Plan Review Details - Permit 05070670
Plan Review Stops For Permit 05070670
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By rmcdouga Date 2005-08-15 Time 11:55 Rev Time 0.00
Received By rmcdouga Date 2005-08-15 Time 11:54 Sent To  
Notes
2005-08-15 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE TRUSS LAYOUT HAS THE SIGNATURE
 AND SEAL OF TWO DIFFERENT ENGINEERS.
 ONLY THE ENGINEER IN RESPONSIBLE CHARGE
 OF THE PREPARATION AND PRODUCTION OF THE
 DOCUMENT SHOULD SIGN AND SEAL IT. SEE
 FAC 61G-15-23.002.
  
 4) THE DESIGNER OF RECORD FOR THE
 STRUCTURE SHOULD PROVIDE A ROOF FRAMING
 PLAN. FBC 104.2
  
 5) SHEET A-1 SPECIFIES HEADER
 CONNECTIONS AS (2) HETA 20 CONNECTORS.
 PLEASE CLARIFY. DOES THIS REFER TO THE
 CONNECTORS FOR THE WOOD BEAMS AT THE
 FRONT PORCH? IF SO, THEY SHOULD BE WOOD
 TO WOOD CONECTORS. SPECIFY CONNECTORS
 FOR THIS LOCATION.
  
 6) THE TRUSS DRAWINGS AND LAYOUT ARE NOT
 REQUIRED TO BE SUBMITTED FOR PLAN
 REVIEW. SIGNED AND SEALED DRAWINGS AND
 LAYOUT ARE REQUIRED TO BE GIVEN TO THE
 FIELD INSPECTOR AT TIME OF INSPECTION.
  
 7) SPECIFY THE SIZE AND LOCATION OF THE
 ATTIC ACCESS AS REQUIRED BY FBC 2309.6.
  
  
 8) ON SHEET A-1 THE FOOTING SIZE IS
 SPECIFIED AS 18" X 14". THIS CONFLICTS
 WITH THE SIZE SPECIFIED ON SHEET A-2.
 THE FOOTING IS REQUIRED BY FBC 1804.1.3
 TO EXTEND A MINIMUM OF 12" BELOW GRADE
 AND CITY AMENDMENTS TO FBC 1804.1.7
 REQUIRE THE FLOOR ELEVATION TO BE A
 MINIMUM OF 4 INCHES ABOVE GRADE AT
 HABITABLE AREAS.
  
 9) THE DESIGN PRESSURE TABLE ON A-1 HAS
 NOTES THAT REFERENCE THE PBC. THE
 CORRECT REFERENCE IS 2001 FBC.
  
 10) PLEASE LABEL THE COMPONENT AND
 CLADDING TABLE ON A-1 FOR ZONES 4 AND 5.
 SEE FBC TABLE 1606.2B.
  
 11) THE WINDOW BUCK DETAIL ON A-2 DOES
 NOT COMPLY WITH FBC 1707.4.4.2 WHICH
 REQUIRES WINDOW AND DOOR FRAMES TO BE
 FASTENED THROUGH 1X BUCKS INTO THE
 STRUCTURAL SUBSTRATE. THIS DETAIL ALSO
 CONFLICTS WITH THE ONE ON SHEET A-1.
  
 12) SPECIFY ON SHEET A-1 THAT THE
 INTERNAL PRESSURE IS POSITIVE AND
 NEGATIVE 0.18. SEE ASCE 7-98.
  
 13) THE CORRECT COMPONENT AND CLADDING
 TABLE IS 1606.2B. PLEASE CORRECT THIS
 UNDER WIND INFORMATION ON A-1.
  
 14) PLEASE REMOVE THE COPIES OF THE BUCK
 DETAILS ATTACHED TO THE PRODUCT
 APPROVALS. BUCK DETAILS ARE REQUIRED ON
 THE PLANS.
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. THIS IS
 REQUIRED IN ADDITION TO THE NOA OR OTHER
 EVAUALATION DOCUMENTS.
  
 16) SUBMIT PRODUCT APPROVAL FOR STATE OR
 LOCAL WITH INSTALLATION INSTRUCTIONS FOR
 THE SLIDING GLASS DOORS.
  
 17) THE INSTALLATION DRAWINGS WITH THE
 KD WINDOWS NOA DO NOT HAVE THE MIAMI
 DADE NOA STAMP AND SIGNATURE ON THEM.
 THEY ARE NOT VALID WITHOUT THE STAMP AND
 SIGNATURE.
  
 18) SUBMIT TWO COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANLES. LIST THE ANCHOR TYPE AND
 SPACING. SPECIFY THE MOUNT TYPE THAT
 WILL BE INSTALLED. A SEPARATE PERMIT
 WILL BE REQUIRED IF THIS INFORMATION IS
 NOT PROVIDED AT TIME OF PERMIT.
  
 19) THE INFORMATION ON THE ENERGY
 CALULATION FORMS DOES NOT MATCH THE
 PLANS. SEVERAL OTHER ITEMS ARE INCORRECT
 ON THE FORM.
  
 20) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN INCREASE BASED ON ICC
 CONSTRUCTION VALUE TABLES.
  
 PLEASE SUBMIT ONE COPY OF OLD PLAN
 SHEETS IF NEW SHEETS ARE SUBMITTED AS
 THIS WILL HELP TO FACILITATE THE PLAN
 REVIEW PROCESS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By dpalmer Date 2005-08-02 Time 11:46 Rev Time 1.00
Received By dpalmer Date 2005-08-02 Time 11:46 Sent To M
Notes
2005-08-02 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 IT IS NOTED ON RISER, HOWEVER PLEASE
 INDICATE ON PLANS.
 215.5
  
 3)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12 AWG.
  
 4 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E, MISSING REAR.
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE. PLEASE SEE
 POSSIBLE MISSING PER 2' OF WALL.
  
 6)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12, 2002 NEC.
  
 7)NOTE: PLEASE SHOWS REQ'D DISC'S FOR
 A/C EQUIPMENT. PER 440.11
 PLEASE SEE A "RECEPT" FOR 220V IS SHOWN
 FOR DISCONNECT.
  
 8)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 KITCHEN COUNTERSPACE RECEPTS REQUIRED.
  
 9)NOTE: PLEASE SEE RISER AND PLANS
 INDICATE PANEL AS BEING FED THROUGH
 WALL? PLEASE SEE 230.70, NO MORE THAN 8'
 OF UNPROTECTED CONDUCTORS MAY BE
 INSTALLED INSIDE A BLDG W/OUT AMEANS
 OF DISCONNECT OUTSIDE WITH OVER CURRENT
 PROTECTION.230.6,215.5
  
 10)NOTE: PLEASE SEE MISSING FOOTER STEEL
 AAS REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 11)NOTE: PLEASE VERIFY A/C HEAT ONLY
 SHOWN AS 5KW? THIS SEEMS SMALL FOR A
 HOUSE THIS SIZE?
 PLEASE SEE 424.3B FOR THE MIN OCP, AMIN
 125%.
  
 12)NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT IS SHOWN, WHERE NEC
 210.52B, 210.11C1, 220.16 REQUIRES A MIN
 OF TWO. PLEASE ALSO SEE MIN LOAD (KVA)
 FOR EACH. PLEASE ADJUST LOAD
 CALCULATIONS A NESS.
  
 13)NOTE: PLEASE SEE BY PANEL SCHEDULE
 SUBMITTED, PANEL INDICATE "ONE CIRCUIT"
 FOR "ALL" RECEPTS IN THIS HOUSE???
 215.5
  
 14)NOTE: PLEASE SEE "IF" ANY LV
 ELECTRICAL SYSTEMS ARE TO BE INSTALLED
 UNDER THIS PLAN REVIEW,IE: CATV< PHONE
 ETC, PLEASE SHOW AT THIS TIME. IF ALL OF
 THESE ITEMS ARE NOT SHOWN ON PLANS, THIS
 MAY NOT BE REVISED AT A LATER DATE AND
 WILL REQUIRE SEPARATE PLANS AND PERMITS
 FOR ALL OTHER LV SYSTEMS.
 PLEASE NOTE: ALL LV ALARM FOR A SFR
 SHALL BE UNDER A SEPARATE PERMIT.
  
 15)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 BEDRM? SHOWS A SWITH TO A FAN, HOWEVER
 NEC 210.70, LS 101 5-8 REQUIRES A MIN OF
 ONE "LIGHTING OUTLET".
  
 16)NOTE: PLEASE PROVIDE ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
 215.5
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW INTO SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 09:42 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 09:42 Sent To E
Notes
2005-08-02 00:00:00TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-15 Cont ID  
Sent By rmcdouga Date 2005-08-15 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2005-08-02 Time 08:53 Sent To  
Notes
2005-08-02 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-03 Cont ID  
Sent By prafter Date 2005-08-03 Time 10:54 Rev Time 1.00
Received By prafter Date 2005-08-03 Time 10:53 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By jleech Date 2005-08-02 Time 12:47 Rev Time 0.50
Received By jleech Date 2005-08-02 Time 12:47 Sent To M
Notes
2005-08-02 00:00:00DENIED;
 1.RISER DIAGRAM DOESNOT MATCH FLOOR
 PLAN. W/M IS ON THE WRONG SIDE OF
 BATHROOM. BATHROOM RUNS NORTH TO SOUTH
 RISER RUNS WEST TO EAST. OTHER BATHROOM
 THE TUB IS NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By mmclean Date 2005-08-02 Time 09:28 Rev Time 0.00
Received By mmclean Date 2005-08-02 Time 09:28 Sent To I
Notes
2005-08-02 00:00:00DENIED
 1. TOO MUCH CONCRETE WITHIN THE FRONT
 SETBACK OF PROPERTY.
 2. MUST REDUCE CONCRETE TO MEET THE
 REQUIREMENTS AND PROVIDE DIMENSIONS.
  
 **MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.**
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720