Plan Review Details - Permit 05070765
Plan Review Stops For Permit 05070765
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-15 Cont ID  
Sent By jwitmer Date 2005-09-15 Time 07:15 Rev Time 0.53
Received By jwitmer Date 2005-09-15 Time 07:15 Sent To PC
Notes
2005-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070765
 ADD: 309 35TH ST
 CONT: POOLTIME
 TEL: (561)436-2662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: REVIEWED
  
  
  
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
 424.2.17.1.5 CHILD SAFETY BARRIER
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-20 Cont ID  
Sent By jwitmer Date 2005-08-20 Time 09:54 Rev Time 0.33
Received By jwitmer Date 2005-08-20 Time 09:49 Sent To PC
Notes
2005-08-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070765
 ADD: 309 35TH ST
 CONT: POOLTIME
 TEL: (561)436-2662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: REVIEWED
  
  
  
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
 424.2.17.1.5 CHILD SAFETY BARRIER
  
 2)13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 07:14 Rev Time 0.20
Received By dpalmer Date 2005-08-30 Time 07:14 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By dpalmer Date 2005-07-29 Time 17:27 Rev Time 0.50
Received By dpalmer Date 2005-07-29 Time 17:27 Sent To P
Notes
2005-07-29 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED
 WITH CONTRACT SCHEDULE AND ELECTRICAL
 DETAIL SHEET SUBMITTED.
 PLEASE SEE CONTRACT MENTIONS NEW 100W
 FIXTURE, HOWEVER ELECTRICAL LISTS 75W?
 PLEASE SEE CONTRACT MENTION NEW SALT
 WATER CHORLINATOR SYSTEM BEING
 INSTALLED, HOWEVER, PLEASE SEE THIS IS
 NOT SHOWN IN ELECTRICAL WIRING DIAGRMA
 NOR IS IT SHOWN ON PIPING SCHEDULE(SEE
 PLUMBING NOTES).
 PLEASE SEE ELECTRICAL SHEETS MENTISON A
 NEW POOL PANEL BEING INSTALLED ALONG
 WITH SEPARATE CIRCUITS FOR POOL
 EQUIPMENT? PLEASE CORRELATE.
 PLEASE SEE NEW POOL PANEL IS NOT SHOWN
 ON ELECTRICAL WIRING DIAGRAM.
 PLEASE ALSO SEE IF A NEW POOL PANEL IS
 BEING INSTALLED? PLEASE CLARIFY WHY POOL
 PUMP MOTOR, BLOWER AND LT IS ALSO BEING
 FED WITH SEPARATE CIRCUITS?
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
 215.3,230.42 ETC.
 PLEASE INDICATE LOAD ON EXISTING SERVICE
 AND SIZE.220,215.5
  
 2)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANS/DRAWINGS MUST CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/DESIGNS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:10 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:10 Sent To  
Notes
2005-08-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 09:36 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 09:36 Sent To E
Notes
2005-07-29 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 09:49 Sent To Z
Notes
2005-07-21 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By jleech Date 2005-09-12 Time 07:39 Rev Time 0.33
Received By jleech Date 2005-09-12 Time 07:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 10:13 Rev Time 0.00
Received By jleech Date 2005-08-04 Time 10:13 Sent To B
Notes
2005-08-04 00:00:00SALT WATER CLORINATOR NOT SHOWN ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-28 Cont ID  
Sent By mmclean Date 2005-07-28 Time 17:25 Rev Time 0.00
Received By mmclean Date 2005-07-28 Time 17:25 Sent To I
Notes
***NONE***