Plan Review Details - Permit 05070843
Plan Review Stops For Permit 05070843
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By jwitmer Date 2005-09-06 Time 13:19 Rev Time 0.77
Received By jwitmer Date 2005-09-06 Time 12:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:08 Rev Time 1.11
Received By jwitmer Date 2005-07-31 Time 08:08 Sent To Z
Notes
2005-07-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070843
 ADD: 829 MADDOCK ST
 CONT: O/B JONES, THOMAS
 TEL: (561)909-8355
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE: ADDITIONAL ELECTRICAL PERMIT WILL
 BE REQUIRED.
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WOOD/ WOOD STRAPS
 B) STORM SHUUTERSWINDOWS & DOORS
 C) HARDI PLANK SIDING
  
 3) PLANS DO NOT INDICATE HOW INFILL WALL
 SECTIONS WILL BE SECURED TO EXISTING
 CONCRETE SLAB, COLUMNS & BEAM.
 1606.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDING. STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS
 AND CLADDING IN A BUILDING OR
 STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT
 AND SLIDING AND TO PROVIDE CONTINUOUS
 LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE
 RESISTANCE TO THESE FORCES IS PROVIDED
 BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN
 WIND EVENT SHALL BE USED.
  
 4) PLANS DO NOT INDICATE USAGE OF ROOM?
 PLANS ALSO INDICATE THAT THIS ROOM DOES
 NOT COMMUNICATE WITH THE REMAINDER OF
 THE HOUSE?
  
 4) PLANS INDICATE TO REPLACE OLD SIDING
 AND REPLACE WITH 3/8" AND HARDI PLANK,
 WHERE, ON THE REMAINDER OF THE HOUSE?
  
 5) PROVIDE A CUT SECTION, ELEVATION
 INDICATING COMPLINCE THESE CODE
 SECTIONS:
 2303.3 MOISTURE PROTECTION. SURFACES
 EXPOSED TO THE WEATHER SHALL HAVE
 AN APPROVED BARRIER TO PROTECT THE
 STRUCTURAL FRAME AND THE INTERIOR WALL
 COVERING.THE BARRIER SHALL BE AT LEAST
 TYPE 15 FELT OR KRAFT WATERPROOF
 BUILDING PAPER.BUILDING PAPER AND FELT
 SHALL BE FREE FROM HOLES AND
 BREAKS OTHER THAN THOSE CREATED BY
 FASTENERS AND CONSTRUCTION SYSTEMS USED
 IN ATTACHING OF THE BARRIER, AND SHALL
 BE APPLIED OVER STUDS OR SHEATHING
 OF ALL EXTERIOR WALLS.SUCH FELT OR
 PAPER SHALL BE APPLIED HORIZONTALLY
 WITH THE UPPER LAYER LAPPED OVER THE
 LOWER LAYER NOT LESS THAN 2 INCHES (51
 MM).WHERE VERTICAL JOINTS OCCUR, FELT
 OR PAPER SHALL BE LAPPED NOT LESS
 THAN 6 INCHES (152 MM).
  
 2304.2.5 CLEARANCE BETWEEN WOOD SIDING
 AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL BE NOT LESS THAN 6
 INCHES (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF
 APPROVED PRESERVATIVE-TREATED WOOD OR
 APPROVED NATURALLY DURABLE WOOD.
  
 6) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:29 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 09:19 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 09:19 Sent To B
Notes
2005-09-02 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-09-01 Time 16:51 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 11:37 Sent To Z
Notes
2005-08-24 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 09:58 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 16:03 Sent To  
Notes
2005-07-21 00:00:00TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:28 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:29 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 16:41 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 16:41 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 09:47 Rev Time 0.00
Received By mmclean Date 2005-08-01 Time 09:47 Sent To  
Notes
2005-08-01 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE WORK WITH SETBACKS.
 2. MUST PROVIDE TWO COPIES OF FLOOR PLAN
 SHOWING THE INTERIOR ACCESS TO THE MAIN
 STRUCTURE.
  
 GIVEN TO MS. PHYLLIS REGARDING THE
 CHANGE OF OWNERSHIP OF PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720