Plan Review Details - Permit 05070760
Plan Review Stops For Permit 05070760
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-22 Cont ID  
Sent By shill Date 2006-05-22 Time 16:40 Rev Time 0.00
Received By shill Date 2006-05-22 Time 16:40 Sent To  
Notes
2006-05-22 00:00:00REVISION, SK3 AND SK3A
 DATED 5/13/6

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-21 Cont ID  
Sent By lmartine Date 2006-02-21 Time 17:51 Rev Time 0.00
Received By lmartine Date 2006-02-21 Time 17:51 Sent To  
Notes
2006-02-21 00:00:00 
  
  
  
  
 "PROVISO"
 -------
  
  
 SUBMIT FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL ON THE METAL ROOF COVER,
 SOUTHERN METALS IS NOT LISTED ON
 FLORIDA'S WEBSITE.
  
  
  
  
  
  
  
 L. MARTINEZ
 805-6710
2006-02-14 00:00:00NEW A-SHEETS, ENERGY CALCS, AND PRODUCT
 APPROVALS. NEEDS NEW RECORDED NOC.
 TO LUIS M.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By shill Date 2005-11-10 Time 16:10 Rev Time 0.00
Received By shill Date 2005-11-10 Time 16:10 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-09 Cont ID  
Sent By shill Date 2005-11-09 Time 17:34 Rev Time 2.00
Received By shill Date 2005-11-09 Time 16:14 Sent To  
Notes
2005-11-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 TO REMAIN THE SAME FOR CONSISTENCY:
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY (CHANGE OF USE).THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION. 233-5025
  
 7.)THE PLANS ARE TO BE SIGNED, SEALED,
 AND DATED ORIGINALS, FAC61G1-16.003.
  
 27.)THE HANDRAIL EXTENSIONS FOR BOTH
 STAIRS ARE TO COMPLY WITH FBC11-4.9.4.
 PLEASE PROVIDE A DETAIL SHOWING ALL
 DIMENSIONS.
  
 HANDRAILS NOT SHOWN FOR INTERIOR STAIR,
 FBC1007.5.5, FBC11-4.9.4.
  
 NOTE - NO PRODUCT APPROVALS SUBMITTED.
 FROM PREVIOUS REVIEW:
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 35.)PROVIDE LEGIBLE NOAS. THEY MAY BE
 AVAILABLE AT WWW.FLORIDABUILDNG.ORG OR
 WWW.MIAMIDADE.GOV (FIND A DEPARTMENT,
 BUILDING CODE COMPLIANCE, PRODUCT
 CONTROL SEARCH).
  
 36.)NON IMPACT GLAZED DOOR PRODUCT
 APPROVALS WERE SUBMITTED.PLEASE SEE
 ATTACHED POLICY IN REGARDS TO MISSILE
 IMPACT PROTECTION, ITEM #13.
  
 37.)FOR THE GAF BUILT UP ROOF,
 INDICATE WHICH APPROVED ASSEMBLY YOU ARE
 USING.
  
 38.)FOR THE METAL ROOF PANELS, PROVIDE
 DESIGN PRESSURES AND SEE PRODUCT
 LIMITATION #7.
  
 39.)ANY PRODUCT APPROVALS NOT REVIEWED
 PRIOR TO PERMIT ISSUANCE WILL REQUIRE
 SEPARATE PERMITS.
  
 NEW COMMENTS:
  
 40.)STATE OCCUPANT LOAD FOR THE SECOND
 FLOOR TO DETERMINE VERTICAL
 ACCESSIBILITY REQUIREMENTS,
 FBC11-4.1.3(5).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-17 Cont ID  
Sent By shill Date 2005-08-17 Time 16:15 Rev Time 5.00
Received By shill Date 2005-08-17 Time 10:35 Sent To  
Notes
2005-08-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY (CHANGE OF USE).THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION. 233-5025
  
 3.)THE VALUE APPEARS TOO LOW.PROVIDE
 A REASONABLE VALUE OR AN ESTIMATE USING
 MARSHALL & SWIFT WILL BE DONE FOR YOU.
  
