Plan Review Details - Permit 05070693
Plan Review Stops For Permit 05070693
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-03 Cont ID  
Sent By jgomez Date 2005-10-03 Time 15:25 Rev Time 0.33
Received By jgomez Date 2005-10-03 Time 15:25 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-19 Cont ID  
Sent By jgomez Date 2005-08-19 Time 17:03 Rev Time 0.50
Received By jgomez Date 2005-08-19 Time 17:03 Sent To PC
Notes
2005-08-19 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- PACKAGE SUBMITTED IS MISSING THE
 PERMIT APPLICATION.
  
 2- STORM SHUTTERS:
 A) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 B) CLEARLY MARK ON SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND TYPE OF
 ANCHOR AND SPACING TO BE USED ACCORDING
 TO THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 BLOCK, CONCRETE OR WOOD).
  
 3- STOREFRONT WAS CHANGED FROM ONE BIG
 PANEL TO 3 PANELS MULLED TOGETHER.
 PROVIDE/REVISETHE FOLLOWING
 INFORMATION:
  
 A) ENGINEER OF RECORD TO REVISE THE BUCK
 SIZE. 1X3 BUCK SPECIFIED ON PLANS
 DOESN'T WORK. NEED BUCK TO PROVIDE FULL
 STOREFRONT FRAME SUPPORT AS REQUIRED BY
 SEC. 1707.4.4.2 FBC 2001. SEE STOREFRONT
 PRODUCT APPROVAL FOR SIZE OF STOREFRONT
 TO BE SUPPORTED.
  
 B) ENGINEER OF RECORD NOTES BELOW
 ELEVATION CALLS FOR ATTACHMENT OF FIXED
 GLASS WITH 3/16" TAPCONS. REVISE SIZE.
 SEE STOREFRONT PRODUCT APPROVAL FOR
 CORRECT TAPCON SIZE AND SPACING.
  
 C) CLEARLY SPECIFY STOREFRONT SIZE TO BE
 INSTALLED IN THE LARGE OPENING. (RIGHT
 HAND SIDE OPENING).
  
 4- FLOOR PLAN AND ELEVATION DON'T MATCH.
 FLOOR PLAN CALLS FOR EXISTING SINGLE
 DOOR, WHILE ELEVATIONS SHOWS SINGLE DOOR
 WITH SIDELITES. REVISE AS REQUIRED.
 PERMIT APPLICATION IS FOR WINDOWS ONLY.
  
 5- ENGINEER TO PROVIDE CALCULATIONS FOR
 THE OPENINGS DESIGN PRESSURES. THEY
 DON'T MATCH TABLE 1606.2B FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 6- CLARIFY SCOPE OF WORK NOTE #2. ARE
 OPENINGS REINFORCED AT BOTH SIDES TO
 RECEIVE THE NEW STOREFRONT OR NOT. NOTE
 SAYS OPENINGS WERE BLOCKED UP W/CBS. ARE
 THEY HOLLOW CORE OR CELL FILLED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 7- CLARIFY WHAT ARE THE FLORIDA BUILDING
 CODE TABLE COPIES FOR?. WHO PREPARED THE
 INTERPOLATED VALUES?. WHY ARE THERE
 THREE UNITS IF THERE ARE ONLY TO NEW
 STOREFRONTS TO BE PROTECTED.
  
 8- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 9- CONTRACTOR NEEDS TO UPDATE INSURANCE
 AND WORKERS COMP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By jgomez Date 2005-07-27 Time 13:30 Rev Time 1.00
Received By jgomez Date 2005-07-27 Time 11:46 Sent To PC
Notes
2005-07-27 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- STORM SHUTTERS: A) PROVIDE KEY PLAN
 AND COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
 B) CIRCLE ON SHUTTER DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, TYPE OF ANCHOR AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, THE EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (MASONRY OR
 CONCRETE).
 C) PROVIDE 2 COPIES OF PRODUCT APPROVAL
 AND INFORMATION REQUESTED ABOVE.
  
 2- ENGINEER TO PROVIDE CALCULATIONS TO
 DETERMINE TYPE, SIZE AND THICKNESS OF
 GLASS TO RESIST THE CALCULATED DESIGN
 PRESSURES. CALCULATIONS SHALL BE BASED
 ON ASTM E 1300 1994 EDITION AS REQUIRED
 BY CHAPTER 35 FBC 2001 AND SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 *NOTE: INFORMATION WRITTEN ON PRODUCT
 APPROVAL PAGE 5 OF 8 TO BE ON ENGINEER
 OF RECORD DRAWINGS, NOT IN THE PRODUCT
 APPROVAL. SIZE OF WINDOW DOESN'T MATCH
 PLANS AND NEED TO USE ASTM E 1300 1994
 EDITION.
  
  
 3- SPECIFY GLASS SUPPORTS AS REQUIRED BY
 SEC. 2406.1 FBC 2001 FOR DEFLECTION
 CONSIDERATION.
  
 4- SPECIFY STRUCTURAL BUCK DETAILS FOR
 WINDOW ATTACHMENT. SEC. 1707.4.4 FBC.
  
 5- SIZE OF WINDOW SHOWN ON WALL SECTION
 DOESN'T MATCH SIZE SHOWN ON FLOOR PLAN.
 ALSO, SIZE SHOWN ON FLOOR PLAN DOESN'T
 CORRESPOND TO SIZE SHOWN ON FRONT
 ELEVATION. REVISE AS REQUIRED.
  
 6- PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 19:07 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 19:07 Sent To B
Notes
2005-09-23 00:00:00TO "JGOMEZ' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 10:19 Sent To B
Notes
2005-08-19 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-19 Cont ID  
Sent By jgomez Date 2005-08-19 Time 17:53 Rev Time 0.00
Received By jgomez Date 2005-07-18 Time 15:18 Sent To  
Notes
2005-07-18 00:00:00TO "MISC" BOX #1