Plan Review Details - Permit 05070480
Plan Review Stops For Permit 05070480
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2005-10-07 Cont ID  
Sent By jhiggins Date 2005-10-07 Time 08:47 Rev Time 0.00
Received By jhiggins Date 2005-10-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-10-05 Cont ID  
Sent By shill Date 2005-10-05 Time 17:55 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2005-10-05 00:00:00YELLOW PAGES SHOWS ADDRESS AS 107 OLIVE
 - I ASSIGNED THIS AS THE BUILDING
 EXTENSION RATHER THAN SENDING TO
 ADDRESSING AS THIS WAS ALREADY IN THE
 SYSTEMSMH

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-05 Cont ID  
Sent By shill Date 2005-10-05 Time 17:56 Rev Time 0.50
Received By shill Date 2005-10-05 Time 17:56 Sent To  
Notes
2005-10-05 00:00:00***PROVISO***SEPARATE PERMIT STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 14:18 Rev Time 0.50
Received By shill Date 2005-09-07 Time 14:18 Sent To  
Notes
2005-09-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2.)THIS PERMIT WILL BE ISSUED WITH A
 PROVISO THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE STOREFRONT.NO PRODUCT
 APPROVALS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By shill Date 2005-08-13 Time 20:08 Rev Time 1.50
Received By shill Date 2005-08-13 Time 19:18 Sent To  
Notes
2005-08-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY (CHANGE OF USE).THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION. 233-5025
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; BUILDING TYPE FBC
 CHAPTER 6, HEIGHT.
  
 4.)DECLARE AN OCCUPANCY ON THE PLAN,
 FBC304.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC TABLE
 1003.1.
  
 6.)TWO HOUR OCCUPANCY SEPARATION
 REQUIRED FBC TABLE 704.1 FOR A2.
 PROVIDE AN APPROVED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FOR WALL AND
 CEILING OCCUPANCY SEPARATIONS.
  
 7.)M1 SHOWS WALL PENETRATIONS AND
 REFRIGERANT LINES IN THE STAIRWAY
 ENCLOSURE; NOT ALLOWED AS PER
 FBC1006.1.3.1.
  
 8.)TWO EXITS REQUIRED; OCCUPANCY
 APPEARS TO BE GREATER THAN 50,
 FBC1004.2.
  
 9.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT.FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 EVALUATION OR TEST REPORT, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 10.)PROVIDE DESIGN PRESSURES FOR THE
 STOREFRONT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 06:52 Rev Time 0.45
Received By dpalmer Date 2005-08-31 Time 06:52 Sent To  
Notes
2005-08-31 00:00:00SUITE EXTENSION STILL NEEDED IN SYSTEM.
  
 PLANS REDLINED FOR 700.12E, EXT LT AND
 EM LT NOT CIRCUITED.
  
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By dpalmer Date 2005-07-25 Time 15:41 Rev Time 0.75
Received By dpalmer Date 2005-07-25 Time 15:40 Sent To  
Notes
2005-07-25 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE RESPECTIVE PANEL
 SCHEDULES SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS DO
 NOT CORRELATE WITH LOADS FINALED ON
 PANEL "B". PLEASE SEE A/C SHALL NOT BE
 FIGURE IN WITH LIGHTING/RECEPT LOADS.
 220.31B.
 PLEASE ALSO SEE POSSIBLE ADJUSTMENT OF
 FEED TO PANEL "B".
 SHOWN AS 60A, HOWEVER WITH LOADS SHOWN,
 THIS 60A'S MAY BE EXCEEDED.
  
 3)NOTE: PLEASE SEE EXISTING "OBEE'S"
 ELECTRICLA IS SHOWN , HOWEVER NO "SHOW
 WINDOW" RECEPT IS SHOWN FOR EXIST? THIS
 WAS REDLINED ON PREVIOUS PERMIT FOR THIS
 REST BUILD OUT AND SHOULD HAVE BEEN
 INSTALLED.
 PLEASE CLARIFY IF EXSITNG OR NEW TO BE
 INSTALLED.
 210.62,220.12.
  
 4)NOT: PLEASE CLARIFY 3-3/0'S SHOWN FOR
 60A FEED TO PANEL"B". PLEASE VERIFY.
  
 5)NOTE: PLEASE VERIFY WATER HEATER OCP,
 BRANCH CIRCUIT SIZE. SHOWN AS 2P-20A'S
 ON 4500VA LOAD. PLEASE SEE
 422.13,422.11, MIN 125%, MAX 150%.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS REQUIRED TO
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By mwennerg Date 2005-09-08 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-09-08 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By mwennerg Date 2005-08-12 Time 15:56 Rev Time 0.00
Received By mwennerg Date 2005-08-12 Time 15:56 Sent To  
Notes
2005-08-12 00:00:00******DENIED******
  
 1) STAIRWELL SHOWS NEW REFRIGERATOR
 LINES TO ROOFTOP UNIT. PLEASE NOTE THAT
 PENETRATIONS INTO EXIT ENCLOSURES ARE
 PROHIBITED UNLESS IT MEETS THE
 REQUIREMENT OF NFPA 101, SECTION
 7.1.3.2.1 (6).
  
 2) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING.
  
 3) NO COOKING OF FOODS THAT PRODUCE
 GREASE LADEN VAPORS WITHOUT PROTECTION
 OF HOOD/SUPPRESSION SYSTEM.
  
 4) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHERS THAT SHALL MEET
 THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
 6) PLANS DESCRIBE OCCUPANT
 CLASSIFICATION AS RESTAURANT. PLEASE
 PROVIDE CALCULATED OCCUPANT LOAD AND
 FURNITURE LAY OUT FOR APPROPRIATE AREAS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-04 Cont ID  
Sent By adarroug Date 2006-01-04 Time 10:32 Rev Time 0.00
Received By adarroug Date 2006-01-04 Time 10:32 Sent To M
Notes
2006-01-04 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 15:25 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 15:25 Sent To B
Notes
2005-10-05 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 14:20 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 14:20 Sent To  
Notes
2005-08-29 00:00:00TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-08-16 Cont ID  
Sent By lmartine Date 2005-08-16 Time 10:57 Rev Time 0.00
Received By lmartine Date 2005-07-14 Time 14:35 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#44
2005-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By tgordon Date 2006-01-04 Time 13:56 Rev Time 0.30
Received By tgordon Date 2006-01-04 Time 13:56 Sent To  
Notes
2006-01-04 00:00:00*** PROVISO ***
 1) BATHROOM EXHAUST DISCHARGE SHALL NOT
 CAUSE A NUISANCE, AND AT A POINT WHERE
 IT CAN NOT BE READILY DRAWN IN BY A
 VENTILATING SYSTEM, PER 2001 FBC/M 501.3
 .
 2) EXHAUST AIR MUST BE 10 FEET OR MORE
 AWAY FROM FRESH AIR INTAKE, PER 2001
 FBC/M 401.5 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-19 Cont ID  
Sent By pkrauss Date 2005-09-19 Time 13:42 Rev Time 0.40
Received By pkrauss Date 2005-09-19 Time 13:04 Sent To  
Notes
2005-09-19 00:00:00PROVISO:
 EXHAUST DUCT PENETRATING RATED WALL
 SHALL COMPLY WITH 2001 FBC(M) 607.1.3
 ITEM 3, 1 THROUGH 4, SHOULD A FIRE
 DAMPER NOT BE INSTALLED.
  
 TERMINATION OF EXHAUST SHALL NOT CREATE
 A NUISANCE OR BE DIRECTED ONTO WALKWAYS
 PER 2001 FBC(M)401.5.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-15 Cont ID  
Sent By pkrauss Date 2005-08-15 Time 16:15 Rev Time 0.55
Received By pkrauss Date 2005-08-15 Time 16:13 Sent To  
Notes
2005-08-15 00:00:00DENIED:
 1.PLAN SHEET A-2 UBDUCATES NEW REFRIG
 LINES TO ROOFTOP COND UNIT.PER 2001
 FBC 1006.1.3.1, PENETRATIONS INTO OR
 OPENINGS THROUGH A STAIRWAY ENCLOSURE
 ARE PROHIBITED EXCEPT FOR THOSE REQUIRED
 FOR INDEPENDENT STAIRWELL
 PRESSURIZATION, STANDPIPES & ELECTRICAL
 CONDUIT SERVING THE STAIRWELL.
  
 2.PLAN SHEET M-1 INDICATES FRESH AIR
 INTAKE OPENINGS, PER 2001 FBC(M)401.5 -
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM THE LOT LINE.
 WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED FROM THE CENTERLINE.SEE ALSO
 2001 FBC 705.1.1.2.
  
 3.PLAN SHEET M-1, VENT LOUVERS
 (EXHAUST) SHALL NOT BE DIRECTED ONTO
 WALKWAYS - 2001 FBC(M)401.5.2. SEE ALSO
 2001 FBC(M)501.3.EXHAUST APPEARS TO
 DISCHARGE ABOVE THE DOOR, PLEASE
 CLARIFY.
  
 4.PROVIDE ENERGY CALCULATIONS THAT
 INCLUDE THE ADDITION.2001 FBC CHAPTER
 13 SUB-CHAPTER 400.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By pschmitz Date 2005-09-30 Time 12:14 Rev Time 0.00
Received By pschmitz Date 2005-09-30 Time 12:20 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By kstevens Date 2005-08-09 Time 06:57 Rev Time 3.75
Received By kstevens Date 2005-08-08 Time 18:49 Sent To  
Notes
2005-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT A-1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. SECTION 704.5.
 2. TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 3. SHT A-4 TOILET ROOM DETAIL SHOW THE
 FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 FOR THE LAV:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. FAUCETS
 4. SHT M-1 A VENT IS REQUIRED FOR THE
 FLOOR DRAIN. SECTION 901.2.1.
 5. SHT M-1 HVAC LAYOUT SHOWS CONDENSATE
 "TO FLOOR DRAIN BELOW". THIS IS NOT
 APPROVED. CONDENSATE SHALL BE PIPED
 SEPARATELY OUTSIDE THE BUILDING TO A
 STORM LINE, A CATCH BASIN, A DRYWELL, OR
 A PLANTED AREA. CITY CODE SECTION
 90-125(5). A RELIEF VENT IS REQUIRED IF
 TIED INTO THE STORM LINE.
 6. SHT M-1 PLUMBING NOTES:
 #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE
 PER TABLE 704.1. INDICATE ON NOTE.
 #12 AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM NOTE. SECTION 604.9 & PDI-WH
 201.
 7. SHT A-2 INDICATES "SHELL ONLY, TENANT
 IMPROVEMENTS BY SEPARATE PERMIT". PLANS
 FOR TENANT IMPROVMENTS MIGHT HAVE TO BE
 ROUTED TO DBPR, AND CONTACT WITH UTILITY
 DEPT. FOR SIZING OF GREASE INTERCEPTOR
 MAY BE REQUIRED ONCE SEATING INFORMATION
 IS SUBMITTED.
 8. THE FIXTURES THAT WILL BE DELETED FOR
 THIS ADDITION APPEAR TO BE COMMON
 FACILITIES FOR THE BUILDING. PLEASE
 SUBMIT A FLOOR PLAN FOR THE BUILDING
 SHOWING ALL SPACES AND THE FACILITIES
 FOR EACH SPACE TO VERIFY THAT THESE
 FIXTURES CAN BE DELETED. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]