Plan Review Details - Permit 05070548
Plan Review Stops For Permit 05070548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 14:54 Rev Time 0.55
Received By alange Date 2005-08-30 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By jwitmer Date 2005-08-09 Time 17:03 Rev Time 0.55
Received By jwitmer Date 2005-08-09 Time 17:03 Sent To PC
Notes
2005-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070548
 ADD: QUIDA DR
 CONT: WELLINGTON ELEC
 TEL: (561)798-8811
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE INFORMATION FOR THE SLAB AND
 ANCHORING OF GENERATOR, SEE1606.1.3
 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING. STRUCTURAL MEMBERS AND
 SYSTEMS, AND COMPONENTS AND CLADDING IN
 A BUILDING OR STRUCTURE SHALL BE
 ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 3) SURVEY: FL S S472.025 REQUIRES
 SURVEYSTO BE ORIGINALS, SIGNED, SEALED
 AND DATED
  
 4 ) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-13 Cont ID  
Sent By btrobaug Date 2005-09-13 Time 12:42 Rev Time 0.50
Received By btrobaug Date 2005-09-13 Time 12:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-19 Cont ID  
Sent By btrobaug Date 2005-08-19 Time 07:39 Rev Time 0.50
Received By btrobaug Date 2005-08-19 Time 07:28 Sent To M
Notes
2005-08-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE RISER PROVIDED DOES
 NOT HEVE THE SERVICE FROM THE METER
 FEEDING THE ATS.
  
 2} THERE MUST BE A SERVICE RATED
 DISCONNECT PER 225.36 LOCATED PER 225.31
 SHOWN ON THE RISER, AT THE ENTRANCE TO
 THE BUILDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 12:26 Rev Time 0.33
Received By btrobaug Date 2005-08-01 Time 12:18 Sent To M
Notes
2005-08-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 FOR THE GENERATOR AND TRANSFER SWITCH.
  
 2} PLEASE SIGN AND PRINT NAME ON ALL
 PLANS DRAWN BY THE CONTRACTOR.104.2.1
 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 09:58 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 09:57 Sent To E
Notes
2005-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 15:25 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 15:25 Sent To E
Notes
2005-08-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-11 Cont ID  
Sent By adarroug Date 2005-08-11 Time 18:28 Rev Time 0.00
Received By adarroug Date 2005-08-11 Time 18:28 Sent To Z
Notes
2005-08-11 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-26 Cont ID  
Sent By rregueir Date 2005-08-01 Time 16:56 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:44 Sent To E
Notes
2005-07-26 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By btrobaug Date 2005-09-13 Time 12:43 Rev Time 0.00
Received By btrobaug Date 2005-07-14 Time 15:55 Sent To PC
Notes
2005-07-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By prafter Date 2005-08-30 Time 12:01 Rev Time 1.00
Received By prafter Date 2005-08-30 Time 12:29 Sent To B
Notes
2005-08-30 00:00:00MECH. PLAN REVIEW:
 PROVISO:
  
 GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM BUILDING OPENINGS,
 WIDOWS/DOOR/ROOF VENTS.
 PLUS TEN FEET FROM ADJACENT BUILDINGS
 OPENINGS.
  
 LP GAS REQUIRES LICENED GAS CONTRACTOR
 AND MUST SUBMIT GAS PIPING DRAWING WITH
 GAS PERMIT APP.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 16:53 Sent To P
Notes
2005-08-01 00:00:00---------------DENIED-------------------
  
 PLEASE SPECIFY FUEL TYPE WHEN SUBMITTING
 GENERATOR SPECIFICATIONS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-02 Cont ID  
Sent By jleech Date 2005-08-02 Time 15:02 Rev Time 0.25
Received By jleech Date 2005-08-02 Time 15:02 Sent To B
Notes
2005-08-02 00:00:00APPLICATION FOR FUEL GAS REQUIRED BEFORE
 COMPLETION OF GEN INSTALLATION

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-17 Cont ID  
Sent By mmclean Date 2005-08-17 Time 09:51 Rev Time 0.00
Received By mmclean Date 2005-08-17 Time 09:51 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-07-25 Time 12:15 Rev Time 0.00
Received By mmclean Date 2005-07-25 Time 12:15 Sent To P
Notes
2005-07-25 00:00:00DENIED,
 1. MUST PROVIDE THE HOA APPROVAL LETTER
 WITH SIGN OFF ON THE PLANS FOR THE
 GENERATOR.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720