| Plan Review Stops For Permit 05070499 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-11-02 |
Time |
09:53 |
Rev Time |
1.77 |
| Received By |
jwitmer |
Date |
2006-11-02 |
Time |
09:52 |
Sent To |
PC |
|
| Notes |
| 2006-11-06 14:45:30 | STAMPED BLDG SHEETS AS OK PER JIM WITMER. | | 2006-11-02 09:54:43 | PLANS ARE CODE COMPLIANT FOR BUILDING BUT BECAUSE OF | | | THE ELECTRICAL COMMENTS PLANS CAN NOT BE STAMPED AT | | | THIS TIME. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-08 |
Time |
16:18 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-08-08 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070499 | | | ADD: 7629 S DIXIE #_____ | | | CONT: ONE STOP REMODELING | | | TEL: (954)297-1155 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW | | | ACTION: DENIED | | | | | | 1)61G15-23.002 P. E.- CERTIFICATE OF | | | AUTHORIZATION.IF PRACTICING THROUGH A | | | DULY AUTHORIZED ENGINEERING BUSINESS, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME AND LICENSE NUMBER, AS WELL AS, | | | THE NAME, ADDRESS, AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-07 |
Time |
15:31 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2006-02-07 |
Time |
15:22 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-11-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-11-21 |
Time |
08:17 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-11-21 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2005-11-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070499 | | | ADD: 7629 S DIXIE HWY | | | CONT: SUNTECH BUILDERS | | | TEL: (561)245-4611 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS INDICATE A GENERAL USE ROOM | | | WITH AN OCCUPANT LOAD OF 73. DOOR | | | LEADING FROM THE GENERAL USE ROOM TO | | | VESTIBULE SWINGS IN THE WRONG DIRECTION. | | | 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE.DOORS SHALL SWING | | | IN THE DIRECTION OF EGRESS WHEN SERVING | | | AN OCCUPANT LOAD OF 50 OR MORE. | | | | | | 2) MISSING A DRINKING FOUNTAIN OR WATER | | | COOLER SEE 11-4.15. | | | | | | 3) RESTROOMS ARE TO BE HANDICAPPED | | | ACCESSIBLE, PROVIDE A 1/4" OR 1/2" | | | DETAIL OF RESTROOMS WITH DIMENSIONS | | | SHOWING THE LOCATION OF FIXTURES AND | | | HANDRAILS.FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | 4) KITCHEN: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARENCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-28 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-08-08 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070499 | | | ADD: 7629 S DIXIE HWY | | | CONT: SUNTECH BUILDERS | | | TEL: (561)245-4611 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) INDICATE THE OCCUPANCY AND OR USAGE | | | FOR THIS TENANT SPACE.301.2 OCCUPANCY OR | | | USE CATEGORIES. EVERY NEW AND EXISTING | | | BUILDING, | | | STRUCTURE OR PART THEREOF SHALL, FOR THE | | | PURPOSE OF THIS CODE, BE CLASSIFIED | | | ACCORDING TO ITS USE OR OCCUPANCY AS A | | | BUILDING OR STRUCTURE OR TENANT SPACE. | | | | | | 2) WITH THE USAGE BEING A ASSEMBLY FOR | | | GATHERINGS (CHURCHES) AND NOT HAVING | | | FIXED SEATING A NET 7 SQ FT / PERSON. | | | OCCUPANCY LOAD OF 304. | | | | | | 3)3401.2.2.1 IF THE OCCUPANCY | | | CLASSIFICATION OR OCCUPANCY | | | SUBCLASSIFICATION OF ANY EXISTING | | | BUILDING OR STRUCTURE IS CHANGED, THE | | | BUILDING, ELECTRICAL, GAS, MECHANICAL | | | AND PLUMBING SYSTEMS SHALL BE MADE | | | TO CONFORM TO THE INTENT OF THE | | | TECHNICAL CODES AS REQUIRED BY THE | | | BUILDING OFFICIAL. | | | | | | 4) CHANGE OF OCCUPANCY WILL REQUIRE | | | REVIEW FROM COUNTY FOR IMPACT FEES. | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 5) PLANS TO SHOW WHICH DOORS ARE TO BE | | | EXITS, SIZE OF DOORS AND COMPLIANCE WITH | | | TABLE 1004.PROVIDE A LIFE SAFETY PLAN | | | INDICATING EXITING. | | | | | | 6 PLANS TO PROVIDE THE ILLUMINATED | | | MEANS OF EGRESS, INDICATE EXIT LIGHTS | | | AND EMERGENCY LIGHTING.1016.1.1 | | | ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | PROVIDED INACCORDANCE WITH THIS | | | SECTION FOR EVERY BUILDING AND TRUCTURE. | | | FOR THEPURPOSES OF THIS REQUIREMENT, | | | EXIT ACCESS SHALL INCLUDE ONLY | | | DESIGNATEDSTAIRS, AISLES, CORRIDORS, | | | RAMPS, ESCALATORS AND PASSAGEWAYS | | | LEADING TO AN EXIT.FOR THE PURPOSES OF | | | THIS REQUIREMENT, EXIT DISCHARGE SHALL | | | INCLUDE ONLY DESIGNATED STAIRS,AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS | | | AND EXIT PASSAGEWAYS LEADING TO A PUBLIC | | | WAY. | | | | | | 7)704.2.1.4CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 8) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY: A2, PROVIDE | | | COMPLIANCE. | | | | | | DEPENDING ON THE RESPONCE TO THE | | | COMMENTS ABOVE ADDITITIONAL COMMENTS | | | MAY APPEAR ON THE NEXT REVIEW. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-06 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-06 |
Time |
14:45 |
Sent To |
PC |
|
| Notes |
| 2006-11-06 14:46:54 | REDLINED PLANS EM/ EXT LTS TO BE WIRED PER 700.12E. | | | | | | | | | TWO METERS ON SINGLE OCCUPANCY ORIGINALLY STAMPED, | | | PASSED AND OK'D PER JAKE LEAHY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-19 |
Time |
20:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-19 |
Time |
20:13 |
Sent To |
|
|
| Notes |
| 2006-10-19 20:48:46 | *** UNSAT **** | | | | | | ** PLANS ORIGINALLY REVIEWED BY JAKE LEAHY. | | | | | | | | | 1) NOTE: PLEASE SEE ORIGINAL PLANS WERE REDLINED WIHT | | | CIRCUITING FOR EM AND EXT LTS PER 700.12E WHICH | | | REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT | | | SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE | | | NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY | | | LOCAL SWITCHES. | | | PLEASE ADJUST. | | | | | | 2) NOTE: PLEASE SEE AS THIS WAS A CHANGE IN OCCUPANCY | | | AND IS NOW ONE OCCUPACNY, ONE SERVICE/ METER AND RISER | | | SHOULD BE SHOWN. | | | PLEASE SUBMIT A COMPLETED RISER DIAGRAM AS PLANS DIFFER | | | FROM RISER SHOWN. PLEASE SEE RISER IS NOT COMPLETE. | | | 210.70,210.72,240 ETC. | | | PLEASE ALSO SEE PLANS DO NOT INDICATE THE LOCATION OF | | | THE PANELS. | | | 240.4,240.24, 110.26 | | | | | | 3) NOTE: PLEASE INDICATE ALL REVSIONS, BY CLOUDS AND | | | TRIANGLES ON PLANS. | | | FBC ADMIN SECT 104.1 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-05 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-05 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2006-08-05 00:00:00 | ** SEE NO ELECTRICAL REVISION WAS | | | SUBMITTED, HOWEVER PLEASE SEE MISSING | | | CERTIFICATE OF AUTHORIZATION NUMBER | | | REQUIRED PER FAC 61G15-23.002, FS | | | 471.023 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-02-04 |
Time |
13:27 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2006-02-04 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2006-10-19 20:38:44 | PASSED BY JAKE LEAHY | | | | | | REDLINED 700.12E |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-11-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-11-29 |
Time |
09:11 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2005-11-29 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2005-11-29 00:00:00 | NO ELECTRIC SHOWN FOR SERVICE, PANELS, | | | OUTLETS. | | | | | | PLEASE SUBMIT A RISER DIAGRAM AND HOW | | | YOUR SERVICE IS SPLIT UP BETWEEN THE TWO | | | BAYS. | | | | | | THANKS | | | | | | JAKE 644-7291 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-30 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-30 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2006-08-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-16 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-16 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2006-08-16 00:00:00 | ***DENIED*** | | | | | | PLEASE NOTE THAT REVISIONS DON'T IMPACT | | | PREVIOUS FIRE REVIEW, HOWEVER COMPLIANCE | | | FOR FAC REQUIREMENTS SHALL BE MET. SEE | | | OTHER REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (805-6722) |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-02-07 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-02-07 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-11-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-11-29 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-11-29 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2005-11-29 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE BUILDING COMMENT REF: EXIT | | | DOOR SWINGS IN GENERAL USE AREA. IN | | | ADDITION TO FBC, NFPA 101, SECTION | | | 7.2.1.4.2 WILL NOT ALLOW FOR THIS | | | ARRANGEMENT, UNLESS TWO CONDITIONS ARE | | | MET. | | | | | | 2) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING IN | | | TERMS OF A,B OR C. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-28 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-28 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE BUILDING REVIEW COMMENTS | | | REGARDING OCCUPANCY CLASSIFICATION. | | | PLEASE NOTE THAT MORE INFORMATION IS | | | REQUIRED. | | | | | | 2) PLEASE ILLUSTRATE THE LOCATIONS OF | | | ALL ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING FACILITIES. | | | | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 4) PLEASE INDICATE DOOR SWINGS. | | | | | | 5) 2A-10B,C RATED FIRE EXTINGUUISHER (S) | | | ARE REQUIRED TO BE MOUNTED TO SATISFY | | | THE 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | 6) IS THIS TENANT SPACE PART OF A | | | BUILDING PROTECTED BY FIRE SPRINKLER AND | | | FIRE ALARM SYSTEMS? IF SO, SEPARATE SHOP | | | DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 7) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-10 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-10 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2006-10-19 10:38:14 | TO "BOB"#11 | | 2006-10-10 19:06:12 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-22 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-22 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2006-07-22 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-01 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2006-02-01 00:00:00 | TO "BOB"#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-18 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-18 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2005-11-18 00:00:00 | TO "BOB"#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-25 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-25 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | TO "BOB" #7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-23 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-07-23 |
Time |
18:36 |
Sent To |
I |
|
| Notes |
| 2005-07-23 00:00:00 | SENT TO INCOMING TO BE PUT ON BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-07-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-14 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2005-07-14 00:00:00 | TO "MISC" BOX #1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-19 |
Time |
16:11 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-10-19 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-09 |
Time |
11:16 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-08-09 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2006-08-09 00:00:00 | * MECH. PLANS WITH MECH. PERMIT * | | | #06082189 | | | 1) A MECHANICAL PERMIT WAS NEEDED FOR | | | THE A/C DUCT WORK DONE (NEW RETURN AIR | | | TRANSFER DUCTS, JUMPERS). | | | 2) PLEASE APPLY FOR MECHANICAL PERMIT, | | | SUBMIT MECHANICAL PLANS SHOWING EXISTING | | | A/C SYSTEMS LOCATION AND SIZE (TONS), | | | EXISTING RETURN AND SUPPLY AIR DUCT | | | SYSTEMS, CFM'S AT EACH EXISTING SUPPLY | | | AIR GRILL, AND NEW RETURN AIR TRANSFER | | | DUCTS, JUMPERS. | | | | | | 3) SEE ELECTRICAL REVIEW NOTE, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-10-24 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-10-24 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2006-10-24 14:00:02 | REVISION: ADD ADA DRINKING FOUNTAIN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-08-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-08-12 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-08-12 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2006-08-12 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODE PLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | | | | PROVISO | | | | | | PLUMBING REVISION APPROVED. | | | | | | SEE COMMENTS FROM OTHER PLAN REVIEWERS. | | | | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED PER FAC | | | 61G15-23.002, FS 471.023 | | | | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-12-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-12-03 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-12-03 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2005-12-03 00:00:00 | RESUB, REVISED SHT A-1 | | | PROVISO:SEC 11-4.15 | | | PROVIDE A WATER COOLER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-12-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-12-03 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-11-18 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2005-11-18 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | DENIED | | | 1( CHANGE OF OCCUPANCY FROM BUSINESS TO | | | ASSEMBLY. | | | SECTION P403 MINIMUM PLUMBING FACILITIES | | | | | | ?P403.1 MINIMUM NUMBER OF FIXTURES. | | | PLUMBING FIXTURES SHALL BE PROVIDED | | | FOR THE TYPE OF OCCUPANCY AND IN THE | | | MINIMUM NUMBER SHOWN IN TABLE P403.1. | | | TYPES OF OCCUPANCIES NOT SHOWN IN TABLE | | | P403.1 SHALL BE CONSIDERED | | | INDIVIDUALLY BY THE CODE OFFICIAL.THE | | | NUMBER OF OCCUPANTS SHALL BE | | | DETERMINED BY THE BUILDING CODE. | | | OCCUPANCY CLASSIFICATION SHALL BE | | | DETERMINED IN ACCORDANCE WITH THE | | | FLORIDA BUILDING CODE, BUILDING. | | | PROVIDE SHOW DETAIL | | | 2)1-4.22 TOILET ROOMS.SHOW DETAIL | | | ?11-4.22.1 MINIMUM NUMBER. TOILET | | | FACILITIES REQUIRED TO BE ACCESSIBLE | | | BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. | | | ACCESSIBLE TOILET ROOMS SHALL BE | | | ON AN ACCESSIBLE ROUTE. | | | ?11-4.22.2 DOORS. | | | ?11-4.22.2(1) ALL DOORS TO ACCESSIBLE | | | TOILET ROOMS SHALL COMPLY WITH | | | ?11-4.13.DOORS SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE. | | | ?11-4.22.3 CLEAR FLOOR SPACE. THE | | | ACCESSIBLE FIXTURES AND CONTROLS | | | REQUIRED IN ?11-4.22.4, ?11-4.22.5, | | | ?11-4.22.6, AND ?11-4.22.7 SHALL BE | | | ON AN ACCESSIBLE ROUTE.AN | | | UNOBSTRUCTED TURNING SPACE COMPLYING | | | WITH 11- | | | 4.2.3 SHALL BE PROVIDED WITHIN AN | | | ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR | | | SPACE AT FIXTURES AND CONTROLS, THE | | | ACCESSIBLE ROUTE, AND THE TURNING | | | SPACE MAY OVERLAP. | | | ?11-4.22.4 WATER CLOSETS. IF TOILET | | | STALLS ARE PROVIDED, THEN AT LEAST | | | ONE SHALL BE A STANDARD TOILET STALL | | | COMPLYING WITH ?11-4.17; WHERE 6 OR | | | MORE STALLS ARE PROVIDED, IN ADDITION | | | TO THE STALL COMPLYING WITH | | | ?11-4.17.3, AT LEAST ONE STALL 36 IN | | | (915 MM) WIDE WITH AN OUTWARD | | | SWINGING, SELF-CLOSING DOOR AND | | | PARALLEL GRAB BARS COMPLYING WITH | | | FIGURE 11-30(D) AND ?11-4.26 SHALL BE | | | PROVIDED.WATER CLOSETS IN | | | SUCH STALLS SHALL COMPLY WITH | | | ?11-4.16.IF WATER CLOSETS ARE NOT IN | | | STALLS, THEN AT LEAST ONE SHALL COMPLY | | | WITH ?11-4.16. | | | ?11-4.22.5 URINALS. IF URINALS ARE | | | PROVIDED, THEN AT LEAST ONE SHALL | | | COMPLY WITH ?11-4.18. | | | ?11-4.22.6 LAVATORIES AND MIRRORS. IF | | | LAVATORIES AND MIRRORS ARE | | | PROVIDED, THEN AT LEAST ONE OF EACH | | | SHALL COMPLY WITH ?11-4.19. | | | ?11-4.22.7 CONTROLS AND DISPENSERS. IF | | | CONTROLS, DISPENSERS, | | | RECEPTACLES, OR OTHER EQUIPMENT ARE | | | PROVIDED, THEN AT LEAST ONE OF EACH | | | SHALL BE ON AN ACCESSIBLE ROUTE AND | | | SHALL COMPLY WITH ?11-4.27. | | | END OF COMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-30 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-07-30 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-07-30 |
Time |
08:33 |
Sent To |
M |
|
| Notes |
| 2005-07-30 00:00:00 | PLUMBING PLAN REVIEW FBC 2001 DENIED | | | (1) SEE BUILDING PLAN REVIEW NOTES, | | | RE: OCCUPANCY TO DETERMINE MINIMUM | | | FACILITIES. TAB 403.1 | | | QUESTIONS CONTACT PAUL SCHMITZ | | | 561-805-6692 |
|
|