Plan Review Details - Permit 05070844
Plan Review Stops For Permit 05070844
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 14:20 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 14:20 Sent To Z
Notes
2005-07-21 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By eschneid Date 2005-08-10 Time 09:08 Rev Time 0.00
Received By eschneid Date 2005-08-10 Time 08:30 Sent To  
Notes
2005-08-10 00:00:001) INSTALLATION OF BAFFLES AND PANELS TO
 CREATE AN 8+ FOOT HIGH STRUCTURE AND THE
 INSTALLATION OF FENCES REQUIRE THE
 APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT.
 2) "RETAIL BUILDING CHILLER YARD A-1 -
 PLAN VIEW" INCLUDED AS SHEET 1 OF 8 IS
 NOT FOR THE CHILLER ARRAY AS SHOWN IN
 THE PERMIT.CORRECT DRAWINGS SHALL BE
 SUBMITTED.
 3) THE PARKING STRUCTURE AND THE
 CHILLERS ARE ON TWO SEPERATE PARCELS W/
 TWO SEPERATE ADDRESSES, OWNERS, AND
 PCNS.THE PERMIT SHALL REFLECT THIS.
  
 CONTACT ERIC SCHNEIDER, PRINCIPAL
 PLANNER @ (561) 822-1435.