Plan Review Details - Permit 05070652
| Plan Review Stops For Permit 05070652 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-07-20 |
Time |
13:24 |
Rev Time |
2.50 |
| Received By |
mjacobs |
Date |
2005-07-20 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT:05070652 | | | ADD:2701 BROADWAY | | | CONT:TAYCON CONST.MGT;INC. | | | TEL: (561)622-2699 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:1ST | | | ACTION:DENIED | | | 1) 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2) BEFORE THE REMOVAL OF ANY ASBESTOS, | | | THE DEPARTMENT OF ENVIRONMENTAL | | | PROTECTION MUST BE NOTIFY. PLEASE | | | FBC.104.1.10 AND FS.469.003. | | | | | | 3) THE DESIGN PROFESSIONAL WEATHER | | | ARCHITEC OR ENGINEER WHO IS LEGALLY | | | REGISTERED WITH THE STATE, MUST AFFIX | | | HIS/HER SEAL TO THE DRAWINGS. ALSO THE | | | FIRM LICENSE NUMBER IS REQUIRED IN THE | | | TITLE BLOCK OF EACH SHEET.SEE | | | FAC.61G1-16.004(2) AND FS 481.219 | | | | | | 4) THE APPLICATION STATES INTERIOR DEMO | | | ONLY, HOWEVER THE DRAWINGS INDICATE THE | | | REMOVAL OFA PORTION OF AN EXTERIOR | | | BEARING WALL. PLEASE SHOW HOW THE | | | STRUCTURE WILL BE SUPPORTED WHEN THIS | | | SECTION IS REMOVED. | | | THE APPLICATION DESCRIPTION NEEDS TO BE | | | UP DATED TO SHOW THE CORRECT SCOPE OF | | | WORK AT THIS LOCATION. | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-19 |
Time |
10:33 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-19 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2005-07-19 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE PLANS NOT SIGNED, | | | DATED AND SEALED BY THE ARCHITECT OF | | | RECORD. FS 481.221 | | | PLEASE ALSO SEESHEET ATTACHED TO NOTES | | | WHICH IS APRINT OUT FROM DBPR. PLEASE | | | SEE THE CERTIFICATE OF AUTHORIZATION # | | | WHICH IS PRINTED ON TITLE BLOCK DOES NOT | | | SEEM TO CORRELATE WITH STATE WEBSITE. | | | | | | 2)NOTE: PLEASE SEE PERMIT APPLICATION | | | MENTIONS INTERIOR DEMO WORK ONLY, | | | HOWEVER PLEASE SEE PLANS AND NOTES TO | | | PLANS SHOW MANY ITEMS WHICH ARE | | | EXTERIOR?? | | | PLEASE CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-21 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-21 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2005-07-21 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FS AND FAC REQUIREMENTS FOR | | | DRAWINGS. | | | | | | 2) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-18 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2005-07-18 00:00:00 | TO "BOB" #9 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-21 |
Time |
08:31 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-07-21 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2005-07-21 00:00:00 | DENIED: | | | PLANS INDICATE A TITLE BLOCK, PER FS | | | 471.025 & 481.221, PLANS ARE TO BE | | | SIGNED, SEALED AND DATED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | PLEASE REFERENCE 104.4.4 & FS 469.003 | | | FOR THE REMOVAL OF ASBESTOS. | | | | | | PLEASE NOTE, PLAN SHEET D1.1, ONLY ONE | | | OF THE THREE COPIES INDICATE THE REMOVAL | | | OF ASBESTOS.ALL PLANS SHOULD INDICATE | | | THIS NOTE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-20 |
Time |
07:44 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-07-19 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. IF THE DESIGN PROFESSIONAL IS AN | | | ARCHITECT OR ENGINEER LEGALLY REGISTERED | | | UNDER THE LAWS OF THIS STATE REGULATING | | | THE PRACTICE OF ARCHITECTURE OR | | | ENGINEERING, THEN HE/SHE SHALL AFFIX | | | HIS/HER OFFICIAL SEAL TO SAID DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA AS | | | REQUIRED BY FLORIDA STATUTE. | | | 2. FIRM LICENSE NUMBER IS REQUIRED IN | | | THE TITLE BLOCK OF EACH SHEET PER FAC | | | 61G1-16.004(2), FS R81.2055, & FS | | | 481.219. | | | 3. IN THE REMOVAL OF ANY PARY OF THE | | | DRAINAGE SYSTEM, DEAD ENDS ARE | | | PROHIBITED. SECTION 704.5. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
jlong |
Date |
2005-07-22 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
jlong |
Date |
2005-07-22 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
|