 |
Plan Review Details - Permit 05070627
| Plan Review Stops For Permit 05070627 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-28 |
Time |
16:25 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-05-28 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2008-05-28 16:42:23 | BUILDING PLAN REVIEW | | | PERMIT: 05070627 | | | ADD: 2300 PRESIDENTIAL WAY | | | CONT: GRUBER HALL/ DAVE | | | TEL: (561)662-3377 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. | | | | | | 2) THE GENERATOR, SLAB, TRANSFER SWITCH AND FUEL TANK | | | WERE NOT ON THE ORIGINAL PLANS. THIS WILL REQUIRE A | | | SEPERATE PERMIT WITH REVIEW AND ASSOCIATED FEES. | | | | | | 3) 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | | | | 4) THERE IS NO INFORMATION AS TO THE GENERATOR BLOCK | | | WALLENCLOSURE, PLEASE SUPPLY ADDITIONAL INFORMATION | | | 106.1.2. | | | | | | 5)PROVIDE INFORMATION FOR THE MOMENT OF OVERTURNING, | | | PLEASE PROVIDE ANCHOR INFORMATION AS WELL AS SLAB | | | INFORMATION. 1609.1.3 ANCHORAGE AGAINST OVERTURNING, | | | UPLIFT AND SLIDDING. | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-14 |
Time |
14:00 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-06-14 |
Time |
14:00 |
Sent To |
PC |
|
| Notes |
| 2007-06-14 14:00:52 | REVISION: HANDICAPPED SHOWER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-13 |
Time |
14:08 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2007-06-13 |
Time |
14:08 |
Sent To |
PC |
|
| Notes |
| 2007-06-13 14:16:36 | BUILDING PLAN REVIEW | | | PERMIT: 05070627 | | | ADD:2300 PRESIDENTIAL WAY | | | CONT: CONKLING & LEWIS | | | TEL: (561)833-4441 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | CUT SECTION OF PLAN INDICATES WHAT APPEARS TO BE | | | HANDICAPPED SHOWERS WITH A BENCH BUT THE PLAN FAILS TO | | | SHOW THE LOCATION OF THE CONTROLS. | | | SEE 11-4.21.8 SHOWER ENCLOSURES. | | | IF PROVIDED, ENCLOSURES FOR SHOWER STALLS SHALL NOT | | | OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS | | | ONTO SHOWER SEATS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-13 |
Time |
14:05 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2007-06-13 |
Time |
14:05 |
Sent To |
PC |
|
| Notes |
| 2007-06-13 14:07:20 | ARCHITECT MEMO: REGARDING RESSTROOM SIZE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-05-08 |
Time |
10:32 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-05-08 |
Time |
10:32 |
Sent To |
PC |
|
| Notes |
| 2007-05-08 10:33:17 | REMOVAL OF TIE COLUMNS AND REINFORCEMENT WITH STEEL | | | BEAMS AND BRACKETS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-07-20 |
Time |
16:09 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-07-20 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | REV# 5 OK K. WHITE REVISED (REDLINED) | | | ARCHITECURAL (A) PLAN 7-20-06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2006-07-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-07-12 |
Time |
14:29 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-07-12 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | ADD: 2300 PRESIDENTIAL WAY | | | CONT: CONKLING & LEWIS CONST | | | TEL: (561)833-4441 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION:# 5 | | | ACTION: DENIED | | | | | | | | | 11-4.1.6(1)(B) | | | 11-4.1.6(1)(B) IF EXISTING ELEMENTS, | | | SPACES, OR COMMON AREAS ARE ALTERED, | | | THEN EACH SUCH ALTERED ELEMENT, SPACE, | | | FEATURE, OR AREA SHALL COMPLY WITH THE | | | APPLICABLE PROVISIONS OF 11-4.1.1 TO | | | 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW | | | CONSTRUCTION. | | | | | | 1) LS.1/ A1.3 THE OLD PRO OFFICE 134/ | | | NEW RESTROOMS 131 DO NOT INDICATE | | | ACCESSIBILITY TO UNITS.11-4.1.3(11) | | | TOILET FACILITIES: IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON | | | USE TOILET ROOM SHALL COMPLY WITH | | | 11-4.22. | | | | | | 2) A1.4 MASSAGE ROOM# 147 DOORS 147 & | | | 149B REQUIRE 18" ON THE PULL LATCH SIDE | | | OF THE DOOR. | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 3) SHEET A1.5 ROOM 147 TV/ NAP ROOM | | | 3A) 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 3B) COMPANION SEATING: | | | 11-4.1.6(3)(F)(I)WHERE IT IS TECHNICALLY | | | INFEASIBLE TO DISPERSE ACCESSIBLE | | | EATING THROUGHOUT AN ALTERED ASSEMBLY | | | AREA, ACCESSIBLE SEATING AREAS MAY BE | | | CLUSTERED.EACH ACCESSIBLE SEATING AREA | | | SHALL HAVE PROVISIONS FOR COMPANION | | | SEATING AND SHALL BE LOCATED ON AN | | | ACCESSIBLE ROUTE THAT ALSO SERVES AS A | | | MEANS OF EMERGENCY EGRESS. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-04-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-15 |
Time |
07:42 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-04-14 |
Time |
16:21 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-11 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-04-11 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2006-04-11 00:00:00 | ADD: 2300 PRESIDENTIAL WAY | | | CONT: CONKLING & LEWIS CONST | | | TEL: (561)833-4441 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | ***IMPORTANT NOTICE*** | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE SEE THE FIRST PART OF THIS REVIEW | | | ARE COMMENTS FROM THE FIRST REVIEW NOT | | | ADDRESSED: | | | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT 4B FROM THE PREVIOUS | | | REVIEW,STAIRWELL DOORS SHOW NO RATING | | | NOR DOES ANY STORAGE ROOM DOORS. | | | RESPONSE: SEE ATTACHED LIFE SAFETY | | | DRAWINGS. EXISTING STAIRWELL DOORS ARE | | | FIRE RATED. STORAGE ROOM DOORS ARE NOT | | | REQUIRED TO BE FIRE RATED PER FBC 704.1.2.2(4).STORAGE | | | IS FOR | | | NON-HAZARDOUS MATERIALS, AND DOES NOT | | | EXCEED 1/3RD OF THE MAJOR OCCUPANCY | | | FLOOR AREA. | | | | | | THE EXIT DOORS MAY BE EXISTING DOORS BUT | | | WITH THE ASSEMBLY OCCUPANCY EXIT DOORS | | | REQUIRE A 1 1/2 HR RATING. TABLE | | | 705.1.2ASSEMBLY BUILDINGS SEE NOTE (2). | | | ALL EXITS AND STAIRWAYS IN GROUP A AND H OCCUPANCIES | | | SHALL BE 2 HOURS WITH 1-1/2 | | | HOUR DOOR ASSEMBLIES. | | | | | | THE ABOVE CODE SECTION IS CORRECT FOR | | | STORAGE ROOMS WITHIN THE OCCUPANCY | | | (GROUP A, GROUP B, GROUP E, GROUP M AND | | | GROUP R). THE AREAS IN QUESTION ARE | | | STORAGE CLOSETS THAT ARE ON AN EXIT | | | ACCESS CORRIDOR.SEE TABLE 704.2.4 FIRE RESISTANCE | | | RATING OF EXIT ACCESS | | | CORRIDORS, FOOTNOTE (4). IN BUILDINGS | | | PROTECTED THROUGHOUT WITH AN APPROVED | | | AUTOMATIC SPRINKLER SYSTEM, EXIT ACCESS | | | CORRIDOR WALLS NOT REQUIRED TO BE RATED | | | SHALL, IN CONJUNCTION WITH OPENINGS | | | THEREIN AND CEILINGS AT WHICH THEY | | | TERMINATE, RESIST THE PASSAGE OF SMOKE. | | | | | | ALTHOUGH THE DOORS NEED NOT HAVE A FIRE | | | RATING BECAUSE OF THE APPROVED FIRE | | | SPRINKLERS, WE DO NEED TO HAVE | | | INFORMATION AS TO HOW THEY WILL RESIST | | | THE PASSAGE OF SMOKE. | | | | | | 3) COMMENT# 11 FROM THE PREVIOUS REVIEW, | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | BROKE DOWN BY SHEET: | | | 11A) COMPLIED | | | | | | 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR | | | FLOOR SPACE REQUIRED FOR FIXTURES, | | | URANIAL, DOOR REMOVED SEE 11-4.17.5 THE | | | SAME LEVEL OF PRIVACY TO BE PROVIDED TO | | | THE HANDICAPPED STALL AS THE REST OF THE | | | RESTROOM.11-2.2 EQUIVALENT FACILITATION. | | | | | | 11C) A1.5 DOOR# 154 | | | | | | 11D) A1.6 COMPLIED | | | | | | 11E) A1.7 DOOR# 214 | | | | | | 11F)A1.8 COMPLIED | | | | | | 11G) A1.9 COMPLIED | | | | | | 4) NEW COMMENT, SHEET A1.8 MULTI PURPOSE | | | ROOM 232 INDICATES A REVISION# 2 | | | INDICATING CHANGES TO THIS WALL. PLANS | | | INDICATE THIS WALL IS A TYPE"H" WHEN | | | REFERING BACK TO A8.1 FOR WALL RATINGS | | | THIS WALL IS A INTERIOR FOLDING | | | PARTITION. NOT A 2 HR RATED WALL? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-26 |
Time |
11:58 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2006-01-26 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-01-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070627 | | | ADD: 2300 PRESIDENTIAL WAY | | | CONT: CONKLING & LEWIS CONST | | | TEL: (561)833-4441 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | ***IMPORTANT NOTICE*** | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE SEE THE FIRST PART OF THIS REVIEW | | | ARE COMMENTS FROM THE FIRST REVIEW NOT | | | ADDRESSED: | | | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2A)INDICATE BUILDING TYPE: | | | 601.2.1 EVERY BUILDING SHALL BE | | | CLASSIFIED BY THE BUILDING OFFICIAL | | | INTO ONE OF THE TYPES OF CONSTRUCTION | | | AS SET FORTH IN THIS SECTION. | | | | | | TYPE ITYPE V | | | TYPE II1-HOUR PROTECTED | | | TYPE IIIUNPROTECTED | | | TYPE IV TYPE VI | | | 1-HOUR PROTECTED1-HOUR PROTECTED | | | UNPROTECTED UNPROTECTED | | | | | | 2B) A TYPE V BUILDING IS EITHER 1-HR | | | RATED OR UNPROTECTED, BUT NOT BOTH. | | | | | | 2C)IF BUILDING IS FIRE SPRINKLERED OR | | | NOT?IF FIRE SPRINKLERED PROVIDE FIRE | | | SPRINKLER PLANS. BUILDING DESIGN | | | INDICATES FIRE SPRINKLERED BUT NO PLANS | | | HAVE BEEN SUBMITTED. | | | | | | 2D) PROVIDE TOTAL SQ FT PER FLOOR? WERE | | | AREA INCREASES TAKEN? | | | | | | 3) PROVIDE LIFE SAFETY PLAN, ALSO | | | PROVIDE THE SEATING FOR RESTARAUNTS OR | | | OCCUPANT LOAD WILL BE TAKEN AS 15 NET, | | | FOR PREFUNCTION AREAS 7 NET. | | | | | | 4A) PLANS SHEET A5.1 DOOR SCHEDULE, NO | | | FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE | | | DOOR RATING AS "B" OR "C" SEE TABLE | | | 705.1.2. FOR MINUTE & HR RATING. | | | M1106.4 MACHINE ROOMS REQUIRE 45 MIN | | | OPENING PROTECTION. | | | M1106.4 OPENING PROTECTIVES. OPENING | | | PROTECTION BETWEEN THE MACHINERY | | | ROOM AND OTHER OCCUPIED SPACES SHALL BE | | | APPROVED, SELF-CLOSING, TIGHT- | | | FITTING FIRE DOORS WITH A MINIMUM | | | FIRE-RESISTANCE RATING OF 3/4 HOUR. | | | | | | 4B) STAIRWELL DOORS SHOW NO RATING NOR | | | DOES ANY STORAGE ROOMS. | | | | | | 4C) DOOR SCHEDULE DOESN'T INDICATE | | | HARDWARW GROUPINGS, MAY HAVE MORE | | | COMMENTS WITH ACCESSIBILITY. | | | | | | 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE. | | | 11-4.3.11.1 LOCATION AND CONSTRUCTION | | | PLANS DO NOT PROVIDE FIRE SPRINKLERS, | | | PROVIDE DETAILS FOR REQUIRED AREA OF | | | RESCUE ASSISTANCE IF FIRE SPRINKLER | | | PLANS ARE NOT PROVIDED. THIS BUILDING | | | CAN NOT TAKE AREA INCREASES FOR FIRE | | | SPRINKLERED BUILDINGS PER TABLE 500 | | | WITHOUT SPRINKLER PLANS. | | | | | | | | | 6) SHEET A8.2 PLANS INDICATE THE USE OF | | | IMPACT GLAZING FOR WINDOWS & DOORS, NO | | | WIND PRESSURE INFORMATION PROVIDED. | | | PROVIDE ELEVATIONS WITH THE ASSOCIATED | | | POSITIVE & NEGATIVE PRESSURES INTERIOR | | | AND END ZONES. | | | | | | 7) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 8)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN | | | ONE TYPE | | | B) DOORS ALL EXTERIOR DOORS BEING | | | REPLACED, SOLID OR GLAZED | | | C) EXTERIOR LOUVERS | | | D) MULLIONS | | | | | | 9)OK | | | | | | 10A) IT APPEARS THAT STAIRWELL# 7 HAS | | | BEEN DELETED. | | | 10B) NEW COMMENT 11-4.4.2 HEAD ROOM. | | | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, | | | AILES OR OTHER CIRCULATION SPACES SHALL | | | HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM | | | (SEE FIGURE 8(A)). IF VERTICAL CLEARENCE | | | OF AN AREA ADJOINING AN ACCESSIBLE ROUTE | | | IS REDUCED TO LESS THAN 80 IN. (NOMINAL | | | DIMENSION), A BARRIER TO WARN BLIND OR | | | VISUALLY- IMPARED PERSONS SHALL BE | | | PROVIDED. (SEE FIGURE 8(C-1)). | | | | | | 11)11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. CLEAR 18"LOCK SIDE. | | | EVEN IF DOORS ARE EXISTING, | | | 11-4.1.6(2) DUTY TO PROVIDE AN | | | ACCESSIBLE PATH OF TRAVEL TO ALTERED | | | AREAS SHALL BE DEEMED DISPROPORTIONATE | | | TO THE OVERALL ALTERATION WHEN THE COST | | | EXCEEDS 20 % OF THE COST OF THE ALTERA- | | | TION TO THE PRIMARY FUNCTION AREA. | | | (A)(I) AN ACCESSIBLE ENTRANCE | | | (II) AN ACCESSIBLE ROUTE | | | (III) AT LEAST ONE ACCESSIBLE REST- | | | ROOM FOR EACH SEX OR A SINGLE | | | UNISEX RESTROOM | | | (IIII) ACCESSIBLE TELEPHONE | | | (IV) ELEMENTS SUCH AS PARKING, STOR- | | | AGE OR ALARMS. | | | | | | BROKE DOWN BY SHEET: | | | 11A) A1.3 DOOR# 115, DOOR # 130- NO | | | HARDWARE SCHEDULE, SEE INTERIOR SIDE | | | | | | 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR | | | FLOOR SPACE REQUIRED FOR FIXTURES, | | | URANIAL | | | | | | 11C) A1.5 DOOR# 154 | | | | | | 11D) A1.6 DOOR# 119, DOOR# 125 | | | | | | 11E) A1.7 DOOR# 214 | | | | | | 11F) A1.8 DOOR# 241 | | | | | | 11G) A1.9 DOOR# 240, DOOR# 241 | | | | | | 11H) DOOR# 200, DOOR# 203, DOOR# 204 | | | DOOR# 218AB,C&D, DOOR# 222C NOT LABELED | | | DOOR# 224-A NOT LABELED | | | | | | 12) OK. | | | | | | 13) 1204.2 SURROUNDING MATERIALS. THE | | | WALLS AND FLOORS OF ALL PUBLIC REST | | | ROOMS SHALL BE LINED WITH NONABSORBENT | | | MATERIAL TO A HEIGHT OF 4 FT (1219 | | | MM) ABOVE THE FLOOR. | | | | | | 14) PROVIDE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION TABLE 803.3. | | | | | | ********* | | | NEW COMMENTS | | | 15)A1.4 ROOM BY DOOR# 141 DOESN'T SHOW | | | USEAGE? | | | | | | 16) A1.6 ROOM# 133 INDICATES IT IS A | | | STORAGE AND MECHANICAL ROOM? | | | | | | 17) A1.6 LOCATED IN KITCHEN THERE IS A | | | ROOM NO LABELED, POSSIBLY A WALK IN | | | COOLER? | | | | | | 18) A1.6 STAIRWELL# 2 FIRST FLOOR OPENS | | | AND DUMPS UOT RIGHT IN FRONT OF THE | | | GENERATOR. THE EXIT DISCHARGE MUST | | | MAINTAIN A SAFE ROUTE TO THE RIGHT OF | | | WAY. | | | | | | 19) ALL STAIRWELLS DO NOT INDICATE | | | GAURDRAILS AT THE TOP OF THE LANDING. | | | | | | 20) A1.9 DOOR# 233 IS MISSING | | | INFORMATION ON GAURDRAIL? | | | | | | ADDITIONAL COMMENTS MAY APPEAR SINCE A | | | COMPLETE SET OF PLANS WERE NOT PROVIDED | | | FOR THIS REVIEW. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-26 |
Time |
13:51 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2005-08-26 |
Time |
13:19 |
Sent To |
FIRE |
|
| Notes |
| 2005-08-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070627 | | | ADD: 2300 PRESIDENTIAL WAY | | | CONT: CONKLING & LEWIS CONST | | | TEL: (561)833-4441 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)INDICATE BUILDING TYPE: | | | 601.2.1 EVERY BUILDING SHALL BE | | | CLASSIFIED BY THE BUILDING OFFICIAL | | | INTO ONE OF THE TYPES OF CONSTRUCTION | | | AS SET FORTH IN THIS SECTION. | | | | | | TYPE ITYPE V | | | TYPE II1-HOUR PROTECTED | | | TYPE IIIUNPROTECTED | | | TYPE IV TYPE VI | | | 1-HOUR PROTECTED1-HOUR PROTECTED | | | UNPROTECTED UNPROTECTED | | | IF BUILDING IS FIRE SPRINKLERED OR NOT? | | | IF FIRE SPRINKLERED PROVIDE FIRE | | | SPRINKLER PLANS. | | | | | | 3) PROVIDE LIFE SAFETY PLAN, ALSO | | | PROVIDE THE SEATING FOR RESTARAUNTS OR | | | OCCUPANT LOAD WILL BE TAKEN AS 15 NET, | | | FOR PREFUNCTION AREAS 7 NET. | | | | | | 4) PLANS SHEET A5.1 DOOR SCHEDULE, NO | | | FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE | | | DOOR RATING AS "B" OR "C" SEE TABLE | | | 705.1.2. FOR MINUTE & HR RATING. | | | M1106.4 MACHINE ROOMS REQUIRE 45 MIN | | | OPENING PROTECTION. | | | M1106.4 OPENING PROTECTIVES. OPENING | | | PROTECTION BETWEEN THE MACHINERY | | | ROOM AND OTHER OCCUPIED SPACES SHALL BE | | | APPROVED, SELF-CLOSING, TIGHT- | | | FITTING FIRE DOORS WITH A MINIMUM | | | FIRE-RESISTANCE RATING OF 3/4 HOUR. | | | | | | 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE. | | | 11-4.3.11.1 LOCATION AND CONSTRUCTION | | | PLANS DO NOT INDICATE FIRE SPRINKLERS, | | | PROVIDE DETAILS FOR REQUIRED AREA OF | | | RESCUE ASSISTANCE. | | | | | | 6) SHEET A8.2 PLANS INDICATE THE USE OF | | | IMPACT GLAZING FOR WINDOWS & DOORS, NO | | | WIND PRESSURE INFORMATION PROVIDED. | | | PROVIDE ELEVATIONS WITH THE ASSOCIATED | | | POSITIVE & NEGATIVE PRESSURES INTERIOR | | | AND END ZONES. | | | | | | 7) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 8)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN | | | ONE TYPE | | | B) DOORS ALL EXTERIOR DOORS BEING | | | REPLACED, SOLID OR GLAZED | | | C) EXTERIOR LOUVERS | | | D) MULLIONS | | | | | | 9) MISSING A SHEETS 2 SERIES, 3 SERIES, | | | 4 SERIES, 6 & 7 SERIES. | | | | | | 10) PROVIDE HANDRAIL/ GUARDRAIL DETAILS | | | FOR NEW STAIRWELL# 7. | | | | | | 11)11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. CLEAR 18"LOCK SIDE. | | | DOORS, 148B, 153, 172, 237, 241,& 249. | | | | | | 12) PLANS DO NOT PROVIDE ANY INFORMATION | | | AS TO WALL OR FLOOR FINISHES, PROVIDE | | | INFORMATION. | | | | | | 13) 1204.2 SURROUNDING MATERIALS. THE | | | WALLS AND FLOORS OF ALL PUBLIC REST | | | ROOMS SHALL BE LINED WITH NONABSORBENT | | | MATERIAL TO A HEIGHT OF 4 FT (1219 | | | MM) ABOVE THE FLOOR. | | | | | | 14) PROVIDE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION TABLE 803.3. | | | | | | ADDITIONAL COMMENTS MAY APPEAR SINCE A | | | COMPLETE SET OF PLANS WERE NOT PROVIDED | | | FOR THIS REVIEW. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
F |
Date |
2008-05-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-04 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-04 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2008-05-04 16:15:36 | ** DENIED REVIEW ** | | | | | | | | | 1) NOTE: PLEASE KNOW THE GENERATOR WAS NOT INCLUDED IN | | | THE BASE BUILDING INTERIOR RENOVATIONS AND MAY NOT BE A | | | REVISION TO THE RENOVATION PERMIT. | | | ALL WORK SHALL BE UNDER SEPARATE PERMITS, PLANS, FEES. | | | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR NEW | | | GENERATOR TO INCLUDE ALL REQUIRED FOR MINIMUM DESIGN | | | PER NFPA-70, 101, 72, 110 AS APPLICABLE. | | | PLEASE SEE FBC CHAPTER 27, NFPA-70, NFPA-110 FOR | | | REQUIRED SYSTEMS. | | | PLEASE SUBMIT COMPLETE LAYOUT OF THE LOCATION ON PLANS | | | FOR SITE, ELEVATION IF LOCATED IN FLOOD ZONE, | | | STRUCTURAL CONNECTIONS ETC | | | PLEASE SEE NFPA-110, CHAPTER 6 AND 7. | | | | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | 2) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE PROPOSED GENERATOR, TRANSFER EQUIPMENT, | | | FUEL TANKS ETC. | | | PLEASE KNOW THE FUEL TANK WILL BE REVIEW BY OTHER | | | TRADES. | | | 90.7, 110.3, ETC | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE KNOW FOR INFORMATION PLEASE SEE NEC | | | 225.31-225.39, 702.11, 700.12B6, 70111B5. AS THE SYSTEM | | | IS NOT SPECIFIED ALL THREE CODED SECTIONS WERE GIVEN. | | | ALL APPLY TO THE SAME REQUIREMENT. | | | | | | 4) NOTE: PLEASE KNOW IT IS IMPORTANT TO KNOW AS THERE | | | ARE NUMEROUS ITEMS MISSING FOR CODE COMPLIANCE REVIEW, | | | WHEN ALL PLANS, DOCUMENTS ETC ARE SUBMITTED FOR REVIEW | | | THERE MAY VERY WELL BE NEW REVIEW COMMENTS WHICH CAN | | | NOT POSSIBLY BE MADE AT THIS TIME. THE PLANS SUBMITTED | | | ARE NOT COMPLETE AND IS MISSING A SUBSTANTIAL AMOUNT OF | | | INFORMATION NEEDED FOR REVIEW. | | | | | | 5) NOTE: PLEASE KNOW THE COMPLETE VALUE FOR PROPOSED | | | SCOPE OF WORK SHALL BE DECLARED ON PERMIT APPLICATION. | | | PLEASE KNOW WORK FOR | | | WALLS/SLAB/GENERATOR/EQUIPMENT/ELECTRICAL ETC SHALL ALL | | | BE INCLUDE WHETHER OR NOT ANY OF THESE ITEMS SUCH AS | | | EQUIPMENT IS OWNER SUPPLIED. | | | THIS INCLUDES GENERATOR, ATS, TANK, ETC. | | | FBC 108.3 | | | | | | 6) NOTE: PLANS AS SUBMITTED DO NOT COORDINATE. | | | FOR EXAMPLE: | | | PLEASE SEE PLANS SHOWS NEW CHAIN LINK FENCE AROUND THE | | | GENERATOR YET NOTES CLEARLY STATE THERE IS GOING TO BE | | | A NEW BLOCK ENCLOSURE? | | | PLEASE BE SURE ALL MINIMUM CLEARANCES AND VENTILATION | | | PER NFPA-110 CHAPTER 7 AND NEC 110.26 ARE MET ALONG | | | WITH MINIMUM REQUIRED PER MANUFACTURE. | | | | | | 7) NOTE: WHEN NEW PLANS ARE COMPLETED PLEASE BE SURE | | | THE ADDRESS OF THE PROJECT COORDINATES WITH THE APPLIED | | | LOCATION. | | | FOR EXAMPLE: | | | PLEASE SEE PLANS CALL FOR 230 PRESIDENTIAL WAY NOT | | | 2300. | | | FAC 61G1-16.004, 61G15-23.002 | | | FBC 106.5 | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
F |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-17 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-17 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2007-05-17 12:02:59 | ** UNSAT ** | | | | | | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA | | | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH. | | | | | | * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | | | | 1) NOTE: PLEASE SUBMIT REVISED UPDATED REVISIONS DONE | | | BY THE DESIGNER OF RECORD AS REQUIRED UNDER FS 471, FAC | | | 61G15-23.002 | | | PLEASE KNOW THAT CHANGES MADE IN PENCIL ARE NOT | | | PERMITTED ON ANY PLANS. | | | PLEASE SEE THE REVISIONS SHALL BE CLOUDED/TRIANGLES AND | | | REVISED IN TITLE BLOCKS. | | | PLEASE SEE THE PLANS AS DATED ARE ALREADY ON FILE WITH | | | THE CITY. | | | | | | | | | ** PLEASE COORDINATE ALL REVISIONS AND SUBMIT AS | | | REQUESTED. | | | | | | *** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-14 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-14 |
Time |
10:18 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-26 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-26 |
Time |
12:13 |
Sent To |
PC |
|
| Notes |
| 2006-12-26 14:40:41 | ** UNSAT *** | | | | | | 1) NOTE: PLEASE COMPLETE RISER WITH NEW CONDUIT SIZE | | | BEING STUBBED OUT FOR FUTURE GENERATOR. PLEASE SEE AS | | | THE CONDUCTOR SIZES FOR FUTURE AND FOR EDP ARE NOT | | | SHOWN ON PLANS AS SUBMITTED, UNABLE TO VERIFY AT THIS | | | TIME. | | | 240.4, 310.16, TABLE(S) CHAPTER 9. | | | | | | 2) NOTE: PLEASE SEE LOAD CALCULATIONS ON THE BOTTOM | | | PART OF DPB SHOW CONNECTED LOAD AT 221 KVA AND DEMAND | | | LOAD THE SAME AT 221 KVA, YET THE DEMAND LOAD ON THE | | | MDP IS OF THE DEMAND LOAD OF 209KVA. | | | PLEASE CORRELATE. | | | FBC 104.1.2 | | | ADMIN SECTION. | | | | | | 3) NOTE: PLEASEKNOW BASED ON AS MANY REVISION ARE | | | BEING DONE TO THIS JOB AND SCOPE OF WORK INVOLVED, | | | PLEASE KNOW IF THE SERVICE ENTRANCE CONDUCTORS WHICH | | | HAVE BEEN SHOWN AS EXISTING TO THE EXISTING 2500A MCB | | | MDP ARE RE-PULLED OR TOUCHED IN ANY WAY, THEY WILL BE | | | REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SEE 240.4(C) | | | WHICH HAS ALWAYS REQUIRED CONDUCTORS FEEDING DEVICES | | | RATED OVER 800A?S TO MEET OR EXCEED THE RATING THAT | | | DEVICE. | | | PLEASE KNOW THIS WAS NOT A CHANGE IN ANY CODE OVER THE | | | PAST 15 YRS AND EVEN IF EXISTING, IF THEY ARE RE-PULLED | | | AS NOTED FOR ANY REASON OR CHANGED, THEY WILL BE | | | REQUIRED TO MEET THE 2500A BREAKER OR BREAKER WOULD BE | | | REQUIRED TO BE BROUGHT DOWN TO 2000A OCP. | | | 90.4 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-16 |
Time |
21:02 |
Sent To |
PC |
|
| Notes |
| 2006-10-18 11:26:59 | RISER TO BE REVISED AS SPECS INDICATE A 800A ATS AND | | | THE PLANS INDICATE 500A'S. | | 2006-10-16 21:02:10 | CALLED AND LEFT MESSAGE FOR MR GREG LEWIS TO CALL, AS | | | NO SPECS/ MANUFACTURE CUT SHEETS WERE SUBMITTED FOR THE | | | ATS AS PREVIOUSLY REQUESTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-30 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-30 |
Time |
16:50 |
Sent To |
FIRE |
|
| Notes |
| 2006-09-30 00:00:00 | *** UNSAT FOR REV #6 ** | | | | | | 1) NOTE: PLEASE SEE "PLAN/REVISION FORM | | | AS BEING SUBMITTED AND FILLED OUT BY | | | CONTRACTOR IS FROM "2001" PLEASE OBTAIN | | | NEW FORM ONLINE OR IN OUR OFFICE AS THE | | | FEES REPRESENTED ON THESE OLD FORMS ARE | | | NO LONGER VALID. | | | | | | 2) NOTE: PLEASE SEE SCOPE OF WORK AT THE | | | LOCATION OF THIS JOB WAS ORIGINALLY | | | SUBMITTED AS 1.1 MIL AND DUE TO CHANGES | | | IN SCOPE AND WORK BEING PERFORMED, | | | PLEASE ADJUST THE APPLIED VALUE FOR | | | SCOPE OF WORK BASED ON ACTUAL VALUE. | | | IT HAS COME TO THE ATTENTION OF THIS | | | OFFICE THE VALUE HAS EXCEEDED THE OLD | | | VALUE SUBSTANTIALLY. PLEASE ADJUSTOR | | | PROVIDE ALL SIGNED CONTRACTS FOR ALL | | | TRADES AND SCOPES AS STATED IN THE FBC | | | 108.3(2004) OR 106.3.5 (2001) . | | | | | | 3) NOTE: PLEASE SEE REVISED RISER IS NOW | | | INDICATING A NEW ATS WHICH WAS NOT PART | | | OF THE ORIGINAL SCOPE INFACT THE SYSTEM | | | WAS STATED AS BEING REMOVED. PLEASE | | | SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR | | | THIS EQUIPMENT FOR REVIEW. PLEASE ALSO | | | KNOW, ANY PERMIT FOR A GENERATOR WILL BE | | | REQUIRED TO BE SUBMITTED SEPARATELY AND | | | WILL ALSO REQUIRE THE SAME SPECS. | | | 110.3, 90.7, | | | FBC 106.1.2 ADMIN SECT. | | | | | | 4) NOTE: PLEASE CORRELATE RISER WITH | | | PANEL FOR NEW FEED TO PANEL "N" FROM | | | "DPB". PLEASE SEE OCP. | | | 106.1.2 | | | | | | 5) NOTE: PLEASE ALSO KNOW, THE PANEL "N" | | | COULD NOT BE LOCATED ON POWER PLANS | | | SUBMITTED. THIS REVIEWER HAS LOOKED | | | THREE TIMES, AS RISER SHOWS THIS LOCATE | | | DON THE FIRST FLR. PLEASE INFORM WHERE | | | THIS IS IN A REPSONSE LTR, OR PLEASE | | | INDICATE ON PLANS. | | | 106.1.2 | | | | | | 6) NOTE: PLEASE LABEL AND SHOW ALL PANEL | | | SIZE ON BOTH RISERS ON 5.1.1, AND 5.2. | | | AS OTHERS ARE SHOWN . (100A, 300A ETC ). | | | | | | 7) NOTE: PLEASE SEE PLANS INDICATE A | | | "SERVER ROOM"? IS THIS INDEED AN "IT" | | | ROOM? | | | PLEASE SEE CHAPTER 2 OF NFPA-75 FOR | | | CLASSIFICATION REQUIREMENTS AND IF AN IT | | | ROOM PLEASE SEE ALL REQUIREMENTS IN | | | NFPA-75 AND SEE NEC 645. | | | | | | *** PLEASE KNOW, PLANS ARE BEING ROUTED | | | TO FIRE MARSHAL'S OFFICE FOR FIRE | | | REVIEW, PLEASE BE AWARE IF LIGHTING | | | PLANS ARE OK WITH FIRE REVIEW, THEN | | | THOSE SHEETS WILL BE STAMPED, HOWEVER | | | RISER , PANEL SCHEDULE, AND POWER PLANS | | | NEED TO BE REVISED. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
N |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-21 |
Time |
20:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-21 |
Time |
20:56 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | PLANS SUBMITTED FOR REVISIONS OF "A" | | | SHEETS ONLY CONTAIN "REFLECTED CEILING" | | | PLANS FOR ELECTRICAL. NO ELEC APPLIES. | | | PLEASE SEE PREVIOUS REVIEW DATED 9/9/06 | | | AS THE ELECTRICAL CONTRACTOR CALLED NOT | | | TO REVIEW ELECTRICAL REVISIONS #6, AS | | | THEY WERE BEING CHNAGED OUT. TO DATE, NO | | | NEW ELECTRICAL PLANS AHVE BEEN | | | SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-09 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-09 |
Time |
18:45 |
Sent To |
PC |
|
| Notes |
| 2006-09-09 00:00:00 | ** NOTE ** | | | | | | | | | 1( RECEIVED CALL FROM ELECTRICAL | | | CONTRACTORNOT TO REVIEW PLANS/ | | | REVISIONS SUBMITTED (#6). | | | PLANS ARE BEING PLACED OUTFRONT AND FEE | | | PAID FOR REVISIONS WILL CARRY OVER TO | | | THE NEXT SET OF REVISIONS FOR THE SAME | | | AMOUNT OF SHEETS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER. | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-20 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-20 |
Time |
11:30 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-06 |
Time |
20:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-06 |
Time |
19:39 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | ****** UNSAT ****** | | | | | | 1) NOTE: PLEASE SEE "ID" PLANS | | | SUBMITTED. PLEASE SEE NUMEROUS SHEETS | | | ARE INDEED SEALED PHOTO-COPIES OF THE | | | DESIGNER'S SIGNATURE WHICH IS REQUIRED | | | TO BE ORIGINAL UNDER FS 481.221 | | | PLEASE SEE ABOVE STATUE WHICH ALSO | | | REQUIRES THE DESIGN PROFESSIONAL TO DATE | | | SAID PLANS WHEN SIGNING AND SEALING. | | | PLEASE SEE SOME SHEETS DO CONTAIN AN | | | ORIGINAL SIGNATURE, AND SOME APPEAR TO | | | SHOW SOME SORT OF "INITIAL"?? | | | PLEASE KNOW, ALL SHEET SHALL CONTAIN THE | | | ORIGINAL LEGAL SIGNATURE OF THE DESIGN | | | PROFESSIONAL. | | | | | | 2) NOTE: PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON SAID TITLE BLOCKS | | | FOR THE FIRM AS SHOWN AS REQUIRED PER | | | FAC 61G1-16.004, AND FS 481.219(1)(2) | | | ETC. | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER, MISSING PRINTED | | | NAME AND LICENSE NUMBER. | | | | | | 3) NOTE: PLEASE SEE THAT THE ID PLANS DO | | | NOT CORRELATE ELECTRICALLY WITH THE | | | PLANS SUBMITTED FOR REVIEW FROM THE | | | ELECTRICAL DESIGN PROFESSIONAL. | | | PLEASE CORRELATE AND SUBMIT. | | | PLEASE SEE LIGHTING PLANS SUBMITTED BY | | | THE ID. | | | | | | ** PLEASE SEE COMMENTS #1 AND #2 DO NOT | | | APPLY TO THE ELECTRICAL ENGINEER OF | | | RECORD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-04-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-04 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-03 |
Time |
16:00 |
Sent To |
I |
|
| Notes |
| 2006-04-04 00:00:00 | PLANS REDLINED: | | | | | | | | | E-4.1, | | | THE "KNOX BOX" LOCATION IS TO VERIFIED | | | AND INSTALLED AT A LOCATION DETERMINED | | | BY THE FIRE MARSHAL'S OFFICE. | | | THIS LOCATION SHALL CONTAIN ALL NEEDED | | | ACCESS KEYS, INCLUDING MAIN ELECTRICAL | | | ROOM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-28 |
Time |
20:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-27 |
Time |
21:12 |
Sent To |
|
|
| Notes |
| 2005-12-28 00:00:00 | ********** UNSAT 2ND REVIEW ********** | | | | | | ** PLEASE SEE THERE ARE NOTES FROM | | | ORIGINAL REVIEW WHICH STILL NEED TO BE | | | ADDRESSED. | | | ** PLEASE SEE SOME NEW NOTES DUE TO | | | CHANGES MADE TO PLANS, AND ITEMS BEING | | | REMOVED FROM SAID DRAWINGS. | | | | | | ** PLEASE SEE FIRST PART OF NOTES BELOW | | | HAVE BEEN TAKEN DIRECTLY FROM PREVIOUS | | | REVIEW. | | | | | | | | | 1)NOTE: NOTE #1 NO, | | | PLEASE SEE MISSING INFORMATION REQUIRED | | | ON TITLE BLOCK FOR ENGINEERING FIRM. | | | PLEASE SEE 61G15-23.002 FOR MISSING | | | PRINTED NAME AND PRINTED LICENSE # FOR | | | ENGINEER. | | | PLEASE SEE ARCHITECTS TITLE BLOCK FOR | | | ALL SHEETS SHALL ALSO CONTAIN THE | | | PRINTED NAME AND LICENSE # FOR ARCH. | | | 61G1-16.004 | | | | | | THIS SEE THIS IS REQUIRED FOR ALL SHEETS | | | AND FOR ALL TRADES WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 2)NOTE: NOTE #2 OK. | | | | | | | | | 3)NOTE: NOTE#3 NO, PLEASE SEE MOST | | | CIRCUITING IS NOW SHOWN ON PLANS, | | | HOWEVER SOME STILL APPEAR TO BE MISSING. | | | PLEASE SEE NEW NOTES PERTAINING TO SOME | | | ERRORS IN CIRUITING AND CORRELATION WITH | | | PANEL SCHEDULES ETC. | | | ** | | | PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | PLEASE SEE ALL CONTROL WIRING FOR | | | LIGHTING PLANS. | | | PLEASE SEE LIGHTING PLANS DO NOT SEEM TO | | | BE COMPLETE AT THIS TIME? | | | PLEASE SEE SOME AREAS DO NOT INDICATE | | | ANY LIGHTING? WOMENS RESTROOM? | | | PLEASE SEE THIS MAINLY SEEMS TO BE | | | MISSING FROM LIGHTING PLANS. | | | **PLEASE ALSO SEE CIRCUTING FOR A/C | | | SYSTEMS, PANELS TEND TO BE INDICATED , | | | HOWEVER NOT THE CIRCUITING. | | | | | | 4)NOTE: OK, HOWEVER SEE NOTE #5, AS | | | AREAS NEED TO BE VERIFIED FOR EGREE ETC. | | | SEE NEW NOTES> | | | ** | | | PLEASE SEE 700.12E FOR CIRCUITING | | | OF EM/EXT LTS. THE BRANCH CIRCUIT | | | FEEDING THE UNIT EQUIPMENT SHALL BE THE | | | SAME BRANCH CIRCUIT AS THAT SERVING THE | | | NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. | | | | | | 5)NOTE: NOTE #5, NO, INFACT ALL OF THE | | | AREAS AND ROOM DESIGNATIONSWHICH WERE | | | SHOWN ON ORIGINAL PLANS HAVE NOW BEEN | | | REMOVED MAKING IT IMPOSSIBLE TO REVIEW | | | SOME THINGS FOR CODE COMPLIANCE. PLEASE | | | SEE NEW COMMENTS. | | | ** | | | PLEASE INCLUDE ROOM/AREA | | | DESIGNATIONS ON PLANS. THIS SHOULD BE ON | | | ALL SHEETS. | | | 215.5 | | | | | | 6)NOTE: NOTE #6 OK. | | | | | | | | | 7)NOTE: NOTE #7 OK,NO, AS THIS AREA HAS | | | NOW BEEN REMOVEDFROM PLANS AND THE KE | | | PLANS NOW MENTIONS CIRCUITING. | | | PLEASE SEE KE PLANS WHICH MENTIONS THESE | | | ARE PRELIMINARY PLANS AND SHOULD NOT BE | | | USED?? | | | ** | | | PLEASE SHOW ALL CIRCUITING ON | | | KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE | | | CORRELATE THIS WITH EQUIPMENT SCHEDULE | | | SUBMITTED AND PANEL SCHEDULES. | | | | | | 8)NOTE: NOTE #8 NO,IT IS UNCLEAR WHERE | | | ANY CHANGES HAVE BEEN MADE FOR THIS. | | | PLEASE SEE NOTE #5 MENTIONS GFI FOR | | | UTILITY OUTLETS? | | | ** | | | PLEASE SEE 2002 NEC 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | 9)NOTE: NOTE #9 NO?? SEE NOTES WITH | | | RESPECT TO ROOM AND AREA DESIGNATIONS | | | BEING REMOVED. | | | ** | | | PLEASE SHOW AND INDICATE ELEVATOR | | | EQUIPMENT ROOM. PLEASE SEE | | | STATE ELEVATOR CODE , NO OTHER EQUIPMENT | | | UNLESS PART OF THE DESIGNATED ELEVATOR | | | EQUIPMENT SHALL BE IN ELEVATOR ROOMS. | | | PLEASE SEE 620.23,620.24, PLEASE VERIFY | | | AND SHOW IF THESE ARE TO BE NEW OR | | | EXISTING. | | | | | | 10)NOTE: NOTE #10 NO, SAME AS PREVIOUS | | | NOTES. PLEASE ALSO SEE NFPA-101 7.8.1.3, | | | 7.9.2 WHICH MAY ALSO BE USED IN | | | REFERENCE IN THESE AREA NEED ING BATTERY | | | BACK UP FIXTURES. | | | ** | | | PLEASE SEE 700.16 FOR | | | ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR | | | RMS. | | | | | | 11)NOTE: NOTE # 11, NO , UNCLEAR AS A | | | "KEYED NOTE" ON RISER (NOTE #1 ON 5.1 | | | MENTIONS PANEL "D" WAS NOT ABLE TO BE | | | LOCATED FOR WHERE FEED COMES FROM,,ETC. | | | PLEASE KNOW, IT WAS DICUSSED WITH | | | ENGINEER OF RECORD THIS WOULD BE A | | | "PROVISO" IN WHICH THE INFORMATION WOULD | | | BE REQUIRED BEFORE ANY INSPECTIONS WERE | | | MADE. | | | PLEASE KNOW AT THAT TIME IT WAS | | | IMPERATIVE TO START PROJECT SO THIS WAS | | | AGREED. PLEASE SEE RISER STILL SHOWS | | | THIS PANEL "D" COMING FROM PANEL "M"? | | | WAS IT DISCOVERED IN THE "DEMO WORK" | | | THAT THIS PANEL IS FED FROM "M" AND | | | REASON WHY IT IS STILL SHOWN FROM "M"? | | | | | | THE FIRST REVIEW WAS DONE IN JULY 05 AND | | | THE AMOUNT OF TIME AND DEMO WORK SINCE | | | SHOULD REVEALED THIS INFORMATION. | | | | | | | | | 12)NOTE: NOTE #12 NO?? COULD NOT LOCATE. | | | ** | | | PLEASE SHOW ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR ARE TO BE SHOWN | | | @125% | | | 215.3,230.42 ETC, | | | | | | | | | | | | **************************************** | | | THE FOLLOWING COMMENT HAS TO DO WITH | | | ELECTRICAL RISER DIAGRAM,ONE-LINE | | | DIAGRAM AND PANEL SCHEDULES. | | | **************************************** | | | | | | 13)NOTE: NOTE #13 NO, MOST OF THESE | | | ITEMS WERE CORRECTED HOWEVER PLEASE SEE | | | TC SHOWN AS 70A AND 100A ON ONE-LINE AND | | | RISER. | | | PLEASE SEE A NEW PANEL BR1 IS SHOWNON | | | ONE-LINE, RISER, PANEL "LL" AND NOTED IN | | | NOTES, HOWEVER NO PANEL SCHEDULE, | | | CIRCUITING SUBMITTED TO VERIFY. | | | ** | | | | | | PLEASE CORRELATE ALL PANELS ON | | | ONELINE, RISER AND PANEL SCHEDULES | | | SUBMITTED. | | | PLEASE SEE THERE ARE TOO NUMEROUS ITEMS | | | WHICH DO NOT MATCH UP WITH EACH OTHER. | | | PLEASE SEE AMERAGES OF PANELS SHOWN | | | DIFFERENTLY ON EACH, SEE SOME SHOWN AS | | | 225A AND 300A ETC. | | | PLEASE SEE SOME PANELS BEING SHOWN BEING | | | FED FROM"DPB", YET OTHER SHEETS SHOW | | | THESE PANELS FROM "DPA" AND YET PANEL | | | SCHEDULES FOR THESE SHOW SOMETHING | | | ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA | | | AND RISER SHOWS FROM "DPB" ETC. | | | PLEASE SEE SOME PANEL SHOWN AS ONE SIZE | | | MLO, YET INDICATE ON PANEL SCHEULE SHOWS | | | A DIFFERENT SIZE.? | | | PLEASE SEE PANELS LABELED AS ONE THING | | | ON ONE-LINE ANDSOEMTHING ELSE ON RISER | | | DIAGRAM AND PANEL SCHEDULE? KDP, KDP1, | | | 600A/ 500A??? ETC,, | | | PLEASE SEE POOL RM PANEL, PANEL N ETC. | | | PLEASE SEE ONE LINE SHOWS DISCONNECT | | | FROM WW MDP TO KDP/KDP1, YET RISER DOES | | | NOT SHOW THIS? | | | PLEASE SEE SOME PANELS SHOWN AS MLO, YET | | | ALSO SHOWS HAVING A MAIN? | | | PLEASE INCLUDE ALL INFORMATION FOR ALL | | | DISCONNECTS ON RISER. | | | PLEASE LABEL ALL PANELS,DISC'S, MDP ETC | | | ON RISER. | | | | | | ******************************** | | | NEW NOTES DUE TO CHANGES AND INFORMATION | | | BEING CHANGED AND/OR SUBMITTED. | | | | | | 1)NOTE: PLEASE SEE ORIGINAL NOTES WITH | | | RESPECT TO SHOWING ALL CIRCUITING,PLEASE | | | SEE MOST CIRCUITING IS NOW SHOWN, | | | HOWEVER PLEASE SEE SOME OF THE FOLLOWING | | | WHICH DO NOT SEEM TO CORRELATE ETC. | | | | | | *PLEASE SEE CIRCUITING ON PANEL "N", | | | MOST A/C EQUIPMENT IS NOTED AS BEING | | | 3-POLE ITEMS, HOWEVER CIRCUITING ON | | | PANEL SCHEDULES, SHOWS ITEMS TAKING THE | | | SPACE AND NUMBERED AS 2-POLE? | | | | | | *PLEASE SEEE-2.1A, SHOWS 86 AHU-9 TO | | | DPB-1, YET DPB, IS BLANK AT THIS | | | LOCATION. | | | | | | *PLEASE SEE E-2.1.C UNIT LABELED AS | | | EDH-1, PANEL "N", YET PANEL "N" DOES NOT | | | SHOW THIS. ALTHOUGH, THERE SEEMS TO BE A | | | UNIT WHICH HAS THE SAME KW RATING ETC, | | | HOWEVER IT IS LABELED"DEH", IS THIS | | | THE SAME AND ONLY A MISPRINT? | | | | | | *PLEASE SEE E-2.1.C WHICH SHOWS 5AHU-7 | | | TO "N", YET THIS COULD NOT BE LOCATED ON | | | "N"? | | | | | | *PLEASE SEE E-2.2A, 86AHU-5 TO D-7,9,11, | | | NEW OR EXSITING. ?AS MANY NEW AREAS | | | ARE NOW SHOWN SHADED, WHICH WERE NOT ON | | | ORIGINAL PLANS? | | | | | | 2)NOTE: PLEASE SEE NOTES ON PLANS | | | CONTAIN NUMERICAL NOTES TO SEE 4.1 FOR | | | PANELS ETC, HOWEVER THIS ROOMS SEEMS TO | | | BE MISSING IDENTIFICATION ETC ETC. | | | | | | 3)NOTE: PLEASE SEE PLANS NOW HAVE NOTES | | | ADDED FOR SOME ITEMS. PLEASE KNOW, NOTES | | | BEING ADDED TO PLANS DO NOT ALLEAVIATE | | | THE DESIGN PROFESSIONAL FROM PROVIDING | | | THE TECHNICAL INFORMATION NEEDED. PLEASE | | | SEE NOTE WHICH MENTIONS TO SEE ARCHITECT | | | TO DETERMINE HEIGHTS ETC. PLEASE KNOW, | | | THESE THINGS SHOULD BE ON SAID PLANS. | | | | | | 4)NOTE: PLEASE SEE PANEL DPB WHICH SHOWS | | | THE DE-RATED LOAD FROM PANEL "N", WHICH | | | SEEMS TO HAVE BEEN DER-RATED ONCE AGAIN | | | FOR DPB CALCS??? | | | PLEASE CLARIFY THIS. | | | | | | 5)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL AND REPEAT COMMENTS. | | | PLEASE KNOW, IF PLANS COME BACK WITH ANY | | | OF THE SAME COMMENT SFROM THE FIRST | | | REVIEWS NOT ADDRESSED FOR CODE | | | COMPLIANCE, THE STATE STATUES, REQUIES A | | | 4X FEE BE ASSESSED FOR THE PLAN REVIEW | | | PORTION OF THE BASE PERMIT FEE. (30% X4) | | | TO THE DESIGN PROFESSIONAL FOR REPEAT | | | COMMENTS. | | | PLEASE KNOW, IT IS STRONGLY SUGGESTED A | | | MEETING BE HELD TO GO OVER COMMENTS AS | | | NOT TO HAVE THIS IMPLEMENTED. | | | THIS AMOUNT WOULD COME TO $13,800.00. | | | PLEASE KNOW THE 10% RE-SUB WILL BE DUE | | | WHEN PLANS COME BACK IN FOR THIRD | | | REVIEW. | | | ** PLEASE KNOW, ONE COPY OF THIS | | | SUBMITTIAL OF ELECTRICAL PLANS WILL BE | | | RETAINED AND PLACED WITH PLANS FROM | | | ORIGINAL REVIEW WHICH WERE ALSO | | | REETAINED. | | | | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS | | | FROM OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | **PLEASE GO THROUGH ALL PLANS PANELS, | | | DISCONNECTS ETC AND CORRELATE. | | | | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS FROM OTHER | | | TRADES SHOULD BE SUBMITTED FOR | | | REFERENCE. THIS WILL NOT BE REQUIRED OF | | | VOIDED ELECTRICAL SHEETS AS ONE SET IS | | | ALREADY RETAINED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-12-27 00:00:00 | REVIEW WILL GO INTO "F" STATUS, REVIEW | | | IN PROGRESS. | | | NOTES TO FOLLOW. | | 2005-12-26 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW. | | | NO RESPONSE LETTER(S) FROM DESIGN | | | PROFESSIONALS SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-28 |
Time |
06:19 |
Rev Time |
7.00 |
| Received By |
dpalmer |
Date |
2005-07-27 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | ********** UNSAT ************ | | | | | | | | | 1)NOTE: PLEASE SEE MISSING INFORMATION | | | REQUIRED ON TITLE BLOCK FOR ENGINEERING | | | FIRM. PLEASE SEE 61G15-23.002 FOR | | | MISSING PRINTED NAME AND PRINTED LICENSE | | | # FOR ENGINEER. | | | PLEASE SEE ARCHITECTS TITLE BLOCK FOR | | | ALL SHEETS SHALL ALSO CONTAIN THE | | | PRINTED NAME AND LICENSE # FOR ARCH. | | | 61G1-16.004 | | | | | | THIS SEE THIS IS REQUIRED FOR ALL SHEETS | | | AND FOR ALL TRADES WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 2)NOTE: PLEASE SEE E1.A, APPEARS SOME | | | IMAGES ARE "SHIFTED" OR "DOUBLE"? | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | PLEASE SEE ALL CONTROL WIRING FOR | | | LIGHTING PLANS. | | | PLEASE SEE LIGHTING PLANS DO NOT SEEM TO | | | BE COMPLETE AT THIS TIME? PLEASE SEE | | | MISSING "KEYED NOTES" ETC. | | | PLEASE SEE SOME AREAS DO NOT INDICATE | | | ANY LIGHTING? WOMENS RESTROOM? | | | PLEASE SEE THIS MAINLY SEEMS TO BE | | | MISSING FROM LIGHTING PLANS. | | | PLEASE ALSO SEE CIRCUTING FOR A/C | | | SYSTEMS, PANELS TEND TO BE INDICATED , | | | HOWEVER NOT THE CIRCUITING. | | | | | | 4)NOTE:PLEASE SEE 700.12E FOR CIRCUITING | | | OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING | | | THE UNIT EQUIPMENT SHALL BE THE SAME | | | BRANCH CIRCUIT AS THAT SERVING THE | | | NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. | | | | | | 5)NOTE: PLEASE INCLUDE ROOM/AREA | | | DESIGNATIONS ON PLANS. THIS SHOULD BE ON | | | ALL SHEETS. | | | 215.5 | | | | | | 6)NOTE:PLEASE SEE SOME PANELS SEEM TO | | | INDICATE A COUNTERTOP IN FRONT OF | | | ELECTRICAL PANELS?? PLEASE SEE BAR | | | PANELS, E2.1.A? PLEASE SEE OUTLINED | | | AREAS ON PLANS.?? F, G, GA, J,,,ETC. | | | | | | 7)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | KITCHEN ELECTRICAL PLAN FOR ALL. PLEASE | | | CORRELATE THIS WITH EQUIPMENT SCHEDULE | | | SUBMITTED AND PANEL SCHEDULES. | | | | | | 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | 9)NOTE: PLEASE SHOW AND INDICATE | | | ELEVATOR EQUIPMENT ROMM. PLEASE SEE | | | STATE ELEVATOR CODE , NO OTHER EQUIPMENT | | | UNLESS PART OF THE DESIGNATED ELEVATOR | | | EQUIPMENT SHALL BE IN ELEVATOR ROOMS. | | | PLEASE SEE 620.23,620.24, PLEASE VERIFY | | | AND SHOW IF THESE ARE TO BE NEW OR | | | EXISTING. | | | | | | 10)NOTE: PLEASE SEE 700.16 FOR | | | ELECTRICAL RMS, EQUIPMENT RMS, ELEVATOR | | | RMS. | | | | | | 11)NOTE: PLEASE SEE RISER MENTIONS ? FOR | | | PANEL "D". THIS INFORMATION IS REQUIRED | | | AT THIS TIME. | | | | | | 12)NOTE: PLEASE SHOW ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR ARE TO BE SHOWN | | | @125% | | | 215.3,230.42 ETC, | | | | | | | | | | | | **************************************** | | | THE FOLLOWING COMMENT HAS TO DO WITH | | | ELECTRICAL RISER DIAGRAM,ONE-LINE | | | DIAGRAM AND PANEL SCHEDULES. | | | **************************************** | | | | | | 13)NOTE: PLEASE CORRELATE ALL PANELS ON | | | ONELINE, RISER AND PANEL SCHEDULES | | | SUBMITTED. | | | PLEASE SEE THERE ARE TOO NUMEROUS ITEMS | | | WHICH DO NOT MATCH UP WITH EACH OTHER. | | | PLEASE SEE AMERAGES OF PANELS SHOWN | | | DIFFERENTLY ON EACH, SEE SOME SHOWN AS | | | 225A AND 300A ETC. | | | PLEASE SEE SOME PANELS BEING SHOWN BEING | | | FED FROM"DPB", YET OTHER SHEETS SHOW | | | THESE PANELS FROM "DPA" AND YET PANEL | | | SCHEDULES FOR THESE SHOW SOMETHING | | | ELSE?? PLEASE SEE "DPA" TO G,GA,B, 2BA | | | AND RISER SHOWS FROM "DPB" ETC. | | | PLEASE SEE SOME PANEL SHOWN AS ONE SIZE | | | MLO, YET INDICATE ON PANEL SCHEULE SHOWS | | | A DIFFERENT SIZE.? | | | PLEASE SEE PANELS LABELED AS ONE THING | | | ON ONE-LINE ANDSOEMTHING ELSE ON RISER | | | DIAGRAM AND PANEL SCHEDULE? KDP, KDP1, | | | 600A/ 500A??? ETC,, | | | PLEASE SEE POOL RM PANEL, PANEL N ETC. | | | PLEASE SEE ONE LINE SHOWS DISCONNECT | | | FROM WW MDP TO KDP/KDP1, YET RISER DOES | | | NOT SHOW THIS? | | | PLEASE SEE SOME PANELS SHOWN AS MLO, YET | | | ALSO SHOWS HAVING A MAIN? | | | PLEASE INCLUDE ALL INFORMATION FOR ALL | | | DISCONNECTS ON RISER. | | | PLEASE LABEL ALL PANELS,DISC'S, MDP ETC | | | ON RISER. | | | | | | PLEASE GO THROUGH ALL PANELS,DISCONNECTS | | | ETC AND CORRELATE. | | | | | | PLEASE KNOW, DUE THE NUMBER OF ITEMS ON | | | ELECTRICAL PLANS, ONE COPY OF ELECTRICAL | | | PLANSHAVE BEEN REMOVED FROM ONE SET. | | | THIS IS BEING HELD FOR REFERENCE. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS FROM OTHER | | | TRADES SHOULD BE SUBMITTED FOR | | | REFERENCE. THIS WILL NOT BE REQUIRED OF | | | VOIDED ELECTRICAL SHEETS AS ONE SET IS | | | ALREADY RETAINED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-07-27 00:00:00 | IN ELEC FOR REVIEW. | | | PLANS WILL BE IN FAILED STATUS,NOTES TO | | | FOLLOW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-27 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-27 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2008-05-27 14:38:14 | ***DENIED*** | | | | | | PLEASE SEE ELECTRICAL COMMENTS: | | | | | | 1) SEPARATE PLANS AND PERMIT REQUIRED FOR GENERATOR. | | | | | | 2) PLEASE INCLUDE SPECIFICATION SHEETS FOR GENERATOR | | | AND ALL ASSOCIATED EQUIPMENT WITH SUBMITTAL. | | | | | | 3) INCLUDE INFORMATION REGARDING FUEL STORAGE TANK | | | CONSTRUCTION, CAPACITY AND LOCATION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-17 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-17 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2006-10-17 12:58:16 | *****APPROVED***** | | | | | | | | | | | | | | | **REVISED ELECTRICAL PLAN SHEETS REVIEWED.** |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-22 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-22 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2006-09-22 00:00:00 | REVISION DATED 7/21/06. | | | | | | 1) IN ADDITION TO THE REVISED SHEETS | | | INDICATED IN THE INDEX OF DRAWINGS, IT | | | APPEARS THAT LS.2 AND FP SHEETS HAVE | | | ALSO BEEN REVISED. ANY REVISIONS TO THE | | | FIRE SPRINKLER SYSTEM SHALL BE REFLECTED | | | ON THE SHOP DRAWINGS ONCE THE FIRE | | | SPRINKLER PERMIT HAS BEEN ISSUED. | | | | | | 2) NO FIRE SPRINKLER COVERAGE IS NOTED | | | IN BATHROOMS. PLEASE BE SURE TO | | | ILLUSTRATE ON SEPARATE SHOP DRAWINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-14 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-14 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2006-07-14 00:00:00 | REVISION DATED 6/30/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-05 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-05 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-01-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-01-04 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-01-04 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2006-01-04 00:00:00 | 1. ALL EXIT DOORS SHALL BE PROPERLY | | | IDENTIFIED BY ILLUMINATED EXIT SIGNS. | | | | | | 2. SUFFICIENT EMERGENCY LIGHTS SHALL BE | | | PROVIDED THROUGHOUT THE CLUBHOUSE. | | | | | | 3. IT APPEARS THAT NO PREVIOUS COMMENTS | | | FROM FIRE RESCUE WERE ADDRESSED. | | | | | | 4. THE RELOCATION OF THE FIRE ALARM | | | CONTROL PANEL, DIALER, AND NEW EQUIPMENT | | | REQUIRES A PERMIT. | | | | | | 5. ANY PENETRATIONS IN REQUIRED FIRE | | | WALS MUST BE PROPERLY SEALED IN AN | | | APPROVED MANNER. | | | | | | 6. THE RELOCATION OF THE FIRE ALARM | | | PANEL AND DIALER SHOULD BE SCHEDULED TO | | | PREVENT LONG PERIODS OF WITHOUT | | | PROTECTION. | | | | | | 7. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR THE REQUIRED HOOD, DUCT, AND FIRE | | | SUPPRESSION SYSTEM. | | | | | | 8. COULD NOT LOCATE ANY INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 9. ANY NEW SOFFITS SHALL NOT INTERFERE | | | WITH ANY REQUIRED FIRE SPRINKLER HEADS. | | | | | | 10. DOOR SCHEDULE ON PAGE A5.1 DOES NOT | | | DISPLAY ANY FIRE RATING. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-30 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-30 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2005-08-30 00:00:00 | ******DENIED****** | | | | | | 1) CONSTRUCTION ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) THE DOOR SWINGS AT 1ST FLOOR | | | MECHANICAL ROOM TO NEW LADIES CARD ROOM, | | | AND MECHANICAL STORAGE NEXT TO MAIN | | | ELECTRICAL ROOM, OBSTRUCT THE HALLWAY BY | | | GREATER THAN 1/2 THE WIDTH. | | | | | | 3) PLEASE NOTE THAT STAIR IDENTIFICATION | | | DOESN'T APPEAR CONSISTENT THROUGHOUT | | | PLANS. | | | | | | 4) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GUARDS. | | | | | | 5) PLEASE INCLUDE LIFE SAFETY PLAN TO | | | DETERMINE REQUIRED MEANS OF EGRESS AND | | | PATH OF TRAVEL. | | | | | | 6) IT WOULD APPEAR THAT WHEN EXITING | | | FROM THE RESTAURANT TO THE CORRIDOR | | | LEADING TO STAIR #1, THE DOOR MAY | | | INTERFERE WITH THE DOOR TO THE MECH/AC | | | ROOM. PLEASE CLARIFY ARRANGEMENT. | | | | | | 7) PLEASE INDICATE THE OCCUPANT LOADS | | | FOR THE RESTAURANT AND FITNESS CLUB. | | | | | | 8) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 9) NOTE THAT DOORS SERVING AREAS OF | | | OCCUPANT LOAD GREATER THAN 50 SHALL | | | SWING IN THE DIRECTION OF TRAVEL. | | | | | | 10) DOORS IN AREAS SERVING OCCUPANT LOAD | | | GREATER THAN 100, SHALL HAVE PANIC | | | HARDWARE WITH UL LISTED CLOSERS. | | | | | | 11) PLEASE ILLUSTRATE FIRE RATINGS FOR | | | APPROPRIATE DOORS. | | | | | | 12) PLEASE INDICATE THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | 13) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR HOOD AND SUPPRESSION | | | SYSTEMS IF APPLICABLE AND PART OF THIS | | | JOB SCOPE. | | | | | | 14) MONITORING OF SPRINKLER SYSTEM TO BE | | | UL CERTIFIED FOR CENTRAL STATION | | | SERVICE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
12 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-07 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-07 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2007-12-07 11:19:59 | REVISION OK-SHEET P5.1 GAS REVISION |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
10 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-15 |
Time |
05:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-12 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2007-09-15 05:49:10 | GAS REVISION DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.--MANY LENGTHS MISSING FOR MANY CUT | | | SECTIONS.--INDICATE THE LENGHTS OF PIPE FROM THE | | | REGULATORS TO THE GAS APPLIANCES AND ALL SECTIONS IN | | | BETWEEN. ALSO CHECK RED LINE SECTIONS ON ONE SHEET | | | SUBMITTED FOR REVISION. | | | | | | 2. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE.--A UNION IS REQUIRED | | | DOWNSTREAM OF ALL SHUT OFF VALVES FOR REGULATORS AND/OR | | | SOLENOID VALVES. PLEASE INDICATE THE REQUIRED UNIONS. | | | | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES.--ALL PIPE SIZES ARE NOT | | | INDICATED ON THE REVISION. SHOW ALL PIPE SIZES. | | | | | | 4. INDICATE THE MAXIMUM BTUS ALLOWED FOR FUTURE FIXTURE | | | E13 PER TABLE 402.4(2) FOR TOTAL DEVELOPED LENGTH FROM | | | THE REGULATOR TO THE MOST REMOTE GAS APPLIANCE, (E13). | | | | | | | | | 5. SHT P5.1 BUILDING GAS REQUIREMENTS TABLE/SCHEDULE. | | | RECHECK ADDITION AFTER LEG #2 THRU LEG #5. SUBTOTALS & | | | TOTAL INCORRECT. SECTION 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
9 |
Status |
P |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-03-20 |
Time |
13:23 |
Rev Time |
0.55 |
| Received By |
mperson |
Date |
2007-03-20 |
Time |
13:23 |
Sent To |
PC |
|
| Notes |
| 2007-03-20 13:29:31 | REVISION:**OK** SHEET P5.1 GAS ISOMETRIC RISER DIAGRAM | | | AND APPLIANCE SUBMITTALS. GAS APPLIANCE SUBMITTALS WITH | | | PERMIT APPLICATION. | | | | | | ****************PROVISO**************** | | | A} EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
8 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-03-01 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-02-28 |
Time |
15:41 |
Sent To |
PC |
|
| Notes |
| 2007-02-28 16:59:30 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS; THE CITY OF WEST PALM | | | BEACH GAS PERMIT APPLICATION REQUIREMENTS; | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN | | | REVIEW TO MEET CODE COMPLIANCE. PLEASE NOTE ON THE | | | SHEET P5.1 THERE IS APPROVED PLUMBING SANITARY AND | | | WATER RISER DIAGRAMS DATED 4-22-06, BUT ON THE | | | SUBMITTED REVISION OF SHEET P5.1 THERE IS NO INDICATION | | | OF THESE SANITARY AND WATER RISER DIAGRAMS. IF IT IS | | | IMPOSSIBLE TO FIT BOTH THE GAS AND THE PLUMBING ON THE | | | SAME SHEET IT IS SUGGESTED A NEW SHEET BE DESIGNATED | | | FOR THE GAS REVISION P5.1A. PLEASE CLARIFY THIS ON THE | | | RESUBMITTAL. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | THE FOLLOWING ARE FROM THE PREVIOUS REVIEW COMMENTS: | | | | | | 1. NO/OK** SHEET P5.1 NEW GAS SERVICE RISER: PLEASE | | | SUBMIT ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS | | | CODE SECTION 402.4. | | | NOTE: THE SUBMITTED MANUFACTURER SHEETS DO VERIFY THE | | | BTU LOADS BUT HOWEVER NOT ALL SHEETS INDICATE THAT THE | | | APPLIANCES ARELISTED. PLEASE REFERENCE THE RED CIRCLE | | | ON ITEMS #7 AND #8 INDICATING THAT THOSE APPLIANCES ARE | | | LISTED. THE FOLLOWING IS A LIST OF THE APPLIANCES AND | | | GAS EQUIPMENT INDICATING WHAT IS REQUIRED. | | | A} #1- FRYER; NEED LISTING | | | B} #2 FRYER; NEED LISTING | | | C} #3- BROILER; NEED LISTING | | | D} #4-GRIDDLE; NEED LISTING | | | E} #5-CONVECTION OVEN; NEED LISTING | | | F} #6-RANGE; NEED LISTING | | | G} #7-SALAMANDER BROILER; OK | | | H} #8-PIZZA OVEN; OK | | | I} #9-STEAMER; NEED LISTING | | | J} MP REGULATOR (2 PSI TO 0.5 PSI)- MANUFACTURER CUT | | | SHEET REQUIRED INDICATING MAKE, MODEL NUMBER, AND THIRD | | | PARTY LISTING. | | | K} EMERGENCY HOOD SHUT DOWN VALVE- MANUFACTURER CUT | | | SHEETS REQUIRED INDICATING MAKE, MODEL NUMBER, AND | | | THIRD PARTY LISTING. | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. NO**SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | NOTE: THE RESUBMITTED REVISION STILL DOES NOT INDICATE | | | ALL CORRESPONDING LENGTHS IN LEG #5. THE ONLY LENGTH | | | INDICATED IS 22'. THE TOTAL DEVELOPED LENGTH OF THE GAS | | | PIPING FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE | | | WHICH IS A STEAMER IN THE NEW KITCHEN IS REQUIRED FOR | | | GAS PLAN REVIEW TO VERIFY CODE COMPLIANCE. | | | | | | THE FOLLOWING ARE NEW COMMENTS: | | | | | | 5. TYPE OF GAS, (LP OR NATURAL) | | | NOTE: ON THE APPROVED SHEET P5-1 THE GAS TYPE IS | | | CLEARLY INDICATED AS NATURAL GAS IN THE GAS SIZING | | | TABLE CALCULATIONS, BUT ON THE RESUBMITTED REVISION | | | THERE IS NO GAS TYPE INDICATED. THERE IS A FBC-2004 | | | FUEL GAS TABLE 402.4(3) REFERENCE WHICH IS FOR NATURAL | | | GAS BUT THERE IS NO CLEAR INDICATION OF GAS TYPE. IT | | | CAN NOT BE ASSUMED THAT THE GAS TYPE IS NATURAL GAS. | | | PLEASE INDICATE THE GAS TYPE ON THE RESUBMITTED | | | REVISION. | | | | | | 6. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | NOTE: ON THE APPROVED SHEET P5-1 IT CLEARLY INDICATES | | | THE THE EMERGENCY HOOD SHUT OFF VALVE, BUT ON THE | | | RESUBMITTED REVISION THIS VALVE IS NOT INDICATED. THE | | | ONLY VALVES INDICATED ON THE RESUBMITTED REVISION ARE A | | | SHUT OFF VALVE AND A MP REGULATOR (2 PSI TO 0.5 PSI). | | | PLEASE CLEARLY INDICATE AND IDENTIFY THE SHUT OFF | | | VALVE, MP REGULATOR, AND ADD THE EMERGENCY SHUT OFF | | | VALVE ON THE RESUBMITTED REVISION. | | | | | | ******IMPORTANT INFORMATION | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
7 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-01-08 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-01-08 |
Time |
13:02 |
Sent To |
PC |
|
| Notes |
| 2007-01-08 14:10:11 | GAS REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1.SHEET P5.1 NEW GAS SERVICE RISER: PLEASE SUBMIT ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS CODE SECTION | | | 402.4. | | | NOTE:NEED MANUFACTURER CUT SHEETS FOR ALL NEW GAS | | | EQUIPMENT INCLUDING THE NEW MP REGULATOR (2PSI TO | | | 0.5PSI) FOR THE NEW KITCHEN. THE SUBMITTED MANUFACTURER | | | CUT SHEETS SHALL SHOW A LISTING, MODEL NUMBER, AND BTU | | | LOAD. MANUFACTURER SHEETS SHALL REFLECT THE BTU LOADS | | | INDICATED ON THE NEW GAS RISER DIAGRAM. IT IS NOTED ON | | | THE REVISION SUBMITTAL FORM THAT THE ARCHITECT E-MAILED | | | THE EQUIPMENT INFORMATION TO K.STEVENS. IN CHECKING | | | WITH K.STEVENS HE HAS NO RECORD OF THIS INFOMATION. | | | PLEASE REMEMBER WHEN ITEMS ARE E-MAILED THEY GO THROUGH | | | A MIS SCREENING PROCESS AND MAY TAKE WEEKS TO CLEAR | | | THAT PROCESS. IT IS BETTER TO SUBMIT TWO COPIES OF | | | MANUFACTURER CUT SHEETS WITH THE RESUBMITTAL TO ADVOID | | | E-MAIL SCREENING PROBLEMS. | | | | | | THE FOLLOWING ARE NEW COMMENTS THAT ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 2. SHEET P5.1 NEW GAS SERVICE RISER: THE EXISTING BTU | | | LOAD AND THE GAS SIZING CALCULATION TABLE INDICATING | | | THE EXISTING BTU LOADS DO NOT MATCH. ON THE NEW GAS | | | SERVICE RISER THE EXISTING INDICATES THREE DRYERS AT | | | 165,000 BTU/HR EACH WITH A TOTAL OF 495,000 BTU/HR, THE | | | TWO EXISTING KITCHEN MANIFOLDS INDICATE 825,000 BTU/HR | | | WITH A TOTAL OF 1,650,000 BTU/HR, AND THE THREE | | | EXISTING BOILERS ARE INDICATED AT 250,000 BTU/HR WITH A | | | TOTAL OF 750,000 BTU/HR. THE ADDED TOTAL SUM OF THE | | | EXISTINGBTU'S IS 2,895,000. THE GAS CALCULATION TABLE | | | INDICATES AN EXISTING BTU OF 2,070,000 WITH A | | | DIFFERENCE OF 825,000 BTU'S BETWEEN THE TWO. THE TOTAL | | | BTU'S OF THE EXISTING AND NEW SHOULD BE 3,861,000 NOT | | | THE INDICATED 3,036,000. PLEASE CORRECT AND CORRELATE | | | THE BTU'S ON THE RESUBMITTAL. | | | | | | 3. SHEET P5.1 NEW GAS RISER: PLEASE CLARIFY IF THIS | | | SYMBOL IS THE POINT OF DELIVERY (METER) ON THE | | | RESUBMITTAL. | | | | | | 4. WHAT IS THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING | | | FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE IN THE | | | NEW KITCHEN. THE ONLY INDICATED LENGTH IS 22'. TO | | | ADVOID CONFUSSION ALL CUT SECTIONS AND CORRESPONDING | | | LENGTHS SHOULD BE INDICATED ON THE NEW GAS SERVICE | | | RISER FOR THE NEW KITCHEN FOR THE RESUBMITTAL. | | | | | | ***************IMPORTANT INFORMATION | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
F |
Date |
2006-12-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-02 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-02 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2006-12-02 17:57:14 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM | | | PREVIOUS REVIEW) | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR | | | ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU | | | DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE. | | | ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS | | | RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE | | | INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE | | | SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS | | | APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU | | | LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS | | | INDICATED ON THE GAS RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2006-11-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-04 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-04 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2006-11-04 14:28:42 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). EXPLAIN | | | THE VENT LINES CONNECTING TO THE GAS PIPES. - INDICATE | | | THE MATERIAL FOR THE VENTS, (SHALL BE NONCOMBUSTABLE). | | | - MORE INFORMATION IS REQUIRED ON THE SQUARE BOXES | | | LOCATED IN VARIOUS LOCATIONS IN THE RISER DIAGRAM. IF | | | THEY ARE REGULATORS, THEY MUST BE LOCATED DOWNSTREAM OF | | | THE SHUT OFF VALVES. SUBMIT MANUF. SPECIFICATIONS FOR | | | THE REGULATORS. SPECIFY THE MODEL NUMBER. REGULATORS | | | SHALL SHOW A LISTING IN SPECIFICATIONS SHEETS. ALSO | | | SUBMIT THE FOLLOWING INFORMATION: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN. | | | SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW | | | GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES | | | IS ALL BUTITEM #4 THE GRIDDLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-28 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-28 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. REVISION REQUIRED FOR THE GAS PIPING | | | SYSTEM. IF NEW GAS APPLIANCES, NEW | | | MANUF. SPECIFICATION SHEETS WILL BE | | | REQUIRED. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-28 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-28 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2006-08-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | A. SHT P5.1 GAS RISER DIAGRAM REVISION. | | | MORE INFORMATION REQUIRED. THIS IS A | | | CHANGE OF GAS APPLIANCES, PIPING LAYOUT, | | | BTU AMOUNT, AND DEVELOPED LENGTH. PLEASE | | | SUBMIT THE FOLLOWING: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). - THIS IS | | | SHOWN AS BOTH 150' AND 190'. BY | | | INDICATING THE LENGTH OF ALL CUT | | | SECTIONS FROM THE METER THROUGH OUT THE | | | SYSTEM, TOTAL DEVELOPED LENGTH CAN BE | | | VERIFIED. | | | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 - THERE | | | IS MANY NEW GAS APPIANCES ON THIS | | | REVISION. ALL MANUF. SPECIFICATIONS | | | SHALL BE SUBMITTED TO VERIFY BTU'S SO | | | INDICATE MODELS AND EACH APPLIANCE SHALL | | | SHOW LISTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-15 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-15 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | UNSAT | | | SEE PREVIOUS PROVISO NOTES BELOW | | | DATED 4-26-06 BY KEN STEVENS | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P5.2 GAS | | | ISOMETRIC FOR ALL RED LINE CORRECTIONS. | | | | | | REVISION AS SOON AS POSSIBLY TO AVOID A | | | DELAY IN CERTIFICATE OF AUTHROIZAION. | | | | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P5.2 GAS | | | ISOMETRIC FOR ALL RED LINE CORRECTIONS. | | | | | | REVISION AS SOON AS POSSIBLY TO AVOID A | | | DELAY IN CERTIFICATE OF AUTHROIZAION. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2006-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-22 |
Time |
21:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-22 |
Time |
21:55 |
Sent To |
|
|
| Notes |
| 2006-04-22 00:00:00 | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P5.2 GAS | | | ISOMETRIC FOR ALL RED LINE CORRECTIONS. | | | | | | REVISION AS SOON AS POSSIBLY TO AVOID A | | | DELAY IN CERTIFICATE OF AUTHROIZAION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
28 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-02 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-02 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2008-05-02 08:30:42 | TO "COMM" BD#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
27 |
Status |
N |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-24 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-24 |
Time |
14:41 |
Sent To |
M |
|
| Notes |
| 2007-10-24 14:41:54 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-30 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-30 |
Time |
09:04 |
Sent To |
P |
|
| Notes |
| 2007-08-30 09:04:39 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-12 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-12 |
Time |
16:51 |
Sent To |
B |
|
| Notes |
| 2007-06-12 16:51:32 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-23 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-23 |
Time |
09:03 |
Sent To |
P |
|
| Notes |
| 2007-05-23 09:04:10 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-07 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-07 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2007-05-16 10:32:42 | TO "COMM" BD#31 | | 2007-05-07 15:36:04 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2007-04-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-27 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-27 |
Time |
11:49 |
Sent To |
B |
|
| Notes |
| 2007-04-27 11:49:36 | TO "JWITMER' DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-08 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-08 |
Time |
15:52 |
Sent To |
P |
|
| Notes |
| 2007-03-08 15:52:44 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-06 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-06 |
Time |
14:35 |
Sent To |
E |
|
| Notes |
| 2007-02-06 14:36:01 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-06 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-06 |
Time |
14:33 |
Sent To |
P |
|
| Notes |
| 2007-02-06 14:34:05 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2006-12-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-20 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-20 |
Time |
16:08 |
Sent To |
M |
|
| Notes |
| 2006-12-20 16:09:10 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2006-12-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-20 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-20 |
Time |
16:05 |
Sent To |
E |
|
| Notes |
| 2006-12-20 16:05:57 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2006-12-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-20 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-20 |
Time |
16:02 |
Sent To |
P |
|
| Notes |
| 2006-12-20 16:02:37 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-16 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-16 |
Time |
17:41 |
Sent To |
P |
|
| Notes |
| 2006-12-16 17:41:46 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2006-11-28 14:36:01 | REVISIONS SENT TO PLUMBING 11-28-06 | | 2006-11-21 12:27:04 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-12 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-12 |
Time |
18:17 |
Sent To |
E |
|
| Notes |
| 2006-10-12 18:18:14 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-04 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-04 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2006-10-26 08:31:59 | TO "COMM" BD#45 | | 2006-10-04 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-25 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-25 |
Time |
15:55 |
Sent To |
E |
|
| Notes |
| 2006-09-25 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-07 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-07 |
Time |
15:50 |
Sent To |
E |
|
| Notes |
| 2006-09-07 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | TO "COMM" BD#8 | | 2006-09-06 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
09:41 |
Sent To |
M |
|
| Notes |
| 2006-09-06 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-16 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-16 |
Time |
11:00 |
Sent To |
E |
|
| Notes |
| 2006-08-16 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-09 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-09 |
Time |
10:22 |
Sent To |
P |
|
| Notes |
| 2006-08-09 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-23 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-23 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | TO "COMM" BD#15 | | 2006-06-23 00:00:00 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-22 |
Time |
21:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-14 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-21 |
Time |
20:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-21 |
Time |
20:25 |
Sent To |
|
|
| Notes |
| 2006-03-21 00:00:00 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-10 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-10 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2005-12-05 00:00:00 | TO "COMM" BD#2/PLANS ON RACK | | 2005-11-18 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-30 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-18 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | TO "COMM" BD#21/PLANS ON "COMM" RACK | | 2005-07-18 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
12 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-05 |
Time |
14:14 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-05-05 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2008-05-05 14:20:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** ADD GENERATOR TO PLANS AS REVISION. ** | | | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTES. | | | | | | 2) SHOW ON PLAN THE FUEL CAPACITY FOR THE DIESEL | | | STORAGE TANK. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
11 |
Status |
P |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-29 |
Time |
10:23 |
Rev Time |
2.00 |
| Received By |
tgordon |
Date |
2007-10-29 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2007-10-29 10:24:07 | REVISION TO MECH. PLANS PAGE M1.1A AND M1.1C. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
F |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-21 |
Time |
16:21 |
Rev Time |
2.00 |
| Received By |
tgordon |
Date |
2007-05-21 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2007-05-21 16:48:11 | REVISION TO MECHANICAL PLANS PAGES M1.1A, M1.1B, M1.1C, | | | AND M8.2. | | | *** DENIED *** | | | 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT. | | | FIRM'S NAME. SEE FAC 61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | | SEE CITY WPB AMEND. 106.1.1). | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 2) SEE YELLOW HIGH LIGHTS ON PAGE M1.1A NORTH ENTRY | | | LOBBY #129 SHOWS TWO WALLS THAT ARE NOT ON THE BUILDING | | | PLANS PAGE A1.1, THE WALLS ARE STOPPING AIR FROM | | | RETURNING TO THE AIR HANDLER, PLEASE CORRECT AND IF | | | NEEDED REVISE BUILDING PLANS. | | | | | | 3) SEE YELLOW HIGH LIGHT ON PAGE M1.1B CORRIDOR #140 | | | SHOWS TWO RETURN AIR GRILLS IN CORRIDOR, IF THE WALLS | | | ARE RATED THAN THE AIR CAN NOT RETURN TO THE AIR | | | HANDLER, PLEASE CORRECT. ALSO SEE THE SUPPLY AIR GRILL | | | SHOWS THE FIRE DAMPER AT THE GRILL NOT AT THE FIRE | | | WALL, PLEASE CORRECT. | | | | | | 4) SEE YELLOW HIGH LIGHT ON PAGE M1.1C RESTROOMS #114 | | | AND 115 AND MANICURE ROOM #121 EXHAUST FAN GRILLS NEED | | | TO SHOW THE CFM'S. ALSO SEE EMPLOYEE RESTROOM #104 | | | EXHAUST FAN GRILL NEEDS TO SHOW CFM'S IT APPEARS TO BE | | | 300 CFM'S AT THIS TIME, PLEASE CORRECT. | | | | | | 5 PAGE M8.2 ONLY NEEDS THE TITLE BLOCK CORRECTED AS THE | | | OTHER PAGES DO (SEE NOTE #1). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2006-12-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-28 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-28 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2006-12-28 08:27:30 | REVISED SHEETS: | | | M1.1B - LS.1 WAS ALSO REVISED (RATED CEILING INSTEAD OF | | | PARTITIONS), M1.1D & MP1.1B. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2006-11-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-28 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-28 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2006-11-28 13:33:52 | REVSION TO PLAN SHEET M1.1A, M1.1B, M1.1C & M1.1D - | | | PLEASE NOTE THE FOLLOWING: | | | | | | PLAN SHEET M1.1A, M1.1C & M1.1D - APPROVED | | | | | | PLAN SHEET M1.1B - APPROVED WITH THE EXCEPTION TO THE | | | 36" X 8" TRANSFER DUCT FROM ROOM #139 TO RM #146.THIS | | | COORIDOR IS FIRE RATED THEREFORE A FIRE DAMPER WILL BE | | | REQUIRED WHERE DUCT PENETRATES EACH ROOM.SHOULD THE | | | CEILING BE RATED FIRE DAMPERS WILL NOT BE REQUIRED BUT | | | THE LIFE SAFETY AND ARCHITECTURAL PLANS NEED TO BE | | | REVISED TO REFLECT THE CHANGE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-18 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-18 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2006-10-18 13:50:30 | PROVISO: | | | 1.PLAN SHEET M1.1A , M1.1C, AND M1.1D NOTE 15 & M1.1 | | | NOTE 16, INDICATE ALL FLEXIBLE EXHAUST DUCTING SHALL BE | | | HEAVY GAUGE CORREGATED STEEL DUCTWORK. PER 2004 FMC | | | 501.4 EXHAUST DUCTS SHALL BE OF METAL & SUCH | | | CONSTRUCTION SHALL COMPLY WITH CHAPTER 6. | | | | | | 2.PLEASE PROVIDE MANUFACTURE SUBMITTAL DATA ONTHE | | | CORREGATED STEEL DUCT. | | | | | | 3.PLEASE NOTE, CORRIGATED DUCT CAN NOT BE UTILIZED | | | WITH THE DRYER EXHAUST SHALL HAVE A SMOOTH INTERIOR | | | FINISH PER 2004 FMC 504.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
