Plan Review Details - Permit 05070846
Plan Review Stops For Permit 05070846
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-04 Cont ID  
Sent By jwitmer Date 2005-08-04 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2005-08-04 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By jwitmer Date 2005-07-28 Time 14:42 Rev Time 1.22
Received By jwitmer Date 2005-07-28 Time 14:42 Sent To  
Notes
2005-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070846
 ADD: 1717 EDGER ST
 CONT: EXCEL CONTRACTORS
 TEL: (561)626-8781
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)PROVIDENOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE THE OCCUPANCY OR USE CATEGORY
 THIS SPACE WILL BE?
 301.2 OCCUPANCY OR USE CATEGORIES. EVERY
 NEW AND EXISTING BUILDING,
 STRUCTURE OR PART THEREOF SHALL, FOR THE
 PURPOSE OF THIS CODE, BE
 CLASSIFIED ACCORDING TO ITS USE OR
 OCCUPANCY AS A BUILDING OR STRUCTURE.
  
 3) A-1 DETAIL# 2 HAS THE UPPER HALF
 SCATCHED OUT STATING N/A, SEE:
 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 4) PLANS DO NOT INDICATE WHAT THE HEIGHT
 OF THE DEMISSING WALL IS NOR THE
 CEILING/ROOF OF SPACE?
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-25 Cont ID  
Sent By dpalmer Date 2005-07-25 Time 10:29 Rev Time 0.25
Received By dpalmer Date 2005-07-25 Time 10:29 Sent To  
Notes
2005-07-25 00:00:00NOTED 700.12E

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jwitmer Date 2005-08-04 Time 12:30 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-07-29 Cont ID  
Sent By mwennerg Date 2005-07-29 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 15:48 Sent To  
Notes
2005-07-29 00:00:00PLEASE SEE BUILDING REVIEW COMMENTS IN
 REGARDS TO OCCUPANCY CLASSIFICATION
 WHICH COULD EFFECT OTHER REVIEW NOTES.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722
 PLAN REVIEW(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 14:22 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 14:21 Sent To P
Notes
2005-09-08 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 15:39 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 15:39 Sent To B
Notes
2005-08-03 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-07-29 Time 15:39 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 15:44 Sent To  
Notes
2005-07-22 00:00:00TO "BOB" #6
2005-07-21 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-26 Cont ID  
Sent By hmoser Date 2005-08-26 Time 12:51 Rev Time 0.00
Received By hmoser Date 2005-08-26 Time 12:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jwitmer Date 2005-08-04 Time 12:31 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-20 Cont ID  
Sent By jleech Date 2005-09-20 Time 13:11 Rev Time 0.50
Received By jleech Date 2005-09-20 Time 13:11 Sent To  
Notes
2005-09-20 00:00:00PLUMBING REVISION MOVED ONE SINK TO NEW
 LOCATION OK

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 08:22 Rev Time 0.00
Received By jwitmer Date 2005-08-04 Time 12:30 Sent To M
Notes
2005-07-30 00:00:00BACK FLOW PREVENTER REQUIRED ON WATER
 SERVICE

Review Stop Z ZONING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jwitmer Date 2005-08-04 Time 12:30 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***