| 2005-07-22 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING BEDRM RECEPT |
| | PER 210.52 |
| | |
| | 3)NOTE: PLEASE SEE 210.52C2 FOR MISSING |
| | ISLAND RECEPT. PLEASE ALSO SEE 210.8A6 |
| | FOR REQUIRED GFI PROTECTION. |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS/LTS |
| | FOR AHU'S IN ATTIC SPACE. 210.70,210.63 |
| | |
| | 5)NOTE: PLEASE SEE 250.50 FOR MIN |
| | GROUNDING ELECTRODE SYSTEM. FOOTER |
| | STEEL, COLD WATER PIPE(IF METAL. |
| | |
| | 6)NOTE: PLEASE SEE A MAIN IS REQUIRED IN |
| | MDP. THIS IS SHOWN AS MLO WITH MORE THAN |
| | 6 SPACES. 230.71 |
| | A MCB WILL BE REQUIRED. |
| | |
| | 7)NOTE: PLEASE CORRELATE SEC'S FOR MDP. |
| | PLEASE SEE NOTES DO NOT CORRELATE WITH |
| | MDP.(METER TO MDP) |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE NOTES TO RISER |
| | MENTIONS AN EQUIPMENT GROUNDING |
| | CONDUCTOR BEING INSTALLED FROM METER TO |
| | FIRST MEANS OF DICSCONNECT. PLEASE SEE |
| | 250.6,250.24, AN "EQUIPMENT GROUNDING" |
| | CONDUCTOR SHALL ONLY BE INSTALLED AFTER |
| | THE FIRST MEANS OF DISCONNECT. |
| | |
| | 9)NOTE: PLEASE CLARIFY MULTIPLE BRKRS |
| | FEEDING ONE A/CAHU?? |
| | PLEASE SEE A 2P BRKR IS SHOWN FOR AHU |
| | AND A SEPARATE FEED AND BRKR FOR AHU |
| | HEAT?? |
| | THIS IS NOT PERMITTED, ALL EQUIPMENT |
| | MUST BE DISCONNECTED WITH A SINGLE THROW |
| | OF A SWITCH DISC ETC. |
| | 440.11ETC. |
| | |
| | 10)NOTE: PLEASE SEE TWO AHU'S NO #1 ON |
| | PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE CORRLEATE OCP, AWG AND |
| | LOAD CALCUALTIONS FOR AHU'S AND HEAT. |
| | PLEASE SEE ONE SHOWS WHAT APPEARS TO BE |
| | 5KW, HOWEVER LOAD CALCULATIONS INDICATE |
| | 10KW?? |
| | PLEASE ALSO SEE SIZING OF BRANCH CIRCUIT |
| | CONDUCTORS AS SHOWN ON RISER. |
| | 240.4,424.3B,310.16, 215.5 ETC |
| | |
| | 12)NOTE: PLEASE SEE A WHIRLPOOL TUB IS |
| | SHOWN ON PANEL SCHEDULE AND IS INDICATED |
| | IN LOAD CALCS, HOWEVER THIS COULD NOT BE |
| | LOCATED ON PLANS? |
| | PLEASE ALSO SEE 680.71 FOR REQUIRED GFI |
| | PROTECTION. |
| | |
| | 13)NOTE: PLEASE CLARIFY SIZE OF BRANCH |
| | CIRCUIT SHOWN FOR RANGE? 70A? |
| | PLEASE SEE 422.11 FOR MAX SIZE OF BRANCH |
| | CIRCUIT FOR APPL. |
| | PLEASE SEE MAX SINGLE OCP IS |
| | 60A'S.(48A'S). |
| | PLEASE ADJUST. |
| | |
| | 14)NOTE: PLEASE SEE PLANS INDICATE BY |
| | NOTE "ARC-FAULT" PROTECTION FOR BEDRMS, |
| | HOWEVER ONLY TWO ARC FAULT CIRCUITS ARE |
| | SHOWN ON PLANS?? |
| | PLEASE ALSO SEE SD'S ARE SHOWN ON PANEL |
| | SCHEDULE, HOWEVER THESE ARE NOT LISTED |
| | AS BEING ARC FAULT PROTECTED?? |
| | PLEASE SEE 2002 NEC 210.12, WHICH |
| | REQUIRES ALL OUTLETS IN BEDRMS, FANS, |
| | LTS, RECEPTS, SD'S ETC. |
| | |
| | 15)NOTE: PLEASE INDICATE GFI PROTECTION |
| | FOR FOUNTAIN PUMP,LTS. |
| | 680.50-680.56 |
| | |
| | 16)NOTE:PLEASE CLARIFY IF LOAD SHOWN |
| | FOR POOL PUMP IS SHOWN @ CONTINUOUS |
| | LOAD? 125%? |
| | PLEASE SEE ALL CONTINUOUS LOADS SHOULD |
| | BE INDICATED AT 125%. |
| | 215.3,230.42, ETC. |
| | |
| | 17)NOTE:PLEASE VERIFY, PLANS INDICATE |
| | PANELS TO BE INSTALLED ARE SQ D |
| | "HOMELINE"?? PLEASE CLARIFY AND ADJUST |
| | IF NEEDED. THIS IS ONLY A NOTE AND NO |
| | CORRECTION NEEDS TO BE MADE UNLESS |
| | "HOMELINE" PANELS WILL NOT BE USED. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICLA |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIOW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |