Plan Review Details - Permit 05070374
Plan Review Stops For Permit 05070374
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-27 Cont ID  
Sent By lmartine Date 2007-04-27 Time 13:00 Rev Time 0.00
Received By lmartine Date 2007-04-27 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-20 Cont ID  
Sent By alange Date 2005-09-20 Time 13:00 Rev Time 1.75
Received By alange Date 2005-09-20 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-05 Cont ID  
Sent By alange Date 2005-08-05 Time 14:20 Rev Time 2.50
Received By alange Date 2005-08-05 Time 11:10 Sent To  
Notes
2005-08-05 00:00:00DENIED
  
 1.PLEASE SUBMIT A DETAIL FOR SPIRAL
 STAIRCASE SHOWING COMPLIANCE WITH FBC
 1007.8.2
  
 2.SHOW SAFTEY GLAZING ON WINDOW AT TUB
 LOCATION.FBC 2405.2.1
  
 3.BASE ON SBCCI BUILDING VALUATION
 DATA AND MARSHALL AND SWIFT ESTIMATING
 GUIDE, THE PERMIT VALUATION HAS BEEN
 REVISED TO $218,697.00.ADDITIONAL
 PERMIT FEES OF $713.24 ARE DUE.
  
 4.ACCORDING TO PALM BEACH COUNTY
 PROPERTY APPRAISER'S LIST, SEVERAL
 PROPERTIES HAVE BEEN FOUND UNDER THE
 SAME OWNERSHIP ALONG WITH A HOMESTEADED
 PROPERTY AT 3701 S FLAGLER.
 A CONTRACTOR IS REQUIRE TO OBTAIN A
 PERMIT. FS 489
  
 5.DESCIPTION OF WORK ON APPLICATION
 DOES NOT REFLECT WORK ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-23 Cont ID  
Sent By btrobaug Date 2007-04-23 Time 10:52 Rev Time 0.75
Received By btrobaug Date 2007-04-23 Time 07:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By btrobaug Date 2007-02-26 Time 11:18 Rev Time 1.00
Received By btrobaug Date 2007-02-26 Time 06:47 Sent To M
Notes
2007-02-26 11:13:55 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THERE IS A DELTA '2' INDICATING THE REVISION, BUT
 NOT MARKED ON THE PLAN. PLEASE INDICATE BY CLOUDING OR
 SOME OTHER MEANS WHERE THESE CHANGES ARE.
  
 2} THE WIRING IN THE "OFFICE" WAS DELETED FROM THIS
 PLAN. IF THESE SHEETS ARE REVISING PREVIOUS PLANS, ALL
 WORK ORIGINALLY SHOWN MUST BE ON THE REVISED SHEET AS
 IT REPLACES THE PREVIOUS SHEET.
  
 3} THERE ARE SOME STRUCTURAL CHANGES ON THIS PLAN, BUT
 NO STRUCTURAL REVISIONS HAVE BEEN SUBMITTED. ANY
 ELECTRICAL CHANGES AFFECTED BY STRUCTURAL CHANGES MUST
 BE SUBMITTED AT THE SAME TIME, OR AFTER THE STRUCTURAL
 CHANGES HAVE BEEN PREVIOUSLY REVIEWED.
  
 4} AS PREVIOUSLY NOTED ON THE PLAN, A GFI IS REQUIRED
 FOR THE WHIRLPOOL TUB PER 680.71. THIS MAY BE AT THE
 PANEL IN THE FORM OF A BREAKER OR A RECEPTACLE, BUT
 MUST BE SHOWN ON THE PLAN.
  
 5} SHEET E1.2 EXISTING BATH INDICATES BY NOTE
 COMPLIANCE WITH ARTICLE 3401.7.1.2, REVIEW REQUIRES
 THAT THE RECEPTACLE REQUIRED TO COMPLY BE LOCATED ON
 THE PLAN FOR COMPLIANCE WITH 210.52(D) AS WELL AS
 210.8(A)(1).
  
 6} THE #2 THHN EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. SHEET E2.1,
 RISER DIAGRAM.
  
 7} THE FEEDERS TO THE EXISTING PANEL (3/0) AND THE NEW
 PANEL "A" (4/0) IN THE MDP, DO NOT CORRELATE WITH THE
 "3-2/0 " FEEDERS ON THE RISER DIAGRAM.
  
 8} THREE PANELS HAVE BEEN REMOVED FROM THE PERMITTED
 PLANS. INDICATE THE ORIGINAL LOCATIONS OF THESE PANELS
 AND THE LOCATION OF THE JUNCTION BOXES THAT MUST HAVE
 REPLACED THESE PANELS.215.5.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By btrobaug Date 2005-09-13 Time 08:48 Rev Time 0.75
Received By btrobaug Date 2005-09-12 Time 16:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By btrobaug Date 2005-07-26 Time 17:29 Rev Time 0.75
Received By btrobaug Date 2005-07-26 Time 16:22 Sent To M
Notes
2005-07-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE FEEDER CONDUCTOR SIZES
 TO THE PANELS FROM MDP ARE TOO LARGE.
 THIS IS NOT A VIOLATION BUT MUST BE
 INSTALLED IF THEY REMAIN ON THE PLAN, OR
 A REVISION TO THE PLAN WILL BE REQUIRED.
 ALSO SOO THE 3/0 & 4/0S WILL NOT FIT ON
 100 AMP BREAKERS.
  
 2} PANEL "B" IS 200 AMP ON THE SCHEDULE
 , 100 AMP IN THE MDP.PLEASE CORRELATE.
  
 3} BOTH AC UNITS ARE MARKED #1 ON THE
 RISER. SEE PANEL "B" CIRCUITS 9,10,11 &
 12.
  
 4} PLEASE VERIFY BOND WIRE SIZES, SEE
 COMMENT #1.
  
 5} PLEASE VERIFY THE SIZE AND NUMBER OF
 THE SERVICE CONDUCTORS FROM THE METER TO
 THE MDP. INDICATE CONDUIT(S) SIZES AND
 NUMBER OF CONDUCTORS IN EACH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 14:16 Sent To E
Notes
2007-04-20 14:17:09TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 09:20 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 09:20 Sent To Z
Notes
2007-04-16 09:20:50TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 09:56 Sent To E
Notes
2007-02-15 09:57:05TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 14:05 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 14:05 Sent To E
Notes
2005-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 16:10 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 16:10 Sent To Z
Notes
2005-09-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 10:26 Sent To E
Notes
2005-07-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-05 Cont ID  
Sent By alange Date 2005-08-05 Time 14:20 Rev Time 0.00
Received By alange Date 2005-07-14 Time 16:40 Sent To  
Notes
2005-07-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-23 Cont ID  
Sent By tgordon Date 2007-04-23 Time 14:50 Rev Time 0.30
Received By tgordon Date 2007-04-23 Time 14:50 Sent To B
Notes
2007-04-23 14:52:17REVISION TO MECH. PLANS, E-CAL'S, AND COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 15:20 Rev Time 0.45
Received By tgordon Date 2007-03-07 Time 15:20 Sent To  
Notes
2007-03-07 15:40:25MECHANICAL REVISION PAGE M1.1 AND M1.2.
 *** DENIED ***
 1)PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC
 9B-72.010(31)(G).
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 2) 14" SUPPLY AND RETURN AIR DUCT FROM A/C SYSTEM 2 IS
 TO SMALL. A 14" DUCT AT 1200 CFM'S IS A VELOCITY OF
 1100 FPM, MANUAL J CALCULATIONS STATE THE MAXIMUM
 VELOCITY IS 900 FPM, ALSO THE 12" SUPPLY AIR DUCT TO
 THE MIXING BOX. PLEASE CORRECT.
  
 3) PLEASE RE-DO MANUAL J CALCULATIONS AS A THREE TON
 A/C SYSTEM WOULD BE A LOT OF A/C FOR JUST 563 SQUARE
 FEET.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By hmoser Date 2005-09-14 Time 17:30 Rev Time 0.00
Received By hmoser Date 2005-09-14 Time 17:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By hmoser Date 2005-07-28 Time 17:54 Rev Time 0.00
Received By hmoser Date 2005-07-28 Time 17:54 Sent To P
Notes
2005-07-28 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 609.1.ABC.1.#
 2 FLORIDA ENERGY CODE A/C MAKE UP AIR.
 2) PLEASE REFER TO SECTION 601.4 FBC(M)
 BALANCED RETURN AIR 1ST.FLOOR OFFICE.
 3) PLEASE PROVIDE BATHROOM EXHAUST ON
 MECHANICAL PLANS.
 4) PLEASE SHOW LOCATION OF ZONE 1
 CONDENSOR ON PLANS.
 PLAN REVIEW BY HAROLD MOSER.561-805-6732
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 14:31 Rev Time 0.75
Received By jleech Date 2005-08-01 Time 14:31 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2007-04-27 Cont ID  
Sent By adavila Date 2007-04-27 Time 14:29 Rev Time 0.00
Received By adavila Date 2007-04-27 Time 14:29 Sent To B
Notes
2007-04-27 14:29:27PER KELLY FREEMAN, PLANNER.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-04-18 Cont ID  
Sent By adavila Date 2007-04-18 Time 18:43 Rev Time 0.00
Received By adavila Date 2007-04-17 Time 12:50 Sent To I
Notes
2007-04-18 18:43:37PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE SETBACK DIMENSIONS FROM PROPERTY LINE TO
 CONDENSING UNIT.PURSUANT TO SECTION 94-305(B)(4) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS, MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By mmclean Date 2005-09-07 Time 18:39 Rev Time 0.00
Received By mmclean Date 2005-09-07 Time 18:39 Sent To I
Notes
2005-09-07 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS/GATE WITH EASEMENT
 APPROVAL FROM CITY OF WEST PALM BEACH.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By mmclean Date 2005-07-21 Time 12:23 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 12:23 Sent To I
Notes
2005-07-21 00:00:00DENIED,
 1. SITEPLAN & SURVEY SIDE SETBACK DOES
 NOT MATCH.
 2. MUST PROVIDE THE DIMENSION OF THE NEW
 DRIVEWAY/ENTRY WALKWAY (LENGTH & WIDTH)
 TO CALCULATE IF THE DRIVEWAY MEETS THE
 ZONING REGULATIONS. MUST MAINTAIN 1000SQ
 FT OR 75% OF LANDSCAPE WITHIN THE FIRST
 25FT FRONT SETBACK.
 3. SEPERATE PERMIT MUST BE PULLED FOR
 FENCE/WALL/COLUMNS/GATE WITH EASMENT
 APPROVAL FROM CITY OF WEST PALM BEACH.
 4. GATE/WALL/COLUMNS/FENCE CAN ONLY BE A
 MAXIMUM HIGH OF 4FT WITHIN THE FIRST
 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720