Plan Review Details - Permit 05070578
Plan Review Stops For Permit 05070578
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By jwitmer Date 2005-09-06 Time 08:10 Rev Time 0.33
Received By jwitmer Date 2005-09-06 Time 08:10 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 09:02 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 09:02 Sent To P
Notes
2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070578
 ADD: 5801 S OLIVE AVE
 CONT: O/B SYLVESTER, STEPHEN
 TEL: (561)346-1773
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) SURVEY IS A COPY:
 FL S S 472.025 / 61G17-6.002(8)(E)
  
 61G17-6.002(8)(E) ALL SURVEY MAPS AND
 REPORTS OR COPIES THEREOF ARE NOT VALID
 WITHOUT THE ORIGINAL SIGNATURE, AND THE
 ORIGINAL RAISED SEAL OF A FLORIDA FOR
 LICENSED SURVEYORS AND MAPPERS.
  
 61G17-6.002(8)(C) ALL SURVEY MAPS AND
 REPORTS MUST BEAR THE NAME, "CERTIFICATE
 OF AUTHORIZATION NUMBER", AND THE STREET
 MAILING ADDRESS OF THE BUSINESS ENITITY
 ISSUING THE MAP OR REPORT, ALONG WITH
 NAME AND LICENSE NUMBER OF THE SURVEYOR
 AND MAPPER IN RESPONSIBLE CHARGE.
  
 2) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 11:36 Rev Time 0.33
Received By dpalmer Date 2005-09-04 Time 11:19 Sent To B
Notes
2005-09-04 00:00:00GEN RES, OK , STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 14:16 Rev Time 0.25
Received By btrobaug Date 2005-08-01 Time 14:16 Sent To M
Notes
2005-08-01 00:00:00 
 PLEASE PROVIDE TWO COPIES OF
 MANUFACTURERS SPECIFICATIONS PER 104.2.1
 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 09:13 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 09:13 Sent To M
Notes
2005-08-03 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 16:09 Sent To E
Notes
2005-07-20 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 14:46 Rev Time 0.00
Received By rregueir Date 2005-08-03 Time 17:29 Sent To G
Notes
2005-08-03 00:00:00------------------PROVISO---------------
  
 GENERATOR EXHAUST TERMINATION SHALL
 COMPLY WITH THE REQUIREMENTS OF FBC,M
 804.3
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 07:23 Rev Time 0.25
Received By jleech Date 2005-08-04 Time 07:23 Sent To B
Notes
2005-08-04 00:00:00NAT GAS PERMIT REQUIRED BEFORE FINAL
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-20 Cont ID  
Sent By mmclean Date 2005-07-20 Time 12:40 Rev Time 0.00
Received By mmclean Date 2005-07-20 Time 12:40 Sent To I
Notes
2005-07-20 00:00:00NOTE: GENERATOR CAN ONLY ENROACH 4FT
 INTO SETBACK.