| Plan Review Stops For Permit 05070592 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-01 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-01 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-07-15 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-07-15 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE TITLE BLOCK INFORMATION IS | | | INCOMPLETE. THE FIRM LICENSE NUMBER AND | | | PRINTED NAME OF THE PERSON SEALING THE | | | DOCUMENT ARE REQUIRED. SEE FAC | | | 61G1-16.004. | | | | | | 3) THE FIRE RATED TENANT SEPARATION | | | WALLS ARE TO REMAIN INTACT DURING DEMO. | | | | | | 4) THE LOCATION MAP ON A-100 HAS PARKER | | | AVE. MISLABELED AS S. LAKE AVE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-04 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-08-04 |
Time |
13:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-02 |
Time |
09:49 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-08-02 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2005-08-02 00:00:00 | ****** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE REVISED SHEET DE/P201 | | | HAS NOW COME BACK WITH TITLE BLOCK FOR | | | ENGINEER OF RECORD. | | | PLEASE ALSO SEE TITLE BLOCK FOR | | | ENGINEERING FIRM SHALL ALSO INDICATE THE | | | PRINTED NAME AND LICENSE NUMBER FOR | | | ENGINEER OF RECORD. | | | FAC 61G15-23.002, FS 471.023 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-15 |
Time |
19:38 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-07-15 |
Time |
19:34 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | ********* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE MISSING INFORMAITON | | | AS REQUIRED UDNER FAC 61G1-16.004 AND | | | MISSING LICENSE INFORMATION INCLUDING | | | CERTIFICATE OF AUTHORIZATION NUMBER | | | REQUIRED PER FS 481.219. | | | | | | PLEASE SEE ELECTRICAL DEMO WORK IS NOT | | | BEING SHOWN, HOWEVER IN ORDER FOR PLANS | | | TO BE STAMPED/ NOTED FOR ELECTRICAL DEMO | | | WORK, NOTE #1 NEEDS TO BE ADDRESSED. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-28 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-28 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | PLANS RED LINED REF: NFPA 241 | | | REQUIREMENT NOT ADDRESSED FROM FIRST | | | REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-20 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-20 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FS AND FAC REQUIREMENTS FOR | | | PLANS. | | | | | | 2) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 3) HOW WILL DEMOLITION EFFECT THE | | | EXISTING FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS. | | | | | | 4) DEBRIS SHALL BE REMOVED DAILY AND ALL | | | REQUIRED MEANS OF EGRESS MAINTAINED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-01 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-01 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2005-08-01 00:00:00 | SUBMITTALS ADDED TO "BOB"#11 W/PLANS IN | | | REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-26 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-26 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | TO "BOB" #11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-05 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-07-15 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | TO "BOB" BD#5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-07-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-16 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-16 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2005-07-16 00:00:00 | NO PLANS HM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-07-30 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-07-30 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-07-30 |
Time |
11:54 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-16 |
Time |
05:53 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2005-07-16 |
Time |
05:43 |
Sent To |
|
|
| Notes |
| 2005-07-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. THE TITLE BLOCK MUST CONTAIN AT A | | | MINIMUM THE FIRM LICENSE NUMBER, | | | (CERTIFICATE OF AUTHORIZATION), AND THE | | | PRINTED NAME OF THE PERSON SEALING THE | | | DOCUMENT. FAC 61G1-16.004(2) & (6). | | | 2. PLUMBING DEMO WORK IS NOT SHOWN ON | | | THE PLANS. IN THE REMOVAL OF ANY PART OF | | | A DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. SECTION 704.5 - ALL DEMO'D | | | PLUMBING WORK SHALL NOT BE COVERED PRIOR | | | TO FIELD INSPECTION OF CAPPED OFF | | | PLUMBING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|