Plan Review Details - Permit 05070649
Plan Review Stops For Permit 05070649
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-08-01 Cont ID  
Sent By alange Date 2006-08-01 Time 13:50 Rev Time 0.00
Received By alange Date 2006-08-01 Time 13:50 Sent To  
Notes
2006-08-01 00:00:00TRUSS DRAWINGS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 10:43 Rev Time 1.00
Received By alange Date 2006-05-04 Time 10:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-04-20 Cont ID  
Sent By alange Date 2006-04-20 Time 10:32 Rev Time 0.50
Received By alange Date 2006-04-20 Time 10:32 Sent To  
Notes
2006-04-20 00:00:00STRUCTURAL REV. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-03-15 Cont ID  
Sent By alange Date 2006-03-15 Time 12:05 Rev Time 0.50
Received By alange Date 2006-03-15 Time 12:05 Sent To  
Notes
2006-03-15 00:00:00WINDOW BEAM REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-01-04 Cont ID  
Sent By alange Date 2006-01-04 Time 11:53 Rev Time 1.25
Received By alange Date 2006-01-04 Time 11:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-22 Cont ID  
Sent By alange Date 2005-12-22 Time 13:40 Rev Time 0.75
Received By alange Date 2005-12-22 Time 13:35 Sent To  
Notes
2005-12-22 00:00:00DENIED
 FIFTH REVIEW:
  
 4.MIAMI-DADE PRODUCT APPROVAL
 SUBMITTED FOR PGT C-740 ALUMINUM
 CASEMENT WINDOW DOES NOT HAVE THE
 CORRECT STATE PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-07 Cont ID  
Sent By alange Date 2005-12-07 Time 16:22 Rev Time 0.50
Received By alange Date 2005-12-07 Time 16:19 Sent To  
Notes
2005-12-07 00:00:00DENIED
 FOURTH REVIEW:
  
  
 3. ENERGY CALCS SUBMITTED SHALL BE
 SIGNED BY THE OWNER-AGENT.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ** EACH COPY OF PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE STATE PRODUCT
 APPROVAL ATTACHED, TWO COPIES REQUIRED.
 MANY PRODUCT APPROVALS SUBMITTED ARE
 MISSING THE STATE PRODUCT APPROVALS.
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR STRAPS AND TIE-DOWNS.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-11-18 Cont ID  
Sent By alange Date 2005-11-18 Time 13:15 Rev Time 1.25
Received By alange Date 2005-11-18 Time 12:36 Sent To  
Notes
2005-11-18 00:00:00DENIED
 THIRD REVIEW:
  
  
 3. ENERGY CALCS SUBMITTED SHALL BE
 SIGNED BY THE OWNER-AGENT.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR AND STRAPS AND
 TIE-DOWNS.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 10:47 Rev Time 1.25
Received By alange Date 2005-09-19 Time 09:48 Sent To  
Notes
2005-09-19 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3. ENERGY CALCS NOT SUBMITTED.SUBMIT
 TWO COPIES.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR AND STRAPS AND
 TIE-DOWNS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By alange Date 2005-08-10 Time 09:36 Rev Time 3.50
Received By alange Date 2005-08-10 Time 07:23 Sent To  
Notes
2005-08-10 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 4.SUBMIT TWO SET OF MIAMI-DADE PRODUCT
 APPROVALS, ONLY ONE SUBMITTED.
 MANY OF THE MIAMI-DADE PRODUCT APPROVALS
 SUBMITTED ARE MISSING PAGES.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR AND STRAPS AND
 TIE-DOWNS.
  
 6.PAGE 2 DETAIL 2 SHOW GRADE AT 4"
 BELOW FINISH FLOOR.FBC WPB AMMENDMENT
 1804.1.7
  
 7.SHOW UNIFORM DISTRIBUTED LIVE LOADS
 FBC1604.1
  
 8.SHOW UPLIFTS ON ROOF FRAMING PLAN.
  
 9.PAGE 6 A-3 SHOW LENGTH OF ANCHOR
 BOLTS USED FOR LEDGER.
  
 10.SUBMIT A GUARDRAIL DETAIL SHOWING
 HEIGHT AND SPACING AND ANCHORING.FBC
 1026.5.1
  
 11.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS FBC 2309.6
  
 12. SHOW HOW ATTIC VENTING WILL COMPLY
 WITH FBC 2309.7.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2007-06-18 Cont ID  
Sent By dpalmer Date 2007-06-18 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2007-06-18 Time 14:25 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-06-07 Cont ID  
Sent By dpalmer Date 2007-06-07 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 10:23 Sent To PC
Notes
2007-06-07 10:37:11** UNSAT **
  
 1) NOTE: PLEASE SEE THE REVISED RISER NOW SHOWS
 PREVIOUS ITEMS WHICH WERE INDICATED AS *FUTURE* BEING
 INSTALLED AT THIS TIME.
 PLEASE SUBMIT REVISE PANEL SCHEDULE(S) AND LOAD
 CALCULATIONS FOR ANY INCREASED LOADS WHICH ARE
 DIFFERENT FROM PREVIOUS SUBMITTED PLANS.
 CONDUCTORS HAVE CHANGED, ETC.
 PLEASE SEE 215.5, 220 ETC.
 FBC 106.3.5.4
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 09:18 Sent To PC
Notes
2007-02-27 09:19:19ELECTRICAL CONTRACTOR CAME IN AND SIGNED SECOND SHEET.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 14:42 Sent To  
Notes
2007-02-25 14:49:042007-02-25 14:49: 04
 *** PLANS UNSAT/ON HOLD, CONTRACTOR TO COME IN AND SIGN
 SECOND SHEET IN BOTH SETS.
 CALLED AND LEFT MESSAGE ON CHARLIE'S VM.
 PLANS AT DVP' S DESK.
  
  
  
  
 REDLINED 210.52 TO VIF.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 14:48 Sent To PC
Notes
2007-02-18 15:16:39*** UNSAT ***
  
 1) NOTE: PLEASE SEE POOL SUB PANEL WHICH IS BEING SHOWN
 BEING FED FROM TWO SINGLE POLE 20AMP BREAKERS??
 PLEASE SEE THE SPACE (CIRCUITS ABOVE 10/12) SHOW 2-POLE
 25AMP BREAKER?
 PLEASE CORRELATE.
  
 2) NOTE: PLEASE SEE PLANS INDICATE THE DISHWASHER AND
 DISPOSAL AS TWO SEPARATE RECEPTACLE DEVICES, YET PANEL
 SCHEDULE SHOWS A 2-POLE BREAKER FEEDING THESE. PLEASE
 SEE 210.4, IF YOU WERE FEEDING BOTH APPLIANCES THROUGH
 ONE SINGLE DEVICE/YOKE, THEN A 2-POLE BREAKER WOULD BE
 REQUIRED, HOWEVER IF THESE ARE BOTH SEPARATE RECEPT
 DEVICES, THESE WOULD BE SINGLE POLE BREAKERS.
  
 3) NOTE: PLEASE VERIFY THE PANEL *B* WHICH SHOWS THIS
 AS A 125AMP PANEL AND 125A BREAKER ON RISER, YET PANEL
 SCHEDULE SHOWS THIS AS 150AMP PANEL WITH A BACK FED
 125AMP BREAKER? PLEASE BE SURE IF THIS IS A BACK FED
 BREAKER AND IS PRT OF THE SERVICE RATED MAIN DISCONNECT
 THAT THIS BREAKER CONTAINS A REJECTION CLIP. (IF THIS
 IS THE CASE) PLEASE CORRELATE WHAT SIZE PANEL ETC.
 FBC 106.1.2 PLEASE COORDINATE.
  
 4) NOTE: PLEASE SEE MISSING SMOKE ALARM AT THE LOWER
 FLOOR LEVEL IN THE IMMEDIATE VICINITY LEADING TO THE
 FLOOR ABOVE.
 NFPA-72 11.5.1.1
  
 **PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS FOR DESIGN.
 2002 NFPA-70, 2002 NFPA-72
  
 6) NOTE: PLEASE SEE POSSIBLE MISSING RECEPT IN KITCHEN
 FOR 2FT OR MORE OF WALL. THIS IS ONLY NOTED AS WALL
 DIMENSION AND KITCHEN SET UP WILL BE VERIFIED IN FIELD.
 210.52 (REDLINED ON PLAN).
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 13:14 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 12:57 Sent To PC
Notes
2007-02-03 13:16:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT THE PLANS SUBMITTED ARE COPIES
 OF PLANS WHICH WERE DONE BY THE ARCHITECT OF RECORD.
 PLEASE KNOW IF A NEW DESIGNER OF RECORD IS TAKING OVER
 PROJECT THIS PERSON MAY NOT USE PLANS DONE BY THE
 ARCHITECT. THEY ARE REQUIRED TO BE RE-DRAWN, CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE NEW DESIGNER OF
 RECORD.
 THE ARCHITECT'S PLANS OF RECORD ARE PROTECTED UNDER
 FLORIDA STATUTES 481.
  
 2) NOTE: PLEASE SEE THE LETTER FROM THE OWNER IS
 REQUIRED TO BE AN ORIGINAL SIGNED LETTER, WITH AN
 ORIGINAL NOTARY;MAY NOT BE A PHOTO-COPY.
 FS117.05
  
 3) NOTE: PLEASE SEE MULTIPLE COMMENTS FROM PREVIOUS
 REVIEW WERE NOT CORRECTED.
 PLEASE SEE THE RISER AND PANEL SCHEDULES FOR SIZE AND
 SERVICE ENTRANCE CONDUCTORS, MAINS, MISSING PANELS,
 MISSING LOADS ETC.
  
 ***PLEASE SEE COMMENTS ATTACHED FROM PREVIOUS REVIEW.
 PLEASE SEE THE PLANS SUBMITTED CAN NOT CONTAIN A FULL
 REVIEW FOR CODE COMPLIANCE AS THE PLANS SUBMITTED ARE
 PLANS NOT SIGNED, DATED AND SEALED BY THE ARCHITECT OF
 RECORD WHICH IS STILL LEGALLY THE DESIGNER OF RECORD.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2007-01-10 Time 12:56 Sent To PC
Notes
2007-01-10 17:37:47** UNSAT **
  
 1) NOTE:PLEASE CORRELATE ALL OF THE ITEMS ON THE
 PANEL SCHEDULES WITH THE LOAD CALCULATIONS. PLEASE SEE
 MANY OF THE ITEMS BELOW WHICH MAY HELP.
  
 A) PLEASE SEE SPRINKLER PUMP ON LOAD CALCULATIONS
 INDICATE 1800VA AND PANEL SCHEDULE SHOWS 300VA. PLEASE
 ALSO SEE MISSING OVER CURRENT PROTECTION SIZE ON PANEL
 SCHEDULE.
  
 B) PLEASE SEE LOAD ON POOL PANEL IS SHOWN AS 3.7KW AND
 PANEL A SHOWS A LOAD OF 3.4.KW
 PLEASE SEE THIS WILL CHANGE IF THE SPRIKLER PUMP IS
 REMOVED?
  
 C) PLEASE SEE A RANGE IS SHOWN ON PANEL AND OVEN ON
 LOAD CALCULATIONS, IS THIS SAME OR IS THERE AN ELECTRIC
 OVEN? PANEL SCHEDULE SHOWS THIS RANGE AS GAS, HOWEVER
 ALSO SHOWS ELECTRIC AS 50A BREAKER WITH #6 CONDUCTORS.
 PLEASE SEE PLANS ALSO INDICATE A 220V OUTLET.
  
 D) PLEASE SEE THE SAME IS IN QUESTION FOR THE DRYER? IS
 THIS ELECTRIC OR GAS? PLEASE SEE PLANS DESIGNATE WHAT
 APPEARS TO BE THE WASHER AS A DRYER AND THE DRYER AS
 THE WASHER? PLEASE SEE THE WASHER SHOWN WITH THE W
 SHOWS A 220V RECEPT. 220.18
  
 E) PLEASE SEE THE WATER HEATER IS BEING SHOWN AS GAS,
 YET ALSO SHOWS 220V/30A RATED BRANCH CIRCUIT. PLEASE
 SEE PLANS SHOWS A J-BOX? NO RECEPT, DISCONNECT ETC?
 422.31 ETC
  
 F) PLEASE SEE WHIRLPOOL BRANCH CIRCUIT IS SHOWN ON
 PANEL SCHEDULE; HOWEVER NO RECEPT IS BEING SHOWN ON
 PLANS. THE LOCATION FOR THIS IS BEING ASSUMED TO BE AT
 THE MASTER BATH, HOWEVER PLEASE SEE PLANS. PLEASE ALSO
 SEE MISSING GFI PROTECTION EITHER AT THE UNIT OR AS THE
 BREAKER WHICH FEEDS THIS IS REQUIRED. 680.71
  
 * ABOVE PER 408.4, 220, 310.16, 240.4, ETC
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND FOR CORRELATION OF SAID PLANS.
  
 2) NOTE: PLEASE SEE RISER SHOWS THE PANEL B CONTAINING
 A 125A MAIN BREAKER; HOWEVER THE PANEL SCHEDULE SHOWS
 THIS CONTAINING A 100A MAIN BREAKER.
  
 3) NOTE: PLEASE SEE LOCATION OF RECEPT IN FAMILY ROOM
 IS NOT WITHIN 6FT OF DOOR ON PLANS, PLEASE VERIFY AND
 CORRECT LOCATION AS NEEDED. PLEASE SEE REDLINED PLANS.
 THIS LOCATION IN THE FIELD MAY VERY WELL BE OK. 210.52
  
 4) NOTE: PLEASE KNOW THE PANEL B ON THE NEW CABANA
 PLANS FEEDS A NEW PANEL FOR THE CABANA; HOWEVER THERE
 IS NO INDICATION ON PANEL B SCHEDULE FOR THIS SUB FEED
 TO THE OTHER PANEL WHICH IS BEING INSTALLED AT THIS
 TIME UNDER PERMIT # 06061694.
 PLEASE REVISE PANEL SCHEDULE FOR B, PLEASE REVISE LOAD
 ON B, AND PLEASE REVISE LOAD CALCULATIONS FOR MAIN
 SERVICE.
 PLEASE KNOW, WHEN ADDING HEAT LOADS AND LOADS TO AN
 EXISTING SERVICE 220.31B IS REQUIRED FOR LOAD
 CALCULATIONS. AS THE NEW BUILDING WAS ADDED TO THE
 EXISTING SERVICE UNDER THE MAIN HOUSE, PLEASE SEE THE
 SECTION ABOVE IF ADDING THE LOADS MENTIONED AS THIS
 WILL AFFECT THE LOADS ON THE MAINS SERVICE.
 PLEASE INCLUDE FEEDERS, ETC.
 408.4, 310.16, 250.32, 225.31, ETC
 IT IS RECOMMENDED THAT COORDINATION IS DONE BETWEEN THE
 MAIN HOUSE ELECTRICAL CONTRACTOR AND THAT OF THE
 CONTRACTOR FOR THE REAR CABANA BUILDING TO OBTAIN AND
 PROVIDE THE LATEST INFORMATION TO THE DESIGNER FOR THE
 MAIN HOUSE.
 ANY CHANGES ON THE DETACHED CABANA WILL ALSO BE
 REQUIRED TO BE REVISED AT A LATER DATE BEFORE FINAL CAN
 BE GIVEN OR POWER IS TURNED ON.
  
  
 ** PLEASE KNOW AS A SIDE NOTE, PLEASE VERIFY AND
 COORDINATE WITH THE ELECTRICAL INSPECTOR AND MOST
 IMPORTANTLY THE MECHANICAL INSPECTOR AS TO WHEN POWER
 CAN BE TURNED ON. POWER RELEASE TO CONDITION SPACE
 BEFORE ALL SANDING AND PAINTING ETC IS COMPLETE IS NOT
 PERMITTED NOT TO MENTION COMPLETION OF THE ELECTRICAL
 SYSTEMS FOR LIFE SAFETY.
 THIS IS ONLY A NOTE AND DOES NOT HAVE AN AFFECT ON THE
 ELECTRICAL REVISIONS AS SUBMITTED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 13:33 Sent To PC
Notes
2006-08-20 00:00:00REDLINED,
  
 POOL PANEL STILL SHOWES ONLY 3#10'S AND
 RISER SHOWS 4. (SEE RISER) INSTALL 4.
  
 PANEL "A" SHOWS TWO SEPARATE GDO
 CIRCUITS AT 1700VA EACH, YET LOAD
 CALCULATIONS SHOWS 2, YET BOTH ARE
 INCLUDED AT THE 1700VA.
  
 BOTH WERE REDLINED AND NOTED ON PREVIOUS
 REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 18:11 Sent To PC
Notes
2006-08-14 00:00:00*** UNSAT ***
  
 ** PLEASE SEE RISER IS REVISED ALONG
 WITH PLANS.
 PLEASE SEE THE FOLLOWING COMMENTS.
  
  
 1) NOTE: PLEASE CORRELATE ALL LOADS
 SHOWN ON PANEL SCHEDULES WITH LOADS
 SHOWN ON SERVICE LOAD CALCUALITONS.
 PLEASE SEE WASHER, DRYER,DISPOSAL,
 GARAGE DOOR OPENERS, POOL EQIPMENT ETC.
 PLEASE KNOW THIS IS IN NO WAY ALL ITEMS.
 PLEASE SEE MANY OF THESE ARE REDLINED.
 PLEASE GO THROUGH PLANS.
 PLEASE CORRELATE POOL LOADS, AS AMPERAGE
 ON POOL PANEL SHOWS "0"?
 106.1.2, 408.4, 220.31 ETC.
  
 2) NOTE: PLEASE SEE RISER NOW SHOWS THE
 NEW POOL PANEL, HOWEVER PLANS DO NOT
 SHOW THIS PANEL?
 PLEASE ALSO SEE PLANS SHOWS WHAT APPEARS
 TO BE THE NEW MAIN DISCONNECT NEXT TO
 METERCAN, HOWEVER THIS IS NOT LABLED.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE FEEDERS FOR POOL
 PANEL AS 3-#10'S AND RISER SHOWS 4-#10'S
 PLEASE CORRELATE.
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR ALL NEW MAINS/BRKRS. THIS
 INFORMATION WAS ON ORIGINAL PLANS AS
 NOTED. 110.9/90.8
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-01 Cont ID  
Sent By dpalmer Date 2006-08-01 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2006-08-01 Time 08:34 Sent To PC
Notes
2006-08-01 00:00:00*********** UNSAT **************
  
 1) NOTE: PLEASE CORRELATE PLANS, RISER
 AND PANEL SCHEDULES.
  
 A)PLEASE SEE PANEL "B" DOES NOT INDICATE
 AMPERAGE RATING. RISER NOTE MENTIONS TO
 SEE PANEL, HOWEVER PANEL "B" IS SHOWN AS
 "1"AMO RATED???
 B) PLEASE SEE RISER NOTE THREE SEEMS TO
 INDICATE THE SEC'S GOING INTO MAIN FOR
 PANEL "B", YET PLEASE SEE 230.7.
 C) PLEASE SEE RISER NOTES MENTIONS
 FEEDERS FOR PANEL "B" AS 2/0'S, YET
 PANEL "B" SHOWS 3-#3'S ALONG WITH RISER
 NOTE #3.
 D) PLEASE SEE NUMEROUS ITEMS SHOWN ON
 PANEL SCHEDULE FOR SM APPL, DISHWASHER,
 DISPOSAL ETC WHICH INDICATE #6 AND #8
 CONDUCTORS. PLEASE VERIFY AS CONDUCTORS
 ARE PERMITTED TO GO HIGHER THAN MINIMUM
 HOWEVER #6'S AND #8'S WILL NOT FIT INOT
 20A BREAKERS. IF PLANS SHOW THESE SIZES,
 THEN THIS IT WHAT IS REQUIRED TO BE
 INSTALLED.
 E) PLEASE SEE POOL PANEL IS NOT SHOWN ON
 PLANS OR ON RISER.
 F)PLEASE SEE SEC'S OR FEEDERS FOR PANEL
 "A" DO NOT CORRELATE WITH PANEL "A".
 G) PLEASE VERIFY WHERE MAIN IS FOR PANEL
 "B". GROUPING, OCP ETC.
 PLEASE SEE THIS IS ONLY FOR RISER, RISER
 NOTES, PLANS AND PANELS WHICH DO NOT
 CORRELATE.
 240.4,230.70,230.72,215.5,310.16,250.50,
 240.21 ETC
  
 2) NOTE: PLEASE VERIFY SEC'S FROM FPL AS
 THESE ARE STILL SHOWN AS 3/0'S. PLEASE
 SEE ORIGINAL PLANS WAS FOR A 200A
 SERVICE AND NOW HAS BEEN ADJUSTED TO
 300A'S.
 PLEASE KNOW, IF THE SEC'S ARE INSTALLED
 BY FPL ALL THE WAY UP TO THE METERCAN,
 THEN THESE CONDUCTOR SIZES NEED NOT BE
 SHOWN, HOWEVER IF THESE CONDUCTORS ARE
 INSTALLED OUT TO A FPL HAND-HOLE, THEN
 THE SIZES SHALL BE SIZED AT A MIN PER
 310.15B6, (250MCM).
  
 3) NOTE: PLEASE SEE 250.66 FOR MIN
 SIZING OF THE GROUNDING ELECTRODE
 CONDUCTOR AS SERVICE HAS NOW BEEN
 INCREASED AND THE GEC IS SIZED BASED ON
 NEW SEC'S.
  
 4) NOTE: PLEASE COMPLETE LOAD
 CALCULATIONS FOR PANEL "B". WHERE ARE
 THE LOADS FOR A/C'S 1 AND 2 CU'S??
 220, 240.4, 310.16
  
 5) NOTE: PLEASE SEE PROVIDE THE
 COMPLETED PANEL SCHEDULE FOR POOL PANEL
 WITH NEW CIRCUITS, LOADS ETC FUTURE?
 SHOWS 10.2 KW ON PANEL "A" HOWEVER IT IS
 UNCLEAR WHERE LOADS ARE DERIVED FROM??
 PLEASE CLARIFYAND SHOW ALL CONTINOUS
 LOADS AT 125%
 215.5, 220, 215.3, 230.42
  
 6) NOTE: PLEASE SEE ONE SHEET CONTAIN A
 TITLE BLOCK FOR "PARKER AND COMPANY"
 WHICH WAS REMOVED FROM RECORD SET AND
 FROM OTHER SHEET SUBMITTED.
 THIS WAS CONFIRMED WITH THE STATE'S
 LEGAL COUSEL TO THE BOARD OF
 ARCHITECT'S.
 FAC 61G1-16.004, FS481.219
  
 7) NOTE: PLEASE VERIFY THE KW RATING FOR
 AHU'S AS 9KW FOR EACH DOES NOT APPEAR TO
 BE A COMMON KW RATING. PLEASE VERIFY IF
 10KW AND ADJUST CALCULATIONS AS NEEDED.
 PLEASE SEE 220
  
 8) NOTE: PLEASE SEE FS 481.221(4).
 PLANS ARE BEING RETAINED.
  
 ** PLEASE KNOW THESE PLANS WERE REVIEWED
 THREE TIME BEFORE THIS REVIEW. THE
 PREVIOUS REVIEW WAS DONE WITH A
 "PROVISO" TO ADDRESS CERTAIN ITEMS
 BEFORE ROUGH. PLEASE SEE PLANS HAVE NOW
 BEEN REVISED TO COMPLETELY CHNAGE THE
 ELECTRICAL SERVICE AS PREVIOUSLY
 SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By dpalmer Date 2005-11-09 Time 09:33 Rev Time 1.00
Received By dpalmer Date 2005-11-09 Time 09:16 Sent To P
Notes
2005-11-09 00:00:00********* PROVISO/REVISION *********
  
  
 PLEASE SEE SOME NOTES FROM PREVIOUS TWO
 REVIEWS NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SEE ITEMS SHOWN ON LOAD
 CALCULATIONS WHICH ARE NOT SHOWN ON
 PANEL SCHEDULES WITH AWG, OCP.
 DRYER, WASHER. LAUNDRY CIR, MICROWAVE,,,
 215.5,240.4,310.16
 BOTH PREVIOUS REVIEWS.
  
 2)NOTE: PLEASE SEE THERE ARE SOME
 RECEPTS MISSING PER 210.52.
 THESE ARE REDLINED .
 BOTH PREVIOUS REVIEWS.
  
 3)NOTE: PLEASE SEE SERVICE NOW INDICATES
 AN "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO PANEL "A". PLEASE SEE
 "EQUIPMENT GRNDS" ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNNECT.
 250.6,250.24.
  
 4)NOTE: PLEASE SEE REDLINED 422.17 FOR
 WATER HEATER LOCATION.
  
 PLEASE MAKE ALL OF THE ABOVE CORRECTIONS
 AND SUBMIT FOR REVIEW AND STAMPING
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-10-21 00:00:00IN ELEC FOR REVIEW, FROM ZONING ON
 10/18/05

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 18:16 Rev Time 0.75
Received By dpalmer Date 2005-09-08 Time 18:16 Sent To P
Notes
2005-09-08 00:00:00*********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE THERE ARE SOME NOTES FROM
 PREVIOUS REVIEW AND SOME NEW NOTES DUE
 TO CHANGES MADE TO PLANS.
  
  
 1)NOTE: PLEASE SEE PANEL SCHEDULES WITH
 OCP, AWG ETC IS NOW SUBMITTED.
 PLEASE CORRELATE ITEMS ON LOAD
 CALCULATIONS AND ITEMS ON PANEL
 SCHEDULE:
 SEE WASHER, DRYER, WHIRLPOOL TUB, TWO
 POOL PUMPS, POOL LIGHTING, EXHASUT HOOD,
 ALL SHOWN ON LOAD CALCS, BUT NOT ON
 PANEL SCHEDULES.
 215.5, 240.4,220.31,310.16 ETC.
  
 2)NOTE: PLEASE CORRELATE HEATING LOADS
 FOR AHU'S,PLEASE SEE LOAD CALCS INDICATE
 10KW , HOWEVER OCP AND AWG ON PANEL
 SCHEDULE IS NOT LARGE ENOUGH FOR 10KW
 UNITS.
 PLEASE SEE 424.3B , 125% MIN OCP FOR
 10KW HEAT.
 PLEASE SEE 310.16 FOR MIN AWG TO
 CORRELATE WITH OCP ABOVE.
  
 3)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52, UPSTAIRS AND DOWNSTAIRS.
  
 4)NOTE: PLEASE SEE NEW SERVICE IS NOW
 SHOWN.
 PLEASE SEE NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED FROM METER TO
 FIRST MEANS OF DISCONNECT.
 250.6,250.24
  
 5)NOTE:PLEASE SEE 250.50 FOR MIN TO BE
 REQUIRED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 PLEASE SEE FOOTER STEEL(SHOWN AND COLD
 WATER PIPE REQUIRED, (IF METAL).
  
 6)NOTE: PLEASE SEE SEE MECHANICAL RM
 WHICH WAS SHOWN ON ORIGINAL PLANS IS NOW
 SHOWN AS A "STORAGE RM"PLEASE SEE
 WATER HEATER MUST HAVE PERMANANT
 SEPARATION FROM COMBUSTIBLES FROM
 STORAGE AREAS OR WH MUST BE PLACED
 OUTSIDE STORAGE AREA.
 422.17
  
 7)NOTE: PLEASE SEEEQUIPMENT GROUNDING
 CONDUCTOR MISSING FROM MAIN PANEL TO
 SUB-PANEL.
 250.110.,250.122
  
 8)NOTE: PLEASE SEE BATH RECEPTS FOR
 BATHS 2 AND 3 ARE SHOWN WITH AFCI
 PROTECTION. PLEASE SEE 210.8 WHICH
 REQUIRESBATH RECEPTS TO BE GFI
 PROTECTED.
  
 9)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS . THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By dpalmer Date 2005-07-29 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2005-07-29 Time 19:34 Sent To M
Notes
2005-07-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR BOTH
 ARCHITECTUAL AND ARCHITECTUAL AND
 INTERIOR DESIGN FIRMS.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR AMES BENNETT
 AND ASSOCIATES AND MISSING ADDRESS ETC
 AS REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219
 PLEASE ALSO SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR PARKER AND
 COMPANYINTERIOR AND ARCHITECTUAL
 DESIGN. PLEASE SEE NO INFORMATION COULD
 BE LOCATED ON STATE WEBSITE (DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION)
 FOR THIS FIRM? PLEASE LIST ALL REQUIRED
 LICENSE INFORMATION AS REQUIRED UNDER
 FAC 61G1-16.004 AND FS 481.219
 PLEASE SEE ONE SET OF PLANS ARE BEING
 RETAINED AND SHALL BE SENT TO THE STATE
 LEGAL COUNSEL FOR THE BOARD OF
 ARCHITECTS WITH PREVIOUS FILED PLANS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: FBC 905.2, NFPA-72
 8-1.4.1.6.2, 8-1.4.2
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING RECEPTS FOR 210.52C1
 AND 210.52C3
 PLEASE ALSO SEE AREA OF WHICH APPEARS TO
 BE KITCHEN COUNTERSPACE?
  
 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 SHOWING ALL MIN CIRCUITS AS REQUIRED
 UNDER 2002 NEC.
 PLEASE INCLUDE, CIRCUIT OVERCURRENT
 PROTECTION FOR EACH, CONDUCTOR SIZES
 ETC.215.5,240.4,310.16 ETC.
 PLEASE SEE COMMENTS:
  
 7)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 SHALL BE #12 AND 20A.
  
 8)NOTE: PLEASE SEE PLANS SHOWS (GDO)
 GARAGE DOOR OPENERS, HOWEVER NONE LISTED
 IN LOAD CALCULATIONS OR LOAD CALCS.
 215.5 PLEASE ALSO LIST ON PANEL SCHEDULE
 TO BE SUBMITTED.
 PLEASE SEE SIZING OF MOTORS LOADS FOR
 BRANCH CIRCUITING. 430.
  
 9)NOTE: PLEASE SEE GARAGE RECEPTS SHALL
 BE SHOWN AS GFI/GFI PROTECTED PER
 210.8A2
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPT
 PER 210.52E,210.8 IN REAR OF DWELLING.
  
 11)NOTE: PLEASE SEE ONLY (2) SMALL
 APPLIANCE CIRCUITS ARE SHOWN ON LOAD
 CALCULATIONS, HOWEVER A 6KW LOAD IS
 SHOWN?? PLEASE SEE 210.11C1 AND 220.16.
 A LOAD OF 1.5KW FRO EACH. IF ADDITIONAL
 CIRCUITS ARE PROVIDED, THEN LOAD SHALL
 BE INDICATED AS 1.5KW FOR EACH. PLEASE
 KNOW THE NUMBER OF CIRCUITS CAN NOT BE
 VERIFIED AT THIS TIME DUE TO MISSING
 PANEL SCHEDULE.
  
 12)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 AND DISCONNECTS AS REQUIRED PER 440.11
 PLEASESEE ROOM LABLED AS "MECH" DOES
 NOT SHOW ANY AHU? ETC
 PLEASE SEE LOAD CALCULATIONS SHOW 36KW
 OF HEAT, HOWEVER ONLY TWO CU'S AND ONE
 AHU, WAS LOCATED ON PLANS??
 PLEASE SEE 36KW APPEARS TO INDICATE A
 MIN OF 3-4 SYSTEMS??
 PLEASE ALSO SEE 2 CU'S ARE SHOWN ON
 PLANS, HOWEVER ONLY ONE CU DISCONNECT IS
 SHOWN?440.11
 PLEASE ALSO SEE AHU SHOWN INSIDE HOUSE
 W/OUT INDICATION OF DISCONNECT.
 PLEASE SEE IF ROOM WITH ACCESS TO
 EXTERIOR IS INDEED MECH RM, PLEASE SHOW
 ALL EQUIPMENT. PLEASE ALSO SEE MISSING
 RECEPT PER 210.63
  
 13)NOTE: PLEASE SEE WATER HEATER SHOWN
 IN "MECH RM" HOWEVER, NO DISCONNECT IS
 SHOWN. 422.30,422.31
  
 14)NOTE: PLEASE SEE RISER DIAGRAM IS
 MISSING CONDUCTORS FROM MAIN DISCONNECT
 TO SUB PANEL AND FROM METER TO MAIN.
 PLEASE SEE 240.4,310.15B6,310.16.215.5
  
 15)NOTE: PLEASE ALSO SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANEL. 250.110,250.24 SIZE PER
 250.122
  
 16)NOTE: PLEASE SEE SUB PANEL IS BEING
 SHOWN AS MCB, WHICH IS FINE, HOWEVER
 THIS IS NOT REQUIRED.
 IF SHOWN ON PLANS, THEN A MCB WILL BE
 REQURIED TO BE INSTALLED.
 THIS IS ONLY A NOTE AND NO CORRECTION OR
 CHANGE IS REQUIRED.
  
 17)NOTE: PLEASE SHOW SERVICE EQUIPMENT
 LOCATION ON PLANS. PLEASE SEE ONLY
 SUB-PANEL IS SHOWN ON PLANS.
 PLEASE ALSO INDICATE AMERAGE ON
 METER-CAN.
 215.5,230.70
  
 18)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52. PLEASE SEE BEDRMS #2 & #3
 UPSTAIRS AND SOME WALLS DOWNSTAIRS.
  
 19)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12.
 PLEASE SEE ALL "OUTLETS" IN BEDROOMS ARE
 REQUIRED TO BE ARC FAULT PROTECTED, THIS
 INCLUDES; RECEPTS,FANS,LTS SD'S ETC.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED AT LOCATIONS FOR NOTES.
 PLEASE KNOW, REDLINES IN NO WAY INDICATE
 ALL LOCATIONS OF NOTES ABOVE.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE ZONING COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 15:49 Sent To E
Notes
2007-06-13 15:49:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-05-30 Cont ID  
Sent By adarroug Date 2007-05-30 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 09:27 Sent To E
Notes
2007-05-30 09:27:35TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 17:50 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 17:50 Sent To E
Notes
2007-02-22 17:50:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 08:49 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 08:49 Sent To E
Notes
2007-02-16 08:50:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 14:41 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 14:41 Sent To E
Notes
2007-02-01 14:42:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 17:42 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 17:42 Sent To E
Notes
2007-01-09 17:42:42TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-08-19 Cont ID  
Sent By adarroug Date 2006-08-19 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-08-19 Time 16:03 Sent To E
Notes
2006-08-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 09:41 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 09:41 Sent To B
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 16:18 Sent To B
Notes
2006-07-27 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 14:57 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 14:57 Sent To E
Notes
2006-07-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:30 Sent To E
Notes
2006-04-24 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 10:00 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 10:00 Sent To B
Notes
2006-04-13 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-03-03 Cont ID  
Sent By adarroug Date 2006-03-03 Time 09:41 Rev Time 0.00
Received By adarroug Date 2006-03-03 Time 09:40 Sent To B
Notes
2006-03-03 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 14:50 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 14:50 Sent To B
Notes
2005-12-27 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 18:52 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 18:52 Sent To B
Notes
2005-12-13 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 13:01 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 13:01 Sent To B
Notes
2005-11-30 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 09:07 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 09:07 Sent To E
Notes
2005-10-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 16:51 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 16:51 Sent To Z
Notes
2005-10-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 19:21 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 19:21 Sent To Z
Notes
2005-09-29 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 10:17 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 10:17 Sent To E
Notes
2005-09-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 14:44 Sent To Z
Notes
2005-08-30 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 10:15 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 10:15 Sent To E
Notes
2005-07-29 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-10 Cont ID  
Sent By alange Date 2005-08-10 Time 09:37 Rev Time 0.00
Received By alange Date 2005-07-18 Time 11:15 Sent To  
Notes
2005-07-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-11-18 Cont ID  
Sent By tgordon Date 2005-11-18 Time 10:43 Rev Time 0.15
Received By tgordon Date 2005-11-18 Time 10:43 Sent To B
Notes
2005-11-18 00:00:00NO MECH. PLANS SUBMITTED, MECHANICAL
 PERMIT # 05070660 HAS BEEN VOIDED TO
 ALLOW BUILDING PERMIT TO GO THROUGH. PER
 CHARLIE REINEKE, MECH. CONTRACTOR WILL
 APPLY LATTER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 09:35 Rev Time 0.30
Received By tgordon Date 2005-09-13 Time 09:35 Sent To B
Notes
2005-09-13 00:00:00*** DENIED ***
 1) AS NOTED ON LAST MECHANICAL REVIEW,
 MECHANICAL PLANS MUST BE SUBMITTED
 (MECHANICAL CONTRACTOR LISTED ON PERMIT
 APPLICATION).
 2) PLEASE SUBMIT ENERGY CALCULATIONS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By prafter Date 2005-08-04 Time 09:34 Rev Time 0.50
Received By prafter Date 2005-08-04 Time 09:34 Sent To B
Notes
2005-08-04 00:00:00MECH. PLAN REVIEW:
  
 MECH. CONT. LISTED ON APP.
  
 NO A/C PLANS OR EQUIPMENT INFORMATION
 SUBMITTED.
  
 PAT RAFTER 561/808/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By jleech Date 2005-11-15 Time 17:44 Rev Time 0.33
Received By jleech Date 2005-11-15 Time 17:44 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 08:07 Rev Time 0.33
Received By jleech Date 2005-09-13 Time 08:07 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By jleech Date 2005-08-02 Time 12:09 Rev Time 0.75
Received By jleech Date 2005-08-02 Time 12:09 Sent To M
Notes
2005-08-02 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTES.
 2.SANITARY RISER DIAGRAM NOT TO CODE.
 KITCHEN SINK TO DISCHARGE DOWN STREAM
 OF FIRST FLOO 1/2 BATH. D/W TO DRAIN
 INDIRECTLY THRU THE KITCHEN SINK TRAP
 NOT TIED DIRECTLY INTO SANITARY SYSTEM.
 KITCHEN SINK IS NOT VENTED.
 1/2 BATH LAV. NOT VENTED.
 W/M AND L/T NOT VENTED.
 BATHROOM 2 TUB IS NOT VENTED.
 A 2 WAY CLEANOUT IS REQUIRED AT THE
 JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2005-10-31 Cont ID  
Sent By mmclean Date 2005-10-31 Time 16:28 Rev Time 0.00
Received By mmclean Date 2005-10-31 Time 15:11 Sent To I
Notes
2005-10-31 00:00:00APPROVED BY GJOYCE

Review Stop Z ZONING
Rev No 3 Status F Date 2005-10-17 Cont ID  
Sent By mmclean Date 2005-10-17 Time 13:25 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 13:25 Sent To I
Notes
2005-10-17 00:00:00DENIED,
 1. THE PROPOSED DRIVEWAY DOES NOT MATCH
 ON THE SURVEY & SITEPLAN.
 2. NEED TO PROVIDE THE DIMENSION FOR THE
 PROPOSED DRIVEWAY ON SURVEY (LENGTH &
 WIDTH).
 3. SETBACK ON THE SITEPLAN & SURVEY DOES
 NOT MATCH SIDE SETBACK. (SITEPLANS SHOWS
 15FT AND SURVEY SHOWS 12.25FT.
 4. ORIGINAL PERMIT APPLICATION WAS NOT
 SUBMITTED IN PACKAGE.
  
 ****************************************
 ****************************************
 NOTE: MUST MAINTIAN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/DECK/POOL. FENCE MUST HAVE
 UTILITY EASEMENT APPROVAL FROM THE CITY
 OF WEST PALM BEACH UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 17:02 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 17:02 Sent To I
Notes
2005-09-06 00:00:00DENIED,
 1. MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA & FENCE/GATE (WITH EASEMENT
 APPROVAL).
 2. STRUCTURE IS OVER THE HEIGHT
 REQUIREMENTS OF 30FT. PLANS SHOWS 31+FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By mmclean Date 2005-07-27 Time 08:37 Rev Time 0.00
Received By mmclean Date 2005-07-27 Time 08:37 Sent To I
Notes
2005-07-27 00:00:00DENIED,
 1. MUST PROVIDE AN UPDATED SURVEY OF THE
 PROPERTY.
 2. MUST PROVIDE THE DIMENSION OF THE NEW
 DRIVEWAY (WIDTH & LENGTH).
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.
 3. MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA & FENCE/GATE (WITH EASEMENT
 APPROVAL).
 4. STRUCTURE IS OVER THE HEIGHT
 REQUIREMENTS OF 30FT. PLANS SHOWS 31+FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720