Plan Review Details - Permit 05070592
Plan Review Stops For Permit 05070592
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By rmcdouga Date 2005-08-01 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2005-08-01 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By rmcdouga Date 2005-07-15 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2005-07-15 Time 13:10 Sent To  
Notes
2005-07-15 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TITLE BLOCK INFORMATION IS
 INCOMPLETE. THE FIRM LICENSE NUMBER AND
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT ARE REQUIRED. SEE FAC
 61G1-16.004.
  
 3) THE FIRE RATED TENANT SEPARATION
 WALLS ARE TO REMAIN INTACT DURING DEMO.
  
 4) THE LOCATION MAP ON A-100 HAS PARKER
 AVE. MISLABELED AS S. LAKE AVE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2005-08-04 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-02 Cont ID  
Sent By dpalmer Date 2005-08-02 Time 09:49 Rev Time 0.25
Received By dpalmer Date 2005-08-02 Time 09:49 Sent To  
Notes
2005-08-02 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE REVISED SHEET DE/P201
 HAS NOW COME BACK WITH TITLE BLOCK FOR
 ENGINEER OF RECORD.
 PLEASE ALSO SEE TITLE BLOCK FOR
 ENGINEERING FIRM SHALL ALSO INDICATE THE
 PRINTED NAME AND LICENSE NUMBER FOR
 ENGINEER OF RECORD.
 FAC 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 19:38 Rev Time 0.25
Received By dpalmer Date 2005-07-15 Time 19:34 Sent To  
Notes
2005-07-15 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING INFORMAITON
 AS REQUIRED UDNER FAC 61G1-16.004 AND
 MISSING LICENSE INFORMATION INCLUDING
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED PER FS 481.219.
  
 PLEASE SEE ELECTRICAL DEMO WORK IS NOT
 BEING SHOWN, HOWEVER IN ORDER FOR PLANS
 TO BE STAMPED/ NOTED FOR ELECTRICAL DEMO
 WORK, NOTE #1 NEEDS TO BE ADDRESSED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-07-28 Cont ID  
Sent By mwennerg Date 2005-07-28 Time 10:26 Rev Time 0.00
Received By mwennerg Date 2005-07-28 Time 10:26 Sent To  
Notes
2005-07-28 00:00:00PLANS RED LINED REF: NFPA 241
 REQUIREMENT NOT ADDRESSED FROM FIRST
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By mwennerg Date 2005-07-20 Time 10:11 Rev Time 0.00
Received By mwennerg Date 2005-07-20 Time 10:11 Sent To  
Notes
2005-07-20 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 2) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) HOW WILL DEMOLITION EFFECT THE
 EXISTING FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS.
  
 4) DEBRIS SHALL BE REMOVED DAILY AND ALL
 REQUIRED MEANS OF EGRESS MAINTAINED.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 11:26 Sent To  
Notes
2005-08-01 00:00:00SUBMITTALS ADDED TO "BOB"#11 W/PLANS IN
 REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 10:12 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 10:12 Sent To  
Notes
2005-07-26 00:00:00TO "BOB" #11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-05 Cont ID  
Sent By alange Date 2005-08-05 Time 09:00 Rev Time 0.00
Received By alange Date 2005-07-15 Time 08:30 Sent To  
Notes
2005-07-15 00:00:00TO "BOB" BD#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 09:03 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 09:07 Sent To  
Notes
2005-07-16 00:00:00NO PLANS HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 11:54 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 11:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-16 Cont ID  
Sent By kstevens Date 2005-07-16 Time 05:53 Rev Time 0.33
Received By kstevens Date 2005-07-16 Time 05:43 Sent To  
Notes
2005-07-16 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. THE TITLE BLOCK MUST CONTAIN AT A
 MINIMUM THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), AND THE
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2) & (6).
 2. PLUMBING DEMO WORK IS NOT SHOWN ON
 THE PLANS. IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5 - ALL DEMO'D
 PLUMBING WORK SHALL NOT BE COVERED PRIOR
 TO FIELD INSPECTION OF CAPPED OFF
 PLUMBING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]