 |
Time |
18:39 |
Sent To |
I |
|
| Notes |
| 2005-07-29 00:00:00 | GENERATOR CAN ONLY ENROACH 4FT INTO | | | SETBACK. |
|
|
|