Plan Review Details - Permit 05070628
Plan Review Stops For Permit 05070628
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-11-10 Cont ID  
Sent By shill Date 2005-11-10 Time 10:48 Rev Time 1.00
Received By shill Date 2005-11-10 Time 10:18 Sent To  
Notes
2005-11-10 00:00:00****CORRECTIONS****
 ****PLAN REVIEW ONLY***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PERMITS APPLIED FOR ON OR AFTER
 OCTOBER 1, 2005 ARE TO BE DESIGNED UNDER
 FBC2004.DECLARE GOVERNING CODE ON THE
 PLANS.
  
 3.)THE DESIGNER OF RECORD IS TO
 ESTABLISH DESIGN CRITERIA FOR CODE
 COMPLIANCE.SEE PREVIOUS LIST, ITEM 4,
 PROVIDE A DETAIL FOR THE SALES COUNTER,
 BREAKFAST ROOM COUNTER AND NEW SANDWICH
 BAR, FBC11-7.2, FBC11-5.THE DETAIL
 PROVIDED IS AN UNSEALED SHOP DRAWING.
 THE MECHANICAL AND ELECTRIC DRAWINGS DO
 NOT INCLUDE THE DIMENSIONS AND HEIGHT
 WHICH SHOW COMPLIANCE.
  
 4.)INDICATE THAT THIS IS A LEVEL 2
 ALTERATION FBC EXISTING BUILDING CODE
 CHAPTER 3.PLEASE READ FBC EXISTING
 BUILDING CODE CHAPTER 6 AND SHOW
 COMPLIANCE WITH APPLICABLE SECTIONS ON
 THE PLAN.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-06 Cont ID  
Sent By shill Date 2005-09-06 Time 14:59 Rev Time 0.50
Received By shill Date 2005-09-06 Time 14:59 Sent To  
Notes
2005-09-06 00:00:00****CORRECTIONS****
 ****PLAN REVIEW****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW, NOT ADDRESSED:
  
 2.)SEE FBC11-5.SHOW COMPLIANCE FOR
 THE BREAKFAST ROOM COUNTER AND THE NEW
 SANDWICH BAR (PROVIDE A DETAIL).
  
 3.)THE ARCHITECT'S TITLE BLOCK IS TO
 BE IN COMPLIANCE WITH FAC61G1-16.003,
 004.PLEASE READ AND INCLUDE ALL
 REQUIRED INFORMATION.
 CA NUMBER, PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS NOT ON THE TITLE
 BLOCK.
  
 NEW COMMENT:
  
 4.)THE SALES COUNTER SHOWN ON E2 IS TO
 COMPLY WITH FBC11-7.2.PROVIDE A
 DETAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-14 Cont ID  
Sent By shill Date 2005-08-14 Time 10:33 Rev Time 1.00
Received By shill Date 2005-08-14 Time 10:33 Sent To  
Notes
2005-08-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 ***NOTE - PLAN REVIEW ONLY***
  
 1.)IT IS NOT CLEAR WHY THERE IS A 1
 HOUR WALL ON ONE SIDE OF THE BREAKFAST
 ROOM, AND AN UNRATED WALL ON THE OTHER
 SIDE.PLEASE CLEARLY SHOW OCCUPANCIES,
 OCCUPANT LOAD, SIZE OF AREA SO THAT
 REQUIRED OCCUPANCY SEPARATION, BOTH
 VERTICAL AND HORIZONTAL (IF REQUIRED)
 AND CODE COMPLIANCE CAN BE DETERMINED.
  
 2.)SEE FBC11-5.SHOW COMPLIANCE FOR
 THE BREAKFAST ROOM COUNTER AND THE NEW
 SANDWICH BAR (PROVIDE A DETAIL).
  
 3.)THE ARCHITECT'S TITLE BLOCK IS TO
 BE IN COMPLIANCE WITH FAC61G1-16.003,
 004.PLEASE READ AND INCLUDE ALL
 REQUIRED INFORMATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-29 Cont ID  
Sent By dpalmer Date 2005-08-29 Time 09:08 Rev Time 0.50
Received By dpalmer Date 2005-08-29 Time 07:48 Sent To  
Notes
2005-08-29 00:00:00*********** UNSAT ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON BOTH TITLE BLOCKS FOR
 ARCHITECT AND ENGINEERING FIRM.
 PLEASE SEE MISSING LICENSE INFORMAITON
 AS REQUIRED UNDER FS 481.219 AND 471.023
 PLEASE SEE ALL INFORMATION REQUIRED PER
 61G1-16.004 (ARCH'S) AND 61G15-23.002
 (ENG'S).
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE GFI PROTECTION
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
 COULD NOTLOCATE REFERENCE TO GFI
 PROTECTION.
  
 3)NOTE: PLEASE PROVIDE LOAD ON EXISTING
 MDP WITH ADDED LOADS FROM NEW PANEL.
  
 *** PLEASE KNOW, PLANS ARE ONLY IN FOR
 "PLAN REVIEW " AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 06:42 Rev Time 0.33
Received By dpalmer Date 2005-07-26 Time 06:39 Sent To  
Notes
2005-07-26 00:00:00*********** UNSAT ***********
  
 PLEASE KNOW, PLANS HAVE BEEN SUBMITTED
 FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION IN TITLE BLOCK AS REQUIRED
 UNDER FAC 61G1-16.004 AND FS 481.219.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE PROVIDE LAYOUT FOR NEW
 ELECTRICAL TO BE INSTALLED.
 PLEASE SHOW ALL NEW CIRCUITING AND
 CORRELATE WITH PANEL SCHEDULE(S) TO BE
 SUBMITTED.
  
 3)NOTE: PLEASE SEE 700.12E FOR ANY
 EM/EXT LTS BEING INSTALLED.
  
 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 REQUIRED GFI PROTECTION FOR KITCHEN IN
 OTHER THAN DWELLING UNITS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS IS
 REQUIRED TO BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESOTATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By kmcvey Date 2005-08-17 Time 14:08 Rev Time 0.10
Received By kmcvey Date   Time   Sent To  
Notes
2005-08-17 00:00:00DELECTED PER LUIS M

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 10:40 Sent To  
Notes
2005-09-12 00:00:001. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL.
  
 2. NEW SOFFIT SHALL NOT INTERFERE
 WITH ANY REQUIRED FIRE SPRINKLER HEADS.
  
 3. ALL WORK SUBJECT TO FIELD INSPECTORS
 APPROVAL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By mwennerg Date 2005-08-12 Time 14:40 Rev Time 0.00
Received By mwennerg Date 2005-08-12 Time 14:40 Sent To  
Notes
2005-08-12 00:00:00******DENIED******
 PLAN REVIEW ONLY
  
 1) PLEASE PROVIDE MORE INFORMATION FOR
 REVIEW.
  
 2) WILL THIS WORK IMPACT ANY EXISTING
 FIRE PROTECTION EQUIPMENT?
  
 3) PLEASE SHOW LOCATION OF EXIT LIGHTS
 AND EMERGENCY LIGHTING NEW OR EXISTING,
 FIRE EXTINGUISHERS ETC.
  
 4) PLEASE SEE OTHER REVIEW COMMENT
 REGARDING FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-29 Cont ID  
Sent By rbrown Date 2005-12-29 Time 18:41 Rev Time 0.00
Received By rbrown Date 2005-12-29 Time 18:41 Sent To  
Notes
2006-01-19 00:00:00TO "COMM" BD#18
2005-12-29 00:00:00CONVERTED TO A PERMIT APPLICATION ON
 12/16/05 UNDER A NEW PERMIT# 05120828.
 THE NEW NUMBER WAS GENERATED DUE TO THE
 CHANGE FROM 2001 CODE TO 2004.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 13:35 Sent To  
Notes
2005-11-09 00:00:00TO "COMM" BD#26
2005-10-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 11:06 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 11:06 Sent To  
Notes
2005-08-23 00:00:00TO "COMM" BD#7
2005-08-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By kmcvey Date 2005-08-17 Time 14:11 Rev Time 0.10
Received By kmcvey Date 2005-07-18 Time 08:42 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#52
2005-07-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-11-15 Cont ID  
Sent By pkrauss Date 2005-11-15 Time 10:14 Rev Time 0.55
Received By pkrauss Date 2005-11-15 Time 08:52 Sent To  
Notes
2005-11-15 00:00:00PLANS SUBMITTED AS '1ST RESUB'.THIS
 HAS NEVER BEEN SUBMITTED FOR 'PERMIT'.
 PREVIOUS REVIEWS HAVE BEEN 'PLAN REVIEW'
 ONLY.PLEASE CLARIFY WHETHER THIS
 SUBMITTAL IS FOR 'PERMIT' OR '3RD PLAN
 REVIEW'.FEES ARE OWED ACCORDINGLY.
  
 PLEASE NOTE, PLANS REVIEWED UNDER THE
 2004 FMC DUE TO THE FACT IT WAS NOT
 SUBMITTED FOR PERMIT PRIOR TO OCTOBER 1,
 2005.
  
 PLANS ARE CODE COMPLIANT.
  
 IF YOUHAVE ANY QUESTIONS, PLEASE CONTACT
 PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 09:25 Rev Time 0.55
Received By pkrauss Date 2005-09-13 Time 09:25 Sent To  
Notes
2005-09-13 00:00:00DENIED:
 1.PLEASE PROVIDE CERTIFICATE OF
 AUTHROIZATION NUMBER FOR THE
 ARCHITECURAL FIRM AS REQUIRED PER FAC
 61G1-16.004.
  
 2.PLEASE PROVIDE THE REQUIRED LICENCE
 NUMBER FOR THE ENGEERING FIRM &
 ENGINEER'S LICENCE NUMBER.PLEASE
 PROVIDE PRINTED NAME OF THE ENGINEER PER
 FS 471.025 & FAC 61G15-23.002.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 20:59 Rev Time 0.35
Received By pkrauss Date 2005-07-26 Time 20:45 Sent To  
Notes
2005-07-26 00:00:00INSUFFICIENT INFORMATION FOR REVIEW.
 APPLICATION INDICATES RESTAURANT
 CONVERSION.PLEASE INDICATE REMOVAL OR
 INSTALLATION OF HOODS OR FIRE
 SUPPRESSION SYSTEMS.PLEASE NOTE, DUCT
 PENETRATIONS THROUGH RATED PARTITION MAY
 REQUIRE FIRE DAMPERS, PLEASE CLARIFY.
  
 SEE ALSO COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By kmcvey Date 2005-08-17 Time 14:10 Rev Time 0.10
Received By kmcvey Date   Time   Sent To  
Notes
2005-08-17 00:00:00NO PLUMBING SUBMITTER PER LUIS M

Review Stop Z ZONING
Rev No 1 Status N Date 2005-08-17 Cont ID  
Sent By kmcvey Date 2005-08-17 Time 14:09 Rev Time 0.10
Received By kmcvey Date   Time   Sent To  
Notes
2005-08-17 00:00:00DELETED PER LUIS M