N |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-18 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-11 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2006-10-11 19:47:47 | NO MECHANICAL PAGES INCLUDED IN THESE REVISIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-09-12 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-09-11 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | THE FOLLOWING PLAN SHEETS ARE DENIED: | | | M1.1A, M1.1B, & M1.1C | | | 1.PLANS ARE MISSING FIRE DAMPERS AT | | | WALL PENETRATIONS.PER 2001 FMC 607.6, | | | SPECIFIC LOATION FOR EACH FIRE DAMPER, | | | ACCESS DOOR, CEILING DAMPER OR SMOKE | | | DAMPER SHALL BE PROPERLY IDENTIFIED ON | | | THE BUILDING PLAN. | | | | | | PLEASE CONTACT PATTY KRAUSS AT | | | (561)805-6719 OR E-MAIL [email protected], | | | FOR COORDINATION MEETING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-07-28 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-07-28 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2006-07-28 00:00:00 | REVISIONS TO PLAN SHEETS M1.1A, M1.1B, | | | M1.1D. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-04-10 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-04-10 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2006-04-10 00:00:00 | PROVISO: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION FOR | | | THE HOOD. PLANS SUBMITTED BY CAPTIVE AIR | | | INDICATES SUPPRESSION FOR THE HOOD. | | | PLEASE PROVIDE ADDITIONAL PLANS FOR THE | | | GREASE DUCT.INDICATE DUCT LAYOUT, | | | MATERIAL AND CLEARANCE TO COMBUSTIBLES. | | | INDICATE EXHAUST TERMINTATION PROVIDE | | | DISTANCE FROM PROPERTY LINES AND FRESH | | | AIR INTAKES SHOW COMPLIANCE WITH NFPA 96 | | | & 2001 FMC 506. | | | | | | PLEASE PROVIDE MANUFACTURERS CUT SHEETS | | | & INSTALLATION INTRUCTIONS WITH | | | MECHANICAL PERMIT FOR THE WALK-IN | | | COOLER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-17 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-13 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2006-01-17 00:00:00 | DENIED: | | | THE FOLLOWING COMMENT FROM REVIEW DATED | | | 8-2-05 BY HAROLD MOSER WAS NOT | | | ADDRESSED: | | | | | | COMMENT 3:PLEASE PROVIDE INFORMATION | | | ON THE PIPING MATERIAL TO BE INSTALLED | | | FOR NEW CHILLED WATER LINES AS INDICATED | | | ON PLAN SHEET M1.1AKEYED NOTE #4. | | | | | | PLEASE PROVIDE DETAIL FOR NEW CHILLED | | | WATER LINES.INDICATE ANY NEW SHUT | | | OFF/ISOLATION, CONTROL/BYPASS VALVES | | | THAT MAY BE INSTALLED. | | | | | | **************NEW COMMENT************ | | | 1.PLEASE PROVIDE ENGINEER'S LICENCE | | | NUMBER ON PLANS PER FAC61G15-23.002. | | | | | | 2.PLAN SHEET M8.3 A/C UNIT SCHEDULE | | | THE NOTE DOES NOT INDICATE AHU-13 HAVING | | | A DUCT SMOKE DETECTOR.SYSTEMS THAT ARE | | | GREATER THAN 2,000 CFM ARE REQUIRED TO | | | HAVE FAN SHUTDOWN BY DUCT SMOKE | | | DETECTORS WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS | | | PER 2004 FMC 606.2.1. | | | | | | 3.ADDITIONAL PERMITS REQUIRED FOR | | | WALK-IN COOLERS/FREEZERS, HOODS AND FIRE | | | SUPPRESSION.PLEASE PROVIDE PLANS AND | | | MANUFACTURER'S SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-08-02 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-08-02 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2005-08-02 00:00:00 | PLAN DENIED | | | 1) PLEASE REFRE TO SECTION 601.4 | | | BALANCED RETURN AIR FBC(M) | | | 2) PLEASE REFER TO SECTION 601.4 #3 | | | HABITABLE ROOMS ONLEY.LAUNDRY AND | | | BATHROOMS DO NOT REQUIRE RETURN AIR. | | | 3) PLEASE PROVIDE TYPE OF METERALS USED | | | FOR CHILLED WATER PIPING OR | | | CONNECTIONS.IF IT IS PVC PLEASE PROVIDE | | | A COPEY OF THE TESTING FROM ASTND 1785 | | | ASTMD 2241. | | | 4) REFER TO NOTE #3 PAGE M1.1C O/A AIR | | | MUST BE 10FT.FROM DOORS,WINDOWS OR | | | EXHAUST. | | | 5) REFER TO NOTE #6 PAGE M1.1C WALK IN | | | COOLERS AND FREEZERS,REFRIGERATION | | | EQUIPMENT SUBMIT UNDER SEPARATE PERMIT. | | | 6) PLEASE SHOW CFM. OF EXISTING | | | BATHROOM EXHAUST ON MECHANICAL PLANS. | | | 7) PLEASE REFER TO SECTION 602.2.1 | | | FBC(M) METERALS EXPOSER IN PLENUMS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-19 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-19 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2007-06-19 10:11:57 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1. SHT P5.3 VENT REQUIRED FOR THE URINALS. SECTION | | | 901.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
P |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-19 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-19 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2007-06-19 10:09:16 | REVISIONS OK--SHTS P1.1A, P1.1C, P5.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-01-08 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-01-05 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2007-01-05 16:36:56 | REVISION: SHEETS P1.1A, P1.1C, P5.2, AND P5.3 | | | | | | ****************PROVISO | | | SHEET P5.3:WATER HAMMER ARRESTORS PER FBC-2004 | | | PLUMBING, SECTION 604.9 | | | | | | ****************PROVISO | | | SHEET P5.3:AIR GAP REQUIRED PER FBC-2004 PLUMBING, | | | SECTIONS 504.6, 504.7.1, AND 802.1.3 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
F |
Date |
2006-12-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-02 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-02 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2006-12-02 17:54:56 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHTS P1.1A, P1.1C & P5.2 VENTING FOR FLOOR DRAINS | | | AND FLOOR SINKS. EVERY DRY VENT SHALL RISE VERTICALLY | | | TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE | | | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION | | | 905.4. VENTS BELOW THE SLAB ARE NOT APPROVED.- FLOOR | | | DRAIN AND FLOOR SINK IN THE KITCHEN VESTIBULE AREA | | | SHALL CONNECT TO THE VENTED BRANCH LINE SEPARATELY, OR | | | SHALL BE VENTED.SECTION 912.2.2. -FLOOR DRAIN | | | UPSTREAM OF FIXTURE 55 ON THE GREASE DRAINAGE SYSTEM | | | SHOWS A VENT ON THE FLOOR PLAN THAT IS NOT SHOWN ON THE | | | RISER DIAGRAM. PLEASE CORRELATE. SECTION 104.2.1. - | | | MAXIMUM 3 FU ON A 2" COMBINATION WASTE AND VENT BRANCH | | | LINE. TABLE 912.3.CHECK BRANCH LINES WITH TWO OR MORE | | | FLOOR DRAINS AND/OR FLOOR SINKS WITH A 2" BRANCH LINE. | | | | | | 2. (FROM PREVIOUS REVIEW) SUBMIT A DETAIL FOR THE NEW | | | TOILET ROOMS SHOWING COMPLIANCE WITH SECTIONS 11-4.16, | | | 11-4.18, 11-4.19 AND 11-4.22 WITH ALL SUBSECTIONS. | | | ****RESPONSE NOTED, THIS HAS NOT BEEN ADDRESSED. | | | | | | 3. SHTS P1.1C & P5.2 FIXTURE 1.1 IS NOT VENTED AS SHOWN | | | ON THE FLOOR PLAN, NOR ON THE RISER DIAGRAM. PLEASE | | | IDENTIFY FIXTURE 1.1. SECTIONS 905.4 AND 104.2.1. | | | | | | 4. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM | | | PREVIOUS REVIEW) | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR | | | ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU | | | DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE. | | | ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS | | | RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE | | | INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE | | | SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS | | | APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU | | | LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS | | | INDICATED ON THE GAS RISER DIAGRAM. | | | | | | 5. SHT P5.2 WATER RISER DIAGRAMS INDICATE WATER HAMMER | | | ARRESTORS INSTALLED UPSIDE DOWN. PLEASE SUBMIT MANUF. | | | SPECIFICATION/INSTALLATION REQUIREMENTS FOR THE WATER | | | HAMMER ARRESTORS INDICATING APPROVED INSTALLATION | | | METHOD. SECTION 104.2.1. ALL WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201 | | | AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE SHT | | | P5.3 DETAIL 2 WATER RISER DIAGRAM). | | | | | | 6. SHT P5.3 DETAIL 1 SANT RISER DIAGRAM. HLAV IN WOMENS | | | TOILET ROOM IS NOT VENTED AS SHOWN. ("S" TRAP). SEE RED | | | LINE EXAMPLE FOR CORRECTION. SECTIONS 901.2.1 & 1002.3. | | | - FLOOR DRAIN NOT VENTED PROPERLY. SECTION 905.4. | | | | | | 7. PLEASE INDICATE WHAT THE LARGE AMOUNT OF SHEETS | | | SUBMITTED WITH PLANS ARE FOR. IF THESE ARE SUBMITTALS, | | | SUBMIT THEM SEPARATELY. IF THEY WERE TO REPRESENT THE | | | GAS APPLIANCE MANUF. SPECIFICATIONS REQUIRED, THEY ARE | | | NOT APPROVED. THE MANUF. SHEETS FOR THE GAS APPLIANCES | | | SHALL SHOW A LISTING, THE MODEL NUMBER INDICATED AND | | | THE BTU LOAD INDICATED THAT REFLECTS THE GAS RISER | | | DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS | | | TO HELP EXPEDITE THE REVISIONS. (THIS WAS NOT ADDRESS | | | WHEN THESE REVISIONS WERE SUBMITTED). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2006-11-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-04 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-04 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2006-11-04 14:08:04 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT P1.1A SHOWS A URINAL IN THE WOMEN'S TOILET ROOM. | | | SUBMIT AN APPROVED MANUF. SUBMITTAL FOR THE URINAL. | | | | | | 2. SHT P1.1A SUBMIT A DETAIL FOR THE NEW TOILET ROOMS | | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, | | | 11-4.19, & 11-4.22 WITH ALL SUBSECTIONS. | | | | | | 3. SHTS P1.1A & P1.1C ALL INDIRECT WASTE SHALL BE | | | DRAINED INTO A FLOOR SINK, OR A HUB DRAIN. SECTIONS | | | 802.3 & 802.3.2. THE TRAP SIZE FOR THESE FIXTURES IS 2" | | | AND THE PIPING LAYOUT SHOW 1" AND 1-1/2" PIPING TO | | | THESE FIXTURES. TABLE 709.1. PLEASE SHOW MINIMUM SIZES | | | TO INDIRECT WASTE RECEPTORS. IDENTIFY ALL INDIRECT | | | WASTE RECEPTORS AND SHOW ALL PIPING FROM THE FIXTURES | | | TO THE INDIRECT WASTE RECEPTORS. SECTION 104.2.1. | | | | | | 4. SHT P1.1AIDENTIFY THE RISER UPSTREAM OF ITEM #26 | | | INDIRECT WASTE RECEPTOR IN THE GREASE SYSTEM. IDENTIFY | | | THE WATER RISER ON THE COLD WATER LINE PRIOR TO ITEM | | | #55. INDICATE WHAT "WWH" WATER LINE SUPPLIES. THIS IS | | | NOT SHOWN ON THE ABBREVIATIONS. ALSO IT DOES NOT | | | CONNECT TO ANYTHING. PLEASE CLARIFY.SECTION 104.2.1. | | | | | | 5. SHT P1.1A SHEET NOTES 2,3,4 REVISED, BUT ARE NOT | | | CLOUDED. COLD WATER LOOP SUPPLYING ITEMS 191,196,55, & | | | 57 DOES NOT CONNECT TO THE WATER MAIN.PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 6. SHT P1.1B CLOUD AND NUMBER REVISIONS. (SEE KEYED | | | NOTES 10,11,13 AND SHEET NOTES 2 & 3.CLEANOUTS IN THE | | | WALLS TO BE ACCESSIBLE PER SECTION 708.10. INDICATE HOW | | | THIS WILL BE COMPLIED WITH. | | | | | | 7. SHT P1.1C WAREWASHER TO CONNECT TO THE SANITARY | | | SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL UTILITY CODE | | | 90-124(7)(B). | | | | | | 8. SHTS P1.1A & P1.1CALL SINKS IN THE FOOD | | | PREPARATION AREA SHALL BE DRAINED INTO AN INDIRECT | | | WASTE RECEPTOR. SECTION 802.1. | | | | | | 9. SHT P1.1D CLOUD AND NUMBER REVISIONS. (SHEET NOTES & | | | NUMBER 1). | | | | | | 10. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). | | | EXPLAIN THE VENT LINES CONNECTING TO THE GAS PIPES. - | | | INDICATE THE MATERIAL FOR THE VENTS, (SHALL BE | | | NONCOMBUSTABLE). - MORE INFORMATION IS REQUIRED ON THE | | | SQUARE BOXES LOCATED IN VARIOUS LOCATIONS IN THE RISER | | | DIAGRAM. IF THEY ARE REGULATORS, THEY MUST BE LOCATED | | | DOWNSTREAM OF THE SHUT OFF VALVES. SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS. SPECIFY THE MODEL | | | NUMBER. REGULATORS SHALL SHOW A LISTING IN | | | SPECIFICATIONS SHEETS. ALSO SUBMIT THE FOLLOWING | | | INFORMATION: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN. | | | SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW | | | GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES | | | IS ALL BUTITEM #4 THE GRIDDLE. | | | | | | 11. SHT P5.2 DETAIL #1 THE GREASE RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE RISER AND | | | THE FLOOR PLAN. | | | | | | 12. SHT P5.2 DETAIL #2 WATER RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. ALSO DROPS ARE SHOWN AS RISERS, | | | AND FULL OPEN VALVES ARE REQUIRED ON ALL WATER | | | DOWN-FEED PIPES. SECTIONS 104.2.1, 606.1(4). WATER | | | HAMMER ARRESTORS ARE REQUIRED FOR ALL QUICK CLOSING | | | VALVES. (WASH MACHINES, ICE MAKERS, DISH WASHERS | | | ETC.). | | | | | | 13. SHT P5.2DETAIL #3 RISER DOES NOT REFLECT THE | | | FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.LAVS ARE | | | NOT VENTED AS SHOWN, AND THE URINAL IS NOT VENTED AS | | | SHOWN. SECTION 901.2.1. (SEE RED LINE EXAMPLE ON ONE | | | SEET OF PLAN. | | | | | | 14. SHT P5.3 DETAIL #1 SANT. RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. (SEE RED LINE MARKING IN ONE | | | SET OF PLANS). SECTION 104.2.1. | | | | | | 15. SHT P5.3 DETAIL #2 WATER RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. NO WATER SHOWN TO THE STEAM | | | GENERATOR, OR TO THE MASSAGE SINK. THERE ARE EXTRA LAVS | | | AND EXTRA FIXTURES PAST THE W/C'S NOT SHOWN ON THE | | | FLOOR PLAN. PIPE ROUTING DIFFERENT. PLEASE CLARIFY. | | | PLEASE LABEL THE HOT AND COLD WATER PIPES. SECTION | | | 104.2.1. | | | | | | 16. SHT P5.3,DETAILS 3 & 4 ARE NOT SHOWN ON SHT | | | P1.1A. PLEASE CLARIFY. SECTION 104.2.1. - DETAIL 5 DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE FLOOR PLAN | | | AND RISER DIAGRAM. SECTION 104.2.1. | | | | | | 17. SHEETS FS1 THRU FS5 SHALL BE SIGNED/SEALED/DATED, | | | AND THE CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE | | | TITLE BLOCK OF THE ENGINEER. FAC G1G15-23.002(2), FS | | | 471.025, AND SECTION 104.2.2. (ONE SET OF FS SHEETS HAS | | | BEEN RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA BOARD | | | OF PROFESSIONAL ENGINEERS. | | | | | | 18. FS4 ITEM P72 TROUGH DRAIN. NO DRAIN TO THE GREASE | | | SYSTEM IS INDICATED. PLEASE CLARIFY. SECTION 104.2.1. | | | | | | 19. FS4 ITEM P82 ON SHT FS2 INDICATES 1/2"CW & A 1" | | | INDIRECT WASTE, BUT IS NOT SHOWN ON THE PLUMBING | | | CONNECTION SCHEDULE. PLEASE CORRELATE EQUIPMENT | | | SCHEDULES. SECTION 104.2.1. | | | | | | 20. ALL GAS HOOD SHEETS 1,2,3 TO BE | | | SIGNED/SEALED/DATED. SOME SETS OF SHEETS SUBMITTED ARE | | | COPIES OF SIGNED/SEALED/DATED SHEETS. SECTION 104.2.2, | | | FAC 61G15-23.002(2) & FS 471.025. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS | | | TO HELP EXPEDITE REVISIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-28 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-28 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. SUBMIT SANITARY AND WATER RISER | | | DIAGRAM ISOMETRICS REFLECTING ALL | | | CHANGES TO THE FLOOR PLAN FOR THE NEW | | | WORK IN THE TOILET ROOMS, KITCHEN AND | | | BAR AREAS. SECTION 104.3.1.1. | | | | | | 2. VALUE OF ALL NEW WORK TO BE ADJUSTED | | | TO THE PERMIT VALUE FOR THE 6 TOILET | | | ROOMS, THE DEMO OF THE TOILET ROOMS, AND | | | THE NEW WORK FOR THE KITCHEN AND BAR | | | AREAS. SECTION 104.6.5. | | | | | | 3. THE NEW TOILET ROOMS FOR THE | | | RESTAURANT SHALL MEET POTTY PARITY PER | | | SECTION 403.1.1 AND SECTION 3401.2. | | | | | | 4. SHTS A1.2, A1.7, A1.8, A1.9, & A1.10 | | | REVISIONS 3, 4, 5 ARE INDICATED ON THE | | | "PERMIT REVISIONS" AREA BUT NOT FOUND ON | | | THE FLOOR PLAN. PLEASE CORRELATE | | | REVISIONS NUMBERS WITH REVISIONS ON THE | | | FLOOR PLAN. SECTION 104.2.1. | | | | | | 5. SHT A1.9 FITNESS ROOM 233 SINK SHALL | | | COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL SHOWING ALL | | | REQUIREMENTS. SECTION 104.2.1. | | | | | | 6. SHTS A4.1 & A10.1 NO REVISIONS FOUND. | | | REVISIONS 3, 4, 5, & 6 ARE INDICATED ON | | | THE "PERMIT REVISIONS" AREA. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | | | | 7. SHT A10.2 IS A NEW SHEET, BUT | | | INDICATES THAT REVISIONS 3, 4, 5, & 6 | | | ARE ON THE FLOOR PLAN. HOW CAN A NEW | | | SHEET HAVE REVISIONS? PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 8. NEW FS SHEETS SHOWING THE CHANGES TO | | | THE KITCHEN & BAR AREA AND NEW PLUMBING | | | REVISIONS ARE REQUIRED. SECTION 104.2.1. | | | THE NEW SHEETS SHALL BE ROUTED TO DBPR, | | | HOTEL & RESTAURANT DIVISION FOR REVIEW | | | AS A REVISION. MINIMUM 2 SETS OF PLANS | | | STAMPED BY DBPR SHALL BE SUBMITTED FOR | | | REVIEW. | | | | | | 9. REVISIONS REQUIRED FOR THE GAS PIPING | | | SYSTEM TO REFLECT THE FLOOR PLAN. | | | SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-28 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-28 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2006-08-28 00:00:00 | THE REVISIONS FOR THE FOLLOWING SHEETS | | | HAVE BEEN APPROVED. P1.1A, P1.1B, P1.1D, | | | AND P5.3. | | | | | | REVISION DENIED | | | | | | 1. SHT P5.1 (SEE GAS REVIEW) | | | | | | 2. SHT P5.2, FITTINGS SHALL BE INSTALLED | | | TO GUIDE SEWAGE AND WASTE IN THE | | | DIRECTION OF FLOW. (SEE NEW FLOOR DRAINS | | | IN GREASE RISER. - SEE ALL FIXTURES IN | | | DETAIL #3 FOR BACK TO BACK TOILET ROOMS. | | | - A TRAP IS REQUIRED FOR THE WASH | | | MACHINE, AND THE VENT CAN NOT CONNECT TO | | | THE WASH MACHINE BOX. - THE URINALS ARE | | | NOT VENTED AS SHOWN. - (SEE RED LINE | | | CORRECTION FOR EXAMPLES). SECTIONS | | | 706.3, 901.2.1, 1002.1. | | | | | | 3. NOTE: A REVISION TO FLOOR PLAN MAY BE | | | REQUIRED FOR THE CHANGES SHOWN SO THAT | | | THE FLOOR PLAN AND THE RISER DIAGRAM | | | REFLECT EACH OTHER. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-15 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-15 |
Time |
06:26 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | UNSAT | | | SEE PREVIOUS PROVISO NOTES BELOW | | | DATED 4-26-06 BY KEN STEVENS | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P1.1B SHOWING | | | VENT FOR LIFT STATION & ROUTING OF STEAM | | | LINE TO PITCH AWAY FROM THE STEAM | | | GENERATOR TO DRAIN THE CONDENSATE. SEE | | | SHT 8 0F 19 MANUF. SPECIFICATION SHEETS. | | | (I WAS INFORMED BY THE DESIGN | | | PROFESSIONAL THAT THE STEAM GENERATOR | | | WILL BE MOVED) | | | | | | REVISION REQUIRED FOR SHT SHT P5.1 FOR | | | ALL RED LINE CHANGES TO GAS ISOMETRIC & | | | PLUMBING RISERS. | | | | | | REVISION REQUIRED FOR SHEET P5.2 | | | INDICATING THAT A STANDPIPE IS REQUIRED | | | FOR THE DISH WASHER PER SECTION 802.17. | | | | | | ALL REVISIONS SHALL BE SUBMITTED AS SOON | | | AS POSSIBLE TO AVOID A DELAY IN GETTING | | | THE CERTIFICATE OF OCCUPANCY. | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2006-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-22 |
Time |
21:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-22 |
Time |
21:33 |
Sent To |
|
|
| Notes |
| 2006-04-22 00:00:00 | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P1.1B SHOWING | | | VENT FOR LIFT STATION & ROUTING OF STEAM | | | LINE TO PITCH AWAY FROM THE STEAM | | | GENERATOR TO DRAIN THE CONDENSATE. SEE | | | SHT 8 0F 19 MANUF. SPECIFICATION SHEETS. | | | (I WAS INFORMED BY THE DESIGN | | | PROFESSIONAL THAT THE STEAM GENERATOR | | | WILL BE MOVED) | | | | | | REVISION REQUIRED FOR SHT SHT P5.1 FOR | | | ALL RED LINE CHANGES TO GAS ISOMETRIC & | | | PLUMBING RISERS. | | | | | | REVISION REQUIRED FOR SHEET P5.2 | | | INDICATING THAT A STANDPIPE IS REQUIRED | | | FOR THE DISH WASHER PER SECTION 802.17. | | | | | | ALL REVISIONS SHALL BE SUBMITTED AS SOON | | | AS POSSIBLE TO AVOID A DELAY IN GETTING | | | THE CERTIFICATE OF OCCUPANCY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-19 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-19 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2006-04-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEWS. COMMENT | | | NUMBERS SHALL REMAIN THE SAME: | | | | | | 2. PLANS SHALL BE ROUTED TO DBPR | | | DIVISION OF HOTELS AND RESTURANTS FOR | | | REVIEW. ALL SETS OF PLANS SHALL BE | | | REVIEWED AND STAMPED WITH TWO PAGE | | | "WORKSHEETS" ATTACHED TO EACH SET PRIOR | | | TO RESUBMITTING TO CITY WPB FOR REVIEW. | | | SECTION 101.4.7. (NO RESPONSE, NOT | | | ADDRESSED). | | | *************************************** | | | RESPONSE NOTED BUT, | | | - ONLY ONE SET OF PLANS WAS STAMPED. | | | EACH SET OF PLANS REQUIRES A SET OF | | | STAMPED PLANS FROM DBPR. ALSO THE TWO | | | PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED | | | TO EACH SET OF PLANS FROM DBPR. MINIMUM | | | OF TWO SETS OF PLANS REQUIRED. (PLANS | | | NOT SIGNED & SEALED SHALL BEAR THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. SECTION | | | 104.2.1) ALL FS SHEETS SHALL COMPLY. | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | NO RESPONSE FROM ARCHITECT: | | | NEW FS-1 THRU FS-8 SHEETS SUBMITTED WITH | | | THE DBPR STAMP. THE TWO PAGE "WORKSHEETS | | | WERE NOT ATTACHED TO EACH SET. (I COPIED | | | THE WORKSHEETS AND ADDED ONE SET TO OUR | | | FILE COPY). PRINTED NAME AND SIGNATURE | | | REQUIRED BY SECTION 104.2.1 NOT ON | | | SHEETS. PLEASE COMPLY. | | | | | | 3. SHT A1.1 STEAM ROOMS 160 AND 163. | | | SUBMIT A DETAIL INDICATING WHERE THE | | | STEAM UNITS FOR THESE ROOMS IS LOCATED. | | | SHOW ALL PIPEING FOR STEAM LINES SHOWING | | | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS | | | IF LOCATED ABOVE THE CEILING AND | | | INDICATE HOW THE P/T LINE WILL BE | | | INSTALLED. SECTION 104.2.1. (THIS HAS | | | BEEN CHANGED TO ONE STEAM ROOM, #154, | | | BUT COMMENT STILL NOT ADDRESSED). | | | *************************************** | | | RESPONSE INDICATES ROOM #152-B IS THE | | | LOCATION OF THE STEAM GENERATOR. THIS | | | ROOM HAS NOT BEEN LOCATED ON SHT A1.1. | | | PLEASE CLARIFY. - 2 DIFFERENT STEAM | | | GENERATORS SPECIFICATION SHEETS HAVE | | | BEEN SUBMITTED. PLEASE INDICATE WHICH | | | GENERATOR WILL BE USED. (SUANATEC (NO | | | LISTING SHOWN) OR AMEREC). - SAFETY | | | VALVE LINE, DRAIN LINE, AND PAN DRAIN | | | LINE DISCHARGE PIPING IS NOT SHOWN. | | | PLEASE INDICATE HOW THE PIPING FOR THESE | | | WILL BE RUN, AND SHOW COMPLIANCE WITH | | | SECTION 701.1. (SEE PAGE 8 OF 19 MANUF. | | | SPECIFICATION SHEETS). SHOW TERMINATION | | | OF ALL LINES. | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | RESPONSE NOTED: PLANS SHOW A REVISION | | | THAT WAS PENCILED IN WHICH IS NOT | | | APPROVED. PLEASE RESUBMIT NEW SHEETS FOR | | | ALL CHANGES. NO PIPING IS SHOWN FOR THE | | | DRAIN LINE FROM THE STEAM GENERATOR AS | | | REQUIRED IN PAGE 8 OF 19 IN THE MANUF. | | | SPECIFICATION SHEETS.. THERE IS NO | | | DRAINAGE PIPING TO COOLING TANK FROM THE | | | SANT. SYSTEM. | | | | | | 14. SUBMIT A GREASE ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, ECT. | | | SECTION 104.3.1.1. (NO RESPONSE, NOT | | | ADDRESSED). | | | *************************************** | | | SHT P5.2 RESPONSE NOTED BUT, | | | THE GREASE RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. A TRENCH DRAIN | | | AND A FLOOR SINK ARE MISSING. ALSO A DRY | | | HORIZONTAL VENT IS SHOWN ON THE END OF | | | ONE RUN PAST A FLOOR SINK. SECTIONS | | | 104.2.1, 905.3 & 905.4. - THE DISHWASHER | | | SHALL CONNECT THE THE SANITARY SYSTEM | | | PER MUNICIPAL CODE SECTION 90-124(7)(B) | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | RESPONSE NOTED: HAND DRAWN CHANGES IN | | | PENCIL ARE NOT APPROVED. SUBMIT NEW | | | SHEETS FOR ALL CHANGES MADE ON THE | | | PLANS. EXTEND CHANGE TO PICK UP RISER TO | | | SECOND FLOOR. (NUMBER 9). - DISHWASHER | | | DELETED FROM THE GREASE SYSTEM IS NOT | | | SHOWN ON THE SANITARY. SYSTEM. (SHTS | | | P5.1 AND P5.2) | | | | | | 16. A SEPARATE GAS PERMIT IS REQUIRED. | | | SUBMIT THE FOLLOWING INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | *************************************** | | | SHT P5.1 RESPONSE NOTED BUT, | | | AN ISOMETRIC SHOWING PIPING FOR THE NEW | | | PIPE WITH ALL PIPE SIZES, VALVES, DRIPS, | | | BTU'S SHOWN AT EACH APPLIANCE, ETC. - | | | FOR EXISTING PIPING THE SIZE PER TABLE | | | 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4", | | | AND FOR 1,895 CU FT/HR @ 195FT IS 3". | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | RESPONSE NOTED: SHOW ALL PIPE SIZES PER | | | TABLE 402(2) FOR NEW PIPE. | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | *************************************** | | | RESPONSE NOTED BUT, | | | THE MANUF. SPECIFICATIONS SHEETS FOR | | | ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND | | | ITEM 6 DOUBLE CONVECTION OVENS DO NOT | | | CORRELATE WITH THE BTU'S INDICATED ON | | | THE GAS RISER DIAGRAM. INDICATE MODEL | | | NUMBER OF EACH NEW GAS APPLIANCE AND | | | MAKE SURE IT CORRELATES WITH THE GAS | | | RISER DIAGRAM. | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | RESPONSE NOTED: SHT P5.1, THE GAS SIZING | | | CALCULATION INFORMATION INDICATES NEW | | | GAS EQUIPMENT AT 788,000 BTU'S, THE THE | | | GAS FIRE KITCHEN EQUIPMENT LIST | | | INDICATES 779,500 BTU'S, BUT THE MANUF. | | | SPECIFICATION SHEETS INDICATE 879,500 | | | BTU'S. PLEASE CORRELATE ALL GAS | | | INFORMATION. | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | *************************************** | | | RESPONSE NOTED BUT, | | | THIS SHALL BE SHOWN ON THE RISER DIAGRAM | | | WITH THE VALVES & UNION PLACED AS | | | INDICATED. | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | RESPONSE NOTED: PLEASE INDICATE THAT THE | | | EMERGENCY SHUT OFF VALVE SHALL BE | | | INSTALLED BETWEEN 42" AND 48" ABOVE THE | | | FLOOR PER NFPA-96 SECTION 10.5.1 AND | | | NFPA-1 SECTION 50.4.7.1. | | | | | | ****NEW COMMENT**** | | | 1B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL, AND FS | | | 553.80.(2)(B) | | | | | | ****NEW COMMENT***** | | | 1C. SHT P1.1B REVISED SHEET REQUIRED TO | | | REFLECT CHANGES MADE TO RISER DIAGRAM. | | | (DRY HORIZONTAL VENT REMOVAL). | | | 2C. SHT P1.1C REVISED SHEET REQUIRED RO | | | REFLECT HAND DRAWN CHANGES MADE TO | | | SHEET. (REV-11) | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | SUBMIT ONE COPY OF PLANS FROM PREVIOUS | | | REVIEW WHEN RESUBMITTING. | | | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ | | | OLD VOIDED SHEETS WERE NOT REMOVED, AND | | | NEW SHEETS WERE NOT ATTACHED TO THE SET | | | OF PLANS. PLEASE SUBMIT TWO SETS OF | | | PLANS FOR REVIEW. SECTIONS 104.2.1. AND | | | 104.2.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-04-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-07 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-04 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2006-04-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEWS. COMMENT | | | NUMBERS SHALL REMAIN THE SAME: | | | | | | 2. PLANS SHALL BE ROUTED TO DBPR | | | DIVISION OF HOTELS AND RESTURANTS FOR | | | REVIEW. ALL SETS OF PLANS SHALL BE | | | REVIEWED AND STAMPED WITH TWO PAGE | | | "WORKSHEETS" ATTACHED TO EACH SET PRIOR | | | TO RESUBMITTING TO CITY WPB FOR REVIEW. | | | SECTION 101.4.7. (NO RESPONSE, NOT | | | ADDRESSED). | | | *************************************** | | | RESPONSE NOTED BUT, | | | - ONLY ONE SET OF PLANS WAS STAMPED. | | | EACH SET OF PLANS REQUIRES A SET OF | | | STAMPED PLANS FROM DBPR. ALSO THE TWO | | | PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED | | | TO EACH SET OF PLANS FROM DBPR. MINIMUM | | | OF TWO SETS OF PLANS REQUIRED. (PLANS | | | NOT SIGNED & SEALED SHALL BEAR THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. SECTION | | | 104.2.1) ALL FS SHEETS SHALL COMPLY. | | | | | | 3. SHT A1.1 STEAM ROOMS 160 AND 163. | | | SUBMIT A DETAIL INDICATING WHERE THE | | | STEAM UNITS FOR THESE ROOMS IS LOCATED. | | | SHOW ALL PIPEING FOR STEAM LINES SHOWING | | | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS | | | IF LOCATED ABOVE THE CEILING AND | | | INDICATE HOW THE P/T LINE WILL BE | | | INSTALLED. SECTION 104.2.1. (THIS HAS | | | BEEN CHANGED TO ONE STEAM ROOM, #154, | | | BUT COMMENT STILL NOT ADDRESSED). | | | *************************************** | | | RESPONSE INDICATES ROOM #152-B IS THE | | | LOCATION OF THE STEAM GENERATOR. THIS | | | ROOM HAS NOT BEEN LOCATED ON SHT A1.1. | | | PLEASE CLARIFY. - 2 DIFFERENT STEAM | | | GENERATORS SPECIFICATION SHEETS HAVE | | | BEEN SUBMITTED. PLEASE INDICATE WHICH | | | GENERATOR WILL BE USED. (SUANATEC (NO | | | LISTING SHOWN) OR AMEREC). - SAFETY | | | VALVE LINE, DRAIN LINE, AND PAN DRAIN | | | LINE DISCHARGE PIPING IS NOT SHOWN. | | | PLEASE INDICATE HOW THE PIPING FOR THESE | | | WILL BE RUN, AND SHOW COMPLIANCE WITH | | | SECTION 701.1. (SEE PAGE 8 OF 19 MANUF. | | | SPECIFICATION SHEETS). SHOW TERMINATION | | | OF ALL LINES. | | | | | | 12. SHT P1.1C KEYED NOTES #3 SUBMIT A | | | DETAIL FOR THE VENT CAP. VENT SHALL | | | TERMINATE IN COMPLIANCE WITH SECTION | | | 904.5. SUBMIT AN ELEVATION FOR THE TRASH | | | AREA TO DETERMINE IF VENT WILL BE | | | APPROVED IN AREA WITHOUT TERMINATING | | | ABOVE THE ROOF OF THE TRASH AREA. | | | SECTION 104.2.1. (NO RESPONSE, NOT | | | ADDRESSED). | | | *************************************** | | | RESPONSE NOTED BUT, | | | NOW THE FLOOR DRAIN HAS NOT VENT AS | | | REQUIRED IN SECTION 901.2.1 - FLOOR | | | DRAIN SHOULD BE CONNECTED TO THE GREASE | | | WASTE SYSTEM SO IT WILL BE EASY TO | | | CONNECT TO THE LINE GOING TO THE FLOOR | | | DRAIN NEAR THE EMPLOYEE RESTROOM. | | | | | | 13. SUBMIT A SANITARY ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, AND DFU'S | | | AS THEY ACCUMULATE IN THE DRAINAGE | | | SYSTEM. SECTION 104.3.1.1. (NO RESPONSE, | | | NOT ADDRESSED). | | | *************************************** | | | SHT P5.1 RESPONSE NOTED BUT, | | | PAST BOTH SETS OF W/C'S IS A DRY | | | HORIZONTAL VENT. THIS IS NOT APPROVED | | | PER SECTIONS 905.3 & 905.4. | | | | | | 14. SUBMIT A GREASE ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, ECT. | | | SECTION 104.3.1.1. (NO RESPONSE, NOT | | | ADDRESSED). | | | *************************************** | | | SHT P5.2 RESPONSE NOTED BUT, | | | THE GREASE RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. A TRENCH DRAIN | | | AND A FLOOR SINK ARE MISSING. ALSO A DRY | | | HORIZONTAL VENT IS SHOWN ON THE END OF | | | ONE RUN PAST A FLOOR SINK. SECTIONS | | | 104.2.1, 905.3 & 905.4. - THE DISHWASHER | | | SHALL CONNECT THE THE SANITARY SYSTEM | | | PER MUNICIPAL CODE SECTION 90-124(7)(B) | | | | | | 15. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM, SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS, (REQD. BY | | | SECTION 604.9), AND LOCATED NEAR THE | | | FIXTURES AS REQUIRED BY PDI-WH 201 & | | | MANUF. INSTALLATION INSTRUCTIONS, AND | | | POINTS OF CONNECTION. SECTION 104.3.1.1. | | | (NO RESPONSE, NOT ADDRESSED). | | | *************************************** | | | SHTS P5.1 & P5.2 RESPONSE NOTED BUT, | | | WATER HAMMER ARRESTORS ARE REQUIRED AT | | | THE DISH WASHER, AND AT ICE MAKERS PER | | | SECTION 604.9. AIR CHAMBERS ARE NOT | | | APPROVED AND SHALL BE DELETED FROM THE | | | RISER DIAGRAMS INCLUDING DETAIL #4 SHT | | | P5.2. | | | | | | 16. A SEPARATE GAS PERMIT IS REQUIRED. | | | SUBMIT THE FOLLOWING INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | *************************************** | | | SHT P5.1 RESPONSE NOTED BUT, | | | AN ISOMETRIC SHOWING PIPING FOR THE NEW | | | PIPE WITH ALL PIPE SIZES, VALVES, DRIPS, | | | BTU'S SHOWN AT EACH APPLIANCE, ETC. - | | | FOR EXISTING PIPING THE SIZE PER TABLE | | | 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4", | | | AND FOR 1,895 CU FT/HR @ 195FT IS 3". | | | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | *************************************** | | | RESPONSE NOTED BUT, | | | THE MANUF. SPECIFICATIONS SHEETS FOR | | | ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND | | | ITEM 6 DOUBLE CONVECTION OVENS DO NOT | | | CORRELATE WITH THE BTU'S INDICATED ON | | | THE GAS RISER DIAGRAM. INDICATE MODEL | | | NUMBER OF EACH NEW GAS APPLIANCE AND | | | MAKE SURE IT CORRELATES WITH THE GAS | | | RISER DIAGRAM. | | | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | *************************************** | | | RESPONSE NOTED BUT, | | | THIS SHALL BE SHOWN ON THE RISER DIAGRAM | | | WITH THE VALVES & UNION PLACED AS | | | INDICATED. | | | | | | | | | ****NEW COMMENT**** | | | 1B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL, AND FS | | | 553.80.(2)(B) | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | SUBMIT ONE COPY OF PLANS FROM PREVIOUS | | | REVIEW WHEN RESUBMITTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-01-30 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-01-30 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. FROM PREVIOUS REVIEW. COMMENT NUMBERS | | | SHALL REMAIN THE SAME: | | | 1. SHT A1.1 EMPLOYEE RESTROOM SHALL BE | | | ACCESSIBLE PER SECTION 11-4.22. (PLEASE | | | SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.19, AND 11-4.22 | | | AND ALL SUBSECTIONS). | | | 2. PLANS SHALL BE ROUTED TO DBPR | | | DIVISION OF HOTELS AND RESTURANTS FOR | | | REVIEW. ALL SETS OF PLANS SHALL BE | | | REVIEWED AND STAMPED WITH TWO PAGE | | | "WORKSHEETS" ATTACHED TO EACH SET PRIOR | | | TO RESUBMITTING TO CITY WPB FOR REVIEW. | | | SECTION 101.4.7. (NO RESPONSE, NOT | | | ADDRESSED). | | | 3. SHT A1.1 STEAM ROOMS 160 AND 163. | | | SUBMIT A DETAIL INDICATING WHERE THE | | | STEAM UNITS FOR THESE ROOMS IS LOCATED. | | | SHOW ALL PIPEING FOR STEAM LINES SHOWING | | | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS | | | IF LOCATED ABOVE THE CEILING AND | | | INDICATE HOW THE P/T LINE WILL BE | | | INSTALLED. SECTION 104.2.1. (THIS HAS | | | BEEN CHANGED TO ONE STEAM ROOM, #154, | | | BUT COMMENT STILL NOT ADDRESSED). | | | 4. SHOWER DELETED. | | | 5. OK | | | 6. SHT A10.1 DETAILS SHALL SHOW THE | | | FOLLOWING: | | | -FOR W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | -FOR LAVS | | | A. 11-4.19.3 CLEAR FLOOR SPACE | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | D. OK | | | (NO RESPONSE, NOT ADDRESSED) | | | 7. OK | | | 8. ALL PME SHEETS ENGINEER SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE | | | NUMBER ON EACH SHEET. NAME AND LICENSE | | | NUMBER NOT SHOWN IN THE TITLE BLOCK. FAC | | | 61G15-23.002(2) AND FS 471.025. (NO | | | RESPONSE, NOT ADDRESSED). | | | 9. WILL PROVISO | | | 10. SHT PD1.1B KEYED NOTES #6 NOT FOUND. | | | PLEASE CLARIFY. SECTION 104.2.1. (NOTE | | | FOUND, BUT FIXTURES NOT SHOWN). | | | 11. OK. | | | 11. SHT P1.1A WATER FILTERS SHALL COMPLY | | | THE "NSF - 42" STANDARD. PLEASE SUBMIT | | | MANUF. SPECIFICATIONS FOR FILTER. | | | SECTION 611.1. (SECOND COMMENT #11 - NO | | | RESPONSE, NOT ADDRESSED). | | | 12. SHT P1.1C KEYED NOTES #3 SUBMIT A | | | DETAIL FOR THE VENT CAP. VENT SHALL | | | TERMINATE IN COMPLIANCE WITH SECTION | | | 904.5. SUBMIT AN ELEVATION FOR THE TRASH | | | AREA TO DETERMINE IF VENT WILL BE | | | APPROVED IN AREA WITHOUT TERMINATING | | | ABOVE THE ROOF OF THE TRASH AREA. | | | SECTION 104.2.1. (NO RESPONSE, NOT | | | ADDRESSED). | | | 13. SUBMIT A SANITARY ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, AND DFU'S | | | AS THEY ACCUMULATE IN THE DRAINAGE | | | SYSTEM. SECTION 104.3.1.1. (NO RESPONSE, | | | NOT ADDRESSED). | | | 14. SUBMIT A GREASE ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, ECT. | | | SECTION 104.3.1.1. (NO RESPONSE, NOT | | | ADDRESSED). | | | 15. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM, SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS, (REQD. BY | | | SECTION 604.9), AND LOCATED NEAR THE | | | FIXTURES AS REQUIRED BY PDI-WH 201 & | | | MANUF. INSTALLATION INSTRUCTIONS, AND | | | POINTS OF CONNECTION. SECTION 104.3.1.1. | | | (NO RESPONSE, NOT ADDRESSED). | | | 16. A SEPARATE GAS PERMIT IS REQUIRED. | | | SUBMIT THE FOLLOWING INFORMATION: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | C. TYPE OF GAS, (LP OR NATURAL). | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ***NO RESPONSE, NOT ADDRESSED ALL GAS | | | PERMIT REQUIREMENTS********************* | | | | | | ****NEW COMMENT**** | | | 1B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL, AND FS | | | 553.80.(2)(B) | | | 2B. FLOOR PLANS HAVE CHANGED FROM FIRST | | | SUBMITTAL TO THE SECOND SUBMITTAL. IF | | | FLOOR PLAN CHANGES PRIOR TO THIRD | | | SUBMITTAL, MORE COMMENTS MAY BE | | | FORTHCOMING. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | SUBMIT ONE COPY OF PLANS FROM PREVIOUS | | | REVIEW WHEN RESUBMITTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-13 |
Time |
11:49 |
Rev Time |
7.15 |
| Received By |
kstevens |
Date |
2005-08-12 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2005-08-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT A1.1 EMPLOYEE RESTROOM SHALL BE | | | ACCESSIBLE PER SECTION 11-4.24. | | | 2. PLANS SHALL BE ROUTED TO DBPR | | | DIVISION OF HOTELS AND RESTURANTS FOR | | | REVIEW. ALL SETS OF PLANS SHALL BE | | | REVIEWED AND STAMPED WITH TWO PAGE | | | "WORKSHEETS" ATTACHED TO EACH SET PRIOR | | | TO RESUBMITTING TO CITY WPB FOR REVIEW. | | | SECTION 101.4.7. | | | 3. SHT A1.1 STEAM ROOMS 160 AND 163. | | | SUBMIT A DETAIL INDICATING WHERE THE | | | STEAM UNITS FOR THESE ROOMS IS LOCATED. | | | SHOW ALL PIPEING FOR STEAM LINES SHOWING | | | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS | | | IF LOCATED ABOVE THE CEILING AND | | | INDICATE HOW THE P/T LINE WILL BE | | | INSTALLED. SECTION 104.2.1. | | | 4. SHTS A1.2 AND A1.9 SHOWER IN ROOM 236 | | | TO BE ACCESSIBLE, AND ALSO REQUIRES A 5' | | | TURNING AREA. SECTION 11-4.1.6(1)(B). | | | 5. SHT A1.10 MENS RESTROOM INDICATES | | | VANITY TO BE RAISED TO 37". ONE LAV | | | SHALL 34" FOR ACCESSIBLILTY | | | REQUIREMENTS. SECTION 11-4.19.2 | | | 6. SHT A10.1 DETAILS SHALL SHOW THE | | | FOLLOWING: | | | -FOR W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | -FOR FAVS | | | A. 11-4.19.3 CLEAR FLOOR SPACE | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.19.6 MIRRORS (SHOWS 52" - | | | REQUIRED TO BE 40"). | | | 7. SHT A10.1 TURNING AREA REQUIRED IN | | | EACH TOILET ROOM. (NOT IN THE ACCESSIBLE | | | STALL). SECTION 11-4.22.3 - ALSO IN | | | DETAIL "A" THE TURNING AREA SHOULD BE | | | NEAR THE ACCESSIBLE SHOWER. | | | 8. ALL PME SHEETS ENGINEER SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE | | | NUMBER ON EACH SHEET. NAME AND LICENSE | | | NUMBER NOT SHOWN IN THE TITLE BLOCK. FAC | | | 61G15-23.002(2) AND FS 471.025. | | | 9. SHT P0.1 PLUMBING GENERAL NOTES #13, | | | PVC NOT APPROVED FOR WATER DISTRIBUTION | | | PIPE PER TABLE 605.5. DELETE FROM | | | REFERENCE, OR INDICATE FOR WATER SERVICE | | | ONLY. | | | 10. SHT PD1.1B KEYED NOTES #6 NOT FOUND. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 11. SHT PD1.1C GREASE INTECEPTORS, | | | ALTHOUGH EXISTING, SHALL BE SIZED BY THE | | | EXVIRONMENTAL COMPLIANCE MANAGER. PLEASE | | | CONTACT LYNN MASSON AT PHONE NUMBER | | | (561) 822-2271, FAX 9561) 822-2279, OR | | | E-MAIL [email protected]. PLEASE SUBMIT | | | THE DETERMINATION SHEET FOR GREASE | | | INTERCEPTORS WITH PLANS WHEN | | | RESUBMITTING. WASTE ORD #3434. | | | 11. SHT P1.1A WATER FILTERS SHALL COMPLY | | | THE "NSF - 42" STANDARD. PLEASE SUBMIT | | | MANUF. SPECIFICATIONS FOR FILTER. | | | SECTION 611.1. | | | 12. SHT P1.1C KEYED NOTES #3 SUBMIT A | | | DETAIL FOR THE VENT CAP. VENT SHALL | | | TERMINATE IN COMPLIANCE WITH SECTION | | | 904.5. SUBMIT AN ELEVATION FOR THE TRASH | | | AREA TO DETERMINE IF VENT WILL BE | | | APPROVED IN AREA WITHOUT TERMINATING | | | ABOVE THE ROOF OF THE TRASH AREA. | | | SECTION 104.2.1. | | | 13. SUBMIT A SANITARY ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, AND DFU'S | | | AS THEY ACCUMULATE IN THE DRAINAGE | | | SYSTEM. SECTION 104.3.1.1. | | | 14. SUBMIT A GREASE ISOMETRIC RISER | | | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, | | | VENTS, POINTS OF CONNECTION, ECT. | | | 15. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM, SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS, (REQD. BY | | | SECTION 604.9), AND LOCATED NEAR THE | | | FIXTURES AS REQUIRED BY PDI-WH 201 & | | | MANUF. INSTALLATION INSTRUCTIONS, AND | | | POINTS OF CONNECTION. | | | 16. A SEPARATE GAS PERMIT IS REQUIRED. | | | SUBMIT THE FOLLOWING INFORMATION: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | C. TYPE OF GAS, (LP OR NATURAL). | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-05-06 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-05-06 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2008-05-06 17:24:10 | ***FAILED*** | | | | | | 1) PLEASE NOTE THAT THE GENERATOR WILL NEED TO BE | | | SUBMITTED UNDER A SEPARATE PERMIT. | | | | | | 2) A SURVEY SHALL BE PROVIDED SHOWING THE LOCATION OF | | | THE PROPOSED GENERATOR RELATIVE TO ALL PROPERTY LINES, | | | EXISTING EASEMENTS, ADJACENT STRUCTURES, ETC. | | | | | | 3) A SITE PLAN SHALL BE PROVIDED SHOWING THE LOCATION | | | OF THE GENERATOR ON THE PROPERTY.SETBACKS SHALL BE | | | PROVIDED FROM ALL PROPERTY LINES. | | | | | | 4) GENERATORS SHALL BE SCREENED IN ACCORDANCE WITH | | | SECTION 94-444(B) OF THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS.SCREEN SHALL BE CONSTRUCTED | | | OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE | | | MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL | | | (CHAIN-LINK IS NOT PERMITTED).THE ENCLOSURE SHALL BE | | | LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO (2) | | | FOOT INTERVALS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |