Plan Review Details - Permit 05070588
Plan Review Stops For Permit 05070588
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-06 Cont ID  
Sent By alange Date 2006-11-06 Time 14:10 Rev Time 0.00
Received By alange Date 2006-11-06 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-17 Cont ID  
Sent By alange Date 2006-10-17 Time 12:59 Rev Time 0.00
Received By alange Date 2006-10-17 Time 12:59 Sent To Z
Notes
2006-10-17 13:36:39REVISION DENIED
  
 1.REVISION WAS SUBMITTED WITHOUT AN ACCURATE
 DISCRIPTION OF THE REVISED CHANGES.
  
 2.REVISE PERMIT VALUE TO INCLUDE ALL CHANGES MADE.
 FBC 2004 WEST PALM BEACH AMMENDMENTS 108.3ADDITIONAL
 PERMIT FEES ARE DUE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-02-23 Cont ID  
Sent By alange Date 2006-02-23 Time 10:44 Rev Time 1.25
Received By alange Date 2006-02-23 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-30 Cont ID  
Sent By alange Date 2005-11-30 Time 16:04 Rev Time 1.50
Received By alange Date 2005-11-30 Time 14:13 Sent To  
Notes
2005-11-30 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By alange Date 2005-08-15 Time 09:27 Rev Time 3.00
Received By alange Date 2005-08-15 Time 09:02 Sent To  
Notes
2005-08-15 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SELECT THE JELD-WEN DOOR BEING USED.
 THE WHOLE JELD-WEN BOOKLET WAS
 SUBMITTED.
  
 4.SUBMIT PRODUCT APPROVALS FOR WINDOW
 MULLIONS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 REVISED TO $180,180.00.ADDITIONAL
 PERMIT FEES OF $533.13 ARE DUE.
  
 7.SUBMIT ENERGY CALCS.
  
 8.SUBMIT FIRE PLACE SPECIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 17:33 Sent To M
Notes
2006-10-01 00:00:00REV FOR THREE ITEMS ON PLANS INITIALED
 BY ENG AND PLAN REVIEWER.;

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-10 Cont ID  
Sent By dpalmer Date 2006-02-14 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2006-02-10 Time 18:31 Sent To M
Notes
2006-02-14 00:00:00OK, NEW 2ND SET BROUGHT IN. OK
2006-02-10 00:00:00*** NOTES ***
  
 PLANS REDLINED, NO RECEPT NEEDED FOR
 FIREPLACE , AS IT IS LV AND CREATES IT'S
 OWN IGNITION.
  
 ** PLEASE SEE MISSING RECEPT SPACING PER
 210.52
  
  
 ************************************
  
 PLEASE SEE 2ND SET OF PLANS IS MISSING
 SHEET #4,.
 PLEASE SEE TITLE BLOCKSWERE NOT
 CORRECTD IN THAT 2ND SET, AS THESE ARE
 OLD SHEETS. SEE REVISED SHEETS IN SET
 ONE WHICH ARE OK AND DATED A LATER DATE.
 HOLDING PLANS, SPOKE TO OWNER.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 07:54 Rev Time 0.75
Received By dpalmer Date 2005-10-20 Time 07:46 Sent To P
Notes
2005-10-20 00:00:00********* UNSAT 2ND REVIEW ***********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS
 UNDER FAC 61G15-23.002 AND FS 471.023.
 PLEASE SEE TITLE BLOCK WAS REVISED ,
 HOWEVER TITLE BLOCK AS SHOWN REQUIRES A
 CA #.
 PLEASE EITHER REVISE AND INLCUDE CA# OR
 CORRECT TITLE BLOCKS.
 THIS IS REQUIRED ON ALL PAGES AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER REVIEWER(S).
 PLEASE KNOW, ONE COPY ONCE AGAIN SHALL
 BE RETAINED AND PLACED IN FILE WITH
 OTHER PLANS FROM PREVIOUS REVIEW AND
 OTHER PROJECTS FOR THE SAME COMMENTS.
 PLEASE ADDRESS.
  
 2)NOTE: PLEASE SEE PREVIOUS NOTES WHICH
 REQUESTED THE AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT.
 PLEASE SEE THIS INCLUDES MAIN
 DISCONNECT, PANEL ETC.
 110.9, 215.5 ETC.
  
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) NOW ATTACHED TO NOTES.
 PLEASE SEE THIS IS IN RESPECT TO THE
 DESIGN PROFESSIONAL AND REPEAT COMMENTS.
 THE STATT STATUES MANDATES A 4X FEE IF
 REPEAT COMMENTS ARE NOT ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By dpalmer Date 2005-07-25 Time 11:25 Rev Time 1.00
Received By dpalmer Date 2005-07-22 Time 16:45 Sent To M
Notes
2005-07-25 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK.
 PLEASE SEE RECORDS FOR DEPARTMENT OF BUS
 AND PROFESSIONAL REGULATION AND FLORIDA
 BOARD OF PROFESSIONAL ENGINEERSDOES
 NOT SHOW ANY LICENSING FOR YURASEK AND
 HUBBARD ASSC, CONSULTING ENGINEERS AND
 PLANNERS.
 PLEASE SEE FAC 61G1-16.004 AND FS
 471.023 FOR MISSING REQUIRED LICENSE
 INFORMATION.
 PLEASE SEE ONE SET OF PLANS WILL BE
 RETAINED AND PLACED INTO FILE FOR
 POSSIBLE REVIEW BY STATE DBPR AND FBPE.
 PLEASE ALSO INCLUDE ALL OTHER
 INFORMATION ON TITLE BLOCK, ADDRESS ETC.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 TRADES AND ALL REVIEWS, WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52, MASTER BEDRM ETC.
  
 3)NOTE: PLEASE SEE MISSING GFI RECEPTS
 PER 210.52C1 FOR KITCHEN COUNTERSPACE.
  
 4)NOTE: PLEASE SEE PLANS INDICATE POWER
 FOR A WHIRLPOOL TUB, HOWEVER THIS COULD
 NOT BE LOCATED ON PANEL SCHEDULE AND DOE
 NOT SHOW LOAD.?? 215.5
 PLEASE ALSO SEE 680.71 FOR REQUIRED GFI/
 GFI PROTECTION.
  
 5)NOTE: PLEASE VERIFY HEAT LOAD SHOWN
 FOR THIS 2-STORY HOUSE OF THIS SIZE.
 PLEASE VERIFY KW RATING OF HEAT STRIP.
 PLEASE ADJUST IF NEEDED.
 PLEASE UNDERSTAND THIS IS ONLY A NOTE:
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 7)NOTE: PLEASE SEE 210.11C2, 220.16, FOR
 MIN OF 1.5KW FOR LAUNDRY/WASHER CIRCUIT.
  
 8)NOTE: PLEASE SEE RISER DIAGRAM SHOWS A
 MAIN DISCONNECT, HOWEVER PLANS DO NOT
 SHOW THIS?
 PLEASE CORRELATE.
 215.5
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-22 00:00:00IN ELEC FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 10:51 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 10:51 Sent To Z
Notes
2007-04-30 10:51:49TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-02 Cont ID  
Sent By adarroug Date 2006-11-02 Time 16:42 Rev Time 0.00
Received By adarroug Date 2006-11-02 Time 16:42 Sent To B
Notes
2006-11-02 16:42:31TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 19:02 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 19:02 Sent To Z
Notes
2006-10-25 19:03:19TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 10:54 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 10:54 Sent To E
Notes
2006-09-26 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-10 Cont ID  
Sent By adarroug Date 2006-02-10 Time 14:48 Rev Time 0.00
Received By adarroug Date 2006-02-10 Time 14:48 Sent To E
Notes
2006-02-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 17:45 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 17:45 Sent To Z
Notes
2006-02-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 09:11 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 09:11 Sent To E
Notes
2005-10-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 13:30 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 13:30 Sent To Z
Notes
2005-10-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 11:03 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 11:03 Sent To E
Notes
2005-07-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 15:12 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 15:12 Sent To Z
Notes
2005-07-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 08:36 Rev Time 0.20
Received By tgordon Date 2006-10-02 Time 08:36 Sent To P
Notes
2006-10-02 00:00:00GAS FIREPLACE ONLY, ON MECHANICAL PLANS
 SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-11-30 Cont ID  
Sent By tgordon Date 2005-11-30 Time 10:57 Rev Time 0.20
Received By tgordon Date 2005-11-30 Time 10:57 Sent To B
Notes
2005-11-30 00:00:00NO MECH. PLANS, OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By rregueir Date 2005-08-02 Time 18:37 Rev Time 0.00
Received By rregueir Date 2005-08-02 Time 18:37 Sent To B
Notes
2005-08-02 00:00:00-----------------DENIED-----------------
  
 NO PLANS, ENERGY CALCULATIONS OR MANUAL
 J PROVIDED.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 13:18 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 13:18 Sent To B
Notes
2006-10-14 13:20:03NO CHANGE TO PLUMBING. GAS UNDER SEPORATE PERMIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-21 Cont ID  
Sent By jleech Date 2006-02-21 Time 08:06 Rev Time 0.00
Received By jleech Date 2006-02-21 Time 08:06 Sent To B
Notes
2006-02-21 00:00:00PROVISO;
 GAS WATER HEATER IS IN A CONFINED SPACE
 AND MUST HAVE VENTILATION. VENTS FOR
 WATER HEATER CAN NOT BE FROM BATHROOM.
 WEATHER STRIPING REQUIRED ON DOOR TO
 HEATER ROOM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-11-29 Cont ID  
Sent By jleech Date 2005-11-29 Time 17:52 Rev Time 0.25
Received By jleech Date 2005-11-29 Time 17:52 Sent To M
Notes
2005-11-29 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTE #1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By jleech Date 2005-07-26 Time 10:39 Rev Time 0.50
Received By jleech Date 2005-07-26 Time 10:39 Sent To B
Notes
2005-07-26 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW COMENT #1.
 2.WATER HEATER ACCESS. SHOWW SIZ OF
 OPENING AND SIZE OF WATER HEATER.
 3.RISER DIAGRAM. 2 WAY C>O> REQUIRED
 WITHIN 5' OF BUILDING.
 4.CLEANOUT REQUIRED ON W/M STACK 48"
 AFF.
 5.MASTER BATHROOM WET VENT FOR TOILET TO
 BE 3" PER TABLE 908.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 8 Status P Date 2007-04-30 Cont ID  
Sent By jroach Date 2007-04-30 Time 22:15 Rev Time 0.00
Received By jroach Date 2007-04-30 Time 22:15 Sent To PC
Notes
2007-04-30 22:16:53***DRIVERWAY REVISION PASSED WITH PROVISO***
  
 PAVERS MUST BE SET IN SAND AND CANNOT BE SEALED!
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 7 Status P Date 2006-11-11 Cont ID  
Sent By mmclean Date 2006-11-11 Time 10:48 Rev Time 0.00
Received By mmclean Date 2006-11-11 Time 10:48 Sent To  
Notes
2006-11-11 10:48:37REVISION FOR REAR PORCH - 2FT FROM POOL, ATTACHED TO
 EXISTING STRUCTURE.

Review Stop Z ZONING
Rev No 6 Status F Date 2006-11-01 Cont ID  
Sent By mmclean Date 2006-11-01 Time 16:32 Rev Time 0.00
Received By mmclean Date 2006-11-01 Time 15:14 Sent To I
Notes
2006-11-01 16:06:58DENIED, 2ND REQUEST REVISION (R PORCH)
  
 1. PLEASE SUBMIT TWO COPIES OF SURVEYS SHOWING THE
 PROPOSED PORCH IN THE REAR OF PROPERTY WITH SETBACKS
 FROM SIDE & REAR PROPERTY LINE.
 2. PLEASE SHOW HOW FAR THE COVERED PORCH WILL BE FROM
 EXISTING POOL.
  
 PLEASE SHOW THE REQUEST ON THE TWO COPIES OF SURVEYS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 5 Status F Date 2006-10-23 Cont ID  
Sent By mmclean Date 2006-10-23 Time 17:25 Rev Time 0.00
Received By mmclean Date 2006-10-23 Time 17:25 Sent To  
Notes
2006-10-23 17:26:53DENIED, - REVISION (R PORCH)
 1. PLEASE SUBMIT TWO COPIES OF SURVEYS SHOWING THE
 PROPOSED PORCH IN THE REAR OF PROPERTY WITH SETBACKS
 FROM SIDE & REAR PROPERTY LINE.
 2. PLEASE SHOW HOW FAR THE COVERED PORCH WILL BE FROM
 EXISTING POOL.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 4 Status P Date 2006-02-24 Cont ID  
Sent By mmclean Date 2006-02-24 Time 14:12 Rev Time 0.00
Received By mmclean Date 2006-02-24 Time 14:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-02-09 Cont ID  
Sent By mmclean Date 2006-02-09 Time 18:14 Rev Time 0.00
Received By mmclean Date 2006-02-09 Time 18:14 Sent To I
Notes
2006-02-09 00:00:00DENIED,
 1. THE PROPOSED DRIVEWAY & WALKWAY MUST
 MEET THE REQUIRED LANDSCAPE WITHIN THE
 FIRST 25FT FRONT SETBACK.
 2. ONLY ALLOWED 312.5SQ FT OF
 CONCRETE/PAVERS/ASPHALT WITHIN THE FIRST
 25FT FRONT SETBACK.
 3. NEED TO RECONFIG. PROPOSED DRIVEWAY
 TO MEET THE REQUIREMENTS.
 4. MUST PROVIDE A CLEAR DIMENSION FOR
 THE PROPOSED DRIVEWAY (LENGTH & WIDTH).
  
 NOTE: CAN HAVE A 4X9=36SQ FT (WALKWAY)
 11X25= 275SQ FT (DRIVEWAY) TOTAL 311SQ
 FT OF CONCRETE/PAVERS/ASPHALT.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75%
 WHICHEVER IS LESS OF LANDSCAPE WITHIN
 THE FIRST 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-10-17 Cont ID  
Sent By mmclean Date 2005-10-17 Time 17:05 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 17:05 Sent To I
Notes
2005-10-17 00:00:00DENIED,
 1. MUST PROVIDE TWO SIGNED & SEAL SURVEY
 OF THE PROPOSED STRUCTURE WITH SETBACKS.
 2. INFORMATION PROVIDED IS INSUFFICIENT
 AND DOES NOT MEET THE REQUIRED
 GUIDELINES. INFORMATION WAS HAND DRAWN
 AND NOT SIGNED & SEAL BY A SURVEYER.
 3. ELEVATION NEEDS TO SHOW THE CHIMNEY
 AND THE LOCATION OF THE CHIMNEY.
 4. TOO MUCH CONCRETE WITHIN THE FRONT
 SETBACK. NEED TO REDUCE THE PROPOSED
 DRIVEWAY AND WALKWAY TO MEET THE
 REQUIRED GUIDELINES.
 5. FRONTAGE OF PROPERTY IS 1875SQ FT AND
 CAN ONLY ADD 875SQ FT OF LANDSCAPE
 WITHIN THE FIRST 25FT FRONT SETBACK.
 6. FLOOR PLANS SHOWS DRIVEWAY AS 18FT
 WIDE AND SURVEY SHOWS 16FT WIDE, PLANS &
 SURVEY MUST MATCH.
  
 ****************************************
 ****************************************
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75%
 WHICHEVER IS LESS WITHIN THE FIRST 25FT
 FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By mmclean Date 2005-07-21 Time 16:10 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 16:10 Sent To I
Notes
2005-07-21 00:00:00DENIED,
 1. NEED TO SHOW THE NEW SINGLE HOME ON
 TWO COPY OF SURVEY WITH SETBACKS
 (FRONT/SIDE/REAR).
 2. MUST PROVIDE THE DIMENSON FOR THE NEW
 DRIVEWAY/WALKWAY (LENGTH & WIDTH).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved