Plan Review Details - Permit 05070499
Plan Review Stops For Permit 05070499
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-02 Cont ID  
Sent By jwitmer Date 2006-11-02 Time 09:53 Rev Time 1.77
Received By jwitmer Date 2006-11-02 Time 09:52 Sent To PC
Notes
2006-11-06 14:45:30STAMPED BLDG SHEETS AS OK PER JIM WITMER.
2006-11-02 09:54:43PLANS ARE CODE COMPLIANT FOR BUILDING BUT BECAUSE OF
 THE ELECTRICAL COMMENTS PLANS CAN NOT BE STAMPED AT
 THIS TIME.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-08 Cont ID  
Sent By jwitmer Date 2006-08-08 Time 16:18 Rev Time 0.77
Received By jwitmer Date 2006-08-08 Time 16:18 Sent To  
Notes
2006-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070499
 ADD: 7629 S DIXIE #_____
 CONT: ONE STOP REMODELING
 TEL: (954)297-1155
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1)61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 15:31 Rev Time 0.55
Received By jwitmer Date 2006-02-07 Time 15:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-21 Cont ID  
Sent By jwitmer Date 2005-11-21 Time 08:17 Rev Time 0.55
Received By jwitmer Date 2005-11-21 Time 08:17 Sent To  
Notes
2005-11-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070499
 ADD: 7629 S DIXIE HWY
 CONT: SUNTECH BUILDERS
 TEL: (561)245-4611
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE A GENERAL USE ROOM
 WITH AN OCCUPANT LOAD OF 73. DOOR
 LEADING FROM THE GENERAL USE ROOM TO
 VESTIBULE SWINGS IN THE WRONG DIRECTION.
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE.DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS WHEN SERVING
 AN OCCUPANT LOAD OF 50 OR MORE.
  
 2) MISSING A DRINKING FOUNTAIN OR WATER
 COOLER SEE 11-4.15.
  
 3) RESTROOMS ARE TO BE HANDICAPPED
 ACCESSIBLE, PROVIDE A 1/4" OR 1/2"
 DETAIL OF RESTROOMS WITH DIMENSIONS
 SHOWING THE LOCATION OF FIXTURES AND
 HANDRAILS.FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 4) KITCHEN:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By jwitmer Date 2005-07-28 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2006-08-08 Time 16:17 Sent To  
Notes
2005-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070499
 ADD: 7629 S DIXIE HWY
 CONT: SUNTECH BUILDERS
 TEL: (561)245-4611
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) INDICATE THE OCCUPANCY AND OR USAGE
 FOR THIS TENANT SPACE.301.2 OCCUPANCY OR
 USE CATEGORIES. EVERY NEW AND EXISTING
 BUILDING,
 STRUCTURE OR PART THEREOF SHALL, FOR THE
 PURPOSE OF THIS CODE, BE CLASSIFIED
 ACCORDING TO ITS USE OR OCCUPANCY AS A
 BUILDING OR STRUCTURE OR TENANT SPACE.
  
 2) WITH THE USAGE BEING A ASSEMBLY FOR
 GATHERINGS (CHURCHES) AND NOT HAVING
 FIXED SEATING A NET 7 SQ FT / PERSON.
 OCCUPANCY LOAD OF 304.
  
 3)3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY
 SUBCLASSIFICATION OF ANY EXISTING
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL
 AND PLUMBING SYSTEMS SHALL BE MADE
 TO CONFORM TO THE INTENT OF THE
 TECHNICAL CODES AS REQUIRED BY THE
 BUILDING OFFICIAL.
  
 4) CHANGE OF OCCUPANCY WILL REQUIRE
 REVIEW FROM COUNTY FOR IMPACT FEES.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) PLANS TO SHOW WHICH DOORS ARE TO BE
 EXITS, SIZE OF DOORS AND COMPLIANCE WITH
 TABLE 1004.PROVIDE A LIFE SAFETY PLAN
 INDICATING EXITING.
  
 6 PLANS TO PROVIDE THE ILLUMINATED
 MEANS OF EGRESS, INDICATE EXIT LIGHTS
 AND EMERGENCY LIGHTING.1016.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED INACCORDANCE WITH THIS
 SECTION FOR EVERY BUILDING AND TRUCTURE.
 FOR THEPURPOSES OF THIS REQUIREMENT,
 EXIT ACCESS SHALL INCLUDE ONLY
 DESIGNATEDSTAIRS, AISLES, CORRIDORS,
 RAMPS, ESCALATORS AND PASSAGEWAYS
 LEADING TO AN EXIT.FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS
 AND EXIT PASSAGEWAYS LEADING TO A PUBLIC
 WAY.
  
 7)704.2.1.4CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY: A2, PROVIDE
 COMPLIANCE.
  
 DEPENDING ON THE RESPONCE TO THE
 COMMENTS ABOVE ADDITITIONAL COMMENTS
 MAY APPEAR ON THE NEXT REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-11-06 Cont ID  
Sent By dpalmer Date 2006-11-06 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2006-11-06 Time 14:45 Sent To PC
Notes
2006-11-06 14:46:54REDLINED PLANS EM/ EXT LTS TO BE WIRED PER 700.12E.
  
  
 TWO METERS ON SINGLE OCCUPANCY ORIGINALLY STAMPED,
 PASSED AND OK'D PER JAKE LEAHY.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 20:48 Rev Time 0.00
Received By dpalmer Date 2006-10-19 Time 20:13 Sent To  
Notes
2006-10-19 20:48:46*** UNSAT ****
  
 ** PLANS ORIGINALLY REVIEWED BY JAKE LEAHY.
  
  
 1) NOTE: PLEASE SEE ORIGINAL PLANS WERE REDLINED WIHT
 CIRCUITING FOR EM AND EXT LTS PER 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE AS THIS WAS A CHANGE IN OCCUPANCY
 AND IS NOW ONE OCCUPACNY, ONE SERVICE/ METER AND RISER
 SHOULD BE SHOWN.
 PLEASE SUBMIT A COMPLETED RISER DIAGRAM AS PLANS DIFFER
 FROM RISER SHOWN. PLEASE SEE RISER IS NOT COMPLETE.
 210.70,210.72,240 ETC.
 PLEASE ALSO SEE PLANS DO NOT INDICATE THE LOCATION OF
 THE PANELS.
 240.4,240.24, 110.26
  
 3) NOTE: PLEASE INDICATE ALL REVSIONS, BY CLOUDS AND
 TRIANGLES ON PLANS.
 FBC ADMIN SECT 104.1
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 12:42 Sent To  
Notes
2006-08-05 00:00:00** SEE NO ELECTRICAL REVISION WAS
 SUBMITTED, HOWEVER PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED PER FAC 61G15-23.002, FS
 471.023

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-05 Cont ID  
Sent By jleahy Date 2006-02-04 Time 13:27 Rev Time 0.30
Received By dpalmer Date 2006-02-04 Time 13:27 Sent To  
Notes
2006-10-19 20:38:44PASSED BY JAKE LEAHY
  
 REDLINED 700.12E

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By jleahy Date 2005-11-29 Time 09:11 Rev Time 0.45
Received By jleahy Date 2005-11-29 Time 09:11 Sent To  
Notes
2005-11-29 00:00:00NO ELECTRIC SHOWN FOR SERVICE, PANELS,
 OUTLETS.
  
 PLEASE SUBMIT A RISER DIAGRAM AND HOW
 YOUR SERVICE IS SPLIT UP BETWEEN THE TWO
 BAYS.
  
 THANKS
  
 JAKE 644-7291

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-10-30 Cont ID  
Sent By mawillia Date 2006-10-30 Time 10:00 Rev Time 0.00
Received By mawillia Date 2006-10-30 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2006-08-16 Cont ID  
Sent By mwennerg Date 2006-08-16 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2006-08-16 Time 13:32 Sent To  
Notes
2006-08-16 00:00:00***DENIED***
  
 PLEASE NOTE THAT REVISIONS DON'T IMPACT
 PREVIOUS FIRE REVIEW, HOWEVER COMPLIANCE
 FOR FAC REQUIREMENTS SHALL BE MET. SEE
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (805-6722)

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-02-07 Cont ID  
Sent By mwennerg Date 2006-02-07 Time 14:18 Rev Time 0.00
Received By mwennerg Date 2006-02-07 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-29 Cont ID  
Sent By mwennerg Date 2005-11-29 Time 13:10 Rev Time 0.00
Received By mwennerg Date 2005-11-29 Time 13:10 Sent To  
Notes
2005-11-29 00:00:00******DENIED******
  
 1) PLEASE SEE BUILDING COMMENT REF: EXIT
 DOOR SWINGS IN GENERAL USE AREA. IN
 ADDITION TO FBC, NFPA 101, SECTION
 7.2.1.4.2 WILL NOT ALLOW FOR THIS
 ARRANGEMENT, UNLESS TWO CONDITIONS ARE
 MET.
  
 2) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN
 TERMS OF A,B OR C.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By mwennerg Date 2005-07-28 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2005-07-28 Time 13:44 Sent To  
Notes
2005-07-28 00:00:00******DENIED******
  
 1) PLEASE SEE BUILDING REVIEW COMMENTS
 REGARDING OCCUPANCY CLASSIFICATION.
 PLEASE NOTE THAT MORE INFORMATION IS
 REQUIRED.
  
 2) PLEASE ILLUSTRATE THE LOCATIONS OF
 ALL ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING FACILITIES.
  
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 4) PLEASE INDICATE DOOR SWINGS.
  
 5) 2A-10B,C RATED FIRE EXTINGUUISHER (S)
 ARE REQUIRED TO BE MOUNTED TO SATISFY
 THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 6) IS THIS TENANT SPACE PART OF A
 BUILDING PROTECTED BY FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS? IF SO, SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL.
  
 7) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 19:05 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 19:05 Sent To  
Notes
2006-10-19 10:38:14TO "BOB"#11
2006-10-10 19:06:12WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 13:53 Sent To  
Notes
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 16:29 Sent To  
Notes
2006-02-01 00:00:00TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 11:02 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 11:02 Sent To  
Notes
2005-11-18 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 08:11 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 08:11 Sent To  
Notes
2005-07-25 00:00:00TO "BOB" #7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 18:36 Rev Time 0.00
Received By shill Date 2005-07-23 Time 18:36 Sent To I
Notes
2005-07-23 00:00:00SENT TO INCOMING TO BE PUT ON BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By   Date 2005-07-28 Time   Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 13:55 Sent To  
Notes
2005-07-14 00:00:00TO "MISC" BOX #1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-10-19 Time 16:11 Rev Time 0.20
Received By tgordon Date 2006-10-19 Time 16:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-08-09 Time 11:16 Rev Time 0.45
Received By tgordon Date 2006-08-09 Time 11:16 Sent To  
Notes
2006-08-09 00:00:00* MECH. PLANS WITH MECH. PERMIT *
 #06082189
 1) A MECHANICAL PERMIT WAS NEEDED FOR
 THE A/C DUCT WORK DONE (NEW RETURN AIR
 TRANSFER DUCTS, JUMPERS).
 2) PLEASE APPLY FOR MECHANICAL PERMIT,
 SUBMIT MECHANICAL PLANS SHOWING EXISTING
 A/C SYSTEMS LOCATION AND SIZE (TONS),
 EXISTING RETURN AND SUPPLY AIR DUCT
 SYSTEMS, CFM'S AT EACH EXISTING SUPPLY
 AIR GRILL, AND NEW RETURN AIR TRANSFER
 DUCTS, JUMPERS.
  
 3) SEE ELECTRICAL REVIEW NOTE, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-10-24 Cont ID  
Sent By pschmitz Date 2006-10-24 Time 13:59 Rev Time 0.00
Received By pschmitz Date 2006-10-24 Time 13:59 Sent To  
Notes
2006-10-24 14:00:02REVISION: ADD ADA DRINKING FOUNTAIN.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-12 Time 06:32 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 06:32 Sent To  
Notes
2006-08-12 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODE PLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 PROVISO
  
 PLUMBING REVISION APPROVED.
  
 SEE COMMENTS FROM OTHER PLAN REVIEWERS.
  
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-03 Cont ID  
Sent By pschmitz Date 2005-12-03 Time 15:16 Rev Time 0.00
Received By pschmitz Date 2005-12-03 Time 15:15 Sent To  
Notes
2005-12-03 00:00:00RESUB, REVISED SHT A-1
 PROVISO:SEC 11-4.15
 PROVIDE A WATER COOLER

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-03 Cont ID  
Sent By pschmitz Date 2005-12-03 Time 15:15 Rev Time 0.00
Received By pschmitz Date 2005-11-18 Time 14:08 Sent To  
Notes
2005-11-18 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1( CHANGE OF OCCUPANCY FROM BUSINESS TO
 ASSEMBLY.
 SECTION P403 MINIMUM PLUMBING FACILITIES
  
 ?P403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED
 FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE P403.1.
 TYPES OF OCCUPANCIES NOT SHOWN IN TABLE
 P403.1 SHALL BE CONSIDERED
 INDIVIDUALLY BY THE CODE OFFICIAL.THE
 NUMBER OF OCCUPANTS SHALL BE
 DETERMINED BY THE BUILDING CODE.
 OCCUPANCY CLASSIFICATION SHALL BE
 DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 PROVIDE SHOW DETAIL
 2)1-4.22 TOILET ROOMS.SHOW DETAIL
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH
 ?11-4.13.DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH 11-
 4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR
 SPACE AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING
 SPACE MAY OVERLAP.
 ?11-4.22.4 WATER CLOSETS. IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH ?11-4.17; WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION
 TO THE STALL COMPLYING WITH
 ?11-4.17.3, AT LEAST ONE STALL 36 IN
 (915 MM) WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND
 PARALLEL GRAB BARS COMPLYING WITH
 FIGURE 11-30(D) AND ?11-4.26 SHALL BE
 PROVIDED.WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH
 ?11-4.16.IF WATER CLOSETS ARE NOT IN
 STALLS, THEN AT LEAST ONE SHALL COMPLY
 WITH ?11-4.16.
 ?11-4.22.5 URINALS. IF URINALS ARE
 PROVIDED, THEN AT LEAST ONE SHALL
 COMPLY WITH ?11-4.18.
 ?11-4.22.6 LAVATORIES AND MIRRORS. IF
 LAVATORIES AND MIRRORS ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL COMPLY WITH ?11-4.19.
 ?11-4.22.7 CONTROLS AND DISPENSERS. IF
 CONTROLS, DISPENSERS,
 RECEPTACLES, OR OTHER EQUIPMENT ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL COMPLY WITH ?11-4.27.
 END OF COMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 08:33 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 08:33 Sent To M
Notes
2005-07-30 00:00:00PLUMBING PLAN REVIEW FBC 2001 DENIED
 (1) SEE BUILDING PLAN REVIEW NOTES,
 RE: OCCUPANCY TO DETERMINE MINIMUM
 FACILITIES. TAB 403.1
 QUESTIONS CONTACT PAUL SCHMITZ
 561-805-6692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved