Plan Review Details - Permit 05070691
Plan Review Stops For Permit 05070691
Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2007-03-16 Cont ID  
Sent By shill Date 2007-03-16 Time 11:16 Rev Time 0.00
Received By shill Date 2007-03-16 Time 11:16 Sent To  
Notes
2007-03-16 11:16:52WINDOW/DOOR SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2007-02-28 Cont ID  
Sent By shill Date 2007-02-28 Time 16:32 Rev Time 0.00
Received By shill Date 2007-02-28 Time 16:32 Sent To  
Notes
2007-02-28 16:40:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)TWO SETS REQUIRED.PLEASE SUBMIT SECOND SET.
  
 2.)ELECTRIC SHEETS OK; THE ONE SET RETURNED IS
 CONTRACTOR SET.DO NOT RESUBMIT.RESUBMIT BUILDING
 REVISION ONLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 16:39 Rev Time 0.00
Received By shill Date 2007-01-23 Time 16:39 Sent To  
Notes
2007-01-23 16:39:48JOIST SHOP DRAWINGS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-01-17 Cont ID  
Sent By shill Date 2007-01-17 Time 15:31 Rev Time 0.00
Received By shill Date 2007-01-17 Time 15:31 Sent To  
Notes
2007-01-17 15:32:07REVISION S2 DATED 1/10/07
  
 TRUSS ENGINEERING SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-01-04 Cont ID  
Sent By shill Date 2007-01-04 Time 13:43 Rev Time 0.00
Received By shill Date 2007-01-04 Time 13:43 Sent To  
Notes
2007-01-04 13:44:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
  
 STEEL SHOPS
  
 1.) SUBMITTALS ARE TO BE APPROVED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 11:10 Rev Time 0.00
Received By shill Date 2007-01-03 Time 11:01 Sent To  
Notes
2007-01-03 11:12:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2001
  
 REVISION, VARIOUS DATES
  
 1.) NA
  
 2.)REGARDING THE LETTER FROM THE ENGINEER WHICH
 ADDRESSES THE CONTRACTOR'S REQUEST THAT THE MASONRY
 CELLS ABOVE THE BAY DOOR OPENINGS BE POURED WITH THE
 SAME CONCRETE MIX AS THE CAST IN PLACE COLUMNS, PLEASE
 CLARIFY THAT THE FOLLOWING FROM ACI 318 6.1.5.2 HAS
 BEEN ADDRESSED:"TO FLOW AROUND REINFORCEMENT AND TO
 COMPLETELY FILL CAVITIES, GROUT, WHETHER PUMPED OR
 POURED, NEEDS TO BE VERY FLUID.THIS NECESSITATES A
 HIGHER WATER CONTENT THAN FOR MASONRY MORTARS. . . .
 CAVITY SIZE AFFECTS THE GROUT'S CONTACT SURFACE AREA.
 THE GREATER THE SURFACE AREA THE GREATER THE AMOUNT OF
 WATER ABSORBED."ADDRESS DESIGN CONCRETE STRENGTH.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-01-02 Cont ID  
Sent By shill Date 2007-01-02 Time 09:41 Rev Time 0.00
Received By shill Date 2007-01-02 Time 09:29 Sent To  
Notes
2007-01-02 09:48:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2001
  
 1.)ALL SUBMITTALS FOR COMMERCIAL BUILDINGS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD.
  
 2.)EACH SHEET IS TO CONTAIN THE NAME OF THE PERSON
 SEALING THE DOCUMENTS, FAC61G16-23.002.
  
 3.)SHEET S2 METAL TRUSS NOTES DESIGN CRITERIA IS TCDL
 30, TCLL 20, BCDL5, BCLL 0.TRUSS ENGINEERING STATES
 TCDL 15.PLEASE ADDRESS.NOTE THAT THE BCLL
 REQUIREMENT OF 10PSF IS FOR RESIDENTIAL, NO STORAGE FBC
 TABLE 1604.1.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-10-26 Cont ID  
Sent By shill Date 2006-10-26 Time 11:16 Rev Time 0.00
Received By shill Date 2006-10-26 Time 11:16 Sent To  
Notes
2006-10-26 11:16:48REVISED S3 & S4
 DATED 10/17/6

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 15:47 Rev Time 0.00
Received By shill Date 2006-08-11 Time 15:47 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2001
  
  
 ROOF:
  
 1.)THE PRODUCT APPROVAL IS NOT
 CURRENT; HAS BEEN UPDATED.
  
 2.)PRINT THE .PDF FILE FOR THE PRODUCT
 YOU ARE INSTALLING FROM THE MOST CURRENT
 FLORIDA STATE PRODUCT APPROVAL.
  
 3.)ON THE EVALUATION REPORT OR OTHER
 DOUCUMENTATION, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.
  
 4.)THIS REQUIRES A SEPARATE PERMIT.
 DO NOT SUBMIT WITH THIS PACKAGE; SUBMIT
 AS A NEW PERMIT.
  
 CIVIL PLANS:
  
 5.)THE ACCESSIBLE PARKING DETAIL IS TO
 COMPLY WITH CITY OF WEST PALM BEACH
 STANDARD, SEE ATTACHED.THE
 NON-ACCESSIBLE DETAIL WAS REVISED BUT
 THE ACCESSIBLE DETAIL DOES NOT COMPLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 15:42 Rev Time 0.00
Received By shill Date 2006-08-11 Time 15:42 Sent To  
Notes
2006-08-11 00:00:00 
 LETTER, REVISED LS1

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-03-23 Cont ID  
Sent By shill Date 2006-03-23 Time 14:51 Rev Time 0.00
Received By shill Date 2006-03-23 Time 14:51 Sent To  
Notes
2006-03-24 00:00:00ROOF REVIEW
 NOA 03-0114.06, SANTAFE TILE CORPORATION
 MISSION BARREL ROOFING TILE
  
 FLAT DECK - FL735, TAMKO MODIFIED,
 NOA01-1011.03
  
  
2006-03-23 00:00:00****PROVISO ITEMS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 PROVISO ITEMS:
  
 1.)REVISE THE LANDSCAPE AND CIVIL
 SHEETS TO SHOW THE NEW SIDEWALK AS
 REQUESTED.NOTE THAT THE SIDEWALK IS
 PLACED WHERE A MAHOGANY TREE IS LOCATED.
  
 2.)REVISE THE LIFE SAFETY PLAN TO SHOW
 ALL REQUIRED EXIT LIGHTS.THE DISTANCE
 BETWEEN THE REMOTELY LOCATED EXITS
 SHOULD BE THE TWO ACCESSIBLE EXITS.
  
 3.)SUBMIT A LETTER FROM THE ENGINEER
 CONFIRMING THAT NONE OF THE OPENINGS ARE
 IN ZONE 5.
  
 4.)PROVIDE THE CHANGE OF CONTRACTOR
 FORM BEFORE FIRST INSPECTION.
  
 5.)THE FIRE SPRINKLER CALCS ARE TO BE
 EITHER SIGNED AND SEALED EACH SHEET OR
 HAVE AN INDEX SHEET.THE INFORMATION
 REQUIRED (PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT, PRINTED LICENSE
 NUMBER OF THAT INDIVIDUAL, AND CA NUMBER
 FOR THE FIRM) IS LACKING.SEE
 FAC61G15-23.
  
 6.)INDICATE WHICH APPROVED ASSEMBLY
 YOU ARE INSTALLING (MODIFIED ROOF).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-03-17 Cont ID  
Sent By shill Date 2006-03-17 Time 16:34 Rev Time 0.00
Received By shill Date 2006-03-17 Time 10:18 Sent To  
Notes
2006-03-17 00:00:00****PROVISO ITEMS****
 ****NO RESUB FEE*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 PROVISO ITEMS:
  
 1.)REVISE THE LANDSCAPE AND CIVIL
 SHEETS TO SHOW THE NEW SIDEWALK AS
 REQUESTED.NOTE THAT THE SIDEWALK IS
 PLACED WHERE A MAHOGANY TREE IS LOCATED.
  
 2.)REVISE THE LIFE SAFETY PLAN TO SHOW
 ALL REQUIRED EXIT LIGHTS.THE DISTANCE
 BETWEEN THE REMOTELY LOCATED EXITS
 SHOULD BE THE TWO ACCESSIBLE EXITS.
  
 3.)SUBMIT A LETTER FROM THE ENGINEER
 CONFIRMING THAT NONE OF THE OPENINGS ARE
 IN ZONE 5.
  
 3.)SOME OF THE PRODUCT APPROVALS ARE
 EXPIRED (FBC2001 RATHER THAN FBC2004).
 NEW PRODUCT APPROVALS WERE
 SUBMITTED FOR THE ROOF.DIFFERENT
 PRODUCTS WERE SUBMITTED WITH THIS
 REVIEW. YOU MAY SUBMIT THE CORRECT
 PRODUCT APPROVALS NOW, OTHERWISE THE
 PERMIT WILL BE ISSUED WITH A PROVISO
 THAT THESE ITEMS BE ON A SEPARATE
 PERMIT.
  
 4.)THE CHANGE OF CONTRACTOR FORM IS
 NOT IN THE PACKAGE.THIS MAY PROVIDED
 AT FIRST INSPECTION IF YOU DO NOT HAVE A
 COPY.
  
 5.)THE FIRE SPRINKLER CALCS ARE TO BE
 EITHER SIGNED AND SEALED EACH SHEET OR
 HAVE AN INDEX SHEET.THE INFORMATION
 REQUIRED (PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT, PRINTED LICENSE
 NUMBER OF THAT INDIVIDUAL, AND CA NUMBER
 FOR THE FIRM) IS LACKING.SEE
 FAC61G15-23.
  
 ITEMS WHICH MUST BE DONE PRIOR TO PERMIT
 ISSUANCE:
  
 6.)PROVIDE THE IMPACT FEE RECEIPT.
  
 7.)THE APPLICATION FOR THE NEW
 CONTRACTOR IS NOT IN THE PACKAGE.
 PLEASE SUBMIT A NEW APPLICATION.ALSO
 PLEASE COMPLETE A SECOND APPLICATION FOR
 THE DUMPSTER ENCLOSURE.
  
 8.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK FS713.13.
 PLEASE RE-FILE.THIS MAY BE DONE BEFORE
 PERMIT PICKUP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-21 Cont ID  
Sent By shill Date 2005-12-21 Time 16:17 Rev Time 6.00
Received By shill Date 2005-12-21 Time 10:29 Sent To  
Notes
2005-12-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEWS,
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.MISSING NUMBERS INDICATE
 COMMENTS WHICH WERE ADDRESSED CORRECTLY.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025 FOR MORE
 INFORMATION.
  
 9.)(SECOND REVIEW) . . . THE CALCS
 REFER TO THE 2003 FBC, GOVERNING CODE IS
 FBC2001.
  
 (THIRD REVIEW)GOVERNING CODE STILL
 STATES 2003 FBC.PLEASE REVISE.
  
 11.)HURRICANE SHUTTER STORAGE IS SHOWN
 ON THE PLAN (TIRE STORAGE AREA).SEE
 ATTACHED IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.SUBMIT A PLAN FOR
 INSTALLATION FOR REVIEW.
  
 (SECOND REVIEW) NOT ADDRESSED.USE OF
 REMOVABLE SHUTTERS AND THE INSTALLATION
 PLAN IS TO BE APPROVED BY THE BUILDING
 OFFICIAL.
  
 (THIRD REVIEW) RESPONSE LETTER PROVIDED
 SOME INFORMATION IN REGARDS TO SHUTTER
 INSTALLATION.THIS IS NOT AN
 INSTALLATION PLAN.PLEASE PROVIDE A
 PLAN AS REQUESTED WITH ALL NECESSARY
 INFORMATION TO SHOW COMPLIANCE WITH THE
 POLICY AND SUBMIT.THIS PLAN WILL BE
 REVIEWED FOR COMPLETENESS PRIOR TO
 SUBMITTAL TO THE BUILDING OFFICIAL, WHO
 WILL MAKE DETERMINATION AS TO WHETHER OR
 NOT APPROVAL IS GRANTED.THE PLAN IS TO
 BE APPROVED PRIOR TO PERMIT ISSUANCE OR
 THE PLAN IS TO BE REVISED FOR IMPACT
 GLASS.
  
 12.)SEE PROCEDURES, ITEM I, ON THE
 ATTACHED STANDARD IN REGARDS TO REQUIRED
 INFORMATION.A FORM IS ATTACHED FOR
 YOUR CONVENIENCE.
  
 (SECOND REVIEW)NOT ADDRESSED.FORM
 WAS RETURNED BLANK.
  
 (THIRD REVIEW)THIS CANNOT BE ISSUED AS
 SUBMITTED UNTIL AN INSTALLATION PLAN HAS
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN
 FROM THE SERVICE AREA AND THE TIRE
 STORAGE FBC11-4.11(3), FBC1004.2.2.
  
 (SECOND REVIEW) SAME PLANS PROVIDED.
 NOTE THAT EXIT 2HAS A RAMP, EXITS 3 AND
 4 HAVE STEPS.THE RESPONSE LETTER
 STATES THAT DOORS 107 AND 108 ARE
 ACCESSIBLE EGRESS DOORS. DOOR 107 IS AN
 INTERIOR DOOR, IS NOT AN EXIT.DOOR 108
 HAS A STEP DOWN, NOT AN ACCESSIBLE EXIT.
  
 (THIRD REVIEW)THE RESPONSE LETTER
 STATES THAT DOORS 101, 107 AND 110 ARE
 ACCESSIBLE EXITS.PLEASE NOTE THE
 FOLLOWING:
  
 DOOR 107 IS NOT AN EXIT, IT IS AN
 INTERIOR DOOR LEADING TO THE WORK AREA.
 SEE FBC CHAPTER 2, DEFINITIONS.
  
 DOORS 107 AND 110 ARE 40 FEET APART.
 THEY DO NOT COMPLY WITH FBC1004.1.4, THE
 REQUIREMENT TO BE REMOTELY LOCATED.
  
 **NOTE - PER ARCHITECT, THE SECOND
 ACCESSIBLE EXIT IS TO BE DOOR 108, WHICH
 WILL BE REVISED TO ELIMINATE THE DOOR
 LANDING.**PLEASE NOTE THAT THE CIVILS
 WILL BE REQUIRED TO BE UPDATED AS WELL
 TO BE CONSISTENT WITH THE
 ARCHITECTURALS.
  
 14.)PROVIDE A DETAIL FOR THE SALES
 COUNTER, FBC11-7.2.
  
 THE RESPONSE LETTER INDICATES THAT SHOP
 DRAWINGS WILL BE SUBMITTED.THE PERMIT
 WILL BE ISSUED WITH THIS AS A PROVISO.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72 IN ADDITION
 TO EVALUATION OR TEST REPORT.SUBMIT
 FOR THE FOLLOWING:
  
 ROOF, FLAT - OK
 ROOF, TILE - OK
 EIFS SYSTEM -
 OVERHEAD DOOR - DOES NOT MEET DP
 METAL DOORS - DOES NOT MEET DP
 STOREFRONT - CANNOT BE APPROVED UNTIL
 AFTER BUILDING OFFICIAL APPROVES USE OF
 REMOVABLE SHUTTERS AND ENGINEER
 SPECIFIES DP.INDICATE DP LIMITATION OF
 YOUR APPLICATION ON SHEETS 4 AND 5 OF
 THE NOA.
  
 WWW.FLORIDABUILDING.ORG
  
 THE HURRICANE SHUTTER PRODUCT APPROVALS
 SUBMITTED MUST INCLUDE THE SCHEDULE FOR
 INSTALLATION, SEE ITEM 12.
  
 THE INSTALLATION SPECIFIES THE SAME SIZE
 SHUTTER AS THE OPENING SIZE FOR ALL
 OPENINGS, DOES NOT STATE IF THEY ARE TO
 BE INSTALLED VERTICALLY OR HORIZONTALLY.
  
 THE SWINGING DOOR DOES NOT MEET THE DP
 SPECIFIED ON S-0.
  
 (SECOND REVIEW)THE PRODUCT APPROVALS
 FOR THE CLOPAY
 OVERHEAD DOORS HAS A DESIGN PRESSURE
 LIMITATION OF +37/-42.ALSO STATES ON
 THE SPEC SHEET THAT IT IS COMPLIANT FOR
 150MPH EXPOSURE B, YOUR BUILDING HAS
 BEEN DECLARED AS EXPOSURE D.
  
 (THIRD REVIEW)THE NEW PRODUCT APPROVAL
 SUBMITTED HAS A DP LIMITATION OF
 +52/-58, SEE S-0.
  
 19.)PROVIDE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING, ROOF.
  
 (SECOND REVIEW) THIS BUILDING HAS
 BEEN DECLARED AS
 150MPH EXPOSURE D DESIGN.THE DESIGN
 PRESSURE FOR A FLAT ROOF, ZONE 3, 150,
 EXPOSURE B IS -102.2.SEE FBC TABLE
 1606.2B, FBC1606.2D.THE DESIGN
 PRESSURES YOU HAVE PROVIDED ON S0, 59
 FOR END ZONES FOR OPENINGS, 68 FOR END
 ZONES FOR ROOF, ARE NOT COMPLIANT FOR
 150MPH EXPOSURE D.PLEASE REVISE OR
 CLARIFY AS TO HOW YOU HAVE ARRIVED AT
 THESE DESIGN PRESSURES.
  
 (THIRD REVIEW)IT IS STILL NOT CLEAR AS
 TO HOW YOU HAVE DETERMINED THE ROOF
 CLADDING DESIGN WIND PRESSURES, S0.YOU
 HAVE THIS BROKEN DOWN IN SQUARE FOOT
 AREAS, LEEWARD AND WINDWARD ZONES.I
 BELIEVE THIS MAY APPLY TO THE MWFRS BUT
 NOT TO THE ROOF, SEE FBC TABLE 1606.2B,
 TABLE 1606.2D, FIGURE 1606.2(C).
 REGARDLESS OF HOW YOU DERIVED THE
 NUMBERS ON SHEET S0, 105.2 PSF FOR 10SF
 OF AREA ROOF ZONE 3 IS NON COMPLIANT FOR
 150MPH EXPOSURE D (-102.2*155=158.41).
  
 20.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 (SECOND REVIEW) I WAS UNABLE TO LOCATE
 THE INFORMATION.
 SOME OF THE INFORMATION IS ON THE PLAN
 IN VARIOUS PLACES BUT OTHER ITEMS ARE
 MISSING.
  
 (THIRD REVIEW)PLEASE ADD THE
 INFORMATION REQUIRED BY FBC1606.1.7(4).
 REVISE ROOF DESIGN PRESSURES AS NOTED IN
 19 ABOVE.
  
 NEW COMMENTS:
  
 21.)ADDRESSED.
  
 22.)WALL SECTIONS ON A5 SHOW A 21?
 TALL MASONRY WALL WITH NO INTERMEDIATE
 BEAM.3-A5 REFERS TO A BOND BEAM AT
 APPROXIMATELY 13?, AND STATES TO SEE
 STRUCTURALS.I AM UNABLE TO FIND THIS
 INTERMEDIATE BEAM AND IT IS NOT SHOWN
 GRAPHICALLY ON THE ARCHITECTURAL OR
 STRUCTURAL DETAILS.
  
 23.)A TABLE WAS PROVIDED WITH DESIGN
 PRESSURES BASED ON SIZE AND ZONE, S0.
 PROVIDE A SCHEDULE OF OPENINGS
 SPECIFYING DESIGN PRESSURES (OPENING;
 COMPONENT TYPE I.E. ROLLUP DOOR,
 STOREFRONT, ETC.; AND DESIGN PRESSURE
 FOR THAT OPENING).ALSO SPECIFY DP FOR
 EIFS.
  
 (SECOND REVIEW)SEE ATTACHED
 FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED AS REQUIRED
 BY FLORIDA STATE STATUTE IF ITEMS ARE
 NOT CORRECTLY ADDRESSED ON THE NEXT
 REVIEW.
  
 (THIRD REVIEW)A 4X FEE HAS BEEN
 CHARGED AS REQUIRED BY FLORIDA STATUTE.
 NO RESUB FEE WILL BE CHARGED.THE 4X
 FEE IS TO BE PAID PRIOR TO RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-14 Cont ID  
Sent By shill Date 2005-09-14 Time 16:11 Rev Time 4.00
Received By shill Date 2005-09-14 Time 11:27 Sent To  
Notes
2005-09-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW; NUMBERING
 REMAINING THE SAME TO MAINTAIN
 CONSISTENCY.
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025 FOR MORE
 INFORMATION.
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
 PHOTOCOPIES WERE SUBMITTED.
  
 4.)THE SQUARE FOOTAGE ON THE PLAN AND
 ENERGY CALCS ARE NOT CONSISTENT (6569
 ON AS1, 6560 LS1, 6885 ENERGY CALC).
  
 AS1 AND LS1 WERE REVISED TO SHOW 6626,
 BUT THE ENERGY CALCS STILL STATE 6885
 AND 1-AS1 SHOWS 6569.
  
 5.)ADDRESSED; OWNER/AGENT LINE OF
 ENERGY CALC SIGNED.HOWEVER, IF THE
 CALCS ARE REVISED PLEASE PROVIDE
 REQUIRED SIGNATURES ON THE NEW ENERGY
 CALCS.
  
 6.)THE SPEC BOOK IS NOT SIGNED AND
 SEALED AND DOES NOT HAVE A TITLE BLOCK
 IN COMPLIANCE WITH FAC61G1-16.003, 004.
 ALSO HALF OF THE PAGES ARE UPSIDE DOWN.
 IF YOU WANT FOR THIS TO BE INCORPORATED
 INTO THE PERMIT PACKAGE, SUBMIT IN
 COMPLIANCE AND IN A READABLE FORMAT.
  
 THE TITLE BLOCKS ARE NOT COMPLIANT WITH
 FAC RULES FOR ARCHITECTS AND ENGINEERS.
 NOTE THAT THIS PACKAGE IS NOT REQUIRED
 FOR PERMITTING.
  
 7.)ADDRESSED.
  
 8.)PLANS PREPARED BY AN ENGINEER ARE
 TO HAVE A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G15-23.002.A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED FOR BUSINESSES
 PRACTICING ENGINEERING IN FLORIDA,
 FAC61G15-19.001(3).
  
 THE CA HAS BEEN APPLIED FOR STRUCTURAL
 INTEGRITY, INC.THE CA NUMBER IS
 REQUIRED TO PRACTICE ENGINEERING AS A
 BUSINESS ORGANIZATION, FS471.023.
  
 9.)THE MASONRY WALL CALCS PREPARED BY
 MR. MITCHELL PE IS:
  
 A. REQUIRED TO HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FAC61G15-23.002.
  
 B.ILLEGIBLE, APPEARS TO HAVE GREY
 LINES (DRAWINGS) WHICH ARE UNREADABLE.
  
 THE REVISED MASONRY CALCS ARE NOT
 SEALED.IT HAS A TITLE BLOCK FOR
 STRUCTURAL INTEGRITY INC. WHICH DOES NOT
 HAVE A VALID CA NUMBER.WHEN SEALED,
 THE TITLE BLOCK IS TO INCLUDE THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 INDIVIDUAL SEALING THE DOCUMENT.
 FAC61G15-23.002.THE CALCS REFER TO THE
 2003 FBC, GOVERNING CODE IS FBC2001.
  
 10.)LS1 CODE INFORMATION, IV INDICATES
 THAT THIS BUILDING WILL BE FULLY
 SPRINKLED.SUBMIT SPRINKLER PLANS
 FBC104.3.1.1(5).
  
 SPRINKLER PLANS NOT PROVIDED.SEE
 FBC104.3.1.1(5) AND ATTACHED LETTER FROM
 DCA IN REGARDS TO SPRINKLER PLANS
 REQUIRED AT TIME OF PERMITTING.
  
 11.)HURRICANE SHUTTER STORAGE IS SHOWN
 ON THE PLAN (TIRE STORAGE AREA).SEE
 ATTACHED IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.SUBMIT A PLAN FOR
 INSTALLATION FOR REVIEW.
  
 NOT ADDRESSED.USE OF REMOVABLE
 SHUTTERS AND THE INSTALLATION PLAN IS TO
 BE APPROVED BY THE BUILDING OFFICIAL.
  
  
 12.)SEE PROCEDURES, ITEM I, ON THE
 ATTACHED STANDARD IN REGARDS TO REQUIRED
 INFORMATION.A FORM IS ATTACHED FOR
 YOUR CONVENIENCE.
  
 NOT ADDRESSED.FORM WAS RETURNED BLANK.
  
 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN
 FROM THE SERVICE AREA AND THE TIRE
 STORAGE FBC11-4.11(3), FBC1004.2.2.
  
 SAME PLANS PROVIDED.NOTE THAT EXIT 2
 HAS A RAMP, EXITS 3 AND 4 HAVE STEPS.
 THE TRANSMITTAL LETTER STATES THAT DOORS
 107 AND 108 ARE ACCESSIBLE EGRESS DOORS.
 DOOR 107 IS AN INTERIOR DOOR, IS NOT AN
 EXIT.DOOR 108 HAS A STEP DOWN, NOT AN
 ACCESSIBLE EXIT.
  
 14.)PROVIDE A DETAIL FOR THE SALES
 COUNTER, FBC11-7.2.
  
 NOT ADDRESSED.THE TRANSMITTAL LETTER
 STATES THAT THE DETAIL WILL BE PROVIDED
 BY THE FIRE PROTECTION CONSULTANT.THIS
 IS BEING REQUESTED TO DETERMINE CODE
 COMPLIANCE AND IS REQUIRED AS A PART OF
 THE PERMITTED SET OF PLANS.ALSO IT IS
 UNCLEAR TO ME AS TO WHY A FIRE SPRINKLER
 ENGINEER WOULD BE DESIGNING CABINETRY.
  
 15.)ADDRESSED.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72 IN ADDITION
 TO EVALUATION OR TEST REPORT.SUBMIT
 FOR THE FOLLOWING:
  
 ROOF, FLAT
 ROOF, TILE
 EIFS SYSTEM
 OVERHEAD DOOR
 METAL DOORS
 FIXED GLASS
 STOREFRONT
  
 WWW.FLORIDABUILDING.ORG
  
 THE TRANSMITTAL LETTER STATES THAT FIXED
 GLASS AND STOREFRONT WERE NOT ATTACHED
 DUE TO THE USE OF HURRICANE SHUTTERS.
 ALL COMPONENTS AND CLADDING STILL
 REQUIRE PRODUCT APPROVALS AS THEY STILL
 MUST MEET DESIGN PRESSURE REQUIREMENTS
 REGARDLESS OF WHETHER GLAZED COMPONENTS
 ARE IMPACT GLASS OR HAVE IMPACT
 PROTECTION.SEE FBC1606.2.2, 1606.2.5,
 1707.4.2.
  
 THE HURRICANE SHUTTER PRODUCT APPROVALS
 SUBMITTED MUST INCLUDE THE SCHEDULE FOR
 INSTALLATION, SEE ITEM 12.
  
 THE ROOF TILE NOA IS MISSING STATE
 PRODUCT APPROVAL.INCLUDE DOCUMENTS
 FROM STATE WEBSITE.
  
 THE BENCHMARK DOORS STATE PRODUCT
 APPROVAL HAS SEVERAL PRODUCTS INCLUDED.
 CIRCLE WHICH PRODUCT YOU ARE USING AND
 SUBMIT MANUFACTURER SPECS/INSTALLATION
 INSTRUCTIONS SO THAT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 THE PRODUCT APPROVALS FOR THE CLOPAY
 OVERHEAD DOORS HAS A DESIGN PRESSURE
 LIMITATION OF +37/-42.ALSO STATES ON
 THE SPEC SHEET THAT IT IS COMPLIANT FOR
 150MPH EXPOSURE B, YOUR BUILDING HAS
 BEEN DECLARED AS EXPOSURE D.
  
 17.)THE ROOF PRODUCT APPROVAL
 SUBMITTED HAS A DESIGN PRESSURE OF -45
 WITH LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING FOR THE PERIMETER AND
 CORNER ZONES.
  
 ON THE NEW ROOF PRODUCT APPROVAL
 SUBMITTED, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE INSTALLING.
  
 18.)ADDRESSED.
  
 19.)PROVIDE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING, ROOF.
  
 THIS BUILDING HAS BEEN DECLARED AS
 150MPH EXPOSURE D DESIGN.THE DESIGN
 PRESSURE FOR A FLAT ROOF, ZONE 3, 150,
 EXPOSURE B IS -102.2.SEE FBC TABLE
 1606.2B, FBC1606.2D.THE DESIGN
 PRESSURES YOU HAVE PROVIDED ON S0, 59
 FOR END ZONES FOR OPENINGS, 68 FOR END
 ZONES FOR ROOF, ARE NOT COMPLIANT FOR
 150MPH EXPOSURE D.PLEASE REVISE OR
 CLARIFY AS TO HOW YOU HAVE ARRIVED AT
 THESE DESIGN PRESSURES.
  
 20.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 I WAS UNABLE TO LOCATE THE INFORMATION.
 SOME OF THE INFORMATION IS ON THE PLAN
 IN VARIOUS PLACES BUT OTHER ITEMS ARE
 MISSING.
  
 NEW COMMENTS:
  
 21.)LS1 STATES THAT THIS IS S1 AND M
 OCCUPANCY.PLEASE READ FBC305.1.2,
 FBC404.3.PLEASE REVISE AFFECTED LIFE
 SAFETY REQUIREMENTS.
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED AS REQUIRED
 BY FLORIDA STATE STATUTE IF ITEMS ARE
 NOT CORRECTLY ADDRESSED ON THE NEXT
 REVIEW.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By shill Date 2005-08-16 Time 09:20 Rev Time 4.00
Received By shill Date 2005-08-14 Time 16:06 Sent To  
Notes
2005-08-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025 FOR MORE
 INFORMATION.
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 4.)THE SQUARE FOOTAGE ON THE PLAN AND
 ENERGY CALCS ARE NOT CONSISTENT (6569
 ON AS1, 6560 LS1, 6885 ENERGY CALC).
  
 5.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 6.)THE SPEC BOOK IS NOT SIGNED AND
 SEALED AND DOES NOT HAVE A TITLE BLOCK
 IN COMPLIANCE WITH FAC61G1-16.003, 004.
 ALSO HALF OF THE PAGES ARE UPSIDE DOWN.
 IF YOU WANT FOR THIS TO BE INCORPORATED
 INTO THE PERMIT PACKAGE, SUBMIT IN
 COMPLIANCE AND IN A READABLE FORMAT.
  
 7.)THE ARCHITECTURAL PLANS ARE TO HAVE
 A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G1-16.003, 004.
  
 8.)PLANS PREPARED BY AN ENGINEER ARE
 TO HAVE A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G15-23.002.A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED FOR BUSINESSES
 PRACTICING ENGINEERING IN FLORIDA,
 FAC61G15-19.001(3).
  
 9.)THE MASONRY WALL CALCS PREPARED BY
 MR. MITCHELL PE IS:
  
 A. REQUIRED TO HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FAC61G15-23.002.
  
 B.ILLEGIBLE, APPEARS TO HAVE GREY
 LINES (DRAWINGS) WHICH ARE UNREADABLE.
  
 10.)LS1 CODE INFORMATION, IV INDICATES
 THAT THIS BUILDING WILL BE FULLY
 SPRINKLED.SUBMIT SPRINKLER PLANS
 FBC104.3.1.1(5).
  
 11.)HURRICANE SHUTTER STORAGE IS SHOWN
 ON THE PLAN (TIRE STORAGE AREA).SEE
 ATTACHED IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.SUBMIT A PLAN FOR
 INSTALLATION FOR REVIEW.
  
 12.)SEE PROCEDURES, ITEM I, ON THE
 ATTACHED STANDARD IN REGARDS TO REQUIRED
 INFORMATION.A FORM IS ATTACHED FOR
 YOUR CONVENIENCE.
  
 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN
 FROM THE SERVICE AREA AND THE TIRE
 STORAGE FBC11-4.11(3), FBC1004.2.2.
  
 14.)PROVIDE A DETAIL FOR THE SALES
 COUNTER, FBC11-7.2.
  
 15.)SEE ZONING?S COMMENTS IN REGARDS
 TO THE STRIPING REQUIREMENTS AND THE
 INCONSISTENCY IN THE NUMBER OF PARKING
 SPACES FOR THE ACCESSIBLE PARKING.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72 IN ADDITION
 TO EVALUATION OR TEST REPORT.SUBMIT
 FOR THE FOLLOWING:
  
 ROOF, FLAT
 ROOF, TILE
 EIFS SYSTEM
 OVERHEAD DOOR
 METAL DOORS
 FIXED GLASS
 STOREFRONT
  
 17.)THE ROOF PRODUCT APPROVAL
 SUBMITTED HAS A DESIGN PRESSURE OF -45
 WITH LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING FOR THE PERIMETER AND
 CORNER ZONES.
  
 18.)THE TOWER DETAILS SHOW PLYWOOD ON
 THE WALLS, S2.WALLS ARE TO BE NON
 COMBUSTIBLE FOR TYPE V CONSTRUCTION.
  
 19.)PROVIDE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING, ROOF.
  
 20.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2007-03-05 Cont ID  
Sent By dpalmer Date 2007-03-05 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2007-03-05 Time 07:36 Sent To ENG
Notes
2007-03-05 07:37:28REVISED SITE/CIVIL/SURVEY SHEET SHOWING SITE ELECTRICAL
 CONDUITS IS NOT NEEDED FOR ELECTRICAL REVIEW. SHEETS
 ROUTED TO ENGINEERING AS THIS MAYBE NEEDED FOR AS-BUILT
 FOR CIVIL/SITE CONDUITS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 08:27 Sent To  
Notes
2007-02-25 08:32:29NEW ELECTRICAL SHEETS BROUGHT IN ON FIRDAY 2/23 AND
 INSERTED TO MAKE TO COMPLETE SETS OF NEW REVISED
 SHEETS.
 STAMPED, OK.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-02-19 Cont ID  
Sent By dpalmer Date 2007-02-19 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2007-02-19 Time 07:41 Sent To  
Notes
2007-02-19 08:32:11*** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT THE TWO SETS OF PLANS
 SUBMITTED ONLY CONTAINED ONE SET OF NEW ELECTRICAL
 SHEETS WHICH ADDRESSED THE PREVIOUS REVIEW COMMENTS.
 PLEASE SEE THE OTHER SET CONTAIN THE PREVIOUS PLANS.
 PLEASE ALSO SEE ONE OTHER COPY OF OLD/VOIDED SHEETS
 WHICH WERE REMOVED FROM ONE SET WAS SUBMITTED.
 PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ** PLEASE BE SURE TO REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS COMPLETELY AND ONLY INSERT THE NEW REVISED SHEETS
 INTO THE TWO COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-12-24 Cont ID  
Sent By dpalmer Date 2006-12-24 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 18:44 Sent To  
Notes
2006-12-24 19:00:22** UNSAT REVISION DATED 8/17/06 **
  
 ** PLEASE SEE NOTE REDLINED ON ORIGINAL ISSUED PLANS
 NOT ADDRESSED ALONG WITH NEW COMMENT BELOW.
  
 1) NOTE: PLEASE SEE AS REDLINED AND NOTED ON PREVIOUS
 REVIEWS, SHOW WINDOW RECEPTACLES WILL BE REQUIRED ABOVE
 WINDOW AREAS.
 PLEASE SEE 210.62, 220.12A FOR LOADS.
 THIS IS REQUIRED BY THIS AHJ TO DISCOURAGE FLOOR
 RECEPTACLES AND UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST BE INSTALLED
 DIRECTLY ABOVE A SHOW WINDOW, AND ONE RECEPTACLE IS
 REQUIRED FOR EVERY 12 LINEAR FT OR ?MAJOR FRACTION
 THEREOF? (6 FT OR MORE).
  
 2) NOTE: PLEASE INDICATE THE AUDIBLE AND VISUAL LEVELS
 FOR HORNS/ STROBES AND COMBO DEVICES PER FBC 11-4.28.1,
 .2 AND .3(4).
 THIS WAS NOT PREVIOUSLY PART OF THE ELECTRICAL PLAN
 REVIEW, HOWEVER IS NOW AND THIS REQUIREMENT WAS THE
 SAME UNDER THE 2001 FBC AND 2004 FBC.
 PLEASE INDICATE MINIMUM LEVELS.
  
 ** WHEN SUBMITTING PLANS PLEASE ATTACH ALL SHEETS
 TOGETHER INTO TWO SETS.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 18:56 Sent To  
Notes
2006-07-21 00:00:00REV'S SUBMITTED, NOT FOR ELEC.
 ONLY FOUND PLANS FOR P, ENG, B, Z

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 10:39 Sent To  
Notes
2005-12-24 00:00:00*** PLANS REDLINED ***
 RESPONSE NEEDED BY CONTRACTOR OR DESIGN
 TEAM BEFORE ISSUING OF PERMIT.
  
  
 PLEASE SEE MISSING RECEPTS REDLINED ONCE
 AGAIN PER 210.62
  
 ** PLEASE SEE THAT ONLY ONE SET OF THE
 ALL ORIGINAL PLANS WHICH WERE STAMPED BY
 REVIEWERS WERE SUBMITTED BACK.
 PLEASE KNOW, ALL PREVIOUS PLANS STAMPED
 BY REVIEWERS ON PREVIOUS REVIEWS NEED TO
 BE VOIDED AS THEY ARE SUPERSEDED BY
 THESE NEW REVISED SETS.
  
 PLEASE BRING IN OTHER ORIGINALLY STAMPED
 PLANS TO BE VOIDED BY THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-11 Cont ID  
Sent By dpalmer Date 2005-09-11 Time 11:13 Rev Time 0.33
Received By dpalmer Date 2005-09-11 Time 11:02 Sent To  
Notes
2005-09-11 00:00:00REDLINED TWO ADDITIONAL RECEPTS REQUIRED
 ABOVE WINDOWS AT FRONT.
  
 STAMPED ELECTRICAL PLANS.
 PENDING ANY COMMENTS FROM OTHER TRADES
 WHIHC MAY AFFECT ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 07:11 Rev Time 1.00
Received By dpalmer Date 2005-08-04 Time 06:50 Sent To  
Notes
2005-08-04 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT **********
  
 TIRE KINGDOM
 1544 PALM BEACH LAKES BLVD.
  
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECTURAL FIRM
 AND ENGINEERING FRIM, AS REQUIRED UNDER
 FAC 61G1-16.004 AND 61G15-23.002
 FS 481.219, 471.023
 PLEASE SEE ARCH'S TITLE BLOCK IS MISSING
 THE PRINTED NAME NAME AND LICENS NUMBER
 FOR ARCHIECT.
 PLEASE SEE ENG'S TITLE BLOCK IS MISSING
 THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER, THE PRINTED NAME
 AND THE PRINTED LICENSE NUMBER FOR
 ENGINEER OF RECORD.
 PLEASE SEE ALL SHEETS ARE ALSO REQUIRED
 TO HAVE THE LOCATION ADDRESS OF JOB ON
 TITLE BLOCK. PLEASE SEE ADDRESS IS NOTED
 ABOVE.
  
 PLEASE SEE THESE COMMENTS ARE REQUIRED
 OF ALL TRADES AND FOR ALL SHEETS
 WHEATHER OR NOT COMMENTS ARE MADE BY
 OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE NOTE ON "LIGHTING
 NOTES"MENTIONS TO SEE SITE LIGHTING ON
 CIVIL SHEETS. PLEASE KNOW, A SITE
 ELECTRICAL LAYOUT WITH ELECTRICAL PLANS
 WILL BE REQUIRED. PLEASE SHOW LOCATIONS
 OF POLE, TYPE, CIRCUITING ETC.
 PLEASE ALSO PROVIDE ALL WIND LOADING
 CALCULATIONS FOR POLES AND FIXTURES FOR
 BLDG REVIEW. MUST MEET FBC 140 MPH.
  
 3)NOTE: PLEASE SEE A RECEPT ABOVE EACH
 WINDOW AT FRONT OF STORE WILL BE
 REQUIRED BASED ON THEMERCHANTILE
 OCCUPANCY AND THE POSSIBLE USE OF
 SHOW/DISPLAY USE.210.62, 220.12
 THE PURPOSE OF THIS TO HELP ALLEVIATE
 THE USE OF ANY EXTENSION CORDS FOR ANY
 POSSIBLE ELCTRICAL WINDOW SIGNAGE WHICH
 MAY OR MAY BE USED.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED FOR PANELS,
 HOWEVER PLEASE INDICATE AIC RATING FOR
 MAIN DISCONNECT.
  
 PLEASE BE SURE ANY OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS ARE INSERTED INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICLA PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2007-03-08 Cont ID  
Sent By rchokshi Date 2007-03-08 Time 10:56 Rev Time 0.00
Received By rchokshi Date 2007-03-08 Time 10:56 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2006-07-31 Cont ID  
Sent By lmartine Date 2006-07-31 Time 13:22 Rev Time 0.00
Received By lmartine Date 2006-07-31 Time 13:22 Sent To  
Notes
2006-07-31 00:00:00REVISIONS SUBMITTED DO NOT REFLECT
 ENGINEERING CHANGES
  
  
  
  
 RASIK CHOKSHI
 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-03-17 Cont ID  
Sent By mamini Date 2006-03-17 Time 11:18 Rev Time 0.50
Received By mamini Date 2006-03-17 Time 11:18 Sent To  
Notes
2006-03-17 00:00:00PASSED:
  
 1. REVIEWED FOR REVISIONS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By mamini Date 2005-09-13 Time 13:45 Rev Time 1.00
Received By mamini Date 2005-09-13 Time 13:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By mamini Date 2005-07-25 Time 14:17 Rev Time 1.00
Received By mamini Date 2005-07-25 Time 14:17 Sent To  
Notes
2005-07-25 00:00:00FAILED:
  
 1. PLEASE NOTE THAT AN OIL/WATER
 SEPARATOR FOR THIS FACILITIES IS
 REQUIRED, TO COMPLY WITH CITY WASTEWATER
 DISCHARGE ORDINANCE.
 2. CIVIL PLANS DO NOT SHOW DEMOLITION
 OR RESTORATION FOR INSTALLATION OF THE
 PROPOSED DOMESTIC AND 6" FIRE LINES,
 SHEET C8.
 3. PLEASE STATE IF, THE PROPOSED FIRE
 HYD. IS PRIVATE OR WILL BE DEDICATED.
 4. PLEASE NOTE THAT CIVIL PLANS MUST BE
 APPROVED BY THE PUBLIC UTILITIES & ENG.
 FOR THE CONNECTIONS PRIOR TO GETTING
 APPROVAL FROM BUILDING DEPT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-02-28 Cont ID  
Sent By mawillia Date 2007-02-28 Time 14:58 Rev Time 0.00
Received By mawillia Date 2007-02-28 Time 14:58 Sent To  
Notes
2007-02-28 15:00:32*****APPROVED*****
  
 REVISED PLAN SHEETS LS-1, A-4, AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-01-11 Cont ID  
Sent By mwennerg Date 2007-01-11 Time 11:50 Rev Time 0.00
Received By mwennerg Date 2007-01-11 Time 11:49 Sent To  
Notes
2007-01-11 11:52:11***PROVISO***
  
 1) NO REVISIONS NOTED TO LIFE SAFETY SHEET OR FIRE
 PROTECTION.
  
 2) PLEASE SEE ELECTRICAL NOTE #2 REGARDING FIRE ALARM
 DEVICE REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-08-18 Cont ID  
Sent By mwennerg Date 2006-08-18 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2006-08-18 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-07 Cont ID  
Sent By mcarsill Date 2005-12-07 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2005-12-07 Time 14:45 Sent To  
Notes
2005-12-07 00:00:001. WHEN PAINTING AREAS BE SURE THAT
 PAINT IS NOT APPLIED TO ANY FIRE
 SPRINKLER HEADS. PAINTED FIRE SPRINKLER
 HEADS WILL NEED TO BE REPLACED AND NOT
 CLEANED.
  
 2. A KNOX-BOX WILL BE REQUIRED.
  
 3. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 SPRINKLER CONNECTION.
  
 4. AREAS WHERE TIRES ARE TO BE STORED
 MUST PROVIDE PROPER CLEARANCES TO FIRE
 SPRINKLER HEADS AND LIGHT FIXTURES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By mwennerg Date 2005-09-22 Time 13:50 Rev Time 0.00
Received By mwennerg Date 2005-09-22 Time 13:50 Sent To  
Notes
2005-09-22 00:00:00******OK******
  
 2 SETS OF PLANS STAMPED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 10:02 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 10:02 Sent To  
Notes
2005-08-18 00:00:00******DENIED******
  
 1) PLEASE NOTE FOR REF:, LIFE SAFETY TO
 COMPLY WITH NFPA 101, AND NFPA 1, 2003
 EDITION IN ADDITION TO OTHER APPLICABLE
 CODES.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 4) AN ADDRESS IS REQUIRED ON THE
 BUILDING TO BE AT LEAST 6" IN HEIGHT AND
 CONRASTING TO THE BACKGROUND.
  
 5) WHEN A FIRE ALARM SYSTEM IS PROVIDED,
 IN ACCORDANCE WITH LOCAL REQUIREMENTS,
 DUCT SMOKE DETECTORS SHALL BE WIRED INTO
 SYSTEM TO CAUSE A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 6) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 7) PLANS SHOW 1 HOUR RATED WALLS,
 HOWEVER NO MENTION REGARDING DOORS OR
 CLOSERS ON DOOR SHEDULE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 09:19 Sent To B
Notes
2007-03-12 09:19:59TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 13:42 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 13:42 Sent To M
Notes
2007-03-09 13:42:50TO "M"BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-02-28 Cont ID  
Sent By adarroug Date 2007-02-28 Time 14:17 Rev Time 0.00
Received By adarroug Date 2007-02-28 Time 14:17 Sent To E
Notes
2007-02-28 14:17:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-02-21 Cont ID  
Sent By adarroug Date 2007-02-21 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 11:11 Sent To M
Notes
2007-02-21 11:11:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 10:27 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 10:27 Sent To  
Notes
2007-02-19 07:41:51TO COMM BOARD #14
2007-02-08 10:28:06WAITING FOR "COMM" BD--CUSTOMER TO BRING IN SHEETS FOR
 "BLDG" REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 09:16 Sent To B
Notes
2007-01-18 09:17:07TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 12:03 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 12:03 Sent To B
Notes
2007-01-17 12:03:44TO "SHILL" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 16:31 Sent To B
Notes
2006-12-27 16:31:54TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 11:28 Sent To B
Notes
2006-12-14 11:28:32TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 09:06 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 09:06 Sent To  
Notes
2006-12-21 09:06:03TO "COMM" BD#19
2006-12-06 09:06:32WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 10:23 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 10:23 Sent To B
Notes
2006-10-25 10:23:38TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 10:51 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 10:51 Sent To  
Notes
2006-07-21 00:00:00TO "COMM" BD#45
2006-07-11 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 14:15 Sent To B
Notes
2006-02-28 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 11:43 Sent To  
Notes
2006-03-13 00:00:00TO "COMM" BD#59
2006-02-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 15:34 Sent To  
Notes
2005-11-30 00:00:00TO "COMM" BD#39
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 08:48 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 08:48 Sent To  
Notes
2005-09-08 00:00:00TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-22 Cont ID  
Sent By kstevens Date 2005-08-22 Time 18:27 Rev Time 0.00
Received By kstevens Date 2005-07-18 Time 15:23 Sent To  
Notes
2005-07-20 00:00:00TO "COMM" BD#39
2005-07-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-03-14 Cont ID  
Sent By rregueir Date 2007-03-14 Time 07:32 Rev Time 0.00
Received By rregueir Date 2007-03-13 Time 15:22 Sent To  
Notes
2007-03-14 07:35:31-----------------PROVISO-----------------
  
 ENGINEERING IS REQUIRED FOR ROOFTOP DUCTWORK. A
 DETAILED DRAWING SHOWING ROOF SUPPORTS MEETING 140MPH
 WIND LOADS WILL BE NEEDED ON SITE (TWO COPIES) FOR
 FINAL INSPECTION. BE SURE TO STATE THE SPECIFIC WIND
 LOADS TO WHICH THE SUPPORTS WERE DESIGNED.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-02-24 Cont ID  
Sent By hmoser Date 2007-02-24 Time 11:04 Rev Time 0.00
Received By hmoser Date 2007-02-24 Time 11:04 Sent To  
Notes
2007-02-24 11:07:38PLEASE HAVE THE ENGINEER WRIGHT IN THE MINIMUM
 PRESCRIBED R- VALUE REQUIRED IN HIS LETTER

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 14:40 Rev Time 0.25
Received By tgordon Date 2007-02-21 Time 14:40 Sent To  
Notes
2007-02-21 14:41:28REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-12 Cont ID  
Sent By hmoser Date 2007-02-12 Time 10:01 Rev Time 0.00
Received By hmoser Date 2007-02-12 Time 10:14 Sent To  
Notes
2007-02-12 10:15:43NO NOTESENERGY CALCULATIONS OK HM.
2007-02-12 10:07:13.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-23 Cont ID  
Sent By pkrauss Date 2006-01-23 Time 10:49 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By pkrauss Date 2005-10-12 Time 10:21 Rev Time 0.50
Received By pkrauss Date 2005-10-12 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By pkrauss Date 2005-08-11 Time 16:43 Rev Time 1.00
Received By pkrauss Date 2005-08-11 Time 15:58 Sent To  
Notes
2005-08-11 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) TABLE 403.3.
  
 2.PROVIDE AIR BALANCE SCHEDULE IN
 ACCORDANCE WITH 2001 FBC(M)501.4
  
 3.INDICATE VENTILATION REQUIREMENTS
 FOR THE GARAGE SERVICE AREA PER 2001 FBC
 411.5.4.
  
 4.PLEASE INDICATE AIR MAKE-UP (THROUGH
 ROLL UP DOORS, LOUVERS, ETC.)
  
 5.PLEASE INDICATE WHAT TYPE OF
 SERVICES WILL BE PROVIDED THAN TIRE
 REPAIR (I.E. OIL CHAGNES, TUNE UPS,
 ETC).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-08-09 Cont ID  
Sent By kstevens Date 2006-08-09 Time 18:52 Rev Time 0.00
Received By kstevens Date 2006-08-09 Time 18:52 Sent To  
Notes
2006-08-09 00:00:00DENIED
 REVISION FOR SHT P-3 OIL INTERCEPTOR.
 MUNICIPAL CODE 90-124(7)(F) EACH
 INTERCEPTOR SHALL BE CONSTRUCTED OF
 STEEL REINFORCED CONCRETE. NO FIBERGLASS
 INTERCEPTORS SHALL BE INSTALLED.
  
 IRRIGATION PLANS OK - SEPARATE
 IRRIGATION PERMIT REQUIRED. I-1 & I-2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-03-17 Cont ID  
Sent By kstevens Date 2006-03-16 Time 10:28 Rev Time 0.00
Received By kstevens Date 2006-03-13 Time 18:38 Sent To  
Notes
2006-03-17 00:00:00PASSED PROVISO - RPZV BACKFLOW TO BE
 LOCATED AS NEAR TO THE METER AS POSSIBLE
 ON PRIVATE PROPERTY. NOT IN THE BUILDING
 UNLESS APPROVED BY ORVILLE POLK

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 06:27 Rev Time 0.00
Received By kstevens Date 2006-01-30 Time 19:01 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEWS: COMMENT
 NUMBERS TO REMAIN THE SAME AS PRIOR
 REVIEWS.
  
 1. SHT A-1 FINISH SCHEDULE SHOWS GYP-BD
 PAINTED FOR THE WALLS OF THE TOILET
 ROOMS. PLEASE INDICATE HOW THIS WILL
 COMPLY WITH THE REQUIREMENT FOR THE
 WALLS TO BE NONABSORBENT UP TO 4' IN
 PUBLIC TOILET ROOMS. SECTION 1204.2
 FBC-2001 BUILDING. (NO RESPONSE, NOT
 ADDRESSED).
 3. SHT A-7 ALL TOILET ROOMS, (INCLUDING
 EMPLOYEES), SHALL BE ACCESSIBLE. SHOW
 THE FOLLOWING:
 FOR LAVS:
 C. 11-4.19.2 HEIGHT & CLEARANCES
 (CLEARANCES NOT SHOWN)
 F. 11-4.19.5 FAUCETS
 FOR TOILET ROOMS:
 11-4.22.3 UNOBSTRUCTED TURNING AREA -
 FOR EMPLOYEES TOILET ROOM.
 4. SHTS P-1 & P-3 THE OIL SEPARATOR
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. #3434. (NO RESPONSE, NOT
 ADDRESSED).
 6. P-3 INDICATE MATERIAL TYPE FOR
 COMPRESSED AIR SYSTEM PIPING. PVC NOT
 APPROVED FOR COMPRESSED AIR PER MANUF.
 INSTALLATION REQUIREMENTS. TYPICAL AIR
 LINE RISER SHOWS 2" PVC TO LIFT. THIS IS
 NOT APPROVED. (NO RESPONSE, NOT
 ADDRESSED). SEE DETAIL SHT P-2
 **NOTE FROM SECOND REVIEW**
 SECTION 310.4 WATER CLOSET COMPARTMENT.
 EXCEPTION: WATER CLOSET COMPARTMENTS
 SHALL NOT BE REQUIRED IN A SINGLE -
 OCCUPANT TOILET ROOM WITH A LOCKABLE
 DOOR. "INCLUDE ALL NOTES ON PLANS".
 ****NEW COMMENT****
 1C. SEE ATTACHED SHEET CONCERNING FS
 533.80(2)(B) AND THE DESIGN
 PROFESSIONAL. IF PLANS ARE RESUBMITTED
 AND HAVE NOT ADDRESSED THE COMMENTS FROM
 PREVIOUS REVIEWS, 4 TIMES THE PLAN
 REVIEW FEE WILL BE ATTACHED AND BE
 REQUIRED TO BE PAID BY THE DESIGN
 PROFESSIONAL. THIS WILL BE IN ADDITION
 TO THE 4 TIMES FEE REQUIRED BY THE
 BUILDING PLANS EXAMINER.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-15 Cont ID  
Sent By pschmitz Date 2005-10-15 Time 14:46 Rev Time 0.00
Received By pschmitz Date 2005-10-15 Time 14:45 Sent To  
Notes
2005-10-15 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1) NOTES 3 THRU 5 ON FROM PREVIOUS PLAN
 REVIEW, DATED 08-22-05 NEED TO BE PLACED
 ON THE PLANS, RE SUBMITTED.
 3)SHT A-7 ALL TOILET ROOMS,
 NEW NOTE:
 SEC 310.4 WATER CLOSET COMPARTMENT.
 EXCEPTION: WATER CLOSET COMPARTMENTS.
 SHALL NOT BE REQUIRED IN A SINGLE-
 OCCUPANT TOILET ROOM WITH A LOCKABLE
 DOOR.
 "INCLUDE ALL NOTES ON PLANS"
 4. SHTS P-1 & P-3 THE OIL SEPARATOR
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. #3434.INC WITH PLANS
 5. RPZ BACKFLOW SHALL BE INSTALLED ON
 THE WATER SERVICE AS CLOSE TO THE METER
 AS POSSIBLE. PER UTILITY DEPT.
 6. P-3 INDICATE MATERIAL TYPE FOR
 COMPRESSED AIR SYSTEM PIPING. PVC NOT
 APPROVED FOR COMPRESSED AIR PER MANUF.
 INSTALLATION REQUIREMENTS. TYPICAL AIR
 LINE RISER SHOWS 2" PVC TO LIFT. THIS IS
 NOT APPROVED.
 END OF COMMENTS QUESTIONS 561-805-6692
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-22 Cont ID  
Sent By kstevens Date 2005-08-22 Time 18:27 Rev Time 1.62
Received By kstevens Date 2005-08-22 Time 18:27 Sent To  
Notes
2005-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1 FINISH SCHEDULE SHOWS GYP-BD
 PAINTED FOR THE WALLS OF THE TOILET
 ROOMS. PLEASE INDICATE HOW THIS WILL
 COMPLY WITH THE REQUIREMENT FOR THE
 WALLS TO BE NONABSORBENT UP TO 4' IN
 PUBLIC TOILET ROOMS. SECTION 1204.2
 FBC-2001 BUILDING.
 2. SHT A-3 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE TOTAL SF OF THE ROOF AND SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS PLUS THE AREA OF ROOFS THAT
 DRAIN ONTO THE ROOF FROM ABOVE. INDICATE
 THE TOTAL AREA DRAINING INTO EACH DRAIN.
 SECTIONS 1106 & 1107. IF PRIMARY AND
 SECONDARY ROOF DRAINS ARE COMBINED INTO
 ONE OPENING, THE SIZE SHALL BE PER
 SECTION 1107.3, 3 TIMES THE CROSS
 SECTIONAL AREA OF THE PRIMARY DRAIN PLUS
 THE AREA OF THE PRIMARY DRAIN. SHOW THE
 SIZE OF ALL DOWNSPOUTS.
 3. SHT A-7 ALL TOILET ROOMS, (INCLUDING
 EMPLOYEES), SHALL BE ACCESSIBLE. SHOW
 THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS:
 C. 11-4.19.2 HEIGHT & CLEARANCES
 D. 11-4.19.3 CLEAR FLOOR SPACE
 E. 11-4.19.4 EXPOSED PIPES & SURFACES
 F. 11-4.19.5 FAUCETS
 G. 11-4.19.6 MIRRORS
 FOR TOILET ROOMS:
 11-4.22.3 UNOBSTRUCTED TURNING AREA -
 FOR EMPLOYEES TOILET ROOM.
 4. SHTS P-1 & P-3 THE OIL SEPARATOR
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. #3434.
 5. RPZ BACKFLOW SHALL BE INSTALLED ON
 THE WATER SERVICE AS CLOSE TO THE METER
 AS POSSIBLE. PER UTILITY DEPT.
 6. P-3 INDICATE MATERIAL TYPE FOR
 COMPRESSED AIR SYSTEM PIPING. PVC NOT
 APPROVED FOR COMPRESSED AIR PER MANUF.
 INSTALLATION REQUIREMENTS. TYPICAL AIR
 LINE RISER SHOWS 2" PVC TO LIFT. THIS IS
 NOT APPROVED.
 7. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER
 AS WELL AS THE CERTIFICATE OF
 AUTHORIZATION OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 6115-23.002(2) & FS 471.025
 8. THE PRINTED NAME OF THE PERSON
 SEALING ALL ARCHITECTURAL SHEET SHALL BE
 IN THE TITLE BLOCK OF EACH SHEET SIGNED,
 SEALED, AND DATED. FAC 61G1-16.004(6) &
 FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By shill Date 2006-03-23 Time 15:01 Rev Time 0.00
Received By shill Date 2006-03-23 Time 15:01 Sent To  
Notes
2006-03-23 00:00:00ROOF REVIEW
 NOA 03-0114.06, SANTAFE TILE CORPORATION
 MISSION BARREL ROOFING TILE
  
 FLAT DECK - FL735, TAMKO MODIFIED,
 NOA01-1011.03
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2007-01-24 Cont ID  
Sent By jroach Date 2007-01-24 Time 16:52 Rev Time 0.00
Received By jroach Date 2007-01-24 Time 16:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-30 Cont ID  
Sent By jroach Date 2006-07-30 Time 13:39 Rev Time 0.00
Received By jroach Date 2006-07-30 Time 13:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By jroach Date 2006-01-03 Time 16:09 Rev Time 0.00
Received By jroach Date 2006-01-03 Time 16:09 Sent To  
Notes
2006-01-03 00:00:001/3/06 ***PASSED***
  
 MONUMENT SIGN SHALL BE APPROVED UNDER
 SEPARATE PERMIT.IT IS NOT A PART OF
 THIS REVIEW.
  
 A TREE REMOVAL/RELOCATION LICENSE SHALL
 BE OBTAINED FROM THE PLANNING DEPARTMENT
 PRIOR TO THE REMOVAL OR RELOCATION OF
 ANY EXISTING TREES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-09-19 Cont ID  
Sent By jroach Date 2005-09-19 Time 15:53 Rev Time 0.00
Received By jroach Date 2005-09-19 Time 15:53 Sent To  
Notes
2005-09-19 00:00:009/19/05 ***FAILED***
  
 1) PARKING DIMENSIONS AND STRIPING SHALL
 MEET THE REQUIREMENTS OF SEC. 95-485 OF
 THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (REGULAR
 SPACES SHALL BE DOUBLE-STRIPED).
  
 2) A 2-WAY (24 FOOT) DRIVE ISLE SHALL BE
 PROVIDED AT THE NW CORNER OF THE
 BUILDING, AS PER THE SITE PLAN APPROVED
 WITH ORDINANCE NO. 3844-05...NOT THE 13
 FOOT PROPOSED 1-WAY ISLE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By jroach Date 2005-08-01 Time 09:45 Rev Time 0.00
Received By jroach Date 2005-08-01 Time 09:45 Sent To  
Notes
2005-08-01 00:00:008/1/05 ***FAILED***
  
 1)SHEET C-9...PARKING DIMENSIONS AND
 STRIPING SHALL MEET THE REQUIREMENTS OF
 SEC. 94-485 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 2) SITE PLAN (SHEET C-2) SHOWS 3 HC
 SPACES WHILE ARCH. SITE PLAN (SHEET
 AS-1) SHOWS 4.ADJUST PLANS FOR
 CONSISTENCY.
  
 3) 24' DRIVE ISLES SHALL BE PROVIDED.
 SITE PLAN (SHEET C-2) SHOWS 13' ISLE AT
 NW CORNER FO THE BUILDING; REQUIRES
 RELOCATION OF TERMINAL LANDSCAPE ISLAND.
 ARCH. SITE PLAN (SHEET AS-1) ALSO ONLY
 SHOWS 23' 9 1/8" AT NORTH DRIVE ISLE.
  
 4) SHEET AS-1...DUMPSTER DETAIL DOES NOT
 MEET MINIMUM DEMINSIONS.REFER TO SEC.
 94-444 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 5) DUMPSTER ON SITE PLAN (SHEET C-2) AND
 ARCH. SITE PLAN (SHEET AS-1) DOES NOT
 MEET THE MINIMUM DEMINSIONS.REFER TO
 COMMENT #4.
  
 6) ARCH. SITE PLAN (SHEET AS-1) DOES NOT
 SHOW THE REMOVAL OF THE PARKING AND THE
 ADDITION OF REQUIRED LANDSCAPING ALONG
 THE NORTH PROPERTY LINE.REFER TO THE
 SITE PLAN.
  
 7) ARCH. SITE PLAN (SHEET AS-1) DOES NOT
 SHOW THE LOADING ZONE.
  
 8) SHEET AS-1...DUMPSTER ENCLOSURE AND
 TIRE STORAGE DETAILS SHALL PROVIDE SOLID
 WALLS AND GATES, NOT CHAINLINK WITH
 SLATS.ADJUST DETAILS ACCORDINGLY.
 NOTICE: AT NO TIME SHALL MATERIALS
 EXCEED THE HEIGHT OF THE ENCLOSURE.
  
 9) MONUMENT SIGN SHALL BE REVIEWED AND
 PERMITTED UNDER A SEPARATE PERMIT.
  
 10) REMOVE DETAILS FROM ARCH. SITE PLAN
 (SHEET AS-1) THAT ARE NOT BEING USED
 AND/OR ARE COVERED BY OTHER SHEETS.
  
 11) ARCH. SITE PLAN (SHEET AS-1) DOES
 NOT SHOW LANDSCAPING ON EITHER SIDE OF
 THE HC RAMP (NEAR FRONT OF BUILDING).
 REFER TO SITE PLAN (SHEET C-2).
  
 12) ADJUST LANDSCAPE DETAIL VERBAGE AND
 DIAGRAMS TO REFLECT THE INFORMATION
 PROVIDED ON THAT ATTACHED INFORMATION
 PAGE (SEE PAGE TAPED TO FRONT OF PLANS.
  
 ENSURE ALL PLANS ADDRESS THE COMMENTS
 AND THAT ALL PLANS ARE CONSISTENT WITH
 EACH OTHER.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.