 4.)THIS IS A CHANGE IN OCCUPANCY,
 FBC3401.2.2.1.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.
  
 5.)THIS IS AN OVER 50% IMPROVEMENT,
 FBC3401.7.2.6.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.
  
 6.)FBC3401.2.2.2, PROVIDE
 CERTIFICATION OF THE FLOOR LOADING.
  
 7.)THE PLANS ARE TO BE SIGNED, SEALED,
 AND DATED ORIGINALS, FAC61G1-16.003.
  
 8.)SHEET ASP-1 DECLARES:
  
 A. CLASSIFICATION AS TYPE B ? THIS IS A
 MIXED OCCUPANCY (LIVE/WORK), SEE FBC
 CHAPTER 3.
  
 B. CONSTRUCTION TYPE V SFBC2001.
 GOVERNING CODE IS FBC2001.
  
 9.)PROVIDE A SURVEY OF THIS PROPERTY.
  
 10.)PROVIDE AREA CALCULATIONS FOR THE
 FIRST FLOOR AND SECOND FLOOR SO THAT
 CODE COMPLIANCE CAN BE DETERMINED.
  
 11.)THE PLANS SUBMITTED HAVE NOTES AND
 CALCULATIONS ON SHEET A2 WHICH WERE HAND
 WRITTEN.IF YOU WANT FOR THESE NOTES
 AND CALCULATIONS TO BE A PART OF THIS
 PLAN, LABEL EACH ONE SO THAT IT IS CLEAR
 AS TO WHAT IT APPLIES TO (OR REMOVE FROM
 THE PLAN).
  
 12.)THE STAIRWAY FROM THE FIRST TO
 SECOND FLOOR IS TO BE PROTECTED,
 FBC1006.1.
  
 13.)PROVIDE AN ASSEMBLY OR CALCULATED
 FIRE RESISTANCE (PROVIDING CALCULATIONS
 TO SHOW COMPLIANCE FBC709) FOR THE
 OCCUPANCY SEPARATION BETWEEN THE FIRST
 AND SECOND FLOOR.
  
 14.)SEE FBC TABLE 600 AND SHOW
 COMPLIANCE FOR THE NORTH WALL WHICH IS
 LESS THAN 3? FROM THE PROPERTY LINE.
  
 15.)MEANS OF EGRESS (FROM SECOND
 FLOOR) CANNOT BE THROUGH ADJACENT TENANT
 SPACE, FBC1001.1.3.
  
 16.)FOR THE RAMP BETWEEN THE WAITING
 AREA AND SECRETARIES? AREA PROVIDE THE
 RISE AND THE WIDTH.SEE FBC11-4.8.5,
 FBC11-4.8.3, SEE EXCEPTION.
  
 17.)PROVIDE THE RAMP WIDTH ADJACENT TO
 WAITING/RECEPTION AREA.THE WIDTH WAS
 PROVIDED ON ONE SIDE ONLY.
  
 18.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-11-4.1.2(1).IT APPEARS TO BE
 FROM 17TH STREET TO THE RAMP, PLEASE
 NOTE CONSTRUCTION AND SLOPE ON THE PLAN.
 ACCESSIBLE PARKING NOT SHOWN.
  
 19.)NOTE THE MAXIMUM RAMP SLOPE ON THE
 PLAN FBC11-4.8.2 FOR THE FRONT RAMP.IF
 THE STAIR RISERS ARE 7? HIGH, THE SLOPE
 OF THE RAMP EXCEEDS 1:12.
  
 20.)NOTE THE LANDING DIMENSION AT THE
 TOP AND BOTTOM OF EACH RAMP,
 FBC11-4.8.4.
  
 21.)WHERE THE RAMP CHANGES DIRECTION,
 MINIMUM LANDING SIZE IS 60X60 (48X48 IS
 SHOWN), FBC11-4.8.3(3).
  
 22.)SHOW MANEUVERING CLEARANCE FOR THE
 DOOR AT THE RAMP, FBC11-4.8.3(4),
 11-4.13.6, CHAPTER 11 FIGURE 25.
  
 23.)A HANDRAIL IS REQUIRED ON BOTH
 SIDES OF THE RAMP (FRONT), 11-4.8.5(1).
 ALSO SEE FBC11-4.8.5(2) IN REGARDS TO
 THE EXTENSION REQUIRED AT THE TOP.
  
 24.)PROVIDE A DETAIL FOR THE HANDRAILS
 SHOWING DIMENSIONS AND HEIGHT FOR BOTH
 THE RAMP HANDRAIL AND STAIR HANDRAIL
 FBC11-4.8.5, 11-4.9.4.
  
 25.)EDGE PROTECTION REQUIRED FOR THE
 EXTERIOR RAMPS, FBC11-4.8.7.
  
 26.)PROVIDE A STAIR DETAIL, FBC11-4.9,
 FBC1007 FOR BOTH STAIRS.
  
 27.)THE HANDRAIL EXTENSIONS FOR BOTH
 STAIRS ARE TO COMPLY WITH FBC11-4.9.4.
 PLEASE PROVIDE A DETAIL SHOWING ALL
 DIMENSIONS.
  
 28.)PROVIDE A BACKING DETAIL FOR THE
 GRAB BARS.
  
 29.)DOOR 111A APPEARS TO SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR THE
 SINK, FBC11-4.22.2.
  
 30.)PROVIDE A DETAIL FOR THE BREAK
 ROOM SINK TO COMPLY WITH FBC11-4.24.
  
 31.)BEDROOMS ARE TO COMPLY WITH
 FBC1005.4, EMERGENCY EGRESS.NOTE
 WINDOW SIZE AND TYPE ON THE PLAN TO SHOW
 COMPLIANCE.
  
 32.)SAFETY GLASS REQUIRED AT THE TUB
 FBC2405.1.
  
 33.)SHOW 2ND FLOOR BATHROOM DOOR SIZE,
 FBC11-11(1).
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 35.)PROVIDE LEGIBLE NOAS. THEY MAY BE
 AVAILABLE AT WWW.FLORIDABUILDNG.ORG OR
 WWW.MIAMIDADE.GOV (FIND A DEPARTMENT,
 BUILDING CODE COMPLIANCE, PRODUCT
 CONTROL SEARCH).
  
 36.)NON IMPACT GLAZED DOOR PRODUCT
 APPROVALS WERE SUBMITTED.PLEASE SEE
 ATTACHED POLICY IN REGARDS TO MISSILE
 IMPACT PROTECTION, ITEM #13.
  
 37.)FOR THE GAF BUILT UP ROOF,
 INDICATE WHICH APPROVED ASSEMBLY YOU ARE
 USING.
  
 38.)FOR THE METAL ROOF PANELS, PROVIDE
 DESIGN PRESSURES AND SEE PRODUCT
 LIMITATION #7.
  
 39.)ANY PRODUCT APPROVALS NOT REVIEWED
 PRIOR TO PERMIT ISSUANCE WILL REQUIRE
 SEPARATE PERMITS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-14 Cont ID  
Sent By dpalmer Date 2006-02-14 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2006-02-14 Time 14:39 Sent To B
Notes
2006-02-14 00:00:00NEEDS NEW RECORDED NOC.
 NOC IN PACKAGE EXPIRED PER FS 713.13(2)

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-01-27 Cont ID  
Sent By dpalmer Date 2006-01-27 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2006-01-27 Time 17:12 Sent To  
Notes
2006-01-27 00:00:00IN ELEC FOR REVIEW
 ********** UNSAT 3RD REVIEW ************
  
 ** PLEASE SEE NOTES FROM TWO PREVIOUS
 REVIEWS WHICH STILL NEED TO BE
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENTS DUE TO
 CHANGES IN PLANS.
  
  
 1)NOTE: PLEASE CORRELATE RISER, PLANS,
 PANEL SCHEDULE(S).
 PLEASE SEE PLANS NOW INDICATE A
 COMPLETELY NEW AND DIFFERENT RISER FROM
 FIRST TWO REVIEWS.
 PLEASE SEE RISER NOW SHOWS A NEW 225A
 MCB, HOWEVER NEW SERVICE ENTRANCE
 CONDUCTORS ARE NOT RATED FOR THE 225A
 MAIN. PLEASE SEE 310.16 FOR SIZING.
 240.4,215.5
 PLEASE CORRELATE AS PANEL SCHEDULE SHOWS
 175A MCB AND PLANS INDICATE 200A??
 PLEASE ALSO SEE PLANS NOW INDICATE A
 J-BOX LOCATED INSIDE ELECTRICAL CLOSET
 WHICH IS OK, HOWEVER PLEASE SEE RISER
 SHOWS THIS AS A 225A J-BOX? PLEASE
 VERIFY WHAT A 225A J-BOX IS?
 215.5
 ** NOTE #4, PREVIOUS REVIEW, NOTE #9
 FROM FIRST REVIEW.
  
 2)NOTE: PLEASE SEE MECHANICAL NOTES AS
 THEY MENTION TO ADDRESS PREVIOUS
 COMMENTS. PLEASE SEE MECHANICAL PLANS
 STILL DO NOT INDICATE THE HEAT KW
 RATING.PLEASE VERIFY THE KW RATING FOR
 HEAT STRIPS IN UNITS, SHOW ON MECHANICAL
 PLANS AS REQUESTED BY MECHANICAL
 REVIEWER AND IF THERE ARE ANY CHANGES
 PLEASE ADJUST ELECTRICAL PLANS.
 215.5
  
 3)NOTE: PLEASE SEE NFPA-101
 7.8.1.3,7.9.2.2 FOR MIN LIGHTING LEVELS
 TO BE PROVIDED IN EGRESS STAIR AREAS.
 PLEASE SEE THE ONE FIXTURE INDICATED
 DOES NOT APPEAR ENOUGH TO PROVIDE 108
 LUX(10FT CANDLES).
 NOTE #5 PREVIOUS REVIEW.
  
 4)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL.
 PLEASE SEE PLANS WITH REPEAT COMMENTS
 THREE OR MORE TIMES FOR THE SAME CODE
 COMPLIANCE COMMENT SHALL BE ACCESSED AS
 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE. THIS FEE IS ACCESSED TO
 THE DESIGN PROFESSIONL.
 PLEASE SEE THE FEE ACCESSED IN THE
 AMOUNT OF $1836.00 IS DUE BEFORE PLANS
 MAY BE RETURNED FOR RESUB AND REVIEW.
 THE IS REQUIRED UNDER STATE STATUE AS
 MENTIONED ABOVE.
 PLEASE SEE FS 481.221 (5)&(6). THIS TEXT
 IS TAKEN DIRECTLY FROM THE FLORIDA
 STATUES.
  
 (6)NO REGISTERED ARCHITECT SHALL AFFIX
 HER OR HIS SIGNATURE OR SEAL TO ANY
 FINAL CONSTRUCTION DOCUMENT OR
 INSTRUMENT OF SERVICE WHICH INCLUDES
 DRAWINGS, PLANS, SPECIFICATIONS, OR
 ARCHITECTURAL DOCUMENTS WHICH WERE NOT
 PREPARED BY HER OR HIM OR UNDER HER OR
 HIS RESPONSIBLE SUPERVISING CONTROL OR
 BY ANOTHER REGISTERED ARCHITECT AND
 REVIEWED, APPROVED, OR MODIFIED AND
 ADOPTED BY HER OR HIM AS HER OR HIS OWN
 WORK ACCORDING TO RULES ADOPTED BY THE
 BOARD
  
 5)NOTE: PLEASE SEE NOTICE OF COMMENCEMNT
 SUBMITTED ANDRECORDED ON 7/14/05 HAS
 SINCE EXPIRED. PLEASE SEE FLORIDA
 STATUES 713.13(2). WORK WHICH HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING
 SAID NOC, THAT NOC SHALL BECOME VOID.
  
 PLEASE KNOW, ONE COPY OF ALL THREE SETS
 OF ELECTRICAL PLANS ARE NOW BEING
 RETAINED AND MAY BE SENT TO THE STATE OF
 FLORIDA BOARD OF ARCHITECTS.
  
 IF THERE ARE ANY QUESTIONS, IT IS
 STRONGLY SUGGESTED A MEETING BE HELD
 WITH THE DESIGN PROFESSIONAL TO GO OVER
 ANY COMMENTS IN QUESTION.
  
  
 5)NOTE: PLEASE REVMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE SEE THIS WAS NOT DONE
 WHEN PLANS WERE SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-29 Cont ID  
Sent By dpalmer Date 2005-11-29 Time 13:55 Rev Time 1.00
Received By dpalmer Date 2005-11-22 Time 08:18 Sent To M
Notes
2005-11-29 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE AT THIS TIME.
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS TO LOCAL BRANCH
 CIRCUIT FEEDING LTS.
  
 3)NOTE: PLEASE INCLUDE MISSING SIGN
 CIRCUIT AS REQUIRED PER 600.5
  
 4)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PLANS AND PANELS.
 PLEASE SEE PLANS INDICATE AN ADDITONAL
 SUB PANEL, HOWEVER RISER DOES NOT
 INDICATE THIS.
 PLEASE SEE PANEL IS BEING SHOWN AS BEING
 DOWN GRADED TO A 150A PANEL.
 215.5
  
 5)NOTE: PLEASE INDICATE THE MIN REQUIRED
 EMERGENCY EGRESS LT FIXTURE(S). PLEASE
 SEE FIRE REVIEW NOTES MENTIONS TO SHOW,
 HOWEVER THIS IS REQUIRED AT THIS TIME.
 PLEASE SEE NFPA-101 7.8,7.9 2003
 PLEASE ALSO SEE MIN EGRESS LIGHTING FOR
 STAIRWAYS IS REQUIRED TO HAVE A MIN OF
 10 FT CANDLES DURING NORMAL POWER AND
 1FT CANDLE UNDER EM POWER.
 PLEASE ALSO SEE ABOVE LS101 WHICH
 REQUIRES THE EM ILLUMINATION TO THE
 PUBLIC RIGHJT OF WAY.
  
 6)NOTE: PLEASE SEE MIN KVA PER KNOWN
 RECEPTS AT 180VA IS SHOWN , HOWEVER LOAD
 EXCEEDS THAT OF THETWO BRANCH CIRCUITS
 SHOWN ON PANEL SCHEDULE FOR ENTIRE COMM
 OFFICES.
 PLEASE ALSO INDICATE ANY DEDICATE LOADS
 FOR ANY, FRIG, COPIER, ETC.
  
 7)NOTE: PLEASE SEE 110.26, 240.24, 408.7
 WHICH REQUIRES ELECTRICAL PANELS ONLY TO
 BE LOCATED IN DEDICATED ELECTRICAL RMS.
 PLEASE LABEL PLANS ACCORD.
  
 8)NOTE: PLEASE SEE PLANS MENTIONS
 UPSTAIRS EXISTING TO REMAIN, YET PLEASE
 KNOW, THAT DUE TO THE CHANGE IN
 OCCUPANCYALL ELECTRICAL IS REQUIRED TO
 BE BROUGHT UP TO CODE.
  
 9)NOTE: PLEASE BE SURE PANEL SCHEDULE
 INDICATES ALL AWG SIZES FOR CORRELATION
 WITH OCP AND LOADS ON CIRCUITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-11-22 00:00:00PLANS TO BE UNSAT, NOTES TO FOLLOW.
2005-11-10 00:00:00PLANS SENT BACK TO INCOMING PER RB,
 AWAITING COMM BOARD.DV PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 12:59 Rev Time 2.00
Received By dpalmer Date 2005-07-28 Time 12:59 Sent To  
Notes
2005-07-28 00:00:00*********** UNSAT ************
  
 SF HOUSE TO "LIVE/WORK" OCCUPANCY.
  
  
 1)NOTE: PLEASE SEE THIS APPEARS TO BEA
 CHANGE IN OCCUPANCY AND SHALL BE
 REQUIRED FOR ELECTRICAL TO BE BROUGHT UP
 TO CODE FOR ELECTRICAL. NEC, LS101,
 NFPA-72 ETC. PLEASE ALSO SEE COMMENTS
 FROM OTHER TRADES.
 FBC 104.1.1
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AT THIS TIME AND CORRELATE WITH
 PANEL SCHEDULES TO BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 3)NOTE: PLEASE SEE REQUIREMENTS FOR
 LIVE/WORK, A KITCHEN WITH A MIN OF TWO
 SMALL APPLIANCE CIRCUITS SHALL BE
 PROVIDED. PLEASE ALSO SEE 210.8A6
 220.16, 210.11C1
  
 4)NOTE: PLEASE SHOW AL MIN CIRCUITS FOR
 DWELLING UNIT ALSO. PLEASE SEE MISSING
 LAUNDRY CIRCUIT, 220.16,210.112
  
 5)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT(S) PER
 210.52D,210.11C3
 MUST BE 20A, #12.
  
 6)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING PER 210.70,LS 101 5-8 IN SOME
 AREAS.
  
 7)NOTE: PLEASE SEE ALL RECEPT SPACING
 SHALL BE BROUGHT UP TO CODE. 210.52
  
 8)NOTE: PLEASE SEE ELECTRICAL PANEL MAY
 NOT BE IN A CLOSET/STORAGE CLOSET.
 408.7, 110.26 ETC.
  
 9)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PLANS. PLEASE INCLUDE ALL ELECTRICAL
 PANELS ETC ON PLANS AND RISER.
 215.5
  
 10)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL NEW AND EXISTING. PLEASE
 INDICATE MIXED USE, PLEASE ALSO ADJUST
 ANY LOAD CALCULATIONS ACCORDINGLY.
 220,215.5,
  
 11)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 INSTALLED PER 8-1.4.2
  
 12)NOTE: PLEASE INDICATE ALL ELECTRICAL
 ON PLANS. IF EXISTING PLEASE SHOW AS "E"
 ETC. PLEASE SHOW ALL A/C EQUIPMENT, EVEN
 IF EXSITNG AND SHOW ALL DISCONNECTING
 MEANS EVEN IF EXSITING.440.11
 PLEASE SHOW ANY LTS/RECEPTS (GFI)
 REQUIRED FOR A/C UNTIS. 210.70,210.63 IF
 EXISTING,PLEASE SHOW.
  
 13)NOTE: PLEASE SEE NEW SIGN CIRCUIT
 REQUIRED PER 600.5
 THIS REQUIREMENT IS NOT CONTINGENT ON
 WHETHER AN ELECTRIC SIGN WILL BE
 INSTALLED AT THE TIME AN OCCUPANT MOVES
 INTO ASPACE.
  
 14)NOTE: PLEASE SHOW ALL RECEPTS WHICH
 ARE REQUIRED TO BE GFI/GFI PROTECTED.
 210.8
  
 15)NOTE: PLEASE SEE BOTH SETS OF PLANS
 SUBMITTED ARE NOT SIGNED, DATED OR
 SEALED BY THE ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
 THIS IS REQUIRED OF ALL TRADES AND ALL
 REVIEW WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESIATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-14 Cont ID  
Sent By nmccray Date 2005-11-14 Time 11:45 Rev Time 0.00
Received By nmccray Date 2005-11-14 Time 11:34 Sent To  
Notes
2005-11-14 00:00:00PROVISO:
  
 PLEASE PROVIDE EMERGENCY LIGHTS IN
 STAIRS, FIRST, AND SECOND FLOOR AREA.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By mwennerg Date 2005-08-16 Time 11:23 Rev Time 0.00
Received By mwennerg Date 2005-08-16 Time 11:23 Sent To  
Notes
2005-08-16 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL REVIEW NOTE IN
 REGARDS TO LIGHTING IN MEANS OF EGRESS.
  
 2) PLEASE ALSO SEE OTHER REVIEW COMMENT
 REF: FS REQUIREMENT FOR PLANS.
  
 3) PLEASE INDICATE OCCUPANCY
 CLASSIFICATION FOR BUILDING AND EXISTING
 USE.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 5) SMOKE DETECTORS SHALL BE INSTALLED A
 MINIMUM DISTANCE OF 3' FROM HVAC
 DIFFUSERS.
  
 6) PLEASE SHOW ADDRESS ON BUILDING THAT
 MUST BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 7) PLEASE PROVIDE MORE INFORMATION
 REGARDING STAIRS AND RAMPS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 13:34 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 13:34 Sent To M
Notes
2006-08-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 15:19 Sent To M
Notes
2006-08-01 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 11:31 Sent To B
Notes
2006-05-18 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 15:08 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 15:08 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#26
2005-12-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 13:47 Sent To E
Notes
2005-11-14 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 10:15 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 10:15 Sent To FIRE
Notes
2005-11-14 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By shill Date 2005-08-17 Time 16:17 Rev Time 0.00
Received By shill Date 2005-07-21 Time 11:08 Sent To PC
Notes
2005-07-21 00:00:00TO "COMM" BD#18

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 10:55 Rev Time 0.20
Received By tgordon Date 2006-08-21 Time 10:55 Sent To  
Notes
2006-08-21 00:00:00REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 15:00 Rev Time 0.30
Received By tgordon Date 2006-08-08 Time 15:00 Sent To  
Notes
2006-08-08 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-08-03 Cont ID  
Sent By tgordon Date 2006-08-03 Time 12:19 Rev Time 0.25
Received By tgordon Date 2006-08-03 Time 12:19 Sent To  
Notes
2006-08-03 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) PLANS SUBMITTED HAVE A COPY OF THE
 ARCHITECT'S SEAL AND SIGNATURE ON THEM,
 BUT NEED A RAISED INPRESSION SEAL AND
 HIS SIGNATURE ON THEM, PER FS
 61G1-16.003 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-14 Cont ID  
Sent By hmoser Date 2006-02-14 Time 09:53 Rev Time 0.00
Received By hmoser Date 2006-02-14 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-01-25 Cont ID  
Sent By hmoser Date 2006-01-25 Time 18:34 Rev Time 0.00
Received By hmoser Date 2006-01-25 Time 18:15 Sent To  
Notes
2006-01-25 00:00:00PLAN DENIED
 1) NO COMMENTS WERE ANSWERED FROM FIRST
 REVIEW.
 2) PLEASE PROVIDE ENERGY CALCULATIONS
 WHEN YOU RESUBMIT THE PLANS.
 3) PLEASE PROVIDE EQUIPMENT SCHEDULE ON
 MECHANICAL PLANS.
 4 ) PLEASE PROVIDE SIZE AND LOCATION OF
 RETURN AIR ON UPSTARS UNIT.
 5) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS FBC(M)2001.
 PLAN ERVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-11-30 Cont ID  
Sent By tgordon Date 2005-11-30 Time 11:25 Rev Time 0.30
Received By tgordon Date 2005-11-30 Time 11:25 Sent To  
Notes
2005-11-30 00:00:00*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS ON 1ST.
 FLOOR ARE SOT SIZED. PLEASE NOTE RETURN
 TRANSFER DUCTS MUST BE 1 1/2 TIMES
 LARGER THAN THE SUPPLY AIR DUCT (6"
 SUPPLU DUCT REQUIRES 8" RETURN TRANSFER
 DUCT, 8" SUPPLY DUCT REQUIRES 10" RETURN
 TRANSFER DUCT). PER 2001 FBC/M601.4 .
 2) RETURN AIR TRANSFER DUCTS ON 2ND.
 FLOOR ARE TO SMALL (10" SUPPLY AIR DUCT
 REQUIRES A 13" RETURN AIR TRANSFER
 DUCT).
 3) THE SUPPLY AIR DUCT TO THE 2ND. FLOOR
 OFFICE IS NOT SIZED.
 4) THE SUPPLY AIR DUCT TO THE 1ST. FLOOR
 BATHROOM IS NOT SIZED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-09 Cont ID  
Sent By pkrauss Date 2005-08-09 Time 09:51 Rev Time 0.20
Received By pkrauss Date 2005-08-09 Time 09:46 Sent To  
Notes
2005-08-09 00:00:00NO MECHANICAL CONTRACTOR INDICATED OR
 PLANS SUBMITTED FOR REVIEW.PLEASE
 PROVIDE PLANS WITH EQUIPMENT SCHEDULE
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-11-29 Cont ID  
Sent By pschmitz Date 2005-11-09 Time 15:30 Rev Time 0.00
Received By pschmitz Date 2005-11-29 Time 15:05 Sent To  
Notes
2005-11-09 00:00:00PROVISO:
 PLUMBING DRAWING AT TIME OF PERMIT,FOR
 PLUMBING.
 SIGNED AND SEALED BY ENGINEER OF RECORD.
 END OF COMMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By jleech Date 2005-08-16 Time 14:03 Rev Time 1.50
Received By jleech Date 2005-08-16 Time 14:03 Sent To  
Notes
2005-08-16 00:00:00DENIED;
 1.PLANS ARE NOT SIGNED OR SEALED AND
 HAND WRITEN DIAMENTIONS ARE NOT
 PERMITED.
 2.BATHROOM 111, DOOR SWINGS INTO THE
 CLEAT FLOOR SPACE OF THE HANDICAP
 LAVATORY. FBC-2001 CHAPTER 11
 SEC.11-4.22.2.
 3.SHOW A DETAIL OF BREAK SINK. MUST
 COMPLY WITH FBC CH. 11 SEC. 11-4.24/1
 THRU 11-4.24.7.
 4.SHOW COMPIANCE WITH FBC PLUMBING TABLE
 403.1. DRIMKING FOUNTAIN,AUTOMATIC
 CLOTHES WASHER ARE REQUIRED. PLEASE SHOW
 SQUIRE FOOTAGE AND NUMBER OF EMPLOYEES
 TO MEET MINIMUM REQUIREMENTS. DRINKING
 FOUNTAIN SHALL COMPLY WITH HANDICAP CODE
 SEC. 11-4.1.3(10). MUST BE ACCESSIBLE
 FOR PEOPLE IN WHEELCHAIRS AND PEOPLE WHO
 HAVE TROUBLE BENDING AND STOOPING.
 5.BACKFLOW PROTECTION REQUIRED ON WATER
 SERVICE PER UTILITY ORD. #2853-95.
 6. SANITARY AND WATER RISER DIAGRAMS ARE
 REQUIRED SHOWING THE CHANGES TO BE MADE
 TO THE PLUMBING SYSTEM.
 7.WHERE IS WATER HEATER LOCATED?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-11-03 Cont ID  
Sent By sgraham Date 2005-11-03 Time 11:49 Rev Time 0.00
Received By sgraham Date 2005-11-03 Time 11:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-05 Cont ID  
Sent By alongo Date 2005-08-05 Time 15:40 Rev Time 0.00
Received By nleiva Date 2005-11-03 Time 09:16 Sent To  
Notes
2005-11-03 00:00:00SGRAHAM TOOK PLANS TO ZONING FOR REVIEW
2005-08-05 00:00:00WEST ELEVATIONS LABELED "EAST", PAGE A-3
  
 EAST ELEVATIONS LABELED "WEST", PAGE A-4
  
 DIMENSION ADA PARKING REQUIREMENTS AS
 PER TABLE XV-3, SECTION 94-485.
  
 THERE ARE TWO SETS OF ELEVATION PLANS -
 PLEASE CLARIFY AND DISTINGUISH BETWEEN
 ELEVATION PLANS (N,S,E, AND W).
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved