Plan Review Details - Permit 05070632
Plan Review Stops For Permit 05070632
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-29 Cont ID  
Sent By alange Date 2005-11-29 Time 13:22 Rev Time 0.66
Received By alange Date 2005-11-29 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 08:31 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 08:30 Sent To PC
Notes
2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070632
 ADD: 152 WORTH COURT S
 CONT: GREEN ELECTRIC
 TEL: (561)262-4857
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SURVEY IS A COPY (2) ORIGINALS
 REQUIRED.) FL S S 472.025 /
 61G17-6.002(8)(E)
  
 61G17-6.002(8)(E) ALL SURVEY MAPS AND
 REPORTS OR COPIES THEREOF ARE NOT VALID
 WITHOUT THE ORIGINAL SIGNATURE, AND THE
 ORIGINAL RAISED SEAL OF A FLORIDA FOR
 LICENSED SURVEYORS AND MAPPERS.
  
 61G17-6.002(8)(C) ALL SURVEY MAPS AND
 REPORTS MUST BEAR THE NAME, "CERTIFICATE
 OF AUTHORIZATION NUMBER", AND THE STREET
 MAILING ADDRESS OF THE BUSINESS ENITITY
 ISSUING THE MAP OR REPORT, ALONG WITH
 NAME AND LICENSE NUMBER OF THE SURVEYOR
 AND MAPPER IN RESPONSIBLE CHARGE.
  
 2) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-21 Cont ID  
Sent By btrobaug Date 2005-11-21 Time 12:34 Rev Time 0.50
Received By btrobaug Date 2005-11-21 Time 12:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-03 Time 11:32 Rev Time 0.50
Received By btrobaug Date 2005-08-03 Time 11:11 Sent To M
Notes
2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE CONDUCTOR AND CONDUIT
 SIZES AND TYPE ON THE RISER DIAGRAM. SEE
 445.13 FOR GEN FEEDER.
  
 2} THE PERSON RESPONSIBLE FOR THE
 DRAWING MUST PRINT AND SIGN NAME TO
 SAME, 104.2.1 FBC.
  
 3} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THESERVICE
 EQUIPMENT AND THE EMERGENCY EQUIPMENT SO
 THAT COMPLIANCE WITH 225.31 THROUGH
 225.37 CAN BE DETERMINED.
  
 4} PLEASE SUBMIT TWO COPIES OF ALL
 DOCUMENTS PER 104.2.1 FBC.
  
 5} INDICATE THE PRIME MOVER (FUEL
 SOURCE) FOR THE GENERATOR.
  
 6) THE VALUE OF THE PROJECT INDICATED ON
 THE APPLICATION MUST INCLUDE THE VALUE
 OF ALL THE EQUIPMENT BEING INSTALLED AND
 LABOR PER 104.6.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 15:00 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 15:00 Sent To E
Notes
2005-11-14 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 10:25 Rev Time 0.00
Received By adarroug Date 2005-07-27 Time 10:25 Sent To E
Notes
2005-07-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 08:52 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 08:52 Sent To E
Notes
2005-07-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-21 Cont ID  
Sent By tgordon Date 2005-11-21 Time 14:06 Rev Time 0.20
Received By tgordon Date 2005-11-21 Time 14:06 Sent To B
Notes
2005-11-21 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF/EAVE VENTS),
 AND TEN FEET AWAY FROM ADJACENT
 BUILDING OPENINGS. 2001 FBC/M 804.3.3
 2) NATURAL GAS PIPING WILL REQUIRE A
 GAS PERMIT APPLICATION BY A LICENSE
 PLUMBING CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By rregueir Date 2005-08-03 Time 17:51 Rev Time 0.00
Received By rregueir Date 2005-08-03 Time 17:51 Sent To P
Notes
2005-08-03 00:00:00PLEASE REVISE AND RESUBMIT FOR REVIEW:
  
 PROVIDE TWO COPIES OF GENERATOR
 SUBMITTAL DATA INDICATING FUEL TYPE TO
 BE USED.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 07:26 Rev Time 0.25
Received By jleech Date 2005-08-04 Time 07:26 Sent To B1
Notes
2005-08-04 00:00:00NAT. GAS PERMIT REQUIRED BEFORE FINAL
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-26 Cont ID  
Sent By mmclean Date 2005-07-26 Time 10:21 Rev Time 0.00
Received By mmclean Date 2005-07-26 Time 10:20 Sent To I
Notes
***NONE***