Plan Review Details - Permit 05070591
Plan Review Stops For Permit 05070591
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-05-22 Cont ID  
Sent By lmartine Date 2006-05-22 Time 16:19 Rev Time 0.00
Received By lmartine Date 2006-05-22 Time 16:19 Sent To  
Notes
2006-05-22 00:00:00IMPACT PROTECTION IS APPROVED PER
 OVERHEAD DOOR PERMIT #05021514, SEE
 N.O.C ATTACHED
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-05-18 Cont ID  
Sent By lmartine Date 2006-05-18 Time 13:52 Rev Time 0.00
Received By lmartine Date 2006-05-18 Time 13:52 Sent To  
Notes
2006-05-18 00:00:00OVERHEAD DOORS ARE NOT IMPACT RATED

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-05-12 Cont ID  
Sent By lmartine Date 2006-05-12 Time 16:39 Rev Time 0.00
Received By lmartine Date 2006-05-12 Time 16:39 Sent To  
Notes
2006-05-12 00:00:00PROVIDE PRODUCT APPROVAL FOR NEW
 STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-04-03 Cont ID  
Sent By lmartine Date 2006-04-02 Time 13:40 Rev Time 0.00
Received By lmartine Date 2006-04-02 Time 13:40 Sent To  
Notes
2006-04-03 00:00:00 
 CHANGES WERE FOUND ON 3/15/06 SUBMITTAL
2006-04-02 00:00:00 
  
 NO CHANGES ON ARCH. OR STRUC. PAGES.
  
 REVIEW NOT REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-02-28 Cont ID  
Sent By lmartine Date 2006-02-28 Time 16:59 Rev Time 0.00
Received By lmartine Date 2006-02-28 Time 16:54 Sent To  
Notes
2006-02-28 00:00:00 
  
  
  
  
  
 RESUBMITTAL OF REVISIONS #3, AND #4
 -----------
  
  
 HANDRAIL AT GRAND STEP DOES NOT COMPLY
 WITH, FBC 2001, 1007.5.7. RELOCATE
 HANDRAIL TO SERVE NATURAL PATH OF
 TRAVEL.
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-02-27 Cont ID  
Sent By lmartine Date 2006-02-27 Time 17:47 Rev Time 0.00
Received By lmartine Date 2006-02-27 Time 17:47 Sent To  
Notes
2006-02-27 00:00:00 
  
  
 PROVIDE IMPACT PROTECTION FOR
 STOREFRONT GLAZING.
  
  
  
  
 PRODUCT APPROVAL SUBMITTAL DATED 2/1/06
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-01-27 Cont ID  
Sent By lmartine Date 2006-01-27 Time 12:02 Rev Time 0.00
Received By lmartine Date 2006-01-27 Time 12:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-01-11 Cont ID  
Sent By shill Date 2006-01-11 Time 14:25 Rev Time 0.50
Received By shill Date 2006-01-11 Time 14:25 Sent To  
Notes
2006-01-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 STRUCTURAL REVISION
  
  
 1.)CHANGES TO THE PLAN ARE TO BE
 SUBMITTED AS REVISIONS.ONE WAS
 SUBMITTED AS A REVISION, THE OTHER AS A
 SUBMITTAL.I HAVE COMBINED THEM AND
 CHARGED A REVISION FEE FOR THE
 ADDITIONAL PAGE(S).
  
 2.)THE TITLE BLOCK FOR THE ARCHITECT
 IS TO INCLUDE THE CA NUMBER,
 FAC61G1-16.003.
  
 3.)THE TITLE BLOCK FOR THE ENGINEER IS
 TO INCLUDE THE CA NUMBER,
 FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-30 Cont ID  
Sent By lmartine Date 2005-09-30 Time 14:46 Rev Time 0.00
Received By lmartine Date 2005-09-30 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-22 Cont ID  
Sent By shill Date 2005-09-22 Time 22:19 Rev Time 6.00
Received By shill Date 2005-09-19 Time 15:07 Sent To  
Notes
2005-09-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS RELATED TO PREVIOUS REVIEW,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY.
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE ARCHITECT'S TITLE BLOCK IS
 LACKING INFORMATION REQUIRED BY
 FAC61G1-16.003,004.
  
 AN ARCHITECT BUSINESS NUMBER WAS
 PROVIDED, BUT IS FOR PIERCE GOODWIN
 ALEXANDER & LINVIL INC., NOT PGAL OR
 PIERCE GOODWIN ALEXANDER & LINVIL.IF
 YOU DISAGREE THAT THE REQUIREMENT FOR
 THE TWO NAMES AS THEY APPEAR ON THE PLAN
 APPLIES, PLEASE CONTACT THE ATTORNEY FOR
 THE FLORIDA BOARD OF ARCHITECTS; LES
 SMITH, 850-402-4100.
  
 3.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.SEE PROPERTY
 APPRAISER'S VALUATION ($2,166,310).
  
 A RESPONSE WAS PROVIDED STATING THAT
 THIS DOES NOT APPLY BECAUSE IT IS A
 TENANT IMPROVEMENT.PLEASE READ THE
 CODE REFERRED, STATES REPAIRS AND
 ALTERATIONS.THIS IS AN ALTERATION.
  
 A CERTIFIED APPRAISAL WAS PROVIDED TO
 LUIS MARTINEZ FOR SUBMITTAL TO THE
 BUILDING OFFICIAL FOR CONSIDERATION.
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE,
 A9. NOTE FLOOR ELEVATIONS, TO BE 6IN
 ABOVE BFE OF 13'.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B)(2).
 PROVIDE EXISTING FFE AND PROPOSED.
  
 ENGINEERING FROM PARAMOUNT ENGINEERING
 GROUP WAS PROVIDED.IF YOU WISH TO USE
 THIS TO SHOW CODE COMPLIANCE, THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 THE FIRM IS TO BE INCLUDED ON THE
 DOCUMENT AS WELL AS THE PRINTED NAME AND
 LICENSE NUMBER OF THE INDIVIDUAL SEALING
 THE DOCUMENT, FAC61G15-23.002.ALL
 ENGINEERING SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED AND DATED
 ORIGINALS.
  
 NOTING THE FFE (FINISHED FLOOR
 ELEVATION) ON SHEET A0.01 IS ACCEPTABLE.
 HOWEVER, PLEASE CLARIFY WHAT BOW, EP AND
 ELEVATION (AT ELEVATION MARKS, A0.01)
 REPRESENT.SEE LEGEND ON PARAMOUNT'S
 ENGINEERING.THE PLANS SHOULD CLEARLY
 SHOW CODE COMPLIANCE.NOTE THAT
 PARAMOUNT'S BOW NOTES ARE FOR THE
 SIDEWALK, AND DO NOT SHOW A NEGATIVE
 ELEVATION.THE FLOOR PLAN SHOWS
 NEGATIVE ELEVATIONS AND BOW WITHIN THE
 BUILDING.I BELIEVE THIS NOTE, BOW,
 REFERS TO THE SIDEWALK ONLY.
  
 5.)THIS PROPERTY IS IN AN AREA WHICH
 REQUIRES A SOILS INVESTIGATION REPORT
 FBC*1804.2.2.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SOILS
 INVESTIGATION REPORT WILL BE SUBMITTED,
 REVIEWED BY ENGINEER OF RECORD, PRIOR TO
 FOOTING INSPECTION.
  
 A SOILS REPORT WAS SUBMITTED.THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 TIERRA IS TO BE ON THE TITLE BLOCK, AND
 A SIGNED SEALED DATED ORIGINAL IS
 REQUIRED FAC61G15-23.002.
  
 6.)ADDRESSED.
  
 7.)PROVIDE INFORMATION ABOUT THE
 EXISTING BUILDING - MINIMUM BUILDING
 TYPE AND PROTECTED OR UNPROTECTED FBC
 CHAPTER 6; HEIGHT, AREA.
  
 TYPE I WAS DECLARED.COMBUSTIBLES NOT
 ALLOWED IN TYPE I CONSTRUCTION,
 FBC707.1.REVISE ALL AFFECTED DETAILS
 ON ALL SHEETS, SUCH AS DETAILS ON A0.31
 WHICH SHOW WOOD BLOCKING, AND AJ-A0.10
 WHICH SHOWS WOOD FRAMING.
  
 40,000 SQUARE FEET WAS DECLARED AS
 BUILDING SIZE.ISN'T THIS THE TENANT
 SPACE, NOT THE TOTAL BUILDING SIZE?SEE
 FBC CHAPTER 2, DEFINITIONS.IT APPEARS
 THAT THE BUILDING IS 102820 SF, SHEET
 A100.
  
 8.)PROVIDE THE FIRE SPRINKLER PLANS,
 FBC104.3.1.1(5).
  
 NOT ADDRESSED.THIS IS REQUIRED BY BOTH
 FLORIDA BUILDING CODE AND FLORIDA
 STATUTE.AS SPRINKLERS ARE REQUIRED FOR
 THIS BUILDING, SPRINKLER DESIGN REQUIRED
 AT THIS TIME.SEE ATTACHED LETTER FROM
 THE DCA.
  
 9.)REGARDING THE USE GROUP NOTE THAT
 STORAGE IS AN ACCESSORY OCCUPANCY, SHEET
 A0.01, THIS IS NOT ACCESSORY
 FBC704.1.2.2(4).
  
 THE STORAGE AREAS ARE NOW MARKED FUTURE
 TENANT.SHOW REQUIRED HORIZONTAL TENANT
 SEPARATION, FBC704.3.PROVIDE
 CALCULATED FIRE RESISTANCE OR APPROVED
 ASSEMBLY, FBC7.
  
 10.)ENCLOSED PARKING GARAGES ARE
 REQUIRED TO COMPLY WITH FBC411.4.2, 6
 AIR CHANGES PER HOUR.PROVIDE
 CALCULATIONS.
  
 NOT ADDRESSED.M201 SHOWS AIR CHANGE OF
 8700 CFM.SHOW COMPLIANCE WITH
 FBC411.4.2, 6 AIR CHANGES PER HOUR.
 CODE COMPLIANCE IS TO BE CLEARLY SHOWN
 ON THE PLAN.
  
 11.)THE ELECTRICAL SERVICE A0.01 IS
 SHOWN OVER AN EXIT DOOR.CLARIFY.
  
 THIS WAS ADDRESSED, BUT THE COMMON PATH
 OF TRAVEL NOW EXCEEDS 75', FBC1004.1.3.
 ALSO, THE PATH OF TRAVEL IS SHOWN ACROSS
 THE DIAGONAL OF THE SPACE.THE ACTUAL
 PATH OF TRAVEL WILL BE GREATER AS THE
 OCCUPANT WILL BE TRAVELLING AROUND
 FURNITURE OR OTHER OBSTRUCTIONS.
  
 12.)NO DOOR IS SHOWN AT THE END OF
 RAMP 130, A0.01.A DOOR IS ALSO
 REQUIRED AT THE TOP OF THE EXIT
 ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF
 THE ACCESSIBLE EXIT.
  
 IT WAS DISCUSSED THAT THE LOBBY AREA
 WOULD BE PROTECTED.NOTE THE FOLLOWING:
  
 THE LIFE SAFETY PLAN AND FLOOR PLAN
 SHOULD CLEARLY SHOW FIRE RESISTANCE
 RATING REQUIREMENTS.PLEASE NOTE THAT
 THE LEGEND INDICATES FIRE RESISTANCE,
 AND NO FIRE RESISTANCE IS SHOWN FOR THE
 NEW PARTITIONS AND INFILL.ON THE FLOOR
 PLAN THERE ARE REFERENCES TO PARTITION
 DETAILS, BUT THEY DO NOT HAVE A PAGE
 REFERENCE.FOR SOMEONE LOOKING AT THE
 PLAN, IT APPEARS THAT THESE NEW WALLS
 ARE NOT FIRE RATED.THE LEGEND SHOWS
 THE GRAPHIC FOR FIRE RESISTANCE (DASHED
 LINES), BUT THIS GRAPHIC HAS NOT BEEN
 INCLUDED FOR ALL WALLS INTENDED TO BE
 FIRE RATED.THE PLAN SHOULD CLEARLY
 SHOW CODE COMPLIANCE REQUIREMENTS FOR
 PERMITTING, CONSTRUCTION AND
 INSPECTIONS.BOTH THE LIFE SAFETY PLAN
 AND THE FLOOR PLAN ARE NOT CLEAR.
  
 A FIRE RATING IS SHOWN BETWEEN THIS
 TENANT SPACE AND THE ADJACENT TENANT
 SPACE WITH A NOTE ON A0.01, BUT NOT ON
 THE FLOOR PLAN A2.01.
  
 AS DISCUSSED IN THE MEETING 9/22/05,
 THIS PERMIT CAN BE ISSUED WITH A PROVISO
 THAT THE LIFE SAFETY AND FLOOR PLANS BE
 REVISED TO CLEARLY INDICATE WHICH WALLS
 ARE TO BE PROTECTED.
  
 THE ROLLUP DOORS ARE STILL SHOWN ON THE
 FLOOR PLANS WHERE YOU ARE ELIMINATING
 THE LOADING DOCK OPENINGS.IF THE
 OPENINGS ARE BLOCKED UP, WHY ARE DOORS
 STILL ON THE PLAN?THE DOOR SCHEDULE ON
 A2.01 SHOWS THE DOORS AS REMAINING.
  
 13.)TWO EXITS REQUIRED REMOTELY
 LOCATED FBC1004.1.4.STAIR 2, A0.02
 LEADS THROUGH THE ELEVATOR LOBBY.THE
 OTHER TWO STAIRS ARE LESS THAN 1/3
 DISTANCE APART.
  
 ADDRESSED, BUT PLEASE REVISE AS PER ITEM
 12 TO CLEARLY SHOW FIRE RESISTANCE
 REQUIREMENTS.
  
 14.)ADDRESSED.
  
 15.)SHOW OCCUPANCY SEPARATION
 FBC704.1, HORIZONTAL SEPARATION BETWEEN
 BETWEEN THE STORAGE AND BUSINESS AREAS.
 PROVIDE A DETAIL WITH A LISTED ASSEMBLY
 OR CALCULATED FIRE RESISTANCE FBC709.
  
 THE OCCUPANCY HAS NOW CHANGED FROM
 STORAGE TO FUTURE TENANT, BUSINESS.A 1
 HOUR TENANT SEPARATION REQUIRED, SEE
 ITEM 9.
  
 16.)ADDRESSED.
  
 17.)ADDRESSED.
  
 18.)ADDRESSED.
  
 19.)ADDRESSED.
  
 20.)ADDRESSED.
  
  
 21.)INTERIOR FINISH CLASSIFICATION
 (A0.01) IS TO COMPLY WITH FBC TABLE
 803.3.A0 HAS A NOTE IN REGARDS TO
 INTERIOR FINISHES AND THE UBC, WHICH IS
 NOT THE GOVERNING CODE.
  
 A0.01 WAS REVISED.SEE A0.20.THERE IS
 A NEW NOTE REFERRING TO CLASS II AND
 CLASS IV FLAME SPREADCLASSIFICATIONS.
 I BELIEVE THAT THIS IS FROM THE UBC.
 FBC USES FLAME SPREAD CLASSIFICATIONS A,
 B, AND C.PLEASE REVISE TO BE CODE
 COMPLIANT AS I CANNOT DETERMINE HOW THE
 FLAME SPREAD CLASSIFICATIONS YOU REFER
 TO IN THIS NEW NOTE RELATE TO THE
 REQUIREMENTS OF FBC.THE NOTE ON THE
 PLAN ALSO REFERS TO A CLASS REDUCTION IN
 TABLE FBC803.3.THE TABLE DOES NOT
 REFER TO A CLASS REDUCTION BUT DOES
 PROVIDE MINIMUM REQUIREMENTS.
  
 22.)ADDRESSED.
  
 23.)LANDINGS ARE REQUIRED AT TOP AND
 BOTTOM OF RAMPS IN COMPLIANCE WITH
 FBC11-4.8.4.NOTE THE FOLLOWING:
  
 A.THE LANDING AT THE BOTTOM OF THE
 RAMP IS TO BE 72IN CLEAR, ONLY 60IN
 SHOWN WHEN SCALED, FBC11-4.8.4(2).
  
 THE RAMP WAS WIDENED AT THE BOTTOM TO
 PROVIDE TURNING CLEARANCE AT THE DOOR.
  
 THE 72IN CLEAR REQUIREMENT WAS NOT
 ADDRESSED.THIS APPLIES TO THE LANDING
 RUN AT THE BOTTOM OF THE RAMP.THERE
 IS STILL ONLY 60IN WHEN SCALED.PLEASE
 PUT REQUIRED DIMENSIONS ON THE PLAN ON
 THE LANDINGS TO AVOID CONFUSION.
  
 B.ADDRESSED.
  
 C.ADDRESSED
  
 THE HANDRAILS DO NOT COMPLY WITH
 FBC11-4.8.5(2).THEY ARE TO EXTEND 18IN
 BEYOND THE SLOPED SEGMENT.
  
 24.)N/A
  
 25.)SHOW ACCESSIBLE PASSENGER LOADING
 ZONES, FBC11-4.6.6 AND VERTICAL
 CLEARANCE FBC11-4.6.5.
  
 PLEASE SHOW STRIPING FOR THE ACCESS
 AISLE FROM THE LOADING ZONE PARKING
 SPACE TO THE ACCESSIBLE ENTRANCE; CANNOT
 GO BEHIND PARKED CARS.
  
 VERTICAL CLEARANCE WAS ADDRESSED IN THE
 LETTER.PLEASE PUT ON THE PLAN SO THAT
 THE PLAN SHOWS CODE COMPLIANCE.
  
 26.)THE HANDRAIL ON THE GUARDRAIL SIDE
 OF THE STAIR 4-A4.-01 IS TO COMPLY WITH
 FBC11-4.9.4(2), NO EXTENSION AT THE
 BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE
 11-19(C).
  
 NOT ADDRESSED.SEE STAIR 4 ENLARGED
 PLAN, A4.01 AND SECTION AT STAIR 4,
 A4.01.STAIRS ARE REQUIRED TO HAVE
 HANDRAILS ON BOTH SIDES FBC11-4.9.4.
 THERE SHOULD BE A HANDRAIL ON THE
 GUARDRAIL SIDE OF THE STAIR, ONLY ONE
 SHOWN ALONG THE WALL.THE HANDRAIL ON
 THE GUARDRAIL SIDE IS TO HAVE AN
 EXTENSION, SEE FBC11 FIGURE 11-19C.
  
 27.)A TURNING SPACE OF 60IN REQUIRED
 FOR THE U-TURN AT THE WOMENS BATHROOM
 122, FBC11-4.2.1.
  
 BATHROOM WAS DELETED.A DRINKING
 FOUNTAIN NOW APPEARS NEXT TO THE
 ELEVATOR ROOM 120.WHAT IS THE GRAPHIC
 ADJACENT TO THE DRINKING FOUNTAIN?
  
 28.)ADDRESSED.
  
 29.)ADDRESSED.
  
 30.)ADDRESSED.
  
 31.)ADDRESSED.
  
 32.)ADDRESSED.
  
 33.)PROVIDE THE ELEVATIONS OF THE
 SIDEWALK AND FINISHED FLOOR AT THE TWO
 EXIT DOORS,FBC11-4.1.2.
  
 THIS WILL BE ADDRESSED WHEN
 CLARIFICATION ON ELEVATIONS IS PROVIDED,
 SEE ITEM 4.
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR THE NEW EXTERIOR
 DOORS, INTAKE LOUVERS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 THE DADE COUNTY NOAS SUBMITTED APPEAR
 CODE COMPLIANT.HOWEVER, FLORIDA STATE
 OR LOCAL PRODUCT APPROVALS ARE REQUIRED
 IN ADDITION TO THE EVALUATION REPORT,
 FAC9B72.WWW.FLORIDABUILDING.ORG.
  
 35.)ADDRESSED.
  
 36.)ADDRESSED.
  
 37.)GARAGE EXHAUST IS SHOWN IN THE
 STAIR AND EXIT ENCLOSURES, SEE
 FBC1006.1.3.1.
  
 EXHAUST WAS REVISED.HOWEVER, DUCTWORK
 AND OUTLETS ARE NOW SHOWN THROUGH THE
 EXIT STAIR.SEE FBC1006.1.3.1.
  
 NEW COMMENTS:
  
 38.)TWO ACCESSIBLE MEANS OF EGRESS
 REQUIRED FOR THE FIRST FLOOR,
 FBC11-4.1.3(9).THIS APPLIES TO BOTH
 THE BUSINESS AREAS AND THE PARKING
 GARAGE.
  
 39.)COLUMN LOCATIONS ARE NOTED ON
 VARIOUS SHEETS.IT APPEARS THAT A
 COLUMN SHOULD BE ALONG THE WALL BETWEEN
 FUTURE TENANT 102 AND THE ADJACENT
 TENANT.IF NOT, HOW IS THAT LOAD
 SUPPORTED?
  
 40.)SHEET S1 CONFLICTS WITH THE
 ARCHITECTURALS (RAMP).
  
 41.)PROVIDE ASSEMBLY LISTING AND
 DETAIL FOR PENETRATIONS THROUGH THE
 RATED WALLS.
  
 42.)PLEASE NOTE THAT ALTHOUGH FBC
 TABLE 704.1 REQUIRES A 1 HOUR SEPARATION
 FOR AUTOMOBILE PARKING GARAGES, FIRE MAY
 HAVE OTHER REQUIREMENTS.SEE FIRE
 COMMENTS.A 2 HOUR IS CURRENTLY SHOWN.
 IF A 2 HOUR IS REQUIRED, OPENING
 PROTECTIVES ARE TO COMPLY WITH TABLE
 705.1.2, 1 1/2 HOUR.ONLY 1 HOUR FOR
 THE ELEVATOR DOOR IS SHOWN.
  
 DOOR 100F IS SHOWN AS A 45 MIN. DOOR.
 IF 2 HOUR IS REQUIRED, THIS SHOULD BE 1
 1/2 HR.
  
 DOOR 114, LOCATED IN A 1 HOUR WALL, DOES
 NOT SHOW A FIRE RATING.
  
 THE DOOR AT THE ELEVATOR ROOM DOES NOT
 HAVE A DOOR NUMBER DESIGNATION.
  
 43.)PLEASE SIGN THE OWNER/AGENT LINE
 OF THE ENERGY CALCS.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL INDICATING HOW
 (AND WHERE) EACH ITEM WAS ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-27 Cont ID  
Sent By shill Date 2005-08-27 Time 14:09 Rev Time 8.00
Received By shill Date 2005-08-18 Time 09:38 Sent To PC
Notes
2005-08-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE ARCHITECT'S TITLE BLOCK IS
 LACKING INFORMATION REQUIRED BY
 FAC61G1-16.003, 004.
  
 3.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6.SOME COMMENTS MAY RELATE
 TO THIS CODE SECTION.SEE PROPERTY
 APPRAISER'S VALUATION ($2,166,310).
  
 4.)THIS PROPERTY IS IN A FLOOD ZONE,
 A9. NOTE FLOOR ELEVATIONS, TO BE 6IN
 ABOVE BFE OF 13'.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B)(2).
 PROVIDE EXISTING FFE AND PROPOSED.
  
 5.)THIS PROPERTY IS IN AN AREA WHICH
 REQUIRES A SOILS INVESTIGATION REPORT
 FBC*1804.2.2.THIS PERMIT WILL BE
 ISSUED WITH A PROVISO THAT A SOILS
 INVESTIGATION REPORT WILL BE SUBMITTED,
 REVIEWED BY ENGINEER OF RECORD, PRIOR TO
 FOOTING INSPECTION.
  
 6.)A0.1, THE AREA CALCULATIONS FOR
 EGRESS CAPACITY DO NOT INCLUDE THE
 ENCLOSED PARKING GARAGE FBC411.4.
  
 7.)PROVIDE INFORMATION ABOUT THE
 EXISTING BUILDING - MINIMUM BUILDING
 TYPE AND PROTECTED OR UNPROTECTED FBC
 CHAPTER 6; HEIGHT, AREA.
  
 8.)PROVIDE THE FIRE SPRINKLER PLANS,
 FBC104.3.1.1(5).
  
 9.)REGARDING THE USE GROUP NOTE THAT
 STORAGE IS AN ACCESSORY OCCUPANCY, SHEET
 A0.01, THIS IS NOT ACCESSORY
 FBC704.1.2.2(4).
  
 10.)ENCLOSED PARKING GARAGES ARE
 REQUIRED TO COMPLY WITH FBC411.4.2, 6
 AIR CHANGES PER HOUR.PROVIDE
 CALCULATIONS.
  
 11.)THE ELECTRICAL SERVICE A0.01 IS
 SHOWN OVER AN EXIT DOOR.CLARIFY.
  
 12.)NO DOOR IS SHOWN AT THE END OF
 RAMP 130, A0.01.A DOOR IS ALSO
 REQUIRED AT THE TOP OF THE EXIT
 ENCLOSURE TO MAINTAIN FIRE RESISTANCE OF
 THE ACCESSIBLE EXIT.
  
 13.)TWO EXITS REQUIRED REMOTELY
 LOCATED FBC1004.1.4.STAIR 2, A0.02
 LEADS THROUGH THE ELEVATOR LOBBY.THE
 OTHER TWO STAIRS ARE LESS THAN 1/3
 DISTANCE APART.
  
 14.)PROVIDE INFORMATION REGARDS WHAT
 WILL BE STORED IN THE STORAGE AREAS AND
 DECLARE SUBCLASSIFICATIONS FBC312.2.
  
 15.)SHOW OCCUPANCY SEPARATION
 FBC704.1, HORIZONTAL SEPARATION BETWEEN
 BETWEEN THE STORAGE AND BUSINESS AREAS.
 PROVIDE A DETAIL WITH A LISTED ASSEMBLY
 OR CALCULATED FIRE RESISTANCE FBC709.
  
 16.)SHOW OCCUPANCY SEPARATION FBC704.1
 BETWEEN ROOMS 260, 211, 212 AND THE
 BUSINESS AREAS ON THE SECOND FLOOR.
  
 17.)SHOW OCCUPANCY SEPARATION
 FBC704.1, SEPARATION BETWEEN THE EXIT
 CORRIDORS AND THE STORAGE AREAS ON THE
 FIRST FLOOR.PROVIDE A DETAIL WITH A
 LISTED ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 18.)SHOW OCCUPANCY OF ADJACENT TENANTS
 AND TENANT SEPARATION, FBC704.1.
  
 19.)ALL OPENING PROTECTIVES ARE TO
 COMPLY WITH FBC705.1.2.PLEASE NOTE
 REQUIREMENTS FOR STORAGE OCCUPANCY.
  
 20.)THE EXTERIOR STAIRS IS TO COMPLY
 WITH FBC1006.2.NOTE THAT FIRE
 RESISTANCE REQUIRED BY FBC1006.2.4 IS
 NOT SHOWN ON THE PLAN.
  
 21.)INTERIOR FINISH CLASSIFICATION
 (A0.01) IS TO COMPLY WITH FBC TABLE
 803.3.A0.20 HAS A NOTE IN REGARDS TO
 INTERIOR FINISHES AND THE UBC, WHICH IS
 NOT THE GOVERNING CODE.
  
 22.)THE ELEVATOR ROOM 120 IS TO COMPLY
 WITH FBC3003.7.1.THE PLAN SHOWS THE
 ELEVATOR?S ACCESS IN THE TENANT SPACE.
  
 23.)LANDINGS ARE REQUIRED AT TOP AND
 BOTTOM OF RAMPS IN COMPLIANCE WITH
 FBC11-4.8.4.NOTE THE FOLLOWING:
  
 A.THE LANDING AT THE BOTTOM OF THE
 RAMP IS TO BE 72IN CLEAR, ONLY 60IN
 SHOWN WHEN SCALED, FBC11-4.8.4(2).
  
 B.THE LANDING AT THE TOP SHALL BE NOT
 LESS THAN 60IN CLEAR,48IN SHOWN
 FBC11-4.8.4.(2).
  
 C.IF RAMPS CHANGE DIRECTION AT
 LANDINGS, THE MINIMUM LANDING SIZE SHALL
 BE 60IN BY 60IN.48IN BY 48IN SHOWN,
 FBC11-4.8.4(3).
  
 24.)N/A
  
 25.)SHOW ACCESSIBLE PASSENGER LOADING
 ZONES, FBC11-4.6.6 AND VERTICAL
 CLEARANCE FBC11-4.6.5.
  
 26.)THE HANDRAIL ON THE GUARDRAIL SIDE
 OF THE STAIR 4-A4.-01 IS TO COMPLY WITH
 FBC11-4.9.4(2), NO EXTENSION AT THE
 BOTTOM IS SHOWN.ALSO SEE FBC11 FIGURE
 11-19(C).
  
 27.)A TURNING SPACE OF 60IN REQUIRED
 FOR THE U-TURN AT THE WOMENS BATHROOM
 122, FBC11-4.2.1.
  
 28.)DOORS 208 AND 204, A2.02 ARE TO
 COMPLY WITH FBC11-4.13.7, FIGURE 26.
 THIS IS A WORK AREA TO COMPLY WITH
 FBC11-4.1(3), ACCESSIBLE APPROACH.
  
 29.)SALES OFFICES, SHEET S2, DOORS ARE
 TO COMPLY WITH MANEUVERING CLEARANCE ON
 THE PULL SIDE, FBC11-4.13.6, FIGURE 11.
 THE FURNITURE IS IN THE REQUIRED CLEAR
 FLOOR SPACE.
  
 30.)PROVIDE DETAILS FOR THE BREAK ROOM
 202 SINK TO COMPLY WITH FBC11-4.24.1
 THROUGH 11-4.24.7.
  
 31.)COFFEE BAR 232 SHOWS A SINK ON
 SOME SHEETS (FOR EXAMPLE, S2, M202) AND
 NOT ON OTHERS (A2.02, P202).PLEASE
 MAKE ALL SHEETS CONSISTENT AND IF THERE
 IS A SINK, PROVIDE A DETAIL COMPLIANT
 WITH FBC11-4.24.1 THROUGH FBC11-4.24.7.
  
 32.)3-A6.00, ELEVATOR CALL BUTTON TO
 BE CENTERED AT 42IN.
  
 33.)PROVIDE THE ELEVATIONS OF THE
 SIDEWALK AND FINISHED FLOOR AT THE TWO
 EXIT DOORS,FBC11-4.1.2.
  
 34.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR THE NEW EXTERIOR
 DOORS, INTAKE LOUVERS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 35.)PROVIDE INFORMATION IN REGARDS TO
 THE CIRCULAR CARPETED AREAS A2.02 IN THE
 TWO WAITING AREAS.ARE THERE HANGING
 FIXTURES?PROVIDE LOADING INFORMATION
 FBC16, FASTENING.
  
 36.)A2.02, THE HALL 262 DOOR APPEARS
 TO SWING ONTO A COLUMN.
  
 37.)GARAGE EXHAUST IS SHOWN IN THE
 STAIR AND EXIT ENCLOSURES, SEE
 FBC1006.1.3.1.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.TO EXPEDITE PLAN REVIEW,
 PROVIDE A TRANSMITTAL INDICATING HOW
 (AND WHERE) EACH ITEM WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 17:37 Sent To FIRE
Notes
2006-05-02 00:00:00REV'S FOR 301 AND 302 FOR EM AND EXT
 LTS.
  
 ** PLANS SENT TO FIRE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-27 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 07:29 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 21:55 Sent To  
Notes
2006-03-27 00:00:00REV'S FOR SHEETS
 201,202,301,302,801
2006-03-24 00:00:00IN ELEC FOR REVIEW, REVIEW TO BE
 COMPLETED ON 3/27

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 11:47 Sent To M
Notes
2006-02-08 00:00:00REDLINED 424.3B

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 19:47 Sent To  
Notes
2005-12-20 00:00:00**** UNSAT ****
  
 AS GONE OVER WITH ENGINEER ON A PREVIOUS
 MEETING WHICH WAS CORRECTED FOR PREVIOUS
 COMMENTS, HOWEVER PLANS HAVE COME BACK
 IN WITHOUT SOME OF THOSE CORRECTIONS
 INCORPORATED INTO PLANS.
  
  
 1)NOTE: PLEASE ADJUST OCP FOR ALL AHU'S,
 AS REQUIRED UNDER 424.3B
 PLEASE SEE CALCULATING HEAT LOAD FROM
 MOTOR LOAD AND THEN ADDING MOTOR LOAD,
 STILL EXCEEDS THE OCP SHOWN ON PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE REMOVE ALL ELECTRICAL
 DEVICES, FIXTURES ETC LOCATED IN "FUTURE
 TENANT SPACE". THIS WAS ALSO REQUESTED
 ON PREVIOUS REVIEW SINCE THESE SPACES
 ARE NOT IN SCOPE.
  
 3)NOTE: PLEASE INDICATE THE GFI
 PROTECTION IN KITCHEN AREA. 2002 NEC
 210.8B3
 ALL 125V, 15 AND 20A RECEPTS, SHALL BE
 GFI OR GFI PROTECTED.
  
 4)NOTE: PLEASE SEE E-2.01, PLEASE ADJUST
 WORDING FOR BAY #4 METER AND MAIN, AS
 PLANS INDICATE THIS AS SERVICE #4.
 PLEASE KNOW, THIS BLDG ONLY CONTAINS ONE
 SERVICE AND THIS SHOULD READ BAY #4
 METER/MAIN OR WORDS TO THAT AFFECT.
  
 5)NOTE: PLEASE SEE MECHANICAL/FIRE
 "PROVISO", NOTES, WITH RESPECT TO THE
 PARKING AREA AND AIR CHNAGES REQUIRED
 AND THE POSSIBLE AFFECT THIS WILL AHVE
 ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-30 Cont ID  
Sent By dpalmer Date 2005-09-30 Time 13:49 Rev Time 1.00
Received By dpalmer Date 2005-09-30 Time 13:49 Sent To  
Notes
2005-09-30 00:00:00** PROVISO**
  
 PLEASE SEE MECHANICAL/ FIRE "PROVISO ".
 WITH RESPECT TO GARAGE PARKING AND
 VENTILATION.
 THIS WILL DIRECTLY AFFECT ELECTRICAL
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-26 Cont ID  
Sent By dpalmer Date 2005-09-26 Time 09:13 Rev Time 0.00
Received By dpalmer Date 2005-09-23 Time 15:39 Sent To  
Notes
2005-09-26 00:00:00******** UNSAT ******
  
 PLEASE SEE SOME NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE ELECTRICAL PLANS INDICATE
 CLOAED IN PARKING AREAS, WHICH MAY
 REQUIRE CHANGES AND AFFECT ELECTRICAL
 PLANS.
 PLEASE ALSO SEE SOME NOTES FROM
 ELECTRICAL REVIEW.
  
 1)NOTE: PLEASE SEE MOST OF KITCHEN/
 BREAK RM AREA RECEPTS WERE CLOUDED FOR
 A/G , HOWEVER PLEASE SEE 2LA 19,21.
 210.8B3
  
 2)NOTE: PLEASE SEE ROOMS ON ELECTRICAL
 PLANS CONTAINING ELECTRICAL EQUIPMENT
 AND PANELS, SHALL CONTAIN LABELING FOR
 SCUH. RESPONSE LTR MENTIONS THIS IS THE
 ARCHITECT'S DECISION TO LABEL ETC.
 PLEASE SEE THIS IS REQUIRED AT THIS
 TIME.
 110.26
  
 3)NOTE: PLEASE SEE IT IS STILL UNCLEAR
 HOW NEW TENANT SPACE IS BEING FED AND
 FROM WHAT "SERVICE" IT IS BEING FED
 FROM.
 PLEASE SEE RESPONSE LTR MENTION THE NEW
 LOADFOR NEW TENANT SPACE IS BEING
 ADDED TO EXISTING 2000A SERVICE AND
 TOTAL NEW LOAD FOR EXSITING AND NEW IS
 1,496A'S.( RESPONSE LTR SEEMS TO BE
 MISPRINTED SHOWING 1,986A'S)
 NEW AND EXISTING LOADS ARE NOTED ON
 RISER SHEET E5.02 AS WELL.
 THIS IS A COMBINATION OF NEW AND
 EXISTING LOADS TO "EXISTING SERVICE".
 HOWEVER, PLEASE SEE NOTES TO RISER WHICH
 MENTIONS A "NEW SERVICE" IS BEING ADDED
 AND "CHANGE OVER ELECTRICAL SERVICE"
 WITH FPL??
 PLEASE CLARIFY.
 IF NEW TENANT ELECTRICAL METER AND MAIN
 IS GOING TO BE FED FROM EXISTING 2000A
 SERVICE, A"SERVICE CHANGE OVER" WITH
 FPL WOULD NOT BE REQUIRED.
 PLEASE ALSO SEE"SHEET NOTES" WHICH
 MENTIONS, NO NEW LOADS ARE CONNECTED TO
 "EXISTING SERVICE", YET PREVIOUS NOETS
 AND RESPONSE LTR MENTIONS SOMETHING
 DIFFERENT.?
  
 PLANS, RISER AND NOTES DO NOT SEEM TO
 CORRELATE.
 PLEASE SEE IF NEW TENANT SPACE IS BEING
 FROM EXISTING SERVICE, THE NEW TEANT
 METER AND MAIN WOULD NOT BE A NEW
 "SERVICE".
 230.2.
  
 4)NOTE: PLEASE SEE RESPONSE TO NOTE #11
 FROM PREVIOUS REVIEW MENTIONS, "ALL
 CONTINUOUS LOADS ARE SHOWN AND
 CALCUALTED AT 125%.
 PLEASE SEE PREVIOUS NOTE #, WAS FOR
 SIZING OF OCP OF AHU HEAT LOADS.
 PLEASE SEE AHU/ CU A/C SYSTEMS ARE
 THERMASTATICALLY CONTROLLED AND ARE NOTE
 CONSIDERED "CONTINUOUS LOADS" (3 OR MORE
 HRS)
 PLEASE SEE 424.3B, WHICH DOES REQUIRE
 THE MIN COP TO BE SIZED AT 125% FOR
 HEAT.
 PLEASE SEE LOADS AND OCPSHOWN FOR
 AHU'S, #4, #3 AND #5 DO NOT SEEM TO
 PROVIDE OCP AT 125%.?
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE RESPONSE TO PREVIOUS
 NOTE #13 WHICH MENTIONS RISERS, ONE
 -LINES ETC ARE NOT REQUIRED TO BE
 SCALED. THIS IS CONFIRMED AND KNOWN THAT
 THESE TIEMS ARE NOT SCALED. PREVIOUS
 NOTE WAS NOT FOR THESE ITEMS.
  
 6)NOTE: PLEASE SEE 220.12B FOR LOAD
 CALCUALTIONS OF TRACK LIGHTING. PLEASE
 SEE NOTE AND RESPONSE LTR MENTIONS 50W
 PER FIXTURE, HOWEVER CODE REQUIRES MAX
 WATTAGE BASED ON LINEAR FT.
  
 7)NOTE: PLEASE SEE E3.01, WHICH SHOWS
 NEW LIGHTING FIXTURES BEING INSTALLED IN
 "FUTURE" TENANT SPACE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By dpalmer Date 2005-07-27 Time 11:12 Rev Time 4.00
Received By dpalmer Date 2005-07-27 Time 11:11 Sent To  
Notes
2005-07-27 00:00:00*************UNSAT *****************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR ADDRESSING, UNIT, SUITE #.
 THE BLDG IS ADDRESSED AS 1016 CLARE.
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK FOR ARCHITECTUAL AND
 ENGINEERING FIRM. PLEASE SEE 61G1-16.004
 FOR ARCH'S, MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER FOR ARCHITECT.
 CA # REQUIRE DUNDER FS 481.219
 PLEASE SEE FAC 61G15-23.002 FOR ENG'S
 TITLE BLOCK AND MISSING THE PRINTED NAME
 AND LICENSE NUMBER FOR ENG.
 PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN
 AREAS IN OTHER THAN DWELLING UNITS,
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 4)NOTE: PLEASE SEE ELEVATOR RMS AND
 REQUIRED DEDICATED CIRCUITS PER 620.23
 AND 620.24
 PLEASE SEE LITGHING AND RECEPTS, MAY NOT
 FEED ANY OTHER AREAS.
  
 5)NOTE: PLEASE SEE SMALL ROOMS/CLOSETS
 ETC SHOWN WITH ELECTRICAL PANELS, SHALL
 BE LABLED AS ELECTRICAL/MECHANICAL ROOMS
 AND SHALL HAVE NO STORAGE. 110.26,408.7
 ETC.
 PLEASE SEE THESE ROOMS WILL BE REQUIRED
 TO HAVE SIGNAGE PLACED ON DOORS FOR
 "ELECTRICAL ROOM","NO STORAGE".
  
 6)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT ITS IS NOTED ON
 PLANS FOR EM FIXTURES TO BE ON WITH
 LOCAL LIGHTING, HOWEVER A COUPLE OF
 AREAS DO NOT SEEM TO CORRELATE WITH
 THIS.
  
 7)NOTE: PLEASE CLARIFY SERVICE SHOWN;
 PLEASE SEE RISER APPEARS TO SHOW AN ALL
 NEW 2000A'S PLUS SERVICE BEING INSTALLED
 TO A NEW ELECTRICAL ROOM FOR FUTURE
 TENANTS? PLEASE CLARIFY HOW THIS IS
 INCLUDE WITH SCOPE OF WORK FOR BLD-OUT
 OF THIS ELECTRICAL SPACE. PLEASE SEE
 PLANS DO NOT APPEAR TO HAVE ANY NEW
 TENANT AREAS IN THIS SCOPE.
 PLEASE ALSO SEE ANY CLEARENCES FOR
 GUTTER/ METER AND DISC'S IS REQUIRED TO
 MEET 110.26.
 THIS SEPARATE ELECTRICAL EQUIPMENT
 NEEDS TO BE UNDER A SEPARATE PERMIT
 WHICH WILL REQUIRE ADDITIONAL, LOAD
 CALCULATIONS ETC.
 215.5
  
 8)NOTE: PLEASE PROIVIDE HP RATING OF
 ELEVATOR MOTOR ALONG WITH ANY SPECIFIC
 CODE LTR ETC.
 KVA LOAD IS SHOWN, HOWEVER MORE
 INFORMATION IS NEEDED.
 215.5
  
 9)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS
 FOR EXISTING 2000A SERVICE AND ANY
 CONNECTED LOADS EXISTING ALONG WITH NEW
 PROPOSED LOADS ADDED.
 215.5,220
  
 10)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42 ETC. LIGHTNING, LARGEST
 MOTOR ETC.
  
 11)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT.125% MIN.
 PLEASE ADJUST OCP, AWG AND ANY CONDUIT
 SIZES.
 240.4,310.16
  
 12)NOTE: PLEASE SHOW TRACK LIGHTING LOAD
 CALCULATIONS PER 220.12.
  
 13)NOTE: PLEASE SEE NOTE MENTIONS "NO
 SCALE" ON PLANS. PLEASE SEE FBC
 104.2.1.3 WHICH REQUIRESA MIN 1/8"
 SCALE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-05-18 Cont ID  
Sent By nmccray Date 2006-05-18 Time 15:40 Rev Time 0.00
Received By nmccray Date 2006-05-18 Time 15:40 Sent To  
Notes
2006-05-18 00:00:00ELECTRICAL REVISION
 E301 & E302 DATED 04/20/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-03-30 Cont ID  
Sent By mwennerg Date 2006-03-30 Time 09:52 Rev Time 0.00
Received By mwennerg Date 2006-03-30 Time 09:52 Sent To  
Notes
2006-03-30 00:00:00REVISION DATED 2/3/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-12-21 Cont ID  
Sent By mcarsill Date 2005-12-21 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2005-12-21 Time 13:19 Sent To  
Notes
2005-12-21 00:00:001. A KNOX-BOX WILL BE REQUIRED IF ONE IS
 NOT ALREADY PRESENT.
  
 2. SEPERATE PLANS AND PERMITS REQUIRED
 FOR NEW FIRE ALARM SYSTEM CONTROL PANEL.
  
 3. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 5. EXITS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 6. GASOLINE POWERED EQUIPMENT SHOULD NOT
 BE USED WITHOUT PROPER VENTILATION DUE
 TO THE POSSIBILITY OF CARBON MONOXIDE
 BUILD-UP.
  
 7. GARAGE EXHAUST FAN APPEARS TO RUN
 THRU ADJACENT TENANT SPACE. PLEASE
 EXPLAIN RATIONALE. HOW IS THE PERMANANT
 EXHAUST DUCT CONTROLLED IF LOCATED
 INSIDE A DIFFERENT TENANT SPACE NOT
 UNDER THE CONTROL OR DIRECTION OF THE
 PRIMARY TENANT.
  
 8. CO DETECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURERS STANDARDS.
 PLEASE VERIFY ALL SET POINTS ON
 DETECTORS PLANNED FOR USE.
  
 9. HANDRAILS AND GUARDRAILS SHALL COMPLY
 WITH ALL PRESCRIPTIVE CODE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 10. PLEASE VERIFY ALL DOORS REQUIRED TO
 BE FIRE RATED ARE ILLUSTRATED ON THE
 DOOR SCHEDULE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By lmartine Date 2005-09-29 Time 10:46 Rev Time 0.00
Received By lmartine Date 2005-09-29 Time 10:46 Sent To  
Notes
2005-09-29 00:00:00APPROVED PER MIKE CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 10:29 Rev Time 0.00
Received By mwennerg Date 2005-08-23 Time 10:29 Sent To  
Notes
2005-08-23 00:00:00******DENIED******
  
 1) PLANS INDICATE THAT DUCT SMOKE
 DETECTORS INITIATE SUPERVISORY SIGNAL
 WHEN ACTIVATED. IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED TO CAUSE A GENERAL FIRE ALARM
 WHERE APPLICABLE.
  
 2) IT APPEARS THAT SOME EXIT SIGNS AT
 FIRST LEVEL EAST SIDE MAY BE MISSING.
 EXIT SIGNS SHALL BE PLACED WHERE OBVIOUS
 AND VISIBLE FROM ALL POINTS OF MEANS OF
 EGRESS, AT A DISTANCE NOT TO EXCEED
 100'.
  
 3) AN ADDRESS ON BUILDING OR SPACE IS
 REQUIRED. MINIMUM 6" FOR MAIN BUILDING
 ADDRESS AND 3" FOR SPECIFIC UNIT OR
 SPACE.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 5) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B ORC.
  
 6) PLANS SHOW A PARKING AREA THAT WOULD
 APPEAR TO BE CLOSED. PLEASE NOTE THAT
 NFPA 88A AND OTHER APPLICABLE CODES
 SHALL BE COMPLIED WITH TO MAINTAIN
 REQUIRED 2 HOUR SEPARATION FROM
 REMAINING AREAS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 12:11 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 12:11 Sent To E
Notes
2006-04-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 10:34 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 10:34 Sent To  
Notes
2006-05-03 00:00:00TO "COMM" BD#20
2006-04-17 00:00:00WAITIANG FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 16:41 Sent To B
Notes
2006-04-12 00:00:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-27 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-03-27 Time 14:12 Sent To B
Notes
2006-03-27 00:00:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 10:21 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 10:21 Sent To  
Notes
2006-03-24 00:00:00TO COMM BOARD #57 B

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 11:38 Sent To  
Notes
2006-03-17 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-01 Cont ID  
Sent By adarroug Date 2006-03-01 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-03-01 Time 11:35 Sent To  
Notes
2006-03-01 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 08:16 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 08:16 Sent To P
Notes
2006-02-09 00:00:00TO "PSCHMITZ" DESK/RESUB--EXPIDITED PLAN

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 11:52 Sent To  
Notes
2006-02-08 00:00:00ROUTED TO D PALMER FOR ELECTRICAL
 REVIEW.
  
  
2006-02-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 12:28 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 12:28 Sent To B
Notes
2006-02-03 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 11:02 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 11:02 Sent To B
Notes
2005-12-30 00:00:00TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 14:28 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 14:28 Sent To  
Notes
2005-11-30 00:00:00TO "COMM" BD#5
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 12:09 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 12:09 Sent To  
Notes
2005-09-13 00:00:00TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-27 Cont ID  
Sent By shill Date 2005-08-27 Time 14:14 Rev Time 0.00
Received By shill Date 2005-07-15 Time 08:18 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#46
2005-07-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-05-22 Cont ID  
Sent By hmoser Date 2006-05-22 Time 13:50 Rev Time 0.00
Received By hmoser Date 2006-05-22 Time 13:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-05-04 Cont ID  
Sent By pkrauss Date 2006-05-04 Time 14:06 Rev Time 0.00
Received By pkrauss Date 2006-05-04 Time 13:22 Sent To  
Notes
2006-05-04 00:00:00PROVISO:
  
 PLEASE NOTE EQUIPMENT LOCATED IN A FLOOD
 ZONE, SHALL BE PLACED ABOVE THE FLOOD
 ELEVATION OR PROTECTED IN A MANNER TO
 PREVENT WATER FROM ENTERING OR
 ACCUMULATING WITHIN THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-03-31 Cont ID  
Sent By pkrauss Date 2006-03-31 Time 07:31 Rev Time 0.00
Received By pkrauss Date 2006-03-31 Time 06:32 Sent To  
Notes
2006-03-31 00:00:00DENIED:5TH REQUEST:
 PLEASE NOTE, THE FOLLOWING ITEM WAS
 APPROVED WITH A PROVISO.THE PLANS HAVE
 NOT BEEN REVISED TO ADDRESS THE PROVISO.
  
 THE PARKING GARAGE IS NOT CODE
 COMPLIANT.A PROVISO WAS GIVEN TO HELP
 EXPEDITE THE JOB.REVISED PLANS SHALL
 REFLECT THE REQUIREMENTS OF THE PROVISO.
  
 GARAGE VENTILATION SHALL COMPLY WITH
 2001 FBC 403.4, 403.4.1, 502.11.PLEASE
 REVISE PLANS TO INDICATE THE FOLLOWING
 INFORMATION:
 1.WILL FANS RUN CONTINIOUS OR
 INTERLOCKED WITH WITH CO SENSORS.
 PLEASE NOTE, CO SENSORS SHALL ACTIVATE
 FANS WHEN SET A MAXIMUM OF 25 PARTS PER
 MILLION.CO SENSORS SHALL BE TESTED.
  
 2.PLEASE INDICATE LAYOUT FOR THE CO
 SENSORS.
  
 3.PLEASE INDICATE FRESH AIR MAKE-UP
 FOR COMPLIANCE WITH 2001 FMC 501.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-02-08 Cont ID  
Sent By hmoser Date 2006-02-08 Time 16:31 Rev Time 0.00
Received By hmoser Date 2006-02-08 Time 16:31 Sent To  
Notes
2006-02-08 00:00:00PASS PRIVISO
 1- PLAN DOES NOT INDICATE NUMBER OF
 VEHICLES THAT CAN BE PARKED IN
 GARAGE.PER 411.4.2 & 411.5.4 UNDER
 NORMAL USE THE VEVTILATION SHALL BE
 CONTINIOUS WITH BOATH INTAKE AND EXHAUST
 2- PLEASE REFER TO SECTION 301.14 2001
 FBC(M) FLOOD HAZARD
 3- PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 4- PLEASE REFER TO SECTION 1107.2.1
 PIPING THROUGH CONCRETE OR MASONRY WALLS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-12-27 Cont ID  
Sent By pkrauss Date 2005-12-27 Time 08:47 Rev Time 0.50
Received By pkrauss Date 2005-12-27 Time 08:46 Sent To  
Notes
2005-12-27 00:00:00PROVISO:
 PLAN DOES NOT INDICATE NUMBER OF
 VEHICLES THAT CAN PARK IN THE GARAGE.
 PER 2001 FBC 411.4.2 & 411.5.4, UNDER
 NORMAL USE THE VENTILATION OF THE GARAGE
 SHALL BE CONTINIOUS WITH POSITIVE MEANS
 FOR BOTH INTAKE AND EXHAUST.
  
 PLEASE NOTE, EQUIPMENT LOCATED IN A
 FLOOD ZONE, SHALL BE PLACED ABOVE THE
 FLOOD ELEVATION OR PROTECED IN A MANNER
 TO PREVENT WATER FROM ENTERING OR
 ACCUMULATING WITHIN THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561-805-6719).

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 06:57 Rev Time 0.55
Received By pkrauss Date 2005-09-30 Time 06:57 Sent To  
Notes
2005-09-30 00:00:00PROVISO:
 PLAN DOES NOT INDICATE NUMBER OF
 VEHICLES THAT CAN PARK IN THE GARAGE.
 PER 2001 FBC 411.4.2 & 411.5.4, UNDER
 NORMAL USE THE VENTILATION OF THE GARAGE
 SHALL BE CONTINIOUS WITH POSITIVE MEANS
 FOR BOTH INTAKE & EXHAUST.
  
 PLEASE NOTE EQUIPMENT LOCATED IN A FLOOD
 ZONE, SHALL BE PLACED ABOVE THE FLOOD
 ELEVATION OR PROTECTED IN A MANNER TO
 PREVENT WATER FROM ENTERING OR
 ACCUMULATING WITHIN THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-28 Cont ID  
Sent By pkrauss Date 2005-09-27 Time 07:41 Rev Time 0.00
Received By pkrauss Date 2005-09-27 Time 07:41 Sent To  
Notes
2005-09-27 00:00:00DENIED:
 RESPONSE TO COMMENTS DATED 8-16-05
 COMMENT #1:
 RESPONSE INDICATES THE GARAGE EXHAUST
 FAN WILL ONLY RUN WHEN GARAGE DOOR IS
 ACTIVATED.PER 2001 FBC 411.4.2,
 PARKING GARAGE SHALL HAVE A MINIMUM OF 6
 AIR CHANGES PER HOUR.PLEASE CLARIFY
 HOW THIS WILL COMPLY.PLEASE INDICATE
 THE NUMBER OF CARS THAT WILL BE ABLE TO
 PARK IN THE GARAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 11:22 Rev Time 3.25
Received By pkrauss Date 2005-08-16 Time 11:22 Sent To  
Notes
2005-08-16 00:00:00DENIED:
 1.PLAN SHEET M201, PLAN INDICATES
 GARAGE EXHAUST TERMINATING OVER AN
 EGRESS DOORWAY.PER 2001 FBC(M)401.5.2,
 EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS.PER 2001 FBC(M)501.3, EXHAUST
 SHALL BE LOCATED AS NOT TO BE DRAWN BACK
 IN BUILDING.
  
 2.PLAN SHEET M202 INDICATES DUCTWORK
 PENETRATING RATED WALLS.PLEASE
 INDICATE LOCATION OF ALL FIRE DAMPERS IN
 ACCORDANCE WITH 2001 FBC(M)607.6.
  
 3.PLAN SHEET M703 NOTES 3, 5, & 6,
 INDICATE CONDENSATE TO TERMINATE INTO
 WASTE.PER CITY CODE, CONDENSATE IS TO
 TERMINATE INTO THE STORM NOT THE
 SANITARY WASTE.
  
 4.AUXILIARY DRAIN LINE ON PLAN SHEET
 M703, INDICATES TERMINATION TO WASTE.
 PER 2001 FBC(M)307.2.3, AUXILIARY DRAIN
 TO TERMINATE AT A CONSPICUOUS POINT TO
 SERVE AS AN ALARM OR INSTALL AN APPROVED
 FLOAT SWITCH.
  
 5.PLEASE INDICATE ANY APPLIANCES
 LOCATED IN THE KITCHEN AREA.
  
 PLEASE SEE ALSO COMMENTS #1 & 2 BY DEWEY
 PALMER ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-05-04 Cont ID  
Sent By pschmitz Date 2006-05-04 Time 11:59 Rev Time 0.00
Received By pschmitz Date 2006-05-04 Time 11:59 Sent To  
Notes
2006-05-04 00:00:00REVISION

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-04-05 Cont ID  
Sent By pschmitz Date 2006-04-05 Time 10:56 Rev Time 0.00
Received By pschmitz Date 2006-04-05 Time 10:56 Sent To  
Notes
2006-04-05 00:00:00SEE LETTER FROM MARY KATHRYN SMITH
 12-02-2005 RE:
 HAVING A LAV OUTSIDE THE STALL IS
 DESIRABLE, THE DEPT OF JUSTICE WOULD
 LIKE TO SEE THIS BUT IS NOT REQUIRED BY
 THE CODE.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-04-05 Cont ID  
Sent By pschmitz Date 2006-04-05 Time 10:55 Rev Time 0.00
Received By pschmitz Date 2006-02-10 Time 10:44 Sent To  
Notes
2006-02-10 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1) SHT.A2.02 MEN AND WOMENS TOILET ROOM
 #204,#206.ONE SINK IN EACH TOILET ROOM
 SHALL COMPLY.
  
 ?11-1.2 ALL NEW OR ALTERED BUILDINGS
 AND FACILITIES SUBJECT TO THIS CODE
 WHICH MAY BE FREQUENTED IN, LIVED IN, OR
 WORKED IN BY THE PUBLIC SHALL
 COMPLY WITH THIS CODE.
  
 ?11-4.1.3(11) TOILET FACILITIES: IF
 TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH ?11-4.22.
  
 ?11-4.24 SINKS.
  
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
  
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
  
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
  
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
  
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-23 Cont ID  
Sent By pschmitz Date 2006-01-23 Time 14:12 Rev Time 0.00
Received By pschmitz Date 2006-01-23 Time 14:12 Sent To B
Notes
2006-01-23 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) SHT.A2.02 MEN AND WOMENS TOILET ROOM
 #204,206.SEE FIG 30E TOILET STALL.
 THE TOILET STALL DOOR SHALL NOT SWING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR
 ANY FIXTURE.
 2)BREAK ROOMS #212, VIGNETTE KITCHEN.
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By pschmitz Date 2005-09-28 Time 14:40 Rev Time 0.00
Received By pschmitz Date 2005-09-28 Time 14:40 Sent To  
Notes
2005-09-28 00:00:009-28-05 REVISIONS RE-SUB OK.PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-10 Cont ID  
Sent By kstevens Date 2005-08-10 Time 09:38 Rev Time 6.78
Received By kstevens Date 2005-08-09 Time 14:45 Sent To  
Notes
2005-08-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A0.20 ROOM FINISH SCHEDULE.
 SUBMIT MANUF. SPECIFICATIONS FOR SEALER
 FOR MEN/WOMEN TOILET ROOM FLOORS. -
 SUBMIT MANUF. SPECIFICATIONS FOR THE
 SATIN PAINT TO SHOW THAT IT IS
 NONABSORBENT AS REQUIRED BY SECTION
 1204.2 BLDG CODE. - BASE FINISH
 INDICATES WOOD BASE. INDICATE HOW THE
 WOOD BASE WILL BE NONABSORBENT AS
 REQUIRED IN SECTION 1204.2.
 2. ALL ARCHITECTURAL SHEETS. A TITLE
 BLOCK NUST APPEAR ON ALL ARCHITECTURAL
 DRAWINGS, AND MUST, AT A MINIMUM CONTAIN
 THE FOLLOWING INFORMATION:
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(6) & FS 481.2055.
 3. ALL MECH. ELECT. & PLMG. SHEETS.
 ENGINEERS SHALL INDICATE THEIR NAME AND
 LICENSE NUMBER ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
 4. SHT A2.01 A DRINKING FOUNTAIN IS
 REQURED FOR THE STORAGE OCCUPANCY PER
 TABLE 403.1.
 5. SHT A2.02 2 DRINKING FOUNTAINS ARE
 REQUIRED IN THE OFFICE OCCUPANCY PER
 TABLE 403.1. A HIGH/LOW DRINKING
 FOUNTAIN WITH ONLY ONE WATER SUPPLY AND
 ONLY ONE DRAIN IS CONSIDERED 1 FIXTURE.
 6. SHT A2.02 ROOM 202 BREAK ROOM SINK.
 SHOW THE CLEAR FLOOR SPACE REQUIRED BY
 SECTION 11-4.24.5. SUBMIT A DETAIL FOR
 THE BREAK ROOM SINK SHOWING THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARACE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
 7. SHTS A2.02 & A4.02 WHERE 6 OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE
 STALL COMPLYING WITH 11-4.17.3, AT LEAST
 ONE STALL 36" WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL
 GRAB BARS COMPLYING WITH FIG 30(D) AND
 11-4-26 SHALL BE PROVIDED. SECTION
 11-4.22.4.
 8. SHTS A4.02 ALL TOILET ROOMS - SHOW
 THE TURNING AREA IN THE TOILET ROOM, NOT
 IN THE STALL. SECTION 11-4.22.3
 9. SHT A4.02 SHOW ACCESSIBLE WC AT 18"
 OFF THE WALL TO CENTERLINE OF THE
 FIXTURE. FIG. 28.
 10. SHT A4.02 SHOW THE CLEAR FLOOR SPACE
 FOR ALL ACCESSIBLE FIXTURES. SECTIONS
 11-4.15.3, 11-4.16.2, 11-4.18.3, AND
 11-4.19.3.
 11. SHT A4.02 SHOW THE FOLLOWING
 INFORMATION FOR THE LAVS:
 A. 11-4.29.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 12. SHT P501 SANT. RISER DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. LAVS FOR THE FIRST FLOOR ARE NOT
 SHOWN. SECTION 104.2.1.
 B. FIRST FLOOR UNINAL NOT VENTED.
 SECTION 901.2.1.
 C. CIRCUIT VENT FOR W/C'S 2ND FLOOR,
 EACH FIXTURE SHALL CONNECT HORIZONTALLY
 TO THE HORIZONTAL BRANCH BEING CIRCUIT
 VENTED OR INDIVIDUALLY VENTED. SECTION
 911.1. THE VENT FOR THE CIRCUIT VENT
 SHALL CONNECT BETWEEN THE TWO MOST
 UPSTREAM FIXTURES, AND THE VENT SHALL
 NOT RECIEVE THE DISCHARGE OF ANY SOIL OR
 WASTE. SECTION 911.2.
 D. THE FLOOR DRAINS ON THE SECOND FLOOR
 ARE NOT VENTED. SECTION 901.2.1.
 E. DRINKING FOUNTAIN IS NOT VENTED.
 SECTION 901.2.1.
 F. URINALS ARE NOT VENTED 2ND FLOOR.
 SECTION 901.2.1.
 13. SHT P501 WATER RISER DIAGRAM, SHOW
 ALL PIPE SIZES. FIRST FLOOR WATER RISER
 SHOWS DROPS TO 6 FIXTURES, BUT 8
 FIXTURES ARE SHOWN ON THE FLOOR PLAN.
 PLEASE SHOW ALL WATER PIPING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]