Plan Review Details - Permit 05070398
Plan Review Stops For Permit 05070398
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-20 Cont ID  
Sent By alange Date 2005-09-20 Time 09:07 Rev Time 2.00
Received By alange Date 2005-09-20 Time 08:38 Sent To  
Notes
2005-09-20 00:00:00FEES DUE
  
 1. BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION OF THE PERMIT HAS
 BEEN REVISED.
 $76.96 PER SQ. FT. X 3466 = $266,743.00
 $41.60 PER SQ. FT. X 1127 = $46,883.00
 REVISED PERMIT VALUATION IS $313,626.00
 ADDITIONAL PERMIT FEES ARE DUE.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By alange Date 2005-08-08 Time 08:12 Rev Time 3.33
Received By alange Date 2005-08-05 Time 16:47 Sent To  
Notes
2005-08-08 00:00:00DENIED
  
 1. PROPERTY IS NOT A HOMESTEADED
 PROPERTY
 AND OWNER APPEARS TO RESIDE IN NEW
 JERSEY.
 A CONTRACTOR IS REQUIRED TO OBTAIN A
 PERMIT.FS 489
  
 2.PLEASE SHOW SQUARE FOOTAGE BREAKDOWN
 FOR NEW AREAS SO THAT BUILDING VALUATION
 CAN BE CALCULATED.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 15:22 Rev Time 0.50
Received By dpalmer Date 2005-10-08 Time 14:53 Sent To M
Notes
2005-10-08 00:00:00PLANS OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 07:46 Rev Time 1.00
Received By dpalmer Date 2005-09-09 Time 07:06 Sent To P
Notes
2005-09-09 00:00:00******** UNSAT **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES.
  
 1)NOTE: PLEASE SEE RANGE OCP HAS NOW
 BEEN CHANGED FROM 70A TO 55A'S. PLEASE
 SEE 240.6, 55A'S IS NOT A SIZE OCP
 AVAILABLE.
  
 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING"
 CONDUCTOR IS STILL BEING SHOWN TO THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24. THIS IS
 INDICATED AS "BOND" ON PLANS.
 ONLY THE UN-GROUNDED (HOT) , AND THE
 GROUNDED (NEUTRAL) CONDUCTORS ARE
 INSTALLED UP TO THE FIRST MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SHALL BE COMPLETE AND CONTINUOUS
 AT ONE LOCATION.
 PLEASE SEE RISER SHOWS SOME FROM METER
 AND THEN , FOOTER AND COLD WATER AT MDP?
 PLEASE MOVE GROUNDING ELECTRODES (FOOTER
 STEEL AND COLD WATER ) OVER TO GRND RODS
 SHOWN AT METER.
 250.50,250.58
  
 4)NOTE: PLEASE CORRELATE ALL A/C
 EQUIPMENT. PLEASE SEE RISER INDICATES
 3-#6'S AND 3-#8'S FOR AHU'S AND CU'S
 ALONG WITH EQUIPMENT GROUNDING
 CONDUCTORS(BOND AS SHOWN). PLEASE SEE
 THE AMOUNT OF CONDUCTORS TEND TO
 INDICATE EQUIPMENT AS 3-PHASE. PLEASE
 SEE RISER/SERVICE AND PANELS INDICATE A
 SINLGE PHASE SERVICE.
 PLEASE ADJUST.
 PLEASE ALSO SEE PANEL SCHEDULE INDICATES
 ALL CONDUCTORS AS #6'S, AS #8'S ARE
 NOTED FOR RISER.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE THE RECEPT WAS ADDED
 FOR WHIRLPOOL TUB, HOWEVER NO INDICATION
 OF REQUIRED GFI PROTECTION IS SHOWN?
 PLEASE SEE 680.71
  
 6)NOTE: PLEASE CLARIFY CONTINUOUS LOAD
 OF 125% IS ALREADY FIGURED FOR POOL
 PUMP?
 215.3, 230.42 ETC.
  
 7)NOTE: NEW. PLEASE SEE SD SHOWN FOR
 MASTER BEDRM WILL BE REQUIRED TO BE
 MOVED INTO BEDRM AREA WITHIN THE 12" OF
 HIGHEST CEILING POINT ON A FLAT CEILING.
 NFPA-72 11.8.3.5
 PLEASE SEE A SD WILL BE REQUIRED INSIDE
 "STUDY" AS THIS IS CONSIDERED AN
 ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 8)NOTE: PLEASE CORRLEATE LOAD AND OCP
 FOR WATER HEATER. SHOWS 9KW FOR WH.
 PLEASE VERIFY THIS , AS 9KW SEEMS TO BE
 HIGH FOR A 60 GAL UNIT. PLEASE SEE MIN
 OCP FOR WH IS 125%. 422.13 MAX 150%.
 (IS THIS 4500 UPPER AND 4500 LOWER?)
  
 9)NOTE: PLEASE SEE TWO GDO'S ARE SHOWN
 ON LOAD CALCS, HOWEVER ONY ONE IS
 INDICATED ON PANEL SCHEDULE.
 PLEASE SEE THREEDEDICATED REFRIGERATOR
 CIRCUITS ARE SHOWN ON PANEL SCHEDULE,
 HOWEVER ONLY TWO ARE IN LOAD CALCS.
  
 10)NOTE: PLEASE SEE LT FIXTURE IN STUDY
 CLOSET WILL BE REQUIRED TO MEET 410.8
 LT IS SHOWN OVER SHELF.
  
 NOTE TO FS 553.80(2)(B), ONLY A NOTICE.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS . (AS PREVIOUSLY
 DONE).
  
 PLEASE SUBMIT THE ABOVEINFORMATION AND
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-22 Cont ID  
Sent By dpalmer Date 2005-07-22 Time 14:45 Rev Time 1.50
Received By dpalmer Date 2005-07-22 Time 13:06 Sent To M
Notes
2005-07-22 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
 215.5
  
 2)NOTE: PLEASE SEE MISSING BEDRM RECEPT
 PER 210.52
  
 3)NOTE: PLEASE SEE 210.52C2 FOR MISSING
 ISLAND RECEPT. PLEASE ALSO SEE 210.8A6
 FOR REQUIRED GFI PROTECTION.
  
 4)NOTE: PLEASE SEE MISSING RECEPTS/LTS
 FOR AHU'S IN ATTIC SPACE. 210.70,210.63
  
 5)NOTE: PLEASE SEE 250.50 FOR MIN
 GROUNDING ELECTRODE SYSTEM. FOOTER
 STEEL, COLD WATER PIPE(IF METAL.
  
 6)NOTE: PLEASE SEE A MAIN IS REQUIRED IN
 MDP. THIS IS SHOWN AS MLO WITH MORE THAN
 6 SPACES. 230.71
 A MCB WILL BE REQUIRED.
  
 7)NOTE: PLEASE CORRELATE SEC'S FOR MDP.
 PLEASE SEE NOTES DO NOT CORRELATE WITH
 MDP.(METER TO MDP)
 215.5
  
 8)NOTE: PLEASE SEE NOTES TO RISER
 MENTIONS AN EQUIPMENT GROUNDING
 CONDUCTOR BEING INSTALLED FROM METER TO
 FIRST MEANS OF DICSCONNECT. PLEASE SEE
 250.6,250.24, AN "EQUIPMENT GROUNDING"
 CONDUCTOR SHALL ONLY BE INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECT.
  
 9)NOTE: PLEASE CLARIFY MULTIPLE BRKRS
 FEEDING ONE A/CAHU??
 PLEASE SEE A 2P BRKR IS SHOWN FOR AHU
 AND A SEPARATE FEED AND BRKR FOR AHU
 HEAT??
 THIS IS NOT PERMITTED, ALL EQUIPMENT
 MUST BE DISCONNECTED WITH A SINGLE THROW
 OF A SWITCH DISC ETC.
 440.11ETC.
  
 10)NOTE: PLEASE SEE TWO AHU'S NO #1 ON
 PANEL SCHEDULE.
 215.5
  
 11)NOTE: PLEASE CORRLEATE OCP, AWG AND
 LOAD CALCUALTIONS FOR AHU'S AND HEAT.
 PLEASE SEE ONE SHOWS WHAT APPEARS TO BE
 5KW, HOWEVER LOAD CALCULATIONS INDICATE
 10KW??
 PLEASE ALSO SEE SIZING OF BRANCH CIRCUIT
 CONDUCTORS AS SHOWN ON RISER.
 240.4,424.3B,310.16, 215.5 ETC
  
 12)NOTE: PLEASE SEE A WHIRLPOOL TUB IS
 SHOWN ON PANEL SCHEDULE AND IS INDICATED
 IN LOAD CALCS, HOWEVER THIS COULD NOT BE
 LOCATED ON PLANS?
 PLEASE ALSO SEE 680.71 FOR REQUIRED GFI
 PROTECTION.
  
 13)NOTE: PLEASE CLARIFY SIZE OF BRANCH
 CIRCUIT SHOWN FOR RANGE? 70A?
 PLEASE SEE 422.11 FOR MAX SIZE OF BRANCH
 CIRCUIT FOR APPL.
 PLEASE SEE MAX SINGLE OCP IS
 60A'S.(48A'S).
 PLEASE ADJUST.
  
 14)NOTE: PLEASE SEE PLANS INDICATE BY
 NOTE "ARC-FAULT" PROTECTION FOR BEDRMS,
 HOWEVER ONLY TWO ARC FAULT CIRCUITS ARE
 SHOWN ON PLANS??
 PLEASE ALSO SEE SD'S ARE SHOWN ON PANEL
 SCHEDULE, HOWEVER THESE ARE NOT LISTED
 AS BEING ARC FAULT PROTECTED??
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ALL OUTLETS IN BEDRMS, FANS,
 LTS, RECEPTS, SD'S ETC.
  
 15)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR FOUNTAIN PUMP,LTS.
 680.50-680.56
  
 16)NOTE:PLEASE CLARIFY IF LOAD SHOWN
 FOR POOL PUMP IS SHOWN @ CONTINUOUS
 LOAD? 125%?
 PLEASE SEE ALL CONTINUOUS LOADS SHOULD
 BE INDICATED AT 125%.
 215.3,230.42, ETC.
  
 17)NOTE:PLEASE VERIFY, PLANS INDICATE
 PANELS TO BE INSTALLED ARE SQ D
 "HOMELINE"?? PLEASE CLARIFY AND ADJUST
 IF NEEDED. THIS IS ONLY A NOTE AND NO
 CORRECTION NEEDS TO BE MADE UNLESS
 "HOMELINE" PANELS WILL NOT BE USED.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIOW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 08:20 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 08:20 Sent To B
Notes
2006-03-06 00:00:00TO "ALANGE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 18:55 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 18:55 Sent To E
Notes
2005-10-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 15:42 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 15:42 Sent To E
Notes
2005-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 13:08 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 13:08 Sent To Z
Notes
2005-08-31 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 10:32 Sent To E
Notes
2005-07-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-08 Cont ID  
Sent By alange Date 2005-08-08 Time 08:33 Rev Time 0.00
Received By alange Date 2005-07-14 Time 10:56 Sent To  
Notes
2005-07-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-10-11 Cont ID  
Sent By tgordon Date 2005-10-11 Time 11:44 Rev Time 0.00
Received By tgordon Date 2005-10-11 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 08:53 Rev Time 0.30
Received By tgordon Date 2005-09-13 Time 08:53 Sent To B
Notes
2005-09-13 00:00:00*** DENIED ***
 1) NEED CALCULATIONS FOR COMBUSTION AIR
 WITH BTU'S OF GAS DRYER, FBC/M504.3 .
 2) WHEN SHOWING MAKE UP AIR PLEASE NOTE
 NO MAKE UP AIR MAY BE TAKEN FROM ROOF
 TOPS, FBC/M CH.13 609.1ABC.1 .
 IF UOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By prafter Date 2005-07-25 Time 11:13 Rev Time 1.00
Received By prafter Date 2005-07-25 Time 11:13 Sent To B
Notes
2005-07-25 00:00:00MECH. PLAN REVIEW.
  
 CLOTHE DRYER MUST COMPLY WITH 2003
 FBC/M 504.5 MAKE AIR AND PROVIDE FOR
 COMBUSTION AIR FOR GAS DRYER.
  
 PLEASE PROVIDE INFORMATION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-09 Cont ID  
Sent By jleech Date 2005-09-09 Time 14:45 Rev Time 0.50
Received By jleech Date 2005-09-09 Time 14:45 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 13:09 Rev Time 1.00
Received By jleech Date 2005-07-23 Time 13:09 Sent To M
Notes
2005-07-23 00:00:00DENIED;
 1.SIZE ALL PIPE ON RISER DIAGRAM. DEETE
 UN- NEEDED VENTS (SEE RED LINE ONE SET
 OF PLANS)
 2.WATER HEATER DETAIL. ADD NOTE FOR
 PIPING INSULATION FOR HOT WATER
 CIRCULATION SYSTEM PER TABLE 607.1. ALSO
 SHOW THERMAL EXPANSION CONTROL MEANS PER
 SEC. 607.3.
 3.PLUMBING NOTES; CHANGE NOTE TO TO
 COMPLY WITH TABLE 704.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By mmclean Date 2005-09-07 Time 18:47 Rev Time 0.00
Received By mmclean Date 2005-09-07 Time 18:47 Sent To I
Notes
2005-09-07 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATE WITH EASEMENT
 APPROVAL FROM CITY OF WEST PALM UTILITY
 DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By mmclean Date 2005-07-21 Time 11:13 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 11:13 Sent To I
Notes
2005-07-21 00:00:00DENIED,
 1. THE SITEPLAN & SURVEY SETBACKS SIDE &
 REAR DOES NOT MATCH. REAR SETBACK MUST
 BE 10% OR 15FT WHICHEVER IS LESS AND
 SIDES MUST GIVE A TOTAL OF 15FT.
 2. MUST PROVIDE DIMENSION OF THE
 DRIVEWAY AND ENTRY WALKWAY (LENGTH &
 WIDTH). MUST MAINTAIN 1000SQ FT OR 75%
 WHICHEVER IS LESS OF LANDSCAPE WITHIN
 THE FIRST 25FT FRONT SETBACK.
 (INFORMATION IS NEEDED TO CALCULATE THE
 DIMENSION OF DRIVEWAY/ENTRY WALKWAY).
 3. MUST PULL A SEPERATE PERMIT FOR
 DRIVEWAY/ENTRY WALKWAY WITH APPROVAL
 FROM CITY OF WEST PALM BEACH UTILITY
 DEPT, EASMENT RELEASE.
 4. GATE/FENCE/WALL/COLUMNS CAN ONLY BE A
 MAXIMUM HEIGHT OF 4FT WITHIN THE 25FT
 FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720