Plan Review Details - Permit 05070627
Plan Review Stops For Permit 05070627
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-05-28 Cont ID  
Sent By jwitmer Date 2008-05-28 Time 16:25 Rev Time 1.22
Received By jwitmer Date 2008-05-28 Time 16:25 Sent To  
Notes
2008-05-28 16:42:23BUILDING PLAN REVIEW
 PERMIT: 05070627
 ADD: 2300 PRESIDENTIAL WAY
 CONT: GRUBER HALL/ DAVE
 TEL: (561)662-3377
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THE GENERATOR, SLAB, TRANSFER SWITCH AND FUEL TANK
 WERE NOT ON THE ORIGINAL PLANS. THIS WILL REQUIRE A
 SEPERATE PERMIT WITH REVIEW AND ASSOCIATED FEES.
  
 3) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) THERE IS NO INFORMATION AS TO THE GENERATOR BLOCK
 WALLENCLOSURE, PLEASE SUPPLY ADDITIONAL INFORMATION
 106.1.2.
  
 5)PROVIDE INFORMATION FOR THE MOMENT OF OVERTURNING,
 PLEASE PROVIDE ANCHOR INFORMATION AS WELL AS SLAB
 INFORMATION. 1609.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDDING.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-06-14 Cont ID  
Sent By jwitmer Date 2007-06-14 Time 14:00 Rev Time 0.77
Received By jwitmer Date 2007-06-14 Time 14:00 Sent To PC
Notes
2007-06-14 14:00:52REVISION: HANDICAPPED SHOWER

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 14:08 Rev Time 0.33
Received By jwitmer Date 2007-06-13 Time 14:08 Sent To PC
Notes
2007-06-13 14:16:36BUILDING PLAN REVIEW
 PERMIT: 05070627
 ADD:2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS
 TEL: (561)833-4441
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 CUT SECTION OF PLAN INDICATES WHAT APPEARS TO BE
 HANDICAPPED SHOWERS WITH A BENCH BUT THE PLAN FAILS TO
 SHOW THE LOCATION OF THE CONTROLS.
 SEE 11-4.21.8 SHOWER ENCLOSURES.
 IF PROVIDED, ENCLOSURES FOR SHOWER STALLS SHALL NOT
 OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS
 ONTO SHOWER SEATS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 14:05 Rev Time 0.33
Received By jwitmer Date 2007-06-13 Time 14:05 Sent To PC
Notes
2007-06-13 14:07:20ARCHITECT MEMO: REGARDING RESSTROOM SIZE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-05-08 Cont ID  
Sent By jwitmer Date 2007-05-08 Time 10:32 Rev Time 1.33
Received By jwitmer Date 2007-05-08 Time 10:32 Sent To PC
Notes
2007-05-08 10:33:17REMOVAL OF TIE COLUMNS AND REINFORCEMENT WITH STEEL
 BEAMS AND BRACKETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-07-20 Cont ID  
Sent By jwitmer Date 2006-07-20 Time 16:09 Rev Time 1.11
Received By jwitmer Date 2006-07-20 Time 16:09 Sent To  
Notes
2006-07-20 00:00:00REV# 5 OK K. WHITE REVISED (REDLINED)
 ARCHITECURAL (A) PLAN 7-20-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-07-12 Cont ID  
Sent By jwitmer Date 2006-07-12 Time 14:29 Rev Time 2.22
Received By jwitmer Date 2006-07-12 Time 13:09 Sent To  
Notes
2006-07-12 00:00:00ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION:# 5
 ACTION: DENIED
  
  
 11-4.1.6(1)(B)
 11-4.1.6(1)(B) IF EXISTING ELEMENTS,
 SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW
 CONSTRUCTION.
  
 1) LS.1/ A1.3 THE OLD PRO OFFICE 134/
 NEW RESTROOMS 131 DO NOT INDICATE
 ACCESSIBILITY TO UNITS.11-4.1.3(11)
 TOILET FACILITIES: IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON
 USE TOILET ROOM SHALL COMPLY WITH
 11-4.22.
  
 2) A1.4 MASSAGE ROOM# 147 DOORS 147 &
 149B REQUIRE 18" ON THE PULL LATCH SIDE
 OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) SHEET A1.5 ROOM 147 TV/ NAP ROOM
 3A) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3B) COMPANION SEATING:
 11-4.1.6(3)(F)(I)WHERE IT IS TECHNICALLY
 INFEASIBLE TO DISPERSE ACCESSIBLE
 EATING THROUGHOUT AN ALTERED ASSEMBLY
 AREA, ACCESSIBLE SEATING AREAS MAY BE
 CLUSTERED.EACH ACCESSIBLE SEATING AREA
 SHALL HAVE PROVISIONS FOR COMPANION
 SEATING AND SHALL BE LOCATED ON AN
 ACCESSIBLE ROUTE THAT ALSO SERVES AS A
 MEANS OF EMERGENCY EGRESS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-15 Cont ID  
Sent By jwitmer Date 2006-04-15 Time 07:42 Rev Time 2.22
Received By jwitmer Date 2006-04-14 Time 16:21 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-11 Cont ID  
Sent By jwitmer Date 2006-04-11 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2006-04-11 Time 13:30 Sent To  
Notes
2006-04-11 00:00:00ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
 ***IMPORTANT NOTICE***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SEE THE FIRST PART OF THIS REVIEW
 ARE COMMENTS FROM THE FIRST REVIEW NOT
 ADDRESSED:
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT 4B FROM THE PREVIOUS
 REVIEW,STAIRWELL DOORS SHOW NO RATING
 NOR DOES ANY STORAGE ROOM DOORS.
 RESPONSE: SEE ATTACHED LIFE SAFETY
 DRAWINGS. EXISTING STAIRWELL DOORS ARE
 FIRE RATED. STORAGE ROOM DOORS ARE NOT
 REQUIRED TO BE FIRE RATED PER FBC 704.1.2.2(4).STORAGE
 IS FOR
 NON-HAZARDOUS MATERIALS, AND DOES NOT
 EXCEED 1/3RD OF THE MAJOR OCCUPANCY
 FLOOR AREA.
  
 THE EXIT DOORS MAY BE EXISTING DOORS BUT
 WITH THE ASSEMBLY OCCUPANCY EXIT DOORS
 REQUIRE A 1 1/2 HR RATING. TABLE
 705.1.2ASSEMBLY BUILDINGS SEE NOTE (2).
 ALL EXITS AND STAIRWAYS IN GROUP A AND H OCCUPANCIES
 SHALL BE 2 HOURS WITH 1-1/2
 HOUR DOOR ASSEMBLIES.
  
 THE ABOVE CODE SECTION IS CORRECT FOR
 STORAGE ROOMS WITHIN THE OCCUPANCY
 (GROUP A, GROUP B, GROUP E, GROUP M AND
 GROUP R). THE AREAS IN QUESTION ARE
 STORAGE CLOSETS THAT ARE ON AN EXIT
 ACCESS CORRIDOR.SEE TABLE 704.2.4 FIRE RESISTANCE
 RATING OF EXIT ACCESS
 CORRIDORS, FOOTNOTE (4). IN BUILDINGS
 PROTECTED THROUGHOUT WITH AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM, EXIT ACCESS
 CORRIDOR WALLS NOT REQUIRED TO BE RATED
 SHALL, IN CONJUNCTION WITH OPENINGS
 THEREIN AND CEILINGS AT WHICH THEY
 TERMINATE, RESIST THE PASSAGE OF SMOKE.
  
 ALTHOUGH THE DOORS NEED NOT HAVE A FIRE
 RATING BECAUSE OF THE APPROVED FIRE
 SPRINKLERS, WE DO NEED TO HAVE
 INFORMATION AS TO HOW THEY WILL RESIST
 THE PASSAGE OF SMOKE.
  
 3) COMMENT# 11 FROM THE PREVIOUS REVIEW,
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 BROKE DOWN BY SHEET:
 11A) COMPLIED
  
 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR
 FLOOR SPACE REQUIRED FOR FIXTURES,
 URANIAL, DOOR REMOVED SEE 11-4.17.5 THE
 SAME LEVEL OF PRIVACY TO BE PROVIDED TO
 THE HANDICAPPED STALL AS THE REST OF THE
 RESTROOM.11-2.2 EQUIVALENT FACILITATION.
  
 11C) A1.5 DOOR# 154
  
 11D) A1.6 COMPLIED
  
 11E) A1.7 DOOR# 214
  
 11F)A1.8 COMPLIED
  
 11G) A1.9 COMPLIED
  
 4) NEW COMMENT, SHEET A1.8 MULTI PURPOSE
 ROOM 232 INDICATES A REVISION# 2
 INDICATING CHANGES TO THIS WALL. PLANS
 INDICATE THIS WALL IS A TYPE"H" WHEN
 REFERING BACK TO A8.1 FOR WALL RATINGS
 THIS WALL IS A INTERIOR FOLDING
 PARTITION. NOT A 2 HR RATED WALL?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-26 Cont ID  
Sent By jwitmer Date 2006-01-26 Time 11:58 Rev Time 4.00
Received By jwitmer Date 2006-01-26 Time 11:58 Sent To  
Notes
2006-01-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070627
 ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 ***IMPORTANT NOTICE***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SEE THE FIRST PART OF THIS REVIEW
 ARE COMMENTS FROM THE FIRST REVIEW NOT
 ADDRESSED:
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A)INDICATE BUILDING TYPE:
 601.2.1 EVERY BUILDING SHALL BE
 CLASSIFIED BY THE BUILDING OFFICIAL
 INTO ONE OF THE TYPES OF CONSTRUCTION
 AS SET FORTH IN THIS SECTION.
  
 TYPE ITYPE V
 TYPE II1-HOUR PROTECTED
 TYPE IIIUNPROTECTED
 TYPE IV TYPE VI
 1-HOUR PROTECTED1-HOUR PROTECTED
 UNPROTECTED UNPROTECTED
  
 2B) A TYPE V BUILDING IS EITHER 1-HR
 RATED OR UNPROTECTED, BUT NOT BOTH.
  
 2C)IF BUILDING IS FIRE SPRINKLERED OR
 NOT?IF FIRE SPRINKLERED PROVIDE FIRE
 SPRINKLER PLANS. BUILDING DESIGN
 INDICATES FIRE SPRINKLERED BUT NO PLANS
 HAVE BEEN SUBMITTED.
  
 2D) PROVIDE TOTAL SQ FT PER FLOOR? WERE
 AREA INCREASES TAKEN?
  
 3) PROVIDE LIFE SAFETY PLAN, ALSO
 PROVIDE THE SEATING FOR RESTARAUNTS OR
 OCCUPANT LOAD WILL BE TAKEN AS 15 NET,
 FOR PREFUNCTION AREAS 7 NET.
  
 4A) PLANS SHEET A5.1 DOOR SCHEDULE, NO
 FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE
 DOOR RATING AS "B" OR "C" SEE TABLE
 705.1.2. FOR MINUTE & HR RATING.
 M1106.4 MACHINE ROOMS REQUIRE 45 MIN
 OPENING PROTECTION.
 M1106.4 OPENING PROTECTIVES. OPENING
 PROTECTION BETWEEN THE MACHINERY
 ROOM AND OTHER OCCUPIED SPACES SHALL BE
 APPROVED, SELF-CLOSING, TIGHT-
 FITTING FIRE DOORS WITH A MINIMUM
 FIRE-RESISTANCE RATING OF 3/4 HOUR.
  
 4B) STAIRWELL DOORS SHOW NO RATING NOR
 DOES ANY STORAGE ROOMS.
  
 4C) DOOR SCHEDULE DOESN'T INDICATE
 HARDWARW GROUPINGS, MAY HAVE MORE
 COMMENTS WITH ACCESSIBILITY.
  
 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE.
 11-4.3.11.1 LOCATION AND CONSTRUCTION
 PLANS DO NOT PROVIDE FIRE SPRINKLERS,
 PROVIDE DETAILS FOR REQUIRED AREA OF
 RESCUE ASSISTANCE IF FIRE SPRINKLER
 PLANS ARE NOT PROVIDED. THIS BUILDING
 CAN NOT TAKE AREA INCREASES FOR FIRE
 SPRINKLERED BUILDINGS PER TABLE 500
 WITHOUT SPRINKLER PLANS.
  
  
 6) SHEET A8.2 PLANS INDICATE THE USE OF
 IMPACT GLAZING FOR WINDOWS & DOORS, NO
 WIND PRESSURE INFORMATION PROVIDED.
 PROVIDE ELEVATIONS WITH THE ASSOCIATED
 POSITIVE & NEGATIVE PRESSURES INTERIOR
 AND END ZONES.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN
 ONE TYPE
 B) DOORS ALL EXTERIOR DOORS BEING
 REPLACED, SOLID OR GLAZED
 C) EXTERIOR LOUVERS
 D) MULLIONS
  
 9)OK
  
 10A) IT APPEARS THAT STAIRWELL# 7 HAS
 BEEN DELETED.
 10B) NEW COMMENT 11-4.4.2 HEAD ROOM.
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS,
 AILES OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM
 (SEE FIGURE 8(A)). IF VERTICAL CLEARENCE
 OF AN AREA ADJOINING AN ACCESSIBLE ROUTE
 IS REDUCED TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY- IMPARED PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)).
  
 11)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. CLEAR 18"LOCK SIDE.
 EVEN IF DOORS ARE EXISTING,
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 BROKE DOWN BY SHEET:
 11A) A1.3 DOOR# 115, DOOR # 130- NO
 HARDWARE SCHEDULE, SEE INTERIOR SIDE
  
 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR
 FLOOR SPACE REQUIRED FOR FIXTURES,
 URANIAL
  
 11C) A1.5 DOOR# 154
  
 11D) A1.6 DOOR# 119, DOOR# 125
  
 11E) A1.7 DOOR# 214
  
 11F) A1.8 DOOR# 241
  
 11G) A1.9 DOOR# 240, DOOR# 241
  
 11H) DOOR# 200, DOOR# 203, DOOR# 204
 DOOR# 218AB,C&D, DOOR# 222C NOT LABELED
 DOOR# 224-A NOT LABELED
  
 12) OK.
  
 13) 1204.2 SURROUNDING MATERIALS. THE
 WALLS AND FLOORS OF ALL PUBLIC REST
 ROOMS SHALL BE LINED WITH NONABSORBENT
 MATERIAL TO A HEIGHT OF 4 FT (1219
 MM) ABOVE THE FLOOR.
  
 14) PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION TABLE 803.3.
  
 *********
 NEW COMMENTS
 15)A1.4 ROOM BY DOOR# 141 DOESN'T SHOW
 USEAGE?
  
 16) A1.6 ROOM# 133 INDICATES IT IS A
 STORAGE AND MECHANICAL ROOM?
  
 17) A1.6 LOCATED IN KITCHEN THERE IS A
 ROOM NO LABELED, POSSIBLY A WALK IN
 COOLER?
  
 18) A1.6 STAIRWELL# 2 FIRST FLOOR OPENS
 AND DUMPS UOT RIGHT IN FRONT OF THE
 GENERATOR. THE EXIT DISCHARGE MUST
 MAINTAIN A SAFE ROUTE TO THE RIGHT OF
 WAY.
  
 19) ALL STAIRWELLS DO NOT INDICATE
 GAURDRAILS AT THE TOP OF THE LANDING.
  
 20) A1.9 DOOR# 233 IS MISSING
 INFORMATION ON GAURDRAIL?
  
 ADDITIONAL COMMENTS MAY APPEAR SINCE A
 COMPLETE SET OF PLANS WERE NOT PROVIDED
 FOR THIS REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-26 Cont ID  
Sent By jwitmer Date 2005-08-26 Time 13:51 Rev Time 4.44
Received By jwitmer Date 2005-08-26 Time 13:19 Sent To FIRE
Notes
2005-08-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070627
 ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)INDICATE BUILDING TYPE:
 601.2.1 EVERY BUILDING SHALL BE
 CLASSIFIED BY THE BUILDING OFFICIAL
 INTO ONE OF THE TYPES OF CONSTRUCTION
 AS SET FORTH IN THIS SECTION.
  
 TYPE ITYPE V
 TYPE II1-HOUR PROTECTED
 TYPE IIIUNPROTECTED
 TYPE IV TYPE VI
 1-HOUR PROTECTED1-HOUR PROTECTED
 UNPROTECTED UNPROTECTED
 IF BUILDING IS FIRE SPRINKLERED OR NOT?
 IF FIRE SPRINKLERED PROVIDE FIRE
 SPRINKLER PLANS.
  
 3) PROVIDE LIFE SAFETY PLAN, ALSO
 PROVIDE THE SEATING FOR RESTARAUNTS OR
 OCCUPANT LOAD WILL BE TAKEN AS 15 NET,
 FOR PREFUNCTION AREAS 7 NET.
  
 4) PLANS SHEET A5.1 DOOR SCHEDULE, NO
 FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE
 DOOR RATING AS "B" OR "C" SEE TABLE
 705.1.2. FOR MINUTE & HR RATING.
 M1106.4 MACHINE ROOMS REQUIRE 45 MIN
 OPENING PROTECTION.
 M1106.4 OPENING PROTECTIVES. OPENING
 PROTECTION BETWEEN THE MACHINERY
 ROOM AND OTHER OCCUPIED SPACES SHALL BE
 APPROVED, SELF-CLOSING, TIGHT-
 FITTING FIRE DOORS WITH A MINIMUM
 FIRE-RESISTANCE RATING OF 3/4 HOUR.
  
 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE.
 11-4.3.11.1 LOCATION AND CONSTRUCTION
 PLANS DO NOT INDICATE FIRE SPRINKLERS,
 PROVIDE DETAILS FOR REQUIRED AREA OF
 RESCUE ASSISTANCE.
  
 6) SHEET A8.2 PLANS INDICATE THE USE OF
 IMPACT GLAZING FOR WINDOWS & DOORS, NO
 WIND PRESSURE INFORMATION PROVIDED.
 PROVIDE ELEVATIONS WITH THE ASSOCIATED
 POSITIVE & NEGATIVE PRESSURES INTERIOR
 AND END ZONES.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN
 ONE TYPE
 B) DOORS ALL EXTERIOR DOORS BEING
 REPLACED, SOLID OR GLAZED
 C) EXTERIOR LOUVERS
 D) MULLIONS
  
 9) MISSING A SHEETS 2 SERIES, 3 SERIES,
 4 SERIES, 6 & 7 SERIES.
  
 10) PROVIDE HANDRAIL/ GUARDRAIL DETAILS
 FOR NEW STAIRWELL# 7.
  
 11)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. CLEAR 18"LOCK SIDE.
 DOORS, 148B, 153, 172, 237, 241,& 249.
  
 12) PLANS DO NOT PROVIDE ANY INFORMATION
 AS TO WALL OR FLOOR FINISHES, PROVIDE
 INFORMATION.
  
 13) 1204.2 SURROUNDING MATERIALS. THE
 WALLS AND FLOORS OF ALL PUBLIC REST
 ROOMS SHALL BE LINED WITH NONABSORBENT
 MATERIAL TO A HEIGHT OF 4 FT (1219
 MM) ABOVE THE FLOOR.
  
 14) PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION TABLE 803.3.
  
 ADDITIONAL COMMENTS MAY APPEAR SINCE A
 COMPLETE SET OF PLANS WERE NOT PROVIDED
 FOR THIS REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 16:15 Sent To  
Notes
2008-05-04 16:15:36** DENIED REVIEW **
  
  
 1) NOTE: PLEASE KNOW THE GENERATOR WAS NOT INCLUDED IN
 THE BASE BUILDING INTERIOR RENOVATIONS AND MAY NOT BE A
 REVISION TO THE RENOVATION PERMIT.
 ALL WORK SHALL BE UNDER SEPARATE PERMITS, PLANS, FEES.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR NEW
 GENERATOR TO INCLUDE ALL REQUIRED FOR MINIMUM DESIGN
 PER NFPA-70, 101, 72, 110 AS APPLICABLE.
 PLEASE SEE FBC CHAPTER 27, NFPA-70, NFPA-110 FOR
 REQUIRED SYSTEMS.
 PLEASE SUBMIT COMPLETE LAYOUT OF THE LOCATION ON PLANS
 FOR SITE, ELEVATION IF LOCATED IN FLOOD ZONE,
 STRUCTURAL CONNECTIONS ETC
 PLEASE SEE NFPA-110, CHAPTER 6 AND 7.
  
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 2) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED GENERATOR, TRANSFER EQUIPMENT,
 FUEL TANKS ETC.
 PLEASE KNOW THE FUEL TANK WILL BE REVIEW BY OTHER
 TRADES.
 90.7, 110.3, ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW FOR INFORMATION PLEASE SEE NEC
 225.31-225.39, 702.11, 700.12B6, 70111B5. AS THE SYSTEM
 IS NOT SPECIFIED ALL THREE CODED SECTIONS WERE GIVEN.
 ALL APPLY TO THE SAME REQUIREMENT.
  
 4) NOTE: PLEASE KNOW IT IS IMPORTANT TO KNOW AS THERE
 ARE NUMEROUS ITEMS MISSING FOR CODE COMPLIANCE REVIEW,
 WHEN ALL PLANS, DOCUMENTS ETC ARE SUBMITTED FOR REVIEW
 THERE MAY VERY WELL BE NEW REVIEW COMMENTS WHICH CAN
 NOT POSSIBLY BE MADE AT THIS TIME. THE PLANS SUBMITTED
 ARE NOT COMPLETE AND IS MISSING A SUBSTANTIAL AMOUNT OF
 INFORMATION NEEDED FOR REVIEW.
  
 5) NOTE: PLEASE KNOW THE COMPLETE VALUE FOR PROPOSED
 SCOPE OF WORK SHALL BE DECLARED ON PERMIT APPLICATION.
 PLEASE KNOW WORK FOR
 WALLS/SLAB/GENERATOR/EQUIPMENT/ELECTRICAL ETC SHALL ALL
 BE INCLUDE WHETHER OR NOT ANY OF THESE ITEMS SUCH AS
 EQUIPMENT IS OWNER SUPPLIED.
 THIS INCLUDES GENERATOR, ATS, TANK, ETC.
 FBC 108.3
  
 6) NOTE: PLANS AS SUBMITTED DO NOT COORDINATE.
 FOR EXAMPLE:
 PLEASE SEE PLANS SHOWS NEW CHAIN LINK FENCE AROUND THE
 GENERATOR YET NOTES CLEARLY STATE THERE IS GOING TO BE
 A NEW BLOCK ENCLOSURE?
 PLEASE BE SURE ALL MINIMUM CLEARANCES AND VENTILATION
 PER NFPA-110 CHAPTER 7 AND NEC 110.26 ARE MET ALONG
 WITH MINIMUM REQUIRED PER MANUFACTURE.
  
 7) NOTE: WHEN NEW PLANS ARE COMPLETED PLEASE BE SURE
 THE ADDRESS OF THE PROJECT COORDINATES WITH THE APPLIED
 LOCATION.
 FOR EXAMPLE:
 PLEASE SEE PLANS CALL FOR 230 PRESIDENTIAL WAY NOT
 2300.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 11:07 Sent To  
Notes
2007-05-17 12:02:59** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SUBMIT REVISED UPDATED REVISIONS DONE
 BY THE DESIGNER OF RECORD AS REQUIRED UNDER FS 471, FAC
 61G15-23.002
 PLEASE KNOW THAT CHANGES MADE IN PENCIL ARE NOT
 PERMITTED ON ANY PLANS.
 PLEASE SEE THE REVISIONS SHALL BE CLOUDED/TRIANGLES AND
 REVISED IN TITLE BLOCKS.
 PLEASE SEE THE PLANS AS DATED ARE ALREADY ON FILE WITH
 THE CITY.
  
  
 ** PLEASE COORDINATE ALL REVISIONS AND SUBMIT AS
 REQUESTED.
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 10:18 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-12-26 Cont ID  
Sent By dpalmer Date 2006-12-26 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2006-12-26 Time 12:13 Sent To PC
Notes
2006-12-26 14:40:41** UNSAT ***
  
 1) NOTE: PLEASE COMPLETE RISER WITH NEW CONDUIT SIZE
 BEING STUBBED OUT FOR FUTURE GENERATOR. PLEASE SEE AS
 THE CONDUCTOR SIZES FOR FUTURE AND FOR EDP ARE NOT
 SHOWN ON PLANS AS SUBMITTED, UNABLE TO VERIFY AT THIS
 TIME.
 240.4, 310.16, TABLE(S) CHAPTER 9.
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS ON THE BOTTOM
 PART OF DPB SHOW CONNECTED LOAD AT 221 KVA AND DEMAND
 LOAD THE SAME AT 221 KVA, YET THE DEMAND LOAD ON THE
 MDP IS OF THE DEMAND LOAD OF 209KVA.
 PLEASE CORRELATE.
 FBC 104.1.2
 ADMIN SECTION.
  
 3) NOTE: PLEASEKNOW BASED ON AS MANY REVISION ARE
 BEING DONE TO THIS JOB AND SCOPE OF WORK INVOLVED,
 PLEASE KNOW IF THE SERVICE ENTRANCE CONDUCTORS WHICH
 HAVE BEEN SHOWN AS EXISTING TO THE EXISTING 2500A MCB
 MDP ARE RE-PULLED OR TOUCHED IN ANY WAY, THEY WILL BE
 REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SEE 240.4(C)
 WHICH HAS ALWAYS REQUIRED CONDUCTORS FEEDING DEVICES
 RATED OVER 800A?S TO MEET OR EXCEED THE RATING THAT
 DEVICE.
 PLEASE KNOW THIS WAS NOT A CHANGE IN ANY CODE OVER THE
 PAST 15 YRS AND EVEN IF EXISTING, IF THEY ARE RE-PULLED
 AS NOTED FOR ANY REASON OR CHANGED, THEY WILL BE
 REQUIRED TO MEET THE 2500A BREAKER OR BREAKER WOULD BE
 REQUIRED TO BE BROUGHT DOWN TO 2000A OCP.
 90.4
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-10-18 Cont ID  
Sent By dpalmer Date 2006-10-18 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2006-10-16 Time 21:02 Sent To PC
Notes
2006-10-18 11:26:59RISER TO BE REVISED AS SPECS INDICATE A 800A ATS AND
 THE PLANS INDICATE 500A'S.
2006-10-16 21:02:10CALLED AND LEFT MESSAGE FOR MR GREG LEWIS TO CALL, AS
 NO SPECS/ MANUFACTURE CUT SHEETS WERE SUBMITTED FOR THE
 ATS AS PREVIOUSLY REQUESTED.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 16:50 Sent To FIRE
Notes
2006-09-30 00:00:00*** UNSAT FOR REV #6 **
  
 1) NOTE: PLEASE SEE "PLAN/REVISION FORM
 AS BEING SUBMITTED AND FILLED OUT BY
 CONTRACTOR IS FROM "2001" PLEASE OBTAIN
 NEW FORM ONLINE OR IN OUR OFFICE AS THE
 FEES REPRESENTED ON THESE OLD FORMS ARE
 NO LONGER VALID.
  
 2) NOTE: PLEASE SEE SCOPE OF WORK AT THE
 LOCATION OF THIS JOB WAS ORIGINALLY
 SUBMITTED AS 1.1 MIL AND DUE TO CHANGES
 IN SCOPE AND WORK BEING PERFORMED,
 PLEASE ADJUST THE APPLIED VALUE FOR
 SCOPE OF WORK BASED ON ACTUAL VALUE.
 IT HAS COME TO THE ATTENTION OF THIS
 OFFICE THE VALUE HAS EXCEEDED THE OLD
 VALUE SUBSTANTIALLY. PLEASE ADJUSTOR
 PROVIDE ALL SIGNED CONTRACTS FOR ALL
 TRADES AND SCOPES AS STATED IN THE FBC
 108.3(2004) OR 106.3.5 (2001) .
  
 3) NOTE: PLEASE SEE REVISED RISER IS NOW
 INDICATING A NEW ATS WHICH WAS NOT PART
 OF THE ORIGINAL SCOPE INFACT THE SYSTEM
 WAS STATED AS BEING REMOVED. PLEASE
 SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR
 THIS EQUIPMENT FOR REVIEW. PLEASE ALSO
 KNOW, ANY PERMIT FOR A GENERATOR WILL BE
 REQUIRED TO BE SUBMITTED SEPARATELY AND
 WILL ALSO REQUIRE THE SAME SPECS.
 110.3, 90.7,
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE CORRELATE RISER WITH
 PANEL FOR NEW FEED TO PANEL "N" FROM
 "DPB". PLEASE SEE OCP.
 106.1.2
  
 5) NOTE: PLEASE ALSO KNOW, THE PANEL "N"
 COULD NOT BE LOCATED ON POWER PLANS
 SUBMITTED. THIS REVIEWER HAS LOOKED
 THREE TIMES, AS RISER SHOWS THIS LOCATE
 DON THE FIRST FLR. PLEASE INFORM WHERE
 THIS IS IN A REPSONSE LTR, OR PLEASE
 INDICATE ON PLANS.
 106.1.2
  
 6) NOTE: PLEASE LABEL AND SHOW ALL PANEL
 SIZE ON BOTH RISERS ON 5.1.1, AND 5.2.
 AS OTHERS ARE SHOWN . (100A, 300A ETC ).
  
 7) NOTE: PLEASE SEE PLANS INDICATE A
 "SERVER ROOM"? IS THIS INDEED AN "IT"
 ROOM?
 PLEASE SEE CHAPTER 2 OF NFPA-75 FOR
 CLASSIFICATION REQUIREMENTS AND IF AN IT
 ROOM PLEASE SEE ALL REQUIREMENTS IN
 NFPA-75 AND SEE NEC 645.
  
 *** PLEASE KNOW, PLANS ARE BEING ROUTED
 TO FIRE MARSHAL'S OFFICE FOR FIRE
 REVIEW, PLEASE BE AWARE IF LIGHTING
 PLANS ARE OK WITH FIRE REVIEW, THEN
 THOSE SHEETS WILL BE STAMPED, HOWEVER
 RISER , PANEL SCHEDULE, AND POWER PLANS
 NEED TO BE REVISED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status N Date 2006-09-21 Cont ID  
Sent By dpalmer Date 2006-09-21 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2006-09-21 Time 20:56 Sent To  
Notes
2006-09-21 00:00:00PLANS SUBMITTED FOR REVISIONS OF "A"
 SHEETS ONLY CONTAIN "REFLECTED CEILING"
 PLANS FOR ELECTRICAL. NO ELEC APPLIES.
 PLEASE SEE PREVIOUS REVIEW DATED 9/9/06
 AS THE ELECTRICAL CONTRACTOR CALLED NOT
 TO REVIEW ELECTRICAL REVISIONS #6, AS
 THEY WERE BEING CHNAGED OUT. TO DATE, NO
 NEW ELECTRICAL PLANS AHVE BEEN
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 18:45 Sent To PC
Notes
2006-09-09 00:00:00** NOTE **
  
  
 1( RECEIVED CALL FROM ELECTRICAL
 CONTRACTORNOT TO REVIEW PLANS/
 REVISIONS SUBMITTED (#6).
 PLANS ARE BEING PLACED OUTFRONT AND FEE
 PAID FOR REVISIONS WILL CARRY OVER TO
 THE NEXT SET OF REVISIONS FOR THE SAME
 AMOUNT OF SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 11:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-07-06 Cont ID  
Sent By dpalmer Date 2006-07-06 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2006-07-06 Time 19:39 Sent To  
Notes
2006-07-06 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE SEE "ID" PLANS
 SUBMITTED. PLEASE SEE NUMEROUS SHEETS
 ARE INDEED SEALED PHOTO-COPIES OF THE
 DESIGNER'S SIGNATURE WHICH IS REQUIRED
 TO BE ORIGINAL UNDER FS 481.221
 PLEASE SEE ABOVE STATUE WHICH ALSO
 REQUIRES THE DESIGN PROFESSIONAL TO DATE
 SAID PLANS WHEN SIGNING AND SEALING.
 PLEASE SEE SOME SHEETS DO CONTAIN AN
 ORIGINAL SIGNATURE, AND SOME APPEAR TO
 SHOW SOME SORT OF "INITIAL"??
 PLEASE KNOW, ALL SHEET SHALL CONTAIN THE
 ORIGINAL LEGAL SIGNATURE OF THE DESIGN
 PROFESSIONAL.
  
 2) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON SAID TITLE BLOCKS
 FOR THE FIRM AS SHOWN AS REQUIRED PER
 FAC 61G1-16.004, AND FS 481.219(1)(2)
 ETC.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, MISSING PRINTED
 NAME AND LICENSE NUMBER.
  
 3) NOTE: PLEASE SEE THAT THE ID PLANS DO
 NOT CORRELATE ELECTRICALLY WITH THE
 PLANS SUBMITTED FOR REVIEW FROM THE
 ELECTRICAL DESIGN PROFESSIONAL.
 PLEASE CORRELATE AND SUBMIT.
 PLEASE SEE LIGHTING PLANS SUBMITTED BY
 THE ID.
  
 ** PLEASE SEE COMMENTS #1 AND #2 DO NOT
 APPLY TO THE ELECTRICAL ENGINEER OF
 RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-04 Cont ID  
Sent By dpalmer Date 2006-04-04 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 16:00 Sent To I
Notes
2006-04-04 00:00:00PLANS REDLINED:
  
  
 E-4.1,
 THE "KNOX BOX" LOCATION IS TO VERIFIED
 AND INSTALLED AT A LOCATION DETERMINED
 BY THE FIRE MARSHAL'S OFFICE.
 THIS LOCATION SHALL CONTAIN ALL NEEDED
 ACCESS KEYS, INCLUDING MAIN ELECTRICAL
 ROOM.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-28 Cont ID  
Sent By dpalmer Date 2005-12-28 Time 20:15 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 21:12 Sent To  
Notes
2005-12-28 00:00:00********** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE THERE ARE NOTES FROM
 ORIGINAL REVIEW WHICH STILL NEED TO BE
 ADDRESSED.
 ** PLEASE SEE SOME NEW NOTES DUE TO
 CHANGES MADE TO PLANS, AND ITEMS BEING
 REMOVED FROM SAID DRAWINGS.
  
 ** PLEASE SEE FIRST PART OF NOTES BELOW
 HAVE BEEN TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
  
 1)NOTE: NOTE #1 NO,
 PLEASE SEE MISSING INFORMATION REQUIRED
 ON TITLE BLOCK FOR ENGINEERING FIRM.
 PLEASE SEE 61G15-23.002 FOR MISSING
 PRINTED NAME AND PRINTED LICENSE # FOR
 ENGINEER.
 PLEASE SEE ARCHITECTS TITLE BLOCK FOR
 ALL SHEETS SHALL ALSO CONTAIN THE
 PRINTED NAME AND LICENSE # FOR ARCH.
 61G1-16.004
  
 THIS SEE THIS IS REQUIRED FOR ALL SHEETS
 AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: NOTE #2 OK.
  
  
 3)NOTE: NOTE#3 NO, PLEASE SEE MOST
 CIRCUITING IS NOW SHOWN ON PLANS,
 HOWEVER SOME STILL APPEAR TO BE MISSING.
 PLEASE SEE NEW NOTES PERTAINING TO SOME
 ERRORS IN CIRUITING AND CORRELATION WITH
 PANEL SCHEDULES ETC.
 **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
 PLEASE SEE ALL CONTROL WIRING FOR
 LIGHTING PLANS.
 PLEASE SEE LIGHTING PLANS DO NOT SEEM TO
 BE COMPLETE AT THIS TIME?
 PLEASE SEE SOME AREAS DO NOT INDICATE
 ANY LIGHTING? WOMENS RESTROOM?
 PLEASE SEE THIS MAINLY SEEMS TO BE
 MISSING FROM LIGHTING PLANS.
 **PLEASE ALSO SEE CIRCUTING FOR A/C
 SYSTEMS, PANELS TEND TO BE INDICATED ,
 HOWEVER NOT THE CIRCUITING.
  
 4)NOTE: OK, HOWEVER SEE NOTE #5, AS
 AREAS NEED TO BE VERIFIED FOR EGREE ETC.
 SEE NEW NOTES>
 **
 PLEASE SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS. THE BRANCH CIRCUIT
 FEEDING THE UNIT EQUIPMENT SHALL BE THE
 SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 5)NOTE: NOTE #5, NO, INFACT ALL OF THE
 AREAS AND ROOM DESIGNATIONSWHICH WERE
 SHOWN ON ORIGINAL PLANS HAVE NOW BEEN
 REMOVED MAKING IT IMPOSSIBLE TO REVIEW
 SOME THINGS FOR CODE COMPLIANCE. PLEASE
 SEE NEW COMMENTS.
 **
 PLEASE INCLUDE ROOM/AREA
 DESIGNATIONS ON PLANS. THIS SHOULD BE ON
 ALL SHEETS.
 215.5
  
 6)NOTE: NOTE #6 OK.
  
  
 7)NOTE: NOTE #7 OK,NO, AS THIS AREA HAS
 NOW BEEN REMOVEDFROM PLANS AND THE KE
 PLANS NOW MENTIONS CIRCUITING.
 PLEASE SEE KE PLANS WHICH MENTIONS THESE
 ARE PRELIMINARY PLANS AND SHOULD NOT BE
 USED??
 **
 PLEASE SHOW ALL CIRCUITING ON
 KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE
 CORRELATE THIS WITH EQUIPMENT SCHEDULE
 SUBMITTED AND PANEL SCHEDULES.
  
 8)NOTE: NOTE #8 NO,IT IS UNCLEAR WHERE
 ANY CHANGES HAVE BEEN MADE FOR THIS.
 PLEASE SEE NOTE #5 MENTIONS GFI FOR
 UTILITY OUTLETS?
 **
 PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: NOTE #9 NO?? SEE NOTES WITH
 RESPECT TO ROOM AND AREA DESIGNATIONS
 BEING REMOVED.
 **
 PLEASE SHOW AND INDICATE ELEVATOR
 EQUIPMENT ROOM. PLEASE SEE
 STATE ELEVATOR CODE , NO OTHER EQUIPMENT
 UNLESS PART OF THE DESIGNATED ELEVATOR
 EQUIPMENT SHALL BE IN ELEVATOR ROOMS.
 PLEASE SEE 620.23,620.24, PLEASE VERIFY
 AND SHOW IF THESE ARE TO BE NEW OR
 EXISTING.
  
 10)NOTE: NOTE #10 NO, SAME AS PREVIOUS
 NOTES. PLEASE ALSO SEE NFPA-101 7.8.1.3,
 7.9.2 WHICH MAY ALSO BE USED IN
 REFERENCE IN THESE AREA NEED ING BATTERY
 BACK UP FIXTURES.
 **
 PLEASE SEE 700.16 FOR
 ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR
 RMS.
  
 11)NOTE: NOTE # 11, NO , UNCLEAR AS A
 "KEYED NOTE" ON RISER (NOTE #1 ON 5.1
 MENTIONS PANEL "D" WAS NOT ABLE TO BE
 LOCATED FOR WHERE FEED COMES FROM,,ETC.
 PLEASE KNOW, IT WAS DICUSSED WITH
 ENGINEER OF RECORD THIS WOULD BE A
 "PROVISO" IN WHICH THE INFORMATION WOULD
 BE REQUIRED BEFORE ANY INSPECTIONS WERE
 MADE.
 PLEASE KNOW AT THAT TIME IT WAS
 IMPERATIVE TO START PROJECT SO THIS WAS
 AGREED. PLEASE SEE RISER STILL SHOWS
 THIS PANEL "D" COMING FROM PANEL "M"?
 WAS IT DISCOVERED IN THE "DEMO WORK"
 THAT THIS PANEL IS FED FROM "M" AND
 REASON WHY IT IS STILL SHOWN FROM "M"?
  
 THE FIRST REVIEW WAS DONE IN JULY 05 AND
 THE AMOUNT OF TIME AND DEMO WORK SINCE
 SHOULD REVEALED THIS INFORMATION.
  
  
 12)NOTE: NOTE #12 NO?? COULD NOT LOCATE.
 **
 PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR ARE TO BE SHOWN
 @125%
 215.3,230.42 ETC,
  
  
  
 ****************************************
 THE FOLLOWING COMMENT HAS TO DO WITH
 ELECTRICAL RISER DIAGRAM,ONE-LINE
 DIAGRAM AND PANEL SCHEDULES.
 ****************************************
  
 13)NOTE: NOTE #13 NO, MOST OF THESE
 ITEMS WERE CORRECTED HOWEVER PLEASE SEE
 TC SHOWN AS 70A AND 100A ON ONE-LINE AND
 RISER.
 PLEASE SEE A NEW PANEL BR1 IS SHOWNON
 ONE-LINE, RISER, PANEL "LL" AND NOTED IN
 NOTES, HOWEVER NO PANEL SCHEDULE,
 CIRCUITING SUBMITTED TO VERIFY.
 **
  
 PLEASE CORRELATE ALL PANELS ON
 ONELINE, RISER AND PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE THERE ARE TOO NUMEROUS ITEMS
 WHICH DO NOT MATCH UP WITH EACH OTHER.
 PLEASE SEE AMERAGES OF PANELS SHOWN
 DIFFERENTLY ON EACH, SEE SOME SHOWN AS
 225A AND 300A ETC.
 PLEASE SEE SOME PANELS BEING SHOWN BEING
 FED FROM"DPB", YET OTHER SHEETS SHOW
 THESE PANELS FROM "DPA" AND YET PANEL
 SCHEDULES FOR THESE SHOW SOMETHING
 ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA
 AND RISER SHOWS FROM "DPB" ETC.
 PLEASE SEE SOME PANEL SHOWN AS ONE SIZE
 MLO, YET INDICATE ON PANEL SCHEULE SHOWS
 A DIFFERENT SIZE.?
 PLEASE SEE PANELS LABELED AS ONE THING
 ON ONE-LINE ANDSOEMTHING ELSE ON RISER
 DIAGRAM AND PANEL SCHEDULE? KDP, KDP1,
 600A/ 500A??? ETC,,
 PLEASE SEE POOL RM PANEL, PANEL N ETC.
 PLEASE SEE ONE LINE SHOWS DISCONNECT
 FROM WW MDP TO KDP/KDP1, YET RISER DOES
 NOT SHOW THIS?
 PLEASE SEE SOME PANELS SHOWN AS MLO, YET
 ALSO SHOWS HAVING A MAIN?
 PLEASE INCLUDE ALL INFORMATION FOR ALL
 DISCONNECTS ON RISER.
 PLEASE LABEL ALL PANELS,DISC'S, MDP ETC
 ON RISER.
  
 ********************************
 NEW NOTES DUE TO CHANGES AND INFORMATION
 BEING CHANGED AND/OR SUBMITTED.
  
 1)NOTE: PLEASE SEE ORIGINAL NOTES WITH
 RESPECT TO SHOWING ALL CIRCUITING,PLEASE
 SEE MOST CIRCUITING IS NOW SHOWN,
 HOWEVER PLEASE SEE SOME OF THE FOLLOWING
 WHICH DO NOT SEEM TO CORRELATE ETC.
  
 *PLEASE SEE CIRCUITING ON PANEL "N",
 MOST A/C EQUIPMENT IS NOTED AS BEING
 3-POLE ITEMS, HOWEVER CIRCUITING ON
 PANEL SCHEDULES, SHOWS ITEMS TAKING THE
 SPACE AND NUMBERED AS 2-POLE?
  
 *PLEASE SEEE-2.1A, SHOWS 86 AHU-9 TO
 DPB-1, YET DPB, IS BLANK AT THIS
 LOCATION.
  
 *PLEASE SEE E-2.1.C UNIT LABELED AS
 EDH-1, PANEL "N", YET PANEL "N" DOES NOT
 SHOW THIS. ALTHOUGH, THERE SEEMS TO BE A
 UNIT WHICH HAS THE SAME KW RATING ETC,
 HOWEVER IT IS LABELED"DEH", IS THIS
 THE SAME AND ONLY A MISPRINT?
  
 *PLEASE SEE E-2.1.C WHICH SHOWS 5AHU-7
 TO "N", YET THIS COULD NOT BE LOCATED ON
 "N"?
  
 *PLEASE SEE E-2.2A, 86AHU-5 TO D-7,9,11,
 NEW OR EXSITING. ?AS MANY NEW AREAS
 ARE NOW SHOWN SHADED, WHICH WERE NOT ON
 ORIGINAL PLANS?
  
 2)NOTE: PLEASE SEE NOTES ON PLANS
 CONTAIN NUMERICAL NOTES TO SEE 4.1 FOR
 PANELS ETC, HOWEVER THIS ROOMS SEEMS TO
 BE MISSING IDENTIFICATION ETC ETC.
  
 3)NOTE: PLEASE SEE PLANS NOW HAVE NOTES
 ADDED FOR SOME ITEMS. PLEASE KNOW, NOTES
 BEING ADDED TO PLANS DO NOT ALLEAVIATE
 THE DESIGN PROFESSIONAL FROM PROVIDING
 THE TECHNICAL INFORMATION NEEDED. PLEASE
 SEE NOTE WHICH MENTIONS TO SEE ARCHITECT
 TO DETERMINE HEIGHTS ETC. PLEASE KNOW,
 THESE THINGS SHOULD BE ON SAID PLANS.
  
 4)NOTE: PLEASE SEE PANEL DPB WHICH SHOWS
 THE DE-RATED LOAD FROM PANEL "N", WHICH
 SEEMS TO HAVE BEEN DER-RATED ONCE AGAIN
 FOR DPB CALCS???
 PLEASE CLARIFY THIS.
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND REPEAT COMMENTS.
 PLEASE KNOW, IF PLANS COME BACK WITH ANY
 OF THE SAME COMMENT SFROM THE FIRST
 REVIEWS NOT ADDRESSED FOR CODE
 COMPLIANCE, THE STATE STATUES, REQUIES A
 4X FEE BE ASSESSED FOR THE PLAN REVIEW
 PORTION OF THE BASE PERMIT FEE. (30% X4)
 TO THE DESIGN PROFESSIONAL FOR REPEAT
 COMMENTS.
 PLEASE KNOW, IT IS STRONGLY SUGGESTED A
 MEETING BE HELD TO GO OVER COMMENTS AS
 NOT TO HAVE THIS IMPLEMENTED.
 THIS AMOUNT WOULD COME TO $13,800.00.
 PLEASE KNOW THE 10% RE-SUB WILL BE DUE
 WHEN PLANS COME BACK IN FOR THIRD
 REVIEW.
 ** PLEASE KNOW, ONE COPY OF THIS
 SUBMITTIAL OF ELECTRICAL PLANS WILL BE
 RETAINED AND PLACED WITH PLANS FROM
 ORIGINAL REVIEW WHICH WERE ALSO
 REETAINED.
  
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 **PLEASE GO THROUGH ALL PLANS PANELS,
 DISCONNECTS ETC AND CORRELATE.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS FROM OTHER
 TRADES SHOULD BE SUBMITTED FOR
 REFERENCE. THIS WILL NOT BE REQUIRED OF
 VOIDED ELECTRICAL SHEETS AS ONE SET IS
 ALREADY RETAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-27 00:00:00REVIEW WILL GO INTO "F" STATUS, REVIEW
 IN PROGRESS.
 NOTES TO FOLLOW.
2005-12-26 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.
 NO RESPONSE LETTER(S) FROM DESIGN
 PROFESSIONALS SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 06:19 Rev Time 7.00
Received By dpalmer Date 2005-07-27 Time 16:12 Sent To  
Notes
2005-07-28 00:00:00********** UNSAT ************
  
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ENGINEERING
 FIRM. PLEASE SEE 61G15-23.002 FOR
 MISSING PRINTED NAME AND PRINTED LICENSE
 # FOR ENGINEER.
 PLEASE SEE ARCHITECTS TITLE BLOCK FOR
 ALL SHEETS SHALL ALSO CONTAIN THE
 PRINTED NAME AND LICENSE # FOR ARCH.
 61G1-16.004
  
 THIS SEE THIS IS REQUIRED FOR ALL SHEETS
 AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE E1.A, APPEARS SOME
 IMAGES ARE "SHIFTED" OR "DOUBLE"?
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
 PLEASE SEE ALL CONTROL WIRING FOR
 LIGHTING PLANS.
 PLEASE SEE LIGHTING PLANS DO NOT SEEM TO
 BE COMPLETE AT THIS TIME? PLEASE SEE
 MISSING "KEYED NOTES" ETC.
 PLEASE SEE SOME AREAS DO NOT INDICATE
 ANY LIGHTING? WOMENS RESTROOM?
 PLEASE SEE THIS MAINLY SEEMS TO BE
 MISSING FROM LIGHTING PLANS.
 PLEASE ALSO SEE CIRCUTING FOR A/C
 SYSTEMS, PANELS TEND TO BE INDICATED ,
 HOWEVER NOT THE CIRCUITING.
  
 4)NOTE:PLEASE SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 5)NOTE: PLEASE INCLUDE ROOM/AREA
 DESIGNATIONS ON PLANS. THIS SHOULD BE ON
 ALL SHEETS.
 215.5
  
 6)NOTE:PLEASE SEE SOME PANELS SEEM TO
 INDICATE A COUNTERTOP IN FRONT OF
 ELECTRICAL PANELS?? PLEASE SEE BAR
 PANELS, E2.1.A? PLEASE SEE OUTLINED
 AREAS ON PLANS.?? F, G, GA, J,,,ETC.
  
 7)NOTE: PLEASE SHOW ALL CIRCUITING ON
 KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE
 CORRELATE THIS WITH EQUIPMENT SCHEDULE
 SUBMITTED AND PANEL SCHEDULES.
  
 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 9)NOTE: PLEASE SHOW AND INDICATE
 ELEVATOR EQUIPMENT ROMM. PLEASE SEE
 STATE ELEVATOR CODE , NO OTHER EQUIPMENT
 UNLESS PART OF THE DESIGNATED ELEVATOR
 EQUIPMENT SHALL BE IN ELEVATOR ROOMS.
 PLEASE SEE 620.23,620.24, PLEASE VERIFY
 AND SHOW IF THESE ARE TO BE NEW OR
 EXISTING.
  
 10)NOTE: PLEASE SEE 700.16 FOR
 ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR
 RMS.
  
 11)NOTE: PLEASE SEE RISER MENTIONS ? FOR
 PANEL "D". THIS INFORMATION IS REQUIRED
 AT THIS TIME.
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR ARE TO BE SHOWN
 @125%
 215.3,230.42 ETC,
  
  
  
 ****************************************
 THE FOLLOWING COMMENT HAS TO DO WITH
 ELECTRICAL RISER DIAGRAM,ONE-LINE
 DIAGRAM AND PANEL SCHEDULES.
 ****************************************
  
 13)NOTE: PLEASE CORRELATE ALL PANELS ON
 ONELINE, RISER AND PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE THERE ARE TOO NUMEROUS ITEMS
 WHICH DO NOT MATCH UP WITH EACH OTHER.
 PLEASE SEE AMERAGES OF PANELS SHOWN
 DIFFERENTLY ON EACH, SEE SOME SHOWN AS
 225A AND 300A ETC.
 PLEASE SEE SOME PANELS BEING SHOWN BEING
 FED FROM"DPB", YET OTHER SHEETS SHOW
 THESE PANELS FROM "DPA" AND YET PANEL
 SCHEDULES FOR THESE SHOW SOMETHING
 ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA
 AND RISER SHOWS FROM "DPB" ETC.
 PLEASE SEE SOME PANEL SHOWN AS ONE SIZE
 MLO, YET INDICATE ON PANEL SCHEULE SHOWS
 A DIFFERENT SIZE.?
 PLEASE SEE PANELS LABELED AS ONE THING
 ON ONE-LINE ANDSOEMTHING ELSE ON RISER
 DIAGRAM AND PANEL SCHEDULE? KDP, KDP1,
 600A/ 500A??? ETC,,
 PLEASE SEE POOL RM PANEL, PANEL N ETC.
 PLEASE SEE ONE LINE SHOWS DISCONNECT
 FROM WW MDP TO KDP/KDP1, YET RISER DOES
 NOT SHOW THIS?
 PLEASE SEE SOME PANELS SHOWN AS MLO, YET
 ALSO SHOWS HAVING A MAIN?
 PLEASE INCLUDE ALL INFORMATION FOR ALL
 DISCONNECTS ON RISER.
 PLEASE LABEL ALL PANELS,DISC'S, MDP ETC
 ON RISER.
  
 PLEASE GO THROUGH ALL PANELS,DISCONNECTS
 ETC AND CORRELATE.
  
 PLEASE KNOW, DUE THE NUMBER OF ITEMS ON
 ELECTRICAL PLANS, ONE COPY OF ELECTRICAL
 PLANSHAVE BEEN REMOVED FROM ONE SET.
 THIS IS BEING HELD FOR REFERENCE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS FROM OTHER
 TRADES SHOULD BE SUBMITTED FOR
 REFERENCE. THIS WILL NOT BE REQUIRED OF
 VOIDED ELECTRICAL SHEETS AS ONE SET IS
 ALREADY RETAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-27 00:00:00IN ELEC FOR REVIEW.
 PLANS WILL BE IN FAILED STATUS,NOTES TO
 FOLLOW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 14:28 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 14:27 Sent To  
Notes
2008-05-27 14:38:14***DENIED***
  
 PLEASE SEE ELECTRICAL COMMENTS:
  
 1) SEPARATE PLANS AND PERMIT REQUIRED FOR GENERATOR.
  
 2) PLEASE INCLUDE SPECIFICATION SHEETS FOR GENERATOR
 AND ALL ASSOCIATED EQUIPMENT WITH SUBMITTAL.
  
 3) INCLUDE INFORMATION REGARDING FUEL STORAGE TANK
 CONSTRUCTION, CAPACITY AND LOCATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-10-17 Cont ID  
Sent By mawillia Date 2006-10-17 Time 12:55 Rev Time 0.00
Received By mawillia Date 2006-10-17 Time 12:55 Sent To  
Notes
2006-10-17 12:58:16*****APPROVED*****
  
  
  
  
 **REVISED ELECTRICAL PLAN SHEETS REVIEWED.**

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-09-22 Cont ID  
Sent By mwennerg Date 2006-09-22 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2006-09-22 Time 11:11 Sent To  
Notes
2006-09-22 00:00:00REVISION DATED 7/21/06.
  
 1) IN ADDITION TO THE REVISED SHEETS
 INDICATED IN THE INDEX OF DRAWINGS, IT
 APPEARS THAT LS.2 AND FP SHEETS HAVE
 ALSO BEEN REVISED. ANY REVISIONS TO THE
 FIRE SPRINKLER SYSTEM SHALL BE REFLECTED
 ON THE SHOP DRAWINGS ONCE THE FIRE
 SPRINKLER PERMIT HAS BEEN ISSUED.
  
 2) NO FIRE SPRINKLER COVERAGE IS NOTED
 IN BATHROOMS. PLEASE BE SURE TO
 ILLUSTRATE ON SEPARATE SHOP DRAWINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-07-14 Cont ID  
Sent By mwennerg Date 2006-07-14 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2006-07-14 Time 13:30 Sent To  
Notes
2006-07-14 00:00:00REVISION DATED 6/30/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-04-05 Cont ID  
Sent By mwennerg Date 2006-04-05 Time 13:26 Rev Time 0.00
Received By mwennerg Date 2006-04-05 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-01-04 Cont ID  
Sent By mcarsill Date 2006-01-04 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2006-01-04 Time 11:19 Sent To  
Notes
2006-01-04 00:00:001. ALL EXIT DOORS SHALL BE PROPERLY
 IDENTIFIED BY ILLUMINATED EXIT SIGNS.
  
 2. SUFFICIENT EMERGENCY LIGHTS SHALL BE
 PROVIDED THROUGHOUT THE CLUBHOUSE.
  
 3. IT APPEARS THAT NO PREVIOUS COMMENTS
 FROM FIRE RESCUE WERE ADDRESSED.
  
 4. THE RELOCATION OF THE FIRE ALARM
 CONTROL PANEL, DIALER, AND NEW EQUIPMENT
 REQUIRES A PERMIT.
  
 5. ANY PENETRATIONS IN REQUIRED FIRE
 WALS MUST BE PROPERLY SEALED IN AN
 APPROVED MANNER.
  
 6. THE RELOCATION OF THE FIRE ALARM
 PANEL AND DIALER SHOULD BE SCHEDULED TO
 PREVENT LONG PERIODS OF WITHOUT
 PROTECTION.
  
 7. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE REQUIRED HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM.
  
 8. COULD NOT LOCATE ANY INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9. ANY NEW SOFFITS SHALL NOT INTERFERE
 WITH ANY REQUIRED FIRE SPRINKLER HEADS.
  
 10. DOOR SCHEDULE ON PAGE A5.1 DOES NOT
 DISPLAY ANY FIRE RATING.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By mwennerg Date 2005-08-30 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2005-08-30 Time 13:02 Sent To  
Notes
2005-08-30 00:00:00******DENIED******
  
 1) CONSTRUCTION ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) THE DOOR SWINGS AT 1ST FLOOR
 MECHANICAL ROOM TO NEW LADIES CARD ROOM,
 AND MECHANICAL STORAGE NEXT TO MAIN
 ELECTRICAL ROOM, OBSTRUCT THE HALLWAY BY
 GREATER THAN 1/2 THE WIDTH.
  
 3) PLEASE NOTE THAT STAIR IDENTIFICATION
 DOESN'T APPEAR CONSISTENT THROUGHOUT
 PLANS.
  
 4) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 5) PLEASE INCLUDE LIFE SAFETY PLAN TO
 DETERMINE REQUIRED MEANS OF EGRESS AND
 PATH OF TRAVEL.
  
 6) IT WOULD APPEAR THAT WHEN EXITING
 FROM THE RESTAURANT TO THE CORRIDOR
 LEADING TO STAIR #1, THE DOOR MAY
 INTERFERE WITH THE DOOR TO THE MECH/AC
 ROOM. PLEASE CLARIFY ARRANGEMENT.
  
 7) PLEASE INDICATE THE OCCUPANT LOADS
 FOR THE RESTAURANT AND FITNESS CLUB.
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 9) NOTE THAT DOORS SERVING AREAS OF
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF TRAVEL.
  
 10) DOORS IN AREAS SERVING OCCUPANT LOAD
 GREATER THAN 100, SHALL HAVE PANIC
 HARDWARE WITH UL LISTED CLOSERS.
  
 11) PLEASE ILLUSTRATE FIRE RATINGS FOR
 APPROPRIATE DOORS.
  
 12) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 13) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR HOOD AND SUPPRESSION
 SYSTEMS IF APPLICABLE AND PART OF THIS
 JOB SCOPE.
  
 14) MONITORING OF SPRINKLER SYSTEM TO BE
 UL CERTIFIED FOR CENTRAL STATION
 SERVICE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 12 Status P Date 2007-12-07 Cont ID  
Sent By kstevens Date 2007-12-07 Time 11:19 Rev Time 0.00
Received By kstevens Date 2007-12-07 Time 11:19 Sent To  
Notes
2007-12-07 11:19:59REVISION OK-SHEET P5.1 GAS REVISION

Review Stop G GAS REVIEW
Rev No 10 Status F Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 05:48 Rev Time 0.00
Received By kstevens Date 2007-09-12 Time 18:31 Sent To  
Notes
2007-09-15 05:49:10GAS REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--MANY LENGTHS MISSING FOR MANY CUT
 SECTIONS.--INDICATE THE LENGHTS OF PIPE FROM THE
 REGULATORS TO THE GAS APPLIANCES AND ALL SECTIONS IN
 BETWEEN. ALSO CHECK RED LINE SECTIONS ON ONE SHEET
 SUBMITTED FOR REVISION.
  
 2. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.--A UNION IS REQUIRED
 DOWNSTREAM OF ALL SHUT OFF VALVES FOR REGULATORS AND/OR
 SOLENOID VALVES. PLEASE INDICATE THE REQUIRED UNIONS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.--ALL PIPE SIZES ARE NOT
 INDICATED ON THE REVISION. SHOW ALL PIPE SIZES.
  
 4. INDICATE THE MAXIMUM BTUS ALLOWED FOR FUTURE FIXTURE
 E13 PER TABLE 402.4(2) FOR TOTAL DEVELOPED LENGTH FROM
 THE REGULATOR TO THE MOST REMOTE GAS APPLIANCE, (E13).
  
  
 5. SHT P5.1 BUILDING GAS REQUIREMENTS TABLE/SCHEDULE.
 RECHECK ADDITION AFTER LEG #2 THRU LEG #5. SUBTOTALS &
 TOTAL INCORRECT. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 9 Status P Date 2007-03-20 Cont ID  
Sent By mperson Date 2007-03-20 Time 13:23 Rev Time 0.55
Received By mperson Date 2007-03-20 Time 13:23 Sent To PC
Notes
2007-03-20 13:29:31REVISION:**OK** SHEET P5.1 GAS ISOMETRIC RISER DIAGRAM
 AND APPLIANCE SUBMITTALS. GAS APPLIANCE SUBMITTALS WITH
 PERMIT APPLICATION.
  
 ****************PROVISO****************
 A} EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.

Review Stop G GAS REVIEW
Rev No 8 Status F Date 2007-03-01 Cont ID  
Sent By mperson Date 2007-03-01 Time 15:41 Rev Time 0.00
Received By mperson Date 2007-02-28 Time 15:41 Sent To PC
Notes
2007-02-28 16:59:30REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS; THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE. PLEASE NOTE ON THE
 SHEET P5.1 THERE IS APPROVED PLUMBING SANITARY AND
 WATER RISER DIAGRAMS DATED 4-22-06, BUT ON THE
 SUBMITTED REVISION OF SHEET P5.1 THERE IS NO INDICATION
 OF THESE SANITARY AND WATER RISER DIAGRAMS. IF IT IS
 IMPOSSIBLE TO FIT BOTH THE GAS AND THE PLUMBING ON THE
 SAME SHEET IT IS SUGGESTED A NEW SHEET BE DESIGNATED
 FOR THE GAS REVISION P5.1A. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 THE FOLLOWING ARE FROM THE PREVIOUS REVIEW COMMENTS:
  
 1. NO/OK** SHEET P5.1 NEW GAS SERVICE RISER: PLEASE
 SUBMIT ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS
 CODE SECTION 402.4.
 NOTE: THE SUBMITTED MANUFACTURER SHEETS DO VERIFY THE
 BTU LOADS BUT HOWEVER NOT ALL SHEETS INDICATE THAT THE
 APPLIANCES ARELISTED. PLEASE REFERENCE THE RED CIRCLE
 ON ITEMS #7 AND #8 INDICATING THAT THOSE APPLIANCES ARE
 LISTED. THE FOLLOWING IS A LIST OF THE APPLIANCES AND
 GAS EQUIPMENT INDICATING WHAT IS REQUIRED.
 A} #1- FRYER; NEED LISTING
 B} #2 FRYER; NEED LISTING
 C} #3- BROILER; NEED LISTING
 D} #4-GRIDDLE; NEED LISTING
 E} #5-CONVECTION OVEN; NEED LISTING
 F} #6-RANGE; NEED LISTING
 G} #7-SALAMANDER BROILER; OK
 H} #8-PIZZA OVEN; OK
 I} #9-STEAMER; NEED LISTING
 J} MP REGULATOR (2 PSI TO 0.5 PSI)- MANUFACTURER CUT
 SHEET REQUIRED INDICATING MAKE, MODEL NUMBER, AND THIRD
 PARTY LISTING.
 K} EMERGENCY HOOD SHUT DOWN VALVE- MANUFACTURER CUT
 SHEETS REQUIRED INDICATING MAKE, MODEL NUMBER, AND
 THIRD PARTY LISTING.
  
 2. OK
  
 3. OK
  
 4. NO**SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED REVISION STILL DOES NOT INDICATE
 ALL CORRESPONDING LENGTHS IN LEG #5. THE ONLY LENGTH
 INDICATED IS 22'. THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE
 WHICH IS A STEAMER IN THE NEW KITCHEN IS REQUIRED FOR
 GAS PLAN REVIEW TO VERIFY CODE COMPLIANCE.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. TYPE OF GAS, (LP OR NATURAL)
 NOTE: ON THE APPROVED SHEET P5-1 THE GAS TYPE IS
 CLEARLY INDICATED AS NATURAL GAS IN THE GAS SIZING
 TABLE CALCULATIONS, BUT ON THE RESUBMITTED REVISION
 THERE IS NO GAS TYPE INDICATED. THERE IS A FBC-2004
 FUEL GAS TABLE 402.4(3) REFERENCE WHICH IS FOR NATURAL
 GAS BUT THERE IS NO CLEAR INDICATION OF GAS TYPE. IT
 CAN NOT BE ASSUMED THAT THE GAS TYPE IS NATURAL GAS.
 PLEASE INDICATE THE GAS TYPE ON THE RESUBMITTED
 REVISION.
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 NOTE: ON THE APPROVED SHEET P5-1 IT CLEARLY INDICATES
 THE THE EMERGENCY HOOD SHUT OFF VALVE, BUT ON THE
 RESUBMITTED REVISION THIS VALVE IS NOT INDICATED. THE
 ONLY VALVES INDICATED ON THE RESUBMITTED REVISION ARE A
 SHUT OFF VALVE AND A MP REGULATOR (2 PSI TO 0.5 PSI).
 PLEASE CLEARLY INDICATE AND IDENTIFY THE SHUT OFF
 VALVE, MP REGULATOR, AND ADD THE EMERGENCY SHUT OFF
 VALVE ON THE RESUBMITTED REVISION.
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 7 Status F Date 2007-01-08 Cont ID  
Sent By mperson Date 2007-01-08 Time 13:02 Rev Time 0.00
Received By mperson Date 2007-01-08 Time 13:02 Sent To PC
Notes
2007-01-08 14:10:11GAS REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.SHEET P5.1 NEW GAS SERVICE RISER: PLEASE SUBMIT ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS CODE SECTION
 402.4.
 NOTE:NEED MANUFACTURER CUT SHEETS FOR ALL NEW GAS
 EQUIPMENT INCLUDING THE NEW MP REGULATOR (2PSI TO
 0.5PSI) FOR THE NEW KITCHEN. THE SUBMITTED MANUFACTURER
 CUT SHEETS SHALL SHOW A LISTING, MODEL NUMBER, AND BTU
 LOAD. MANUFACTURER SHEETS SHALL REFLECT THE BTU LOADS
 INDICATED ON THE NEW GAS RISER DIAGRAM. IT IS NOTED ON
 THE REVISION SUBMITTAL FORM THAT THE ARCHITECT E-MAILED
 THE EQUIPMENT INFORMATION TO K.STEVENS. IN CHECKING
 WITH K.STEVENS HE HAS NO RECORD OF THIS INFOMATION.
 PLEASE REMEMBER WHEN ITEMS ARE E-MAILED THEY GO THROUGH
 A MIS SCREENING PROCESS AND MAY TAKE WEEKS TO CLEAR
 THAT PROCESS. IT IS BETTER TO SUBMIT TWO COPIES OF
 MANUFACTURER CUT SHEETS WITH THE RESUBMITTAL TO ADVOID
 E-MAIL SCREENING PROBLEMS.
  
 THE FOLLOWING ARE NEW COMMENTS THAT ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 2. SHEET P5.1 NEW GAS SERVICE RISER: THE EXISTING BTU
 LOAD AND THE GAS SIZING CALCULATION TABLE INDICATING
 THE EXISTING BTU LOADS DO NOT MATCH. ON THE NEW GAS
 SERVICE RISER THE EXISTING INDICATES THREE DRYERS AT
 165,000 BTU/HR EACH WITH A TOTAL OF 495,000 BTU/HR, THE
 TWO EXISTING KITCHEN MANIFOLDS INDICATE 825,000 BTU/HR
 WITH A TOTAL OF 1,650,000 BTU/HR, AND THE THREE
 EXISTING BOILERS ARE INDICATED AT 250,000 BTU/HR WITH A
 TOTAL OF 750,000 BTU/HR. THE ADDED TOTAL SUM OF THE
 EXISTINGBTU'S IS 2,895,000. THE GAS CALCULATION TABLE
 INDICATES AN EXISTING BTU OF 2,070,000 WITH A
 DIFFERENCE OF 825,000 BTU'S BETWEEN THE TWO. THE TOTAL
 BTU'S OF THE EXISTING AND NEW SHOULD BE 3,861,000 NOT
 THE INDICATED 3,036,000. PLEASE CORRECT AND CORRELATE
 THE BTU'S ON THE RESUBMITTAL.
  
 3. SHEET P5.1 NEW GAS RISER: PLEASE CLARIFY IF THIS
 SYMBOL IS THE POINT OF DELIVERY (METER) ON THE
 RESUBMITTAL.
  
 4. WHAT IS THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING
 FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE IN THE
 NEW KITCHEN. THE ONLY INDICATED LENGTH IS 22'. TO
 ADVOID CONFUSSION ALL CUT SECTIONS AND CORRESPONDING
 LENGTHS SHOULD BE INDICATED ON THE NEW GAS SERVICE
 RISER FOR THE NEW KITCHEN FOR THE RESUBMITTAL.
  
 ***************IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2006-12-02 Cont ID  
Sent By kstevens Date 2006-12-02 Time 17:56 Rev Time 0.00
Received By kstevens Date 2006-12-02 Time 17:56 Sent To  
Notes
2006-12-02 17:57:14REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM
 PREVIOUS REVIEW)
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR
 ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU
 DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE.
 ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS
 RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE
 INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE
 SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS
 APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU
 LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS
 INDICATED ON THE GAS RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2006-11-04 Cont ID  
Sent By kstevens Date 2006-11-04 Time 14:27 Rev Time 0.00
Received By kstevens Date 2006-11-04 Time 14:27 Sent To  
Notes
2006-11-04 14:28:42REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). EXPLAIN
 THE VENT LINES CONNECTING TO THE GAS PIPES. - INDICATE
 THE MATERIAL FOR THE VENTS, (SHALL BE NONCOMBUSTABLE).
 - MORE INFORMATION IS REQUIRED ON THE SQUARE BOXES
 LOCATED IN VARIOUS LOCATIONS IN THE RISER DIAGRAM. IF
 THEY ARE REGULATORS, THEY MUST BE LOCATED DOWNSTREAM OF
 THE SHUT OFF VALVES. SUBMIT MANUF. SPECIFICATIONS FOR
 THE REGULATORS. SPECIFY THE MODEL NUMBER. REGULATORS
 SHALL SHOW A LISTING IN SPECIFICATIONS SHEETS. ALSO
 SUBMIT THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW
 GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES
 IS ALL BUTITEM #4 THE GRIDDLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-09-28 Cont ID  
Sent By kstevens Date 2006-09-28 Time 14:22 Rev Time 0.00
Received By kstevens Date 2006-09-28 Time 14:22 Sent To  
Notes
2006-09-28 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. REVISION REQUIRED FOR THE GAS PIPING
 SYSTEM. IF NEW GAS APPLIANCES, NEW
 MANUF. SPECIFICATION SHEETS WILL BE
 REQUIRED. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-08-28 Cont ID  
Sent By kstevens Date 2006-08-28 Time 12:55 Rev Time 0.00
Received By kstevens Date 2006-08-28 Time 12:55 Sent To  
Notes
2006-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A. SHT P5.1 GAS RISER DIAGRAM REVISION.
 MORE INFORMATION REQUIRED. THIS IS A
 CHANGE OF GAS APPLIANCES, PIPING LAYOUT,
 BTU AMOUNT, AND DEVELOPED LENGTH. PLEASE
 SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - THIS IS
 SHOWN AS BOTH 150' AND 190'. BY
 INDICATING THE LENGTH OF ALL CUT
 SECTIONS FROM THE METER THROUGH OUT THE
 SYSTEM, TOTAL DEVELOPED LENGTH CAN BE
 VERIFIED.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 - THERE
 IS MANY NEW GAS APPIANCES ON THIS
 REVISION. ALL MANUF. SPECIFICATIONS
 SHALL BE SUBMITTED TO VERIFY BTU'S SO
 INDICATE MODELS AND EACH APPLIANCE SHALL
 SHOW LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-15 Cont ID  
Sent By pschmitz Date 2006-07-15 Time 06:47 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time 06:47 Sent To  
Notes
2006-07-15 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT
 SEE PREVIOUS PROVISO NOTES BELOW
 DATED 4-26-06 BY KEN STEVENS
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P5.2 GAS
 ISOMETRIC FOR ALL RED LINE CORRECTIONS.
  
 REVISION AS SOON AS POSSIBLY TO AVOID A
 DELAY IN CERTIFICATE OF AUTHROIZAION.
  
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P5.2 GAS
 ISOMETRIC FOR ALL RED LINE CORRECTIONS.
  
 REVISION AS SOON AS POSSIBLY TO AVOID A
 DELAY IN CERTIFICATE OF AUTHROIZAION.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-04-22 Cont ID  
Sent By kstevens Date 2006-04-22 Time 21:55 Rev Time 0.00
Received By kstevens Date 2006-04-22 Time 21:55 Sent To  
Notes
2006-04-22 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P5.2 GAS
 ISOMETRIC FOR ALL RED LINE CORRECTIONS.
  
 REVISION AS SOON AS POSSIBLY TO AVOID A
 DELAY IN CERTIFICATE OF AUTHROIZAION.

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 08:27 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 08:27 Sent To  
Notes
2008-05-02 08:30:42TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 14:41 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 14:41 Sent To M
Notes
2007-10-24 14:41:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 09:04 Sent To P
Notes
2007-08-30 09:04:39TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 16:51 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 16:51 Sent To B
Notes
2007-06-12 16:51:32TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 09:03 Sent To P
Notes
2007-05-23 09:04:10TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 15:35 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 15:35 Sent To  
Notes
2007-05-16 10:32:42TO "COMM" BD#31
2007-05-07 15:36:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 11:49 Sent To B
Notes
2007-04-27 11:49:36TO "JWITMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-03-08 Cont ID  
Sent By adarroug Date 2007-03-08 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-03-08 Time 15:52 Sent To P
Notes
2007-03-08 15:52:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 14:35 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 14:35 Sent To E
Notes
2007-02-06 14:36:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 14:33 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 14:33 Sent To P
Notes
2007-02-06 14:34:05TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 16:08 Sent To M
Notes
2006-12-20 16:09:10TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 16:05 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 16:05 Sent To E
Notes
2006-12-20 16:05:57TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 16:02 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 16:02 Sent To P
Notes
2006-12-20 16:02:37TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 17:41 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 17:41 Sent To P
Notes
2006-12-16 17:41:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 12:26 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 12:26 Sent To  
Notes
2006-11-28 14:36:01REVISIONS SENT TO PLUMBING 11-28-06
2006-11-21 12:27:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 18:17 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 18:17 Sent To E
Notes
2006-10-12 18:18:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 15:36 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 15:36 Sent To  
Notes
2006-10-26 08:31:59TO "COMM" BD#45
2006-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-25 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-09-25 Time 15:55 Sent To E
Notes
2006-09-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-07 Cont ID  
Sent By adarroug Date 2006-09-07 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-09-07 Time 15:50 Sent To E
Notes
2006-09-07 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 13:18 Sent To  
Notes
2006-09-12 00:00:00TO "COMM" BD#8
2006-09-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 09:41 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 09:41 Sent To M
Notes
2006-09-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 11:00 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 11:00 Sent To E
Notes
2006-08-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 10:22 Sent To P
Notes
2006-08-09 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 15:50 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#15
2006-06-23 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-22 Cont ID  
Sent By kstevens Date 2006-04-22 Time 21:56 Rev Time 0.00
Received By kstevens Date 2006-04-14 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 20:25 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 20:25 Sent To  
Notes
2006-03-21 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-10 Time 17:29 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 17:29 Sent To  
Notes
2005-12-05 00:00:00TO "COMM" BD#2/PLANS ON RACK
2005-11-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-30 Cont ID  
Sent By mwennerg Date 2005-08-30 Time 13:22 Rev Time 0.00
Received By mwennerg Date 2005-07-18 Time 09:13 Sent To  
Notes
2005-07-20 00:00:00TO "COMM" BD#21/PLANS ON "COMM" RACK
2005-07-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2008-05-05 Cont ID  
Sent By tgordon Date 2008-05-05 Time 14:14 Rev Time 0.25
Received By tgordon Date 2008-05-05 Time 14:14 Sent To  
Notes
2008-05-05 14:20:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** ADD GENERATOR TO PLANS AS REVISION. **
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES.
  
 2) SHOW ON PLAN THE FUEL CAPACITY FOR THE DIESEL
 STORAGE TANK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2007-10-29 Cont ID  
Sent By tgordon Date 2007-10-29 Time 10:23 Rev Time 2.00
Received By tgordon Date 2007-10-29 Time 10:23 Sent To  
Notes
2007-10-29 10:24:07REVISION TO MECH. PLANS PAGE M1.1A AND M1.1C.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status F Date 2007-05-21 Cont ID  
Sent By tgordon Date 2007-05-21 Time 16:21 Rev Time 2.00
Received By tgordon Date 2007-05-21 Time 16:21 Sent To  
Notes
2007-05-21 16:48:11REVISION TO MECHANICAL PLANS PAGES M1.1A, M1.1B, M1.1C,
 AND M8.2.
 *** DENIED ***
 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT.
 FIRM'S NAME. SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2) SEE YELLOW HIGH LIGHTS ON PAGE M1.1A NORTH ENTRY
 LOBBY #129 SHOWS TWO WALLS THAT ARE NOT ON THE BUILDING
 PLANS PAGE A1.1, THE WALLS ARE STOPPING AIR FROM
 RETURNING TO THE AIR HANDLER, PLEASE CORRECT AND IF
 NEEDED REVISE BUILDING PLANS.
  
 3) SEE YELLOW HIGH LIGHT ON PAGE M1.1B CORRIDOR #140
 SHOWS TWO RETURN AIR GRILLS IN CORRIDOR, IF THE WALLS
 ARE RATED THAN THE AIR CAN NOT RETURN TO THE AIR
 HANDLER, PLEASE CORRECT. ALSO SEE THE SUPPLY AIR GRILL
 SHOWS THE FIRE DAMPER AT THE GRILL NOT AT THE FIRE
 WALL, PLEASE CORRECT.
  
 4) SEE YELLOW HIGH LIGHT ON PAGE M1.1C RESTROOMS #114
 AND 115 AND MANICURE ROOM #121 EXHAUST FAN GRILLS NEED
 TO SHOW THE CFM'S. ALSO SEE EMPLOYEE RESTROOM #104
 EXHAUST FAN GRILL NEEDS TO SHOW CFM'S IT APPEARS TO BE
 300 CFM'S AT THIS TIME, PLEASE CORRECT.
  
 5 PAGE M8.2 ONLY NEEDS THE TITLE BLOCK CORRECTED AS THE
 OTHER PAGES DO (SEE NOTE #1).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2006-12-28 Cont ID  
Sent By pkrauss Date 2006-12-28 Time 08:24 Rev Time 0.00
Received By pkrauss Date 2006-12-28 Time 08:02 Sent To  
Notes
2006-12-28 08:27:30REVISED SHEETS:
 M1.1B - LS.1 WAS ALSO REVISED (RATED CEILING INSTEAD OF
 PARTITIONS), M1.1D & MP1.1B.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-11-28 Cont ID  
Sent By pkrauss Date 2006-11-28 Time 13:14 Rev Time 0.00
Received By pkrauss Date 2006-11-28 Time 13:14 Sent To  
Notes
2006-11-28 13:33:52REVSION TO PLAN SHEET M1.1A, M1.1B, M1.1C & M1.1D -
 PLEASE NOTE THE FOLLOWING:
  
 PLAN SHEET M1.1A, M1.1C & M1.1D - APPROVED
  
 PLAN SHEET M1.1B - APPROVED WITH THE EXCEPTION TO THE
 36" X 8" TRANSFER DUCT FROM ROOM #139 TO RM #146.THIS
 COORIDOR IS FIRE RATED THEREFORE A FIRE DAMPER WILL BE
 REQUIRED WHERE DUCT PENETRATES EACH ROOM.SHOULD THE
 CEILING BE RATED FIRE DAMPERS WILL NOT BE REQUIRED BUT
 THE LIFE SAFETY AND ARCHITECTURAL PLANS NEED TO BE
 REVISED TO REFLECT THE CHANGE.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-10-18 Cont ID  
Sent By pkrauss Date 2006-10-18 Time 13:39 Rev Time 0.00
Received By pkrauss Date 2006-10-18 Time 11:04 Sent To  
Notes
2006-10-18 13:50:30PROVISO:
 1.PLAN SHEET M1.1A , M1.1C, AND M1.1D NOTE 15 & M1.1
 NOTE 16, INDICATE ALL FLEXIBLE EXHAUST DUCTING SHALL BE
 HEAVY GAUGE CORREGATED STEEL DUCTWORK. PER 2004 FMC
 501.4 EXHAUST DUCTS SHALL BE OF METAL & SUCH
 CONSTRUCTION SHALL COMPLY WITH CHAPTER 6.
  
 2.PLEASE PROVIDE MANUFACTURE SUBMITTAL DATA ONTHE
 CORREGATED STEEL DUCT.
  
 3.PLEASE NOTE, CORRIGATED DUCT CAN NOT BE UTILIZED
 WITH THE DRYER EXHAUST SHALL HAVE A SMOOTH INTERIOR
 FINISH PER 2004 FMC 504.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2006-10-18 Cont ID  
Sent By pkrauss Date 2006-10-18 Time 11:04 Rev Time 0.00
Received By pkrauss Date 2006-10-11 Time 19:23 Sent To  
Notes
2006-10-11 19:47:47NO MECHANICAL PAGES INCLUDED IN THESE REVISIONS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-09-18 Cont ID  
Sent By pkrauss Date 2006-09-12 Time 10:09 Rev Time 0.00
Received By pkrauss Date 2006-09-11 Time 15:26 Sent To  
Notes
2006-09-12 00:00:00THE FOLLOWING PLAN SHEETS ARE DENIED:
 M1.1A, M1.1B, & M1.1C
 1.PLANS ARE MISSING FIRE DAMPERS AT
 WALL PENETRATIONS.PER 2001 FMC 607.6,
 SPECIFIC LOATION FOR EACH FIRE DAMPER,
 ACCESS DOOR, CEILING DAMPER OR SMOKE
 DAMPER SHALL BE PROPERLY IDENTIFIED ON
 THE BUILDING PLAN.
  
 PLEASE CONTACT PATTY KRAUSS AT
 (561)805-6719 OR E-MAIL [email protected],
 FOR COORDINATION MEETING.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-07-28 Cont ID  
Sent By pkrauss Date 2006-07-28 Time 11:18 Rev Time 0.00
Received By pkrauss Date 2006-07-28 Time 10:31 Sent To  
Notes
2006-07-28 00:00:00REVISIONS TO PLAN SHEETS M1.1A, M1.1B,
 M1.1D.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-04-10 Cont ID  
Sent By pkrauss Date 2006-04-10 Time 15:04 Rev Time 0.00
Received By pkrauss Date 2006-04-10 Time 11:47 Sent To  
Notes
2006-04-10 00:00:00PROVISO:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION FOR
 THE HOOD. PLANS SUBMITTED BY CAPTIVE AIR
 INDICATES SUPPRESSION FOR THE HOOD.
 PLEASE PROVIDE ADDITIONAL PLANS FOR THE
 GREASE DUCT.INDICATE DUCT LAYOUT,
 MATERIAL AND CLEARANCE TO COMBUSTIBLES.
 INDICATE EXHAUST TERMINTATION PROVIDE
 DISTANCE FROM PROPERTY LINES AND FRESH
 AIR INTAKES SHOW COMPLIANCE WITH NFPA 96
 & 2001 FMC 506.
  
 PLEASE PROVIDE MANUFACTURERS CUT SHEETS
 & INSTALLATION INTRUCTIONS WITH
 MECHANICAL PERMIT FOR THE WALK-IN
 COOLER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-17 Cont ID  
Sent By pkrauss Date 2006-01-17 Time 13:19 Rev Time 0.00
Received By pkrauss Date 2006-01-13 Time 14:13 Sent To  
Notes
2006-01-17 00:00:00DENIED:
 THE FOLLOWING COMMENT FROM REVIEW DATED
 8-2-05 BY HAROLD MOSER WAS NOT
 ADDRESSED:
  
 COMMENT 3:PLEASE PROVIDE INFORMATION
 ON THE PIPING MATERIAL TO BE INSTALLED
 FOR NEW CHILLED WATER LINES AS INDICATED
 ON PLAN SHEET M1.1AKEYED NOTE #4.
  
 PLEASE PROVIDE DETAIL FOR NEW CHILLED
 WATER LINES.INDICATE ANY NEW SHUT
 OFF/ISOLATION, CONTROL/BYPASS VALVES
 THAT MAY BE INSTALLED.
  
 **************NEW COMMENT************
 1.PLEASE PROVIDE ENGINEER'S LICENCE
 NUMBER ON PLANS PER FAC61G15-23.002.
  
 2.PLAN SHEET M8.3 A/C UNIT SCHEDULE
 THE NOTE DOES NOT INDICATE AHU-13 HAVING
 A DUCT SMOKE DETECTOR.SYSTEMS THAT ARE
 GREATER THAN 2,000 CFM ARE REQUIRED TO
 HAVE FAN SHUTDOWN BY DUCT SMOKE
 DETECTORS WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 PER 2004 FMC 606.2.1.
  
 3.ADDITIONAL PERMITS REQUIRED FOR
 WALK-IN COOLERS/FREEZERS, HOODS AND FIRE
 SUPPRESSION.PLEASE PROVIDE PLANS AND
 MANUFACTURER'S SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By hmoser Date 2005-08-02 Time 16:58 Rev Time 0.00
Received By hmoser Date 2005-08-02 Time 16:17 Sent To  
Notes
2005-08-02 00:00:00PLAN DENIED
 1) PLEASE REFRE TO SECTION 601.4
 BALANCED RETURN AIR FBC(M)
 2) PLEASE REFER TO SECTION 601.4 #3
 HABITABLE ROOMS ONLEY.LAUNDRY AND
 BATHROOMS DO NOT REQUIRE RETURN AIR.
 3) PLEASE PROVIDE TYPE OF METERALS USED
 FOR CHILLED WATER PIPING OR
 CONNECTIONS.IF IT IS PVC PLEASE PROVIDE
 A COPEY OF THE TESTING FROM ASTND 1785
 ASTMD 2241.
 4) REFER TO NOTE #3 PAGE M1.1C O/A AIR
 MUST BE 10FT.FROM DOORS,WINDOWS OR
 EXHAUST.
 5) REFER TO NOTE #6 PAGE M1.1C WALK IN
 COOLERS AND FREEZERS,REFRIGERATION
 EQUIPMENT SUBMIT UNDER SEPARATE PERMIT.
 6) PLEASE SHOW CFM. OF EXISTING
 BATHROOM EXHAUST ON MECHANICAL PLANS.
 7) PLEASE REFER TO SECTION 602.2.1
 FBC(M) METERALS EXPOSER IN PLENUMS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 13 Status F Date 2007-06-19 Cont ID  
Sent By kstevens Date 2007-06-19 Time 10:09 Rev Time 0.00
Received By kstevens Date 2007-06-19 Time 10:09 Sent To  
Notes
2007-06-19 10:11:57REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P5.3 VENT REQUIRED FOR THE URINALS. SECTION
 901.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-06-19 Cont ID  
Sent By kstevens Date 2007-06-19 Time 10:08 Rev Time 0.00
Received By kstevens Date 2007-06-19 Time 10:08 Sent To  
Notes
2007-06-19 10:09:16REVISIONS OK--SHTS P1.1A, P1.1C, P5.2

Review Stop P PLUMBING
Rev No 11 Status P Date 2007-01-08 Cont ID  
Sent By mperson Date 2007-01-08 Time 16:25 Rev Time 0.00
Received By mperson Date 2007-01-05 Time 16:24 Sent To  
Notes
2007-01-05 16:36:56REVISION: SHEETS P1.1A, P1.1C, P5.2, AND P5.3
  
 ****************PROVISO
 SHEET P5.3:WATER HAMMER ARRESTORS PER FBC-2004
 PLUMBING, SECTION 604.9
  
 ****************PROVISO
 SHEET P5.3:AIR GAP REQUIRED PER FBC-2004 PLUMBING,
 SECTIONS 504.6, 504.7.1, AND 802.1.3
  

Review Stop P PLUMBING
Rev No 10 Status F Date 2006-12-02 Cont ID  
Sent By kstevens Date 2006-12-02 Time 16:37 Rev Time 0.00
Received By kstevens Date 2006-12-02 Time 16:37 Sent To  
Notes
2006-12-02 17:54:56REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHTS P1.1A, P1.1C & P5.2 VENTING FOR FLOOR DRAINS
 AND FLOOR SINKS. EVERY DRY VENT SHALL RISE VERTICALLY
 TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION
 905.4. VENTS BELOW THE SLAB ARE NOT APPROVED.- FLOOR
 DRAIN AND FLOOR SINK IN THE KITCHEN VESTIBULE AREA
 SHALL CONNECT TO THE VENTED BRANCH LINE SEPARATELY, OR
 SHALL BE VENTED.SECTION 912.2.2. -FLOOR DRAIN
 UPSTREAM OF FIXTURE 55 ON THE GREASE DRAINAGE SYSTEM
 SHOWS A VENT ON THE FLOOR PLAN THAT IS NOT SHOWN ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION 104.2.1. -
 MAXIMUM 3 FU ON A 2" COMBINATION WASTE AND VENT BRANCH
 LINE. TABLE 912.3.CHECK BRANCH LINES WITH TWO OR MORE
 FLOOR DRAINS AND/OR FLOOR SINKS WITH A 2" BRANCH LINE.
  
 2. (FROM PREVIOUS REVIEW) SUBMIT A DETAIL FOR THE NEW
 TOILET ROOMS SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.18, 11-4.19 AND 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, THIS HAS NOT BEEN ADDRESSED.
  
 3. SHTS P1.1C & P5.2 FIXTURE 1.1 IS NOT VENTED AS SHOWN
 ON THE FLOOR PLAN, NOR ON THE RISER DIAGRAM. PLEASE
 IDENTIFY FIXTURE 1.1. SECTIONS 905.4 AND 104.2.1.
  
 4. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM
 PREVIOUS REVIEW)
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR
 ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU
 DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE.
 ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS
 RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE
 INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE
 SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS
 APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU
 LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS
 INDICATED ON THE GAS RISER DIAGRAM.
  
 5. SHT P5.2 WATER RISER DIAGRAMS INDICATE WATER HAMMER
 ARRESTORS INSTALLED UPSIDE DOWN. PLEASE SUBMIT MANUF.
 SPECIFICATION/INSTALLATION REQUIREMENTS FOR THE WATER
 HAMMER ARRESTORS INDICATING APPROVED INSTALLATION
 METHOD. SECTION 104.2.1. ALL WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE SHT
 P5.3 DETAIL 2 WATER RISER DIAGRAM).
  
 6. SHT P5.3 DETAIL 1 SANT RISER DIAGRAM. HLAV IN WOMENS
 TOILET ROOM IS NOT VENTED AS SHOWN. ("S" TRAP). SEE RED
 LINE EXAMPLE FOR CORRECTION. SECTIONS 901.2.1 & 1002.3.
 - FLOOR DRAIN NOT VENTED PROPERLY. SECTION 905.4.
  
 7. PLEASE INDICATE WHAT THE LARGE AMOUNT OF SHEETS
 SUBMITTED WITH PLANS ARE FOR. IF THESE ARE SUBMITTALS,
 SUBMIT THEM SEPARATELY. IF THEY WERE TO REPRESENT THE
 GAS APPLIANCE MANUF. SPECIFICATIONS REQUIRED, THEY ARE
 NOT APPROVED. THE MANUF. SHEETS FOR THE GAS APPLIANCES
 SHALL SHOW A LISTING, THE MODEL NUMBER INDICATED AND
 THE BTU LOAD INDICATED THAT REFLECTS THE GAS RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS
 TO HELP EXPEDITE THE REVISIONS. (THIS WAS NOT ADDRESS
 WHEN THESE REVISIONS WERE SUBMITTED).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 9 Status F Date 2006-11-04 Cont ID  
Sent By kstevens Date 2006-11-04 Time 11:05 Rev Time 0.00
Received By kstevens Date 2006-11-04 Time 11:05 Sent To  
Notes
2006-11-04 14:08:04REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1.1A SHOWS A URINAL IN THE WOMEN'S TOILET ROOM.
 SUBMIT AN APPROVED MANUF. SUBMITTAL FOR THE URINAL.
  
 2. SHT P1.1A SUBMIT A DETAIL FOR THE NEW TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18,
 11-4.19, & 11-4.22 WITH ALL SUBSECTIONS.
  
 3. SHTS P1.1A & P1.1C ALL INDIRECT WASTE SHALL BE
 DRAINED INTO A FLOOR SINK, OR A HUB DRAIN. SECTIONS
 802.3 & 802.3.2. THE TRAP SIZE FOR THESE FIXTURES IS 2"
 AND THE PIPING LAYOUT SHOW 1" AND 1-1/2" PIPING TO
 THESE FIXTURES. TABLE 709.1. PLEASE SHOW MINIMUM SIZES
 TO INDIRECT WASTE RECEPTORS. IDENTIFY ALL INDIRECT
 WASTE RECEPTORS AND SHOW ALL PIPING FROM THE FIXTURES
 TO THE INDIRECT WASTE RECEPTORS. SECTION 104.2.1.
  
 4. SHT P1.1AIDENTIFY THE RISER UPSTREAM OF ITEM #26
 INDIRECT WASTE RECEPTOR IN THE GREASE SYSTEM. IDENTIFY
 THE WATER RISER ON THE COLD WATER LINE PRIOR TO ITEM
 #55. INDICATE WHAT "WWH" WATER LINE SUPPLIES. THIS IS
 NOT SHOWN ON THE ABBREVIATIONS. ALSO IT DOES NOT
 CONNECT TO ANYTHING. PLEASE CLARIFY.SECTION 104.2.1.
  
 5. SHT P1.1A SHEET NOTES 2,3,4 REVISED, BUT ARE NOT
 CLOUDED. COLD WATER LOOP SUPPLYING ITEMS 191,196,55, &
 57 DOES NOT CONNECT TO THE WATER MAIN.PLEASE CLARIFY.
 SECTION 104.2.1.
  
 6. SHT P1.1B CLOUD AND NUMBER REVISIONS. (SEE KEYED
 NOTES 10,11,13 AND SHEET NOTES 2 & 3.CLEANOUTS IN THE
 WALLS TO BE ACCESSIBLE PER SECTION 708.10. INDICATE HOW
 THIS WILL BE COMPLIED WITH.
  
 7. SHT P1.1C WAREWASHER TO CONNECT TO THE SANITARY
 SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL UTILITY CODE
 90-124(7)(B).
  
 8. SHTS P1.1A & P1.1CALL SINKS IN THE FOOD
 PREPARATION AREA SHALL BE DRAINED INTO AN INDIRECT
 WASTE RECEPTOR. SECTION 802.1.
  
 9. SHT P1.1D CLOUD AND NUMBER REVISIONS. (SHEET NOTES &
 NUMBER 1).
  
 10. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2).
 EXPLAIN THE VENT LINES CONNECTING TO THE GAS PIPES. -
 INDICATE THE MATERIAL FOR THE VENTS, (SHALL BE
 NONCOMBUSTABLE). - MORE INFORMATION IS REQUIRED ON THE
 SQUARE BOXES LOCATED IN VARIOUS LOCATIONS IN THE RISER
 DIAGRAM. IF THEY ARE REGULATORS, THEY MUST BE LOCATED
 DOWNSTREAM OF THE SHUT OFF VALVES. SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS. SPECIFY THE MODEL
 NUMBER. REGULATORS SHALL SHOW A LISTING IN
 SPECIFICATIONS SHEETS. ALSO SUBMIT THE FOLLOWING
 INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW
 GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES
 IS ALL BUTITEM #4 THE GRIDDLE.
  
 11. SHT P5.2 DETAIL #1 THE GREASE RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE RISER AND
 THE FLOOR PLAN.
  
 12. SHT P5.2 DETAIL #2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ALSO DROPS ARE SHOWN AS RISERS,
 AND FULL OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED PIPES. SECTIONS 104.2.1, 606.1(4). WATER
 HAMMER ARRESTORS ARE REQUIRED FOR ALL QUICK CLOSING
 VALVES. (WASH MACHINES, ICE MAKERS, DISH WASHERS
 ETC.).
  
 13. SHT P5.2DETAIL #3 RISER DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.LAVS ARE
 NOT VENTED AS SHOWN, AND THE URINAL IS NOT VENTED AS
 SHOWN. SECTION 901.2.1. (SEE RED LINE EXAMPLE ON ONE
 SEET OF PLAN.
  
 14. SHT P5.3 DETAIL #1 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. (SEE RED LINE MARKING IN ONE
 SET OF PLANS). SECTION 104.2.1.
  
 15. SHT P5.3 DETAIL #2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. NO WATER SHOWN TO THE STEAM
 GENERATOR, OR TO THE MASSAGE SINK. THERE ARE EXTRA LAVS
 AND EXTRA FIXTURES PAST THE W/C'S NOT SHOWN ON THE
 FLOOR PLAN. PIPE ROUTING DIFFERENT. PLEASE CLARIFY.
 PLEASE LABEL THE HOT AND COLD WATER PIPES. SECTION
 104.2.1.
  
 16. SHT P5.3,DETAILS 3 & 4 ARE NOT SHOWN ON SHT
 P1.1A. PLEASE CLARIFY. SECTION 104.2.1. - DETAIL 5 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE FLOOR PLAN
 AND RISER DIAGRAM. SECTION 104.2.1.
  
 17. SHEETS FS1 THRU FS5 SHALL BE SIGNED/SEALED/DATED,
 AND THE CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE
 TITLE BLOCK OF THE ENGINEER. FAC G1G15-23.002(2), FS
 471.025, AND SECTION 104.2.2. (ONE SET OF FS SHEETS HAS
 BEEN RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
  
 18. FS4 ITEM P72 TROUGH DRAIN. NO DRAIN TO THE GREASE
 SYSTEM IS INDICATED. PLEASE CLARIFY. SECTION 104.2.1.
  
 19. FS4 ITEM P82 ON SHT FS2 INDICATES 1/2"CW & A 1"
 INDIRECT WASTE, BUT IS NOT SHOWN ON THE PLUMBING
 CONNECTION SCHEDULE. PLEASE CORRELATE EQUIPMENT
 SCHEDULES. SECTION 104.2.1.
  
 20. ALL GAS HOOD SHEETS 1,2,3 TO BE
 SIGNED/SEALED/DATED. SOME SETS OF SHEETS SUBMITTED ARE
 COPIES OF SIGNED/SEALED/DATED SHEETS. SECTION 104.2.2,
 FAC 61G15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS
 TO HELP EXPEDITE REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status F Date 2006-09-28 Cont ID  
Sent By kstevens Date 2006-09-28 Time 13:13 Rev Time 0.00
Received By kstevens Date 2006-09-28 Time 13:13 Sent To  
Notes
2006-09-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SUBMIT SANITARY AND WATER RISER
 DIAGRAM ISOMETRICS REFLECTING ALL
 CHANGES TO THE FLOOR PLAN FOR THE NEW
 WORK IN THE TOILET ROOMS, KITCHEN AND
 BAR AREAS. SECTION 104.3.1.1.
  
 2. VALUE OF ALL NEW WORK TO BE ADJUSTED
 TO THE PERMIT VALUE FOR THE 6 TOILET
 ROOMS, THE DEMO OF THE TOILET ROOMS, AND
 THE NEW WORK FOR THE KITCHEN AND BAR
 AREAS. SECTION 104.6.5.
  
 3. THE NEW TOILET ROOMS FOR THE
 RESTAURANT SHALL MEET POTTY PARITY PER
 SECTION 403.1.1 AND SECTION 3401.2.
  
 4. SHTS A1.2, A1.7, A1.8, A1.9, & A1.10
 REVISIONS 3, 4, 5 ARE INDICATED ON THE
 "PERMIT REVISIONS" AREA BUT NOT FOUND ON
 THE FLOOR PLAN. PLEASE CORRELATE
 REVISIONS NUMBERS WITH REVISIONS ON THE
 FLOOR PLAN. SECTION 104.2.1.
  
 5. SHT A1.9 FITNESS ROOM 233 SINK SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL SHOWING ALL
 REQUIREMENTS. SECTION 104.2.1.
  
 6. SHTS A4.1 & A10.1 NO REVISIONS FOUND.
 REVISIONS 3, 4, 5, & 6 ARE INDICATED ON
 THE "PERMIT REVISIONS" AREA. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 7. SHT A10.2 IS A NEW SHEET, BUT
 INDICATES THAT REVISIONS 3, 4, 5, & 6
 ARE ON THE FLOOR PLAN. HOW CAN A NEW
 SHEET HAVE REVISIONS? PLEASE CLARIFY.
 SECTION 104.2.1.
  
 8. NEW FS SHEETS SHOWING THE CHANGES TO
 THE KITCHEN & BAR AREA AND NEW PLUMBING
 REVISIONS ARE REQUIRED. SECTION 104.2.1.
 THE NEW SHEETS SHALL BE ROUTED TO DBPR,
 HOTEL & RESTAURANT DIVISION FOR REVIEW
 AS A REVISION. MINIMUM 2 SETS OF PLANS
 STAMPED BY DBPR SHALL BE SUBMITTED FOR
 REVIEW.
  
 9. REVISIONS REQUIRED FOR THE GAS PIPING
 SYSTEM TO REFLECT THE FLOOR PLAN.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-08-28 Cont ID  
Sent By kstevens Date 2006-08-28 Time 13:12 Rev Time 0.00
Received By kstevens Date 2006-08-28 Time 13:12 Sent To  
Notes
2006-08-28 00:00:00THE REVISIONS FOR THE FOLLOWING SHEETS
 HAVE BEEN APPROVED. P1.1A, P1.1B, P1.1D,
 AND P5.3.
  
 REVISION DENIED
  
 1. SHT P5.1 (SEE GAS REVIEW)
  
 2. SHT P5.2, FITTINGS SHALL BE INSTALLED
 TO GUIDE SEWAGE AND WASTE IN THE
 DIRECTION OF FLOW. (SEE NEW FLOOR DRAINS
 IN GREASE RISER. - SEE ALL FIXTURES IN
 DETAIL #3 FOR BACK TO BACK TOILET ROOMS.
 - A TRAP IS REQUIRED FOR THE WASH
 MACHINE, AND THE VENT CAN NOT CONNECT TO
 THE WASH MACHINE BOX. - THE URINALS ARE
 NOT VENTED AS SHOWN. - (SEE RED LINE
 CORRECTION FOR EXAMPLES). SECTIONS
 706.3, 901.2.1, 1002.1.
  
 3. NOTE: A REVISION TO FLOOR PLAN MAY BE
 REQUIRED FOR THE CHANGES SHOWN SO THAT
 THE FLOOR PLAN AND THE RISER DIAGRAM
 REFLECT EACH OTHER. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-07-15 Cont ID  
Sent By pschmitz Date 2006-07-15 Time 06:26 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time 06:26 Sent To  
Notes
2006-07-15 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT
 SEE PREVIOUS PROVISO NOTES BELOW
 DATED 4-26-06 BY KEN STEVENS
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P1.1B SHOWING
 VENT FOR LIFT STATION & ROUTING OF STEAM
 LINE TO PITCH AWAY FROM THE STEAM
 GENERATOR TO DRAIN THE CONDENSATE. SEE
 SHT 8 0F 19 MANUF. SPECIFICATION SHEETS.
 (I WAS INFORMED BY THE DESIGN
 PROFESSIONAL THAT THE STEAM GENERATOR
 WILL BE MOVED)
  
 REVISION REQUIRED FOR SHT SHT P5.1 FOR
 ALL RED LINE CHANGES TO GAS ISOMETRIC &
 PLUMBING RISERS.
  
 REVISION REQUIRED FOR SHEET P5.2
 INDICATING THAT A STANDPIPE IS REQUIRED
 FOR THE DISH WASHER PER SECTION 802.17.
  
 ALL REVISIONS SHALL BE SUBMITTED AS SOON
 AS POSSIBLE TO AVOID A DELAY IN GETTING
 THE CERTIFICATE OF OCCUPANCY.
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-04-22 Cont ID  
Sent By kstevens Date 2006-04-22 Time 21:33 Rev Time 0.00
Received By kstevens Date 2006-04-22 Time 21:33 Sent To  
Notes
2006-04-22 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P1.1B SHOWING
 VENT FOR LIFT STATION & ROUTING OF STEAM
 LINE TO PITCH AWAY FROM THE STEAM
 GENERATOR TO DRAIN THE CONDENSATE. SEE
 SHT 8 0F 19 MANUF. SPECIFICATION SHEETS.
 (I WAS INFORMED BY THE DESIGN
 PROFESSIONAL THAT THE STEAM GENERATOR
 WILL BE MOVED)
  
 REVISION REQUIRED FOR SHT SHT P5.1 FOR
 ALL RED LINE CHANGES TO GAS ISOMETRIC &
 PLUMBING RISERS.
  
 REVISION REQUIRED FOR SHEET P5.2
 INDICATING THAT A STANDPIPE IS REQUIRED
 FOR THE DISH WASHER PER SECTION 802.17.
  
 ALL REVISIONS SHALL BE SUBMITTED AS SOON
 AS POSSIBLE TO AVOID A DELAY IN GETTING
 THE CERTIFICATE OF OCCUPANCY.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-04-19 Cont ID  
Sent By kstevens Date 2006-04-19 Time 10:14 Rev Time 0.00
Received By kstevens Date 2006-04-19 Time 10:14 Sent To  
Notes
2006-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEWS. COMMENT
 NUMBERS SHALL REMAIN THE SAME:
  
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 - ONLY ONE SET OF PLANS WAS STAMPED.
 EACH SET OF PLANS REQUIRES A SET OF
 STAMPED PLANS FROM DBPR. ALSO THE TWO
 PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED
 TO EACH SET OF PLANS FROM DBPR. MINIMUM
 OF TWO SETS OF PLANS REQUIRED. (PLANS
 NOT SIGNED & SEALED SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1) ALL FS SHEETS SHALL COMPLY.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 NO RESPONSE FROM ARCHITECT:
 NEW FS-1 THRU FS-8 SHEETS SUBMITTED WITH
 THE DBPR STAMP. THE TWO PAGE "WORKSHEETS
 WERE NOT ATTACHED TO EACH SET. (I COPIED
 THE WORKSHEETS AND ADDED ONE SET TO OUR
 FILE COPY). PRINTED NAME AND SIGNATURE
 REQUIRED BY SECTION 104.2.1 NOT ON
 SHEETS. PLEASE COMPLY.
  
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1. (THIS HAS
 BEEN CHANGED TO ONE STEAM ROOM, #154,
 BUT COMMENT STILL NOT ADDRESSED).
 ***************************************
 RESPONSE INDICATES ROOM #152-B IS THE
 LOCATION OF THE STEAM GENERATOR. THIS
 ROOM HAS NOT BEEN LOCATED ON SHT A1.1.
 PLEASE CLARIFY. - 2 DIFFERENT STEAM
 GENERATORS SPECIFICATION SHEETS HAVE
 BEEN SUBMITTED. PLEASE INDICATE WHICH
 GENERATOR WILL BE USED. (SUANATEC (NO
 LISTING SHOWN) OR AMEREC). - SAFETY
 VALVE LINE, DRAIN LINE, AND PAN DRAIN
 LINE DISCHARGE PIPING IS NOT SHOWN.
 PLEASE INDICATE HOW THE PIPING FOR THESE
 WILL BE RUN, AND SHOW COMPLIANCE WITH
 SECTION 701.1. (SEE PAGE 8 OF 19 MANUF.
 SPECIFICATION SHEETS). SHOW TERMINATION
 OF ALL LINES.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: PLANS SHOW A REVISION
 THAT WAS PENCILED IN WHICH IS NOT
 APPROVED. PLEASE RESUBMIT NEW SHEETS FOR
 ALL CHANGES. NO PIPING IS SHOWN FOR THE
 DRAIN LINE FROM THE STEAM GENERATOR AS
 REQUIRED IN PAGE 8 OF 19 IN THE MANUF.
 SPECIFICATION SHEETS.. THERE IS NO
 DRAINAGE PIPING TO COOLING TANK FROM THE
 SANT. SYSTEM.
  
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 SHT P5.2 RESPONSE NOTED BUT,
 THE GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. A TRENCH DRAIN
 AND A FLOOR SINK ARE MISSING. ALSO A DRY
 HORIZONTAL VENT IS SHOWN ON THE END OF
 ONE RUN PAST A FLOOR SINK. SECTIONS
 104.2.1, 905.3 & 905.4. - THE DISHWASHER
 SHALL CONNECT THE THE SANITARY SYSTEM
 PER MUNICIPAL CODE SECTION 90-124(7)(B)
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: HAND DRAWN CHANGES IN
 PENCIL ARE NOT APPROVED. SUBMIT NEW
 SHEETS FOR ALL CHANGES MADE ON THE
 PLANS. EXTEND CHANGE TO PICK UP RISER TO
 SECOND FLOOR. (NUMBER 9). - DISHWASHER
 DELETED FROM THE GREASE SYSTEM IS NOT
 SHOWN ON THE SANITARY. SYSTEM. (SHTS
 P5.1 AND P5.2)
  
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 AN ISOMETRIC SHOWING PIPING FOR THE NEW
 PIPE WITH ALL PIPE SIZES, VALVES, DRIPS,
 BTU'S SHOWN AT EACH APPLIANCE, ETC. -
 FOR EXISTING PIPING THE SIZE PER TABLE
 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4",
 AND FOR 1,895 CU FT/HR @ 195FT IS 3".
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: SHOW ALL PIPE SIZES PER
 TABLE 402(2) FOR NEW PIPE.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***************************************
 RESPONSE NOTED BUT,
 THE MANUF. SPECIFICATIONS SHEETS FOR
 ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND
 ITEM 6 DOUBLE CONVECTION OVENS DO NOT
 CORRELATE WITH THE BTU'S INDICATED ON
 THE GAS RISER DIAGRAM. INDICATE MODEL
 NUMBER OF EACH NEW GAS APPLIANCE AND
 MAKE SURE IT CORRELATES WITH THE GAS
 RISER DIAGRAM.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: SHT P5.1, THE GAS SIZING
 CALCULATION INFORMATION INDICATES NEW
 GAS EQUIPMENT AT 788,000 BTU'S, THE THE
 GAS FIRE KITCHEN EQUIPMENT LIST
 INDICATES 779,500 BTU'S, BUT THE MANUF.
 SPECIFICATION SHEETS INDICATE 879,500
 BTU'S. PLEASE CORRELATE ALL GAS
 INFORMATION.
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ***************************************
 RESPONSE NOTED BUT,
 THIS SHALL BE SHOWN ON THE RISER DIAGRAM
 WITH THE VALVES & UNION PLACED AS
 INDICATED.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: PLEASE INDICATE THAT THE
 EMERGENCY SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" ABOVE THE
 FLOOR PER NFPA-96 SECTION 10.5.1 AND
 NFPA-1 SECTION 50.4.7.1.
  
 ****NEW COMMENT****
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80.(2)(B)
  
 ****NEW COMMENT*****
 1C. SHT P1.1B REVISED SHEET REQUIRED TO
 REFLECT CHANGES MADE TO RISER DIAGRAM.
 (DRY HORIZONTAL VENT REMOVAL).
 2C. SHT P1.1C REVISED SHEET REQUIRED RO
 REFLECT HAND DRAWN CHANGES MADE TO
 SHEET. (REV-11)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 SUBMIT ONE COPY OF PLANS FROM PREVIOUS
 REVIEW WHEN RESUBMITTING.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 OLD VOIDED SHEETS WERE NOT REMOVED, AND
 NEW SHEETS WERE NOT ATTACHED TO THE SET
 OF PLANS. PLEASE SUBMIT TWO SETS OF
 PLANS FOR REVIEW. SECTIONS 104.2.1. AND
 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-04-07 Cont ID  
Sent By kstevens Date 2006-04-07 Time 09:33 Rev Time 0.00
Received By kstevens Date 2006-04-04 Time 13:51 Sent To  
Notes
2006-04-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEWS. COMMENT
 NUMBERS SHALL REMAIN THE SAME:
  
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 - ONLY ONE SET OF PLANS WAS STAMPED.
 EACH SET OF PLANS REQUIRES A SET OF
 STAMPED PLANS FROM DBPR. ALSO THE TWO
 PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED
 TO EACH SET OF PLANS FROM DBPR. MINIMUM
 OF TWO SETS OF PLANS REQUIRED. (PLANS
 NOT SIGNED & SEALED SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1) ALL FS SHEETS SHALL COMPLY.
  
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1. (THIS HAS
 BEEN CHANGED TO ONE STEAM ROOM, #154,
 BUT COMMENT STILL NOT ADDRESSED).
 ***************************************
 RESPONSE INDICATES ROOM #152-B IS THE
 LOCATION OF THE STEAM GENERATOR. THIS
 ROOM HAS NOT BEEN LOCATED ON SHT A1.1.
 PLEASE CLARIFY. - 2 DIFFERENT STEAM
 GENERATORS SPECIFICATION SHEETS HAVE
 BEEN SUBMITTED. PLEASE INDICATE WHICH
 GENERATOR WILL BE USED. (SUANATEC (NO
 LISTING SHOWN) OR AMEREC). - SAFETY
 VALVE LINE, DRAIN LINE, AND PAN DRAIN
 LINE DISCHARGE PIPING IS NOT SHOWN.
 PLEASE INDICATE HOW THE PIPING FOR THESE
 WILL BE RUN, AND SHOW COMPLIANCE WITH
 SECTION 701.1. (SEE PAGE 8 OF 19 MANUF.
 SPECIFICATION SHEETS). SHOW TERMINATION
 OF ALL LINES.
  
 12. SHT P1.1C KEYED NOTES #3 SUBMIT A
 DETAIL FOR THE VENT CAP. VENT SHALL
 TERMINATE IN COMPLIANCE WITH SECTION
 904.5. SUBMIT AN ELEVATION FOR THE TRASH
 AREA TO DETERMINE IF VENT WILL BE
 APPROVED IN AREA WITHOUT TERMINATING
 ABOVE THE ROOF OF THE TRASH AREA.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 NOW THE FLOOR DRAIN HAS NOT VENT AS
 REQUIRED IN SECTION 901.2.1 - FLOOR
 DRAIN SHOULD BE CONNECTED TO THE GREASE
 WASTE SYSTEM SO IT WILL BE EASY TO
 CONNECT TO THE LINE GOING TO THE FLOOR
 DRAIN NEAR THE EMPLOYEE RESTROOM.
  
 13. SUBMIT A SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, AND DFU'S
 AS THEY ACCUMULATE IN THE DRAINAGE
 SYSTEM. SECTION 104.3.1.1. (NO RESPONSE,
 NOT ADDRESSED).
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 PAST BOTH SETS OF W/C'S IS A DRY
 HORIZONTAL VENT. THIS IS NOT APPROVED
 PER SECTIONS 905.3 & 905.4.
  
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 SHT P5.2 RESPONSE NOTED BUT,
 THE GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. A TRENCH DRAIN
 AND A FLOOR SINK ARE MISSING. ALSO A DRY
 HORIZONTAL VENT IS SHOWN ON THE END OF
 ONE RUN PAST A FLOOR SINK. SECTIONS
 104.2.1, 905.3 & 905.4. - THE DISHWASHER
 SHALL CONNECT THE THE SANITARY SYSTEM
 PER MUNICIPAL CODE SECTION 90-124(7)(B)
  
 15. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM, SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS, (REQD. BY
 SECTION 604.9), AND LOCATED NEAR THE
 FIXTURES AS REQUIRED BY PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS, AND
 POINTS OF CONNECTION. SECTION 104.3.1.1.
 (NO RESPONSE, NOT ADDRESSED).
 ***************************************
 SHTS P5.1 & P5.2 RESPONSE NOTED BUT,
 WATER HAMMER ARRESTORS ARE REQUIRED AT
 THE DISH WASHER, AND AT ICE MAKERS PER
 SECTION 604.9. AIR CHAMBERS ARE NOT
 APPROVED AND SHALL BE DELETED FROM THE
 RISER DIAGRAMS INCLUDING DETAIL #4 SHT
 P5.2.
  
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 AN ISOMETRIC SHOWING PIPING FOR THE NEW
 PIPE WITH ALL PIPE SIZES, VALVES, DRIPS,
 BTU'S SHOWN AT EACH APPLIANCE, ETC. -
 FOR EXISTING PIPING THE SIZE PER TABLE
 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4",
 AND FOR 1,895 CU FT/HR @ 195FT IS 3".
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***************************************
 RESPONSE NOTED BUT,
 THE MANUF. SPECIFICATIONS SHEETS FOR
 ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND
 ITEM 6 DOUBLE CONVECTION OVENS DO NOT
 CORRELATE WITH THE BTU'S INDICATED ON
 THE GAS RISER DIAGRAM. INDICATE MODEL
 NUMBER OF EACH NEW GAS APPLIANCE AND
 MAKE SURE IT CORRELATES WITH THE GAS
 RISER DIAGRAM.
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ***************************************
 RESPONSE NOTED BUT,
 THIS SHALL BE SHOWN ON THE RISER DIAGRAM
 WITH THE VALVES & UNION PLACED AS
 INDICATED.
  
  
 ****NEW COMMENT****
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80.(2)(B)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 SUBMIT ONE COPY OF PLANS FROM PREVIOUS
 REVIEW WHEN RESUBMITTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By kstevens Date 2006-01-30 Time 17:24 Rev Time 0.00
Received By kstevens Date 2006-01-30 Time 17:24 Sent To  
Notes
2006-01-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW. COMMENT NUMBERS
 SHALL REMAIN THE SAME:
 1. SHT A1.1 EMPLOYEE RESTROOM SHALL BE
 ACCESSIBLE PER SECTION 11-4.22. (PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, AND 11-4.22
 AND ALL SUBSECTIONS).
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1. (THIS HAS
 BEEN CHANGED TO ONE STEAM ROOM, #154,
 BUT COMMENT STILL NOT ADDRESSED).
 4. SHOWER DELETED.
 5. OK
 6. SHT A10.1 DETAILS SHALL SHOW THE
 FOLLOWING:
 -FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 -FOR LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. OK
 (NO RESPONSE, NOT ADDRESSED)
 7. OK
 8. ALL PME SHEETS ENGINEER SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. NAME AND LICENSE
 NUMBER NOT SHOWN IN THE TITLE BLOCK. FAC
 61G15-23.002(2) AND FS 471.025. (NO
 RESPONSE, NOT ADDRESSED).
 9. WILL PROVISO
 10. SHT PD1.1B KEYED NOTES #6 NOT FOUND.
 PLEASE CLARIFY. SECTION 104.2.1. (NOTE
 FOUND, BUT FIXTURES NOT SHOWN).
 11. OK.
 11. SHT P1.1A WATER FILTERS SHALL COMPLY
 THE "NSF - 42" STANDARD. PLEASE SUBMIT
 MANUF. SPECIFICATIONS FOR FILTER.
 SECTION 611.1. (SECOND COMMENT #11 - NO
 RESPONSE, NOT ADDRESSED).
 12. SHT P1.1C KEYED NOTES #3 SUBMIT A
 DETAIL FOR THE VENT CAP. VENT SHALL
 TERMINATE IN COMPLIANCE WITH SECTION
 904.5. SUBMIT AN ELEVATION FOR THE TRASH
 AREA TO DETERMINE IF VENT WILL BE
 APPROVED IN AREA WITHOUT TERMINATING
 ABOVE THE ROOF OF THE TRASH AREA.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 13. SUBMIT A SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, AND DFU'S
 AS THEY ACCUMULATE IN THE DRAINAGE
 SYSTEM. SECTION 104.3.1.1. (NO RESPONSE,
 NOT ADDRESSED).
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 15. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM, SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS, (REQD. BY
 SECTION 604.9), AND LOCATED NEAR THE
 FIXTURES AS REQUIRED BY PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS, AND
 POINTS OF CONNECTION. SECTION 104.3.1.1.
 (NO RESPONSE, NOT ADDRESSED).
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL).
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ***NO RESPONSE, NOT ADDRESSED ALL GAS
 PERMIT REQUIREMENTS*********************
  
 ****NEW COMMENT****
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80.(2)(B)
 2B. FLOOR PLANS HAVE CHANGED FROM FIRST
 SUBMITTAL TO THE SECOND SUBMITTAL. IF
 FLOOR PLAN CHANGES PRIOR TO THIRD
 SUBMITTAL, MORE COMMENTS MAY BE
 FORTHCOMING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 SUBMIT ONE COPY OF PLANS FROM PREVIOUS
 REVIEW WHEN RESUBMITTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By kstevens Date 2005-08-13 Time 11:49 Rev Time 7.15
Received By kstevens Date 2005-08-12 Time 18:52 Sent To  
Notes
2005-08-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A1.1 EMPLOYEE RESTROOM SHALL BE
 ACCESSIBLE PER SECTION 11-4.24.
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7.
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1.
 4. SHTS A1.2 AND A1.9 SHOWER IN ROOM 236
 TO BE ACCESSIBLE, AND ALSO REQUIRES A 5'
 TURNING AREA. SECTION 11-4.1.6(1)(B).
 5. SHT A1.10 MENS RESTROOM INDICATES
 VANITY TO BE RAISED TO 37". ONE LAV
 SHALL 34" FOR ACCESSIBLILTY
 REQUIREMENTS. SECTION 11-4.19.2
 6. SHT A10.1 DETAILS SHALL SHOW THE
 FOLLOWING:
 -FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 -FOR FAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS (SHOWS 52" -
 REQUIRED TO BE 40").
 7. SHT A10.1 TURNING AREA REQUIRED IN
 EACH TOILET ROOM. (NOT IN THE ACCESSIBLE
 STALL). SECTION 11-4.22.3 - ALSO IN
 DETAIL "A" THE TURNING AREA SHOULD BE
 NEAR THE ACCESSIBLE SHOWER.
 8. ALL PME SHEETS ENGINEER SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. NAME AND LICENSE
 NUMBER NOT SHOWN IN THE TITLE BLOCK. FAC
 61G15-23.002(2) AND FS 471.025.
 9. SHT P0.1 PLUMBING GENERAL NOTES #13,
 PVC NOT APPROVED FOR WATER DISTRIBUTION
 PIPE PER TABLE 605.5. DELETE FROM
 REFERENCE, OR INDICATE FOR WATER SERVICE
 ONLY.
 10. SHT PD1.1B KEYED NOTES #6 NOT FOUND.
 PLEASE CLARIFY. SECTION 104.2.1.
 11. SHT PD1.1C GREASE INTECEPTORS,
 ALTHOUGH EXISTING, SHALL BE SIZED BY THE
 EXVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT LYNN MASSON AT PHONE NUMBER
 (561) 822-2271, FAX 9561) 822-2279, OR
 E-MAIL [email protected]. PLEASE SUBMIT
 THE DETERMINATION SHEET FOR GREASE
 INTERCEPTORS WITH PLANS WHEN
 RESUBMITTING. WASTE ORD #3434.
 11. SHT P1.1A WATER FILTERS SHALL COMPLY
 THE "NSF - 42" STANDARD. PLEASE SUBMIT
 MANUF. SPECIFICATIONS FOR FILTER.
 SECTION 611.1.
 12. SHT P1.1C KEYED NOTES #3 SUBMIT A
 DETAIL FOR THE VENT CAP. VENT SHALL
 TERMINATE IN COMPLIANCE WITH SECTION
 904.5. SUBMIT AN ELEVATION FOR THE TRASH
 AREA TO DETERMINE IF VENT WILL BE
 APPROVED IN AREA WITHOUT TERMINATING
 ABOVE THE ROOF OF THE TRASH AREA.
 SECTION 104.2.1.
 13. SUBMIT A SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, AND DFU'S
 AS THEY ACCUMULATE IN THE DRAINAGE
 SYSTEM. SECTION 104.3.1.1.
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 15. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM, SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS, (REQD. BY
 SECTION 604.9), AND LOCATED NEAR THE
 FIXTURES AS REQUIRED BY PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS, AND
 POINTS OF CONNECTION.
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL).
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-06 Cont ID  
Sent By jroach Date 2008-05-06 Time 14:49 Rev Time 0.00
Received By jroach Date 2008-05-06 Time 14:49 Sent To  
Notes
2008-05-06 17:24:10***FAILED***
  
 1) PLEASE NOTE THAT THE GENERATOR WILL NEED TO BE
 SUBMITTED UNDER A SEPARATE PERMIT.
  
 2) A SURVEY SHALL BE PROVIDED SHOWING THE LOCATION OF
 THE PROPOSED GENERATOR RELATIVE TO ALL PROPERTY LINES,
 EXISTING EASEMENTS, ADJACENT STRUCTURES, ETC.
  
 3) A SITE PLAN SHALL BE PROVIDED SHOWING THE LOCATION
 OF THE GENERATOR ON THE PROPERTY.SETBACKS SHALL BE
 PROVIDED FROM ALL PROPERTY LINES.
  
 4) GENERATORS SHALL BE SCREENED IN ACCORDANCE WITH
 SECTION 94-444(B) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS.SCREEN SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL
 (CHAIN-LINK IS NOT PERMITTED).THE ENCLOSURE SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO (2)
 FOOT INTERVALS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved