Plan Review Details - Permit 05070701
Plan Review Stops For Permit 05070701
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-01 Cont ID  
Sent By shill Date 2005-12-01 Time 11:40 Rev Time 3.00
Received By shill Date 2005-12-01 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-14 Cont ID  
Sent By shill Date 2005-08-14 Time 15:50 Rev Time 3.00
Received By shill Date 2005-08-14 Time 12:33 Sent To  
Notes
2005-08-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MAY BE DUE AND MUST BE
 PAID TO PALM BEACH COUNTY (IF IT IS
 DETERMINED THAT THERE HAS BEEN A CHANGE
 OF USE).THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 3.)THIS IS AN OVER 50% IMPROVEMENT.
 SOME COMMENTS MAY BE DUE TO THE
 REQUIREMENTS OF FBC3401.7.2.6.
  
 4.)I WAS UNABLE TO LOCATE CHISHOLM
 ARCHITECTS, INC. AAC001962 ON THE STATE
 WEBSITE.SEE FAC61G1-16.PLEASE
 ADDRESS.
  
 5.)THE SURVEY IS REQUIRED TO CONTAIN
 THE LANGUAGE IN FAC61G17-6.003(2)(E) IN
 REGARDS TO THE SURVEY NOT BEING VALID
 WITHOUT A SEAL.ONLY ONE ORIGINAL
 SUBMITTED.BOTH COPIES REQUIRED TO BE
 ORIGINAL.
  
 6.)FAC61G17-6.003(2)(B) REQUIRES THAT
 THE TYPE OF SURVEY BE STATED AS DEFINED
 IN RULE 61G17-6.002(8)(A)-(K).
 ALTA/ACSM LAND TITLE SURVEY IS NOT ONE
 OF THE SURVEY TYPES.ALSO SEE
 FAC61G17-6.0052.THIS DOES NOT APPEAR
 TO FALL UNDER THIS EXCEPTION.
  
 7.)FAC61G17-6.003(2)(C), THE TITLE
 BLOCK IS TO INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE FIRM.
  
 8.)THE JURISDICTION FOR THE ENERGY
 CALCS IS 604700, FBC13 APPENDIX A.
 INCLUDE ON THE ENERGY CALCS AS REQUIRED.
  
 9.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 10.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING USE AND PROPOSED USE.
 DECLARE AN OCCUPANCY SUBCLASSIFICATION
 FBC311 SO THAT CODE COMPLIANCE WITH
 FBC11, ACCESSIBILITY OR FAIR HOUSING CAN
 BE DETERMINED AS APPLICABLE.
  
 11.)SHOW THE ELEVATIONS AT THE DOORS.
 THERE APPEARS TO BE A CHANGE IN
 ELEVATION, NOTE THE DIMENSION FOR
 ACCESSIBLE UNITS OR UNITS COMPLYING WITH
 FAIR HOUSING.
  
 12.)THE CABINET DETAILS ON A3.2 SHOW
 DOORS ON THE CABINETS.SINKS REQUIRED
 TO BE ACCESSIBLE ARE TO COMPLY WITH
 FBC11-4.24.THERE IS REFERENCE TO AN
 ADA UNIT.NOTE THAT AT THIS TIME
 COMPLIANCE WITH FBC11 HAS NOT YET BEEN
 DETERMINED.
  
 13.)A1-1, ITEM 12, EITHER SPECIFY AN
 APPROVED ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 14.)SHOW TENANT SEPARATION, HORIZONTAL
 AND VERTICAL, FBC704.3.
  
 15.)INDICATE PROTECTION REQUIRED BY
 FBC1006.2.4.
  
 16.)DECLARE TOTAL SF, DECLARE A
 BUILDING TYPE FBC CHAPTER 6.
  
 17.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING STAIRS (CONSTRUCTION, TREAD
 AND RISER DIMENSION, WIDTH).SEE
 FBC1001.3.
  
 18.)PROVIDE BALCONY DIMENSIONS,
 LANDING DIMENSION.
  
 19.)THE STAIR PLAN A3.2 IS NOT CLEAR.
 THE RAILING DETAILS SHOW EXTENSIONS AT
 THE TOP AND BOTTOM, BUT THE PLAN AND
 A1.2 SHOWS EXTENSIONS ON THE TOP ONLY.
  
 20.)PROVIDE PRODUCT APPROVALS FOR
 DOORS AND WINDOWS.NOTE THAT THE PLANS
 SPECIFY IMPACT GLASS.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 FOR THOSE ITEMS.
  
 21.)THE ENERGY CALCS ON ONE SET HAVE A
 PHOTOCOPY OF A SEAL.DOCUMENTS PREPARED
 BY A DESIGN PROFESSIONAL SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS, FAC61G1-16.003,004 AND
 FAC61G15-23.002.
  
 22.)THE ASBESTOS REPORT PREPARED BY
 GAUDET AND ASSOCIATES IS TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002
 AND TO BE SIGNED, SEALED, DATED
 ORIGINALS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 12:45 Sent To  
Notes
2005-12-05 00:00:00** PLANS REDLINED 2ND REVIEW **
  
 PLEASE SEE PLANS WERE INITIALED BY
 ENGINEER TO PLACE SD'S ON BATH CIRCUIT,
 HOWEVER 210.11C3 DOES NOT PERMIT ANY
 OTHER DEVICES ON BATH CIRCUIT.
 SD'S SHOULD BE ON BEDRM CIRCUIT OR ARC
 FAULT CIRCUIT PER 210.12

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 18:49 Rev Time 3.00
Received By dpalmer Date 2005-07-28 Time 18:49 Sent To  
Notes
2005-07-28 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS RENOVATION OF ENTIRE BLDG,
 HOWEVER ELECTRICAL PLANS NOT SUBMITTED
 FOR ENTIRE BLDG? PLEASE SEE MISSING
 UNITS 1-8.
 PLEASE SEE THIS ALSO SEEMS TO BE A
 CHANGE IN OCCUPANCY CLASSIFICATION,
 THERFORE ALL ELECTRICAL ETC WILL BE
 REQUIRED TO BE BROUGHT UP TO CODE.
  
 2)NOTE: PLEASE SEE BOTH SETS OF PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND
 SEALED BY SAID ENGINEER. PLEASE ALSO SEE
 ARCHITECTUAL SHEETS.
 PLEASE SEE PRINT OUT FROM DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION
 (DBPR) WHICH SHOWS FIRM LICENSE NUMBER
 AS SHOWN ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. PLEASE SEE THE LICENSE NUMBER AS
 SHOWN DOES NOT SEEM TO CORRELATE WITH
 STATE PRINT FOR THIS FIRM. PLEASE
 VERIFY.
 PLEASE SEE FAC 61G15-23.002,
 61G1-16.004, FS 471.025, AND 481.221 FOR
 THE ABOVE COMMENTS.
 PLEASE SEE THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENTS ARE MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS FOR ALL NEW AND FOR ALL EXISTING
 BEING BROUGHT UP TO CODE. ITEMS SHOWN AS
 EXISTING WILL BE REQUIRED TO BE BROUGHT
 UP TO CODE FOR ALL GROUND FAULT, ARC
 FAULT, BRANCH CIRCUIT SIZING ETC.
 210.52,210.11,220.16 ETC.
 215.5
 PLEASE SEE FUTHER COMMENTS FOR 2002 NEC.
  
 4)NOTE: PLEASE SEE 210.52B, 210.11C1 AND
 220.16 FOR MIN OF TWO SMALL APPLIANCE
 CIRCUITS.
 PLEASE ADJSUT PANEL SCHEDULES, LOAD
 CALCULATIONS ETC.
  
 5)NOTE: PLEASE SEE 210.52C1-5 FOR
 RECEPTS TO MEET KITCHEN COUNTERSPACE.
 PLEASE SEE MISSING GFI'S AS REQUIRED.
  
 6)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 SHOWN AS GFI/GFI PROTECTED.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED UNDER 210.52 2',6',12 RULE.
 PLEASE EITHER SHOW AS NEW OR EXISTING TO
 NEW CIRCUITING.
  
 8)NOTE: PLEASE LIST ALL THE ARC FAULT
 REQUIRED CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE PLANS ARE NOTED FOR ARC FAULT
 PROTECTION FOR "RECEPT OUTLETS" AND
 SD'S??
 PLEASE SEE 2002 NEC 210.12, "ALL
 OUTLETS" ARE REQUIRED TO HAVE ARC FAULT
 PROTECTION, WHICH WOULD INCLUDE ALL
 LIGHTING, FANS ETC.
 PLEASE SEE NOTE ABOVE ARC FAULT NOTE
 MENTIONS FOR SD'S TO WIRED INTO KITCHEN
 LIGHTING CIRCUIT? THIS IS OK, HOWEVER
 ALL KITCHEN LIGHTING CIRCUITS WOULD ALSO
 BE REQUIRED TO BE ARC FAULT. PLEASE ALSO
 SEE CIRCUITING AS SHOWN ON PLANS AT
 PRESENT TIME DOES NOT SHOWS SD'S BEING
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT?
  
 9)NOTE: PLEASE SHOW DESIGNATIONS ON ALL
 PANELS ON PLANS.
 PLEASE KNOW DEPENDING ON OCCUPANCY AND
 USEAGE, PANELS MAY BE REQUIRED IN SPACE
 OF APT UNIT FOR ACCESS TO BREAKERS FOR
 TENANT OCCUPANTS.
 240.24A,B ,230.72C
  
 10)NOTE: PLEASE SEE 230.79 FOR MIN
 PANEL/SERVICE FOR EACH UNIT OF THIS
 MULTI-FAMILY BLDG. PLEASE SEE A MIN OF
 60A'S OR MORE SHALL BE PROVIDED FOR
 EACH.
  
 11)NOTE: PLEASE SHOW ALL HOUSE
 CIRCUITING ON PLANS AND CORRELATE WITH
 HOUSE PANELS TO BE SUBMITTED.
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. 215.3,230.42 ETC.
  
 12)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE FOR CLOSET LTS AND TYPE OF
 FIXTURES.
  
 13)NOTE: PLEASE SHOW "DINING AREA"
 DESIGNATIONS ON PLANS IN ORDER TO VERIFY
 CIRCUITING.
 215.5
  
 14)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL ELECTRICAL DEVICES TO MEETCHAPTER
 5 OF THE FAIR HOUSING ACT REGULATIONS,
 24 CFR 100.205.
 DEVICES ABOVE KTICHEN COUNTERSPACE SHALL
 NOT BE HIGHER THAN 46"
  
 15)NOTE: PLEASE CORRELATE LOAD SHOWN ON
 LOAD CALCULATIONS FOR NEW LOAD AND LOAD
 SHOWN ON RISER DIAGRMA ON NEW 400A
 DISCONNECT FUSED AT 300A'S.
 215.5
  
 16)NOTE: PLEASE CLARIFY EXISTING SERVICE
 DISCONNECTS/PANELS SHOWN AS CIRCUIT
 BRKR, WITH FUSES??
 215.5
  
 17)NOTE: PLEASE SEE CHAPTER 34 OF THE
 FBC FOR RENOVATIONS TO EXSITING BLDGS.
  
 18)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FORCOMMENTS FOR BLDG PERMIT
 APPLICATION VALUATION.
 PLEASE SEE BUILDING VALUATION IS BASED
 ON ALL LABOR AND MATERIALS, EVNE IF
 MATERIALS ARE OWNER SUPPLIED.
 104.6.5
  
 PLEASE SEE ANY COMMENTS FORM OTHER
 TRADESWHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE PLANS MAY HAVE ADDITIONAL
 COMMENTS DUE TO PLANS NOT BEING COMPLETE
 AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INOT COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 11:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By mwennerg Date 2005-08-16 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2005-08-16 Time 10:21 Sent To  
Notes
2005-08-16 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 2) PLEASE INDICATE THE OCCUPANT
 CLASSIFICATION FOR NEW PROJECT AND
 EXISTING USE OF BUILDING.
  
 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 4) DOOR SWING FROM SECOND FLOOR STORAGE
 ROOM APPEARS TO OBSTRUCT GREATER THAN
 1/2 DISTANCE OF THE EXIT ACCESS.
  
 5) PLANS ILLUSTRATE THAT THE FIRE ALARM
 PANEL IS TO REMAIN. SEPARATE SHOP
 DRAWINGS AND PERMIT ARE REQUIRED FOR
 FIRE ALARM REMODEL.
  
 6) ADDRESS IF NOT ALREADY PROVIDED SHALL
 BE ON BUILDING AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 7) PLEASE SHOW LOCATION OF 2A-10B
 RATED FIRE EXTINGUISHERS TO BE MOUNTED
 TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 8) PLEASE EXPLAIN GATE OPERATION ON EAST
 SIDE OF BUILDING THAT APPEARS TO BE
 COMPONENT OF MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 11:26 Sent To  
Notes
2005-12-09 00:00:00COMM BD#24 NOT #21
  
  
2005-11-21 00:00:00TO "COMM" BD#21
2005-10-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By kstevens Date 2005-08-23 Time 17:23 Rev Time 0.00
Received By kstevens Date 2005-07-19 Time 11:16 Sent To  
Notes
2005-07-20 00:00:00TO "COMM" BD#63
2005-07-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-01 Cont ID  
Sent By pkrauss Date 2005-12-01 Time 15:25 Rev Time 0.00
Received By pkrauss Date 2005-12-01 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By pkrauss Date 2005-08-09 Time 12:36 Rev Time 0.55
Received By pkrauss Date 2005-08-09 Time 12:36 Sent To  
Notes
2005-08-09 00:00:00DENIED:
 1.ONLY ONE SET OF PLANS ARE SIGNED,
 SEALED & DATED BY THE ENGINEER.TWO
 SETS ARE REQUIRED TO BE SIGNED, SEALED &
 DATED BY THE ENGINEER IN ACCORDANCE WITH
 FAC 61G15-23.002, FS 471.025 & 2001 FBC
 104.2.1.
  
 2.PLEASE SEE COMMENTS 1 & 2 BY DEWEY
 PALMER, ELECTRICAL PLAN REVIEW.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By kstevens Date 2005-12-06 Time 10:53 Rev Time 1.00
Received By kstevens Date 2005-12-06 Time 10:53 Sent To  
Notes
2005-12-06 00:00:00PASSED/PROVISO
  
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By kstevens Date 2005-08-23 Time 17:04 Rev Time 2.00
Received By kstevens Date 2005-08-23 Time 17:04 Sent To  
Notes
2005-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. BOTH SETS OF PLANS TO BE SIGNED,
 SEALED, AND DATED, AND THE CERTIFICATE
 OF AUTHORIZATION FOR THE ARCHITECT CAN
 NOT BE VERIFIED ON DBPR WEBSITE. SECTION
 104.2.2. FAC61G1-16.004 & FS 481.2055
 2. SHT P-1.1 WATER RISER DIAGRAMS, AIR
 CHAMBERS ARE NOT APPROVED AND SHALL BE
 DELETED FROM WATER RISER DIAGRAMS.
 SECTION 604.9 AND PDI-WH 201.